Frame 6 b gt igv problem
1. 12/30/2014 Frame 6B GT IGV problem
http://control.com/thread/1379617896 1/2
Frame 6B GT IGV problem
Frame 6B Gas Turbine with MarkV, IGV problem during Startup.
By Jigs on 19 September, 2013 3:11 pm
April 2013 MI was performed. IGV blades, gears, pinion and actuator were replaced. Since then
during start up at @ 85 % of GT speed IGV starts opening and not limiting at 57 Deg A but reaches
upto 72 DEG A for a while and then come back to 57 GEG A before FSNL. Exhaust temp reaches
576 deg C max. before IGV starts opening. What could be cause?
By CSA on 20 September, 2013 1:46 pm
Jigs,
The problem started when the IGV actuator was replaced during the outage. It's not clear if the
electrohydraulic servovalve was also replaced at the same time, and if the proper servovalve was
used for the replacement, and if the polarity of the current applied to each coil was verified during
the commissioning/startup activities.
It is also presumed that the IGV LVDTs were "zeroed" properly and calibrated properly after the
outage.
Have you tried manually positioning ("stroking") the IGVs using AutoCalibrate's Manual Position
feature to see how the IGVs are behaving? If so, what did you observe?
Have you used the 'Verify Position' or 'Verify Current' features of AutoCalibrate, and if so, what
were the results?
Since the IGV actuator was replaced, it's likely the IGV LVDTs were calibrated. Was the Null Bias
Current value changed during the calibration procedure, and if so, what is the current value? Was
the regulator gain changed during the commissioning/startup, and if so, what was it changed to?
Even if the Null Bias Current and IGV Regulator Gains weren't changed during
commissioning/startup, what are they?
From the information provided, it would seem that no Control Constants were changed. So,
presuming the reference is being calculated correctly (and there's no reason to believe changing the
IGV actuator would change the way the IGV position reference is being calculated) then the most
likely cause is some problem with the IGV assembly (actuator, bushings, etc.) binding, or the
actuator isn't properly bolted down, or the servovalve isn't the right one, or the actuator isn't
working properly. But, from the information provided, it would seem something is causing the
actuator/IGV assembly to overshoot (travel past) the reference setpoint and then the Mark V has to
change servocurrent to make it return to the proper value.
If the Mark V has to keep putting out more current to make the IGVs move because they are either
not moving or are sluggish to move (mechanically sticking or binding) and then when they do move
they travel past the reference setpoint and the Mark V has to change servo current to get them to