Have you got what factors should be taken when choosing a chiller? COOLSOON REFRIGERATION CO., LTD specialized in water chillers designed and developed chillers for your specific requirements.
1. Factors on Choosing Industrial Water Chillers
An industrial water chiller is a compressor-based cooling system that takes out heat from a liquid,
controlling and chilling it. Components include temperature controller, reservoir, and a recirculating
pump. It comes in different types: portable, air cooled chiller and water chilled chiller. Industrial
applications for a chiller involve die-casting and machine tooling, food and beverage processing,
chemical processing, paper and cement processing, welding equipment, pharmaceutical formulation
and X-ray diffraction, so chiller comes into different types: laser chiller, PCB chiller, screw chiller and
others. A chiller is also used to cool high-powered electronics inside diagnostic machines like PET
scans and MRIs.
Choosing an industrial chiller requires more than just knowing the cooling requirements, the
reservoir or internal water tank size, and the chiller cooling capacity. Every business must also
consider the power source or if there is a need to get additional power to stabilise temperature for
differing loads; the total life-cycle cost, whether a new system will eventually be required to increase
performance or an existing unit’s repair or maintenance cost will be minimal; condenser capacity and
material, which can affect efficiency, and chiller design.
A chiller’s design can be as significant as its components. Some designs support high rates of fluid
while others are meant to use specific fluids – for instance, a chiller with no brass or copper when
the fluid being cooled is distilled or demineralised water. Both can actually cause metal corrosion,
which is why plastic or stainless steel components are used in the chiller.
Other considerations to think of when getting a chiller are ambient temperature, evaporator capacity
and material, chiller IP rating, pump specifications, control panel features (e.g. fault, pressure, and
temperature indicators, etc.), noise level, internal piping materials, and a host of other factors that
should correspond to future cooling needs.
Have you got what factors should be taken when choosing a chiller? COOLSOON
REFRIGERATION CO., LTD specialized in water chillers designed and developed chillers for your
specific requirements. Just contact us at your convenience.
Following are specifications of water cooled Chillers from Coolsoon:
CW Series Water cooled industrial chiller
Mode
CW‐03 CW‐05 CW‐06 CW‐08(D) CW‐10(D) CW‐12 CW‐15 CW‐20(D) CW‐25(D) CW‐30(D) CW‐40(F) CW‐50(F) CW‐60(F)
Item
kcal/h 7912 12900 15222 20296 25800 29412 41710 52460 58738 83420 104920 117476 159960
Nominal
50HZ/60HZ 9288 15394 18490 24338 30960 35260 50052 62092 70606 100104 125904 140972 191952
cooling
KW 9.2 15 17.7 23.6 30.0 34.2 48.5 61 68.3 97 122 136.6 186
capacity
50HZ/60HZ 10.8 17.9 21.5 28.3 36.0 41 58.2 72.2 82.1 116.4 146.4 163.9 223.2
2. Total input
KW 3.07 5.06 5.95 7.87 9.57 10.92 15.22 19.71 21.89 31.19 38.7 48.5 62.38
power
Power supply voltage 3PH 380V 50HZ(200V/220V/415V 50HZ/60HZ)
Type R22(R134a/R407c)
Refrigerant
Control Mode Capillary Expansion valve
Type Hermetic Scroll type(Piston)
Compressor
Power(KW) 2.7 4.41 5.2 3.52×2 4.41×2 9.82 13.72 8.3×2 9.82×2 13.72×2 8.3×4 9.82×4 13.72*4
Type Shell and Tube
2.1 3.5 3.6 5.2 6.76 7.9 10.7 13.9 15.8 20.5 27.8 31.6 40.9
Cooling fluid
flow(m3/h) 2.5 4.2 4.4 6.1 7.4 9.3 11.7 16.3 18.6 22.7 33.35 37.9 49.08
Condenser
Inlet/outlet
1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 2" 2" 2 1/2" 3" 3" 3" 4"
pipe caliber
Type Water tank with coil(Shell and Tube)
1.58 2.58 3 4.1 5.2 5.89 8.35 10.3 11.76 16.7 20.6 23.52 31.88
Chilled fluid
flow(m3/h) 1.86 3.08 3.7 4.9 6.24 7.06 10.02 12.11 14.13 20 24.72 28.22 38.26
Evaporator Tank volume
60 60 90 150 200 200 330 330 350 450 580 620 750
(L)
Inlet/outlet
1" 1" 1" 1‐1/2" 1‐1/2" 2" 2" 2‐1/2" 2‐1/2" 2‐1/2" 3" 3" 3"
pipe caliber
Power(KW) 0.37 0.75 0.75 0.75 0.75 1.5 1.5 2.25 2.25 3.75 5.5 5.5 7.5
Chilled water
Pump head
pump 20 20 20 22 20 20 20 20 20 22 30 30 30
(m)
Compressor overheating , over current, high and low pressure, over temperature , flow switch, phase sequence,
Safty protection
phase‐missing, exhaust overheating, anti‐freezing.
L(mm) 890 890 890 1170 1170 1170 1700 1700 1700 1880 2000 2100 2200
Dimension W(mm) 500 500 500 710 710 710 810 810 810 910 1100 1100 1150
H(mm) 840 840 840 1200 1200 1200 1620 1620 1620 1800 1960 1960 2100
Weight Kg 130 150 165 300 430 500 735 820 900 1150 1250 1400 1500
Note:
1. nominal cooling capacity calculated according to:Inlet/outlet chilled fluid temperature : 12℃/7℃, Inlet/outlet cooling water temperature: 30℃/35℃.
2. Working condition:The temperature range of chilled fluid is from 5℃ to 35℃ Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water from 18℃ to 37℃ Temperature difference between inlet and outlet cooling water is from 3.5℃ to 10℃.
We reserve the right to modify the above information without further notice.
Author: JERRY
Resource: http://www.cool-chiller.com/n/factors-on-choosing-industrial-chillers/31/
http://www.cool-chiller.com/water-cooled-chiller