Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Re 700
1. RAVEL ELECTRONICS PVT. LTD.,
No. 150-A, Elec. Indsl. Estate, Perungudi, Chennai 600 096. India
Tel.: 24961004 / 24960825 Fax: 044 - 4204 9599.
Email: marketing@ravelfirepanels.com Web: www.ravelfirepanels.com
FEATURES:
!
O p e r a t e s o n 2 3 0 V, A . C s u p p l y.
!
B a t t e r y b a c k u p w i t h b u i l t i n c h a rg i n g .
!
Fire / fault status in unambiguous coloured LED
RE - 700
indication.
!
20 X 4 LCD Dot Matrix display.
!
Low battery / warning audio/ visual display.
!
Battery fail warning audio
!
Charger on indication.
!
A.C fail audio / visual warning.
!
Relay output for actuators.
!
RS485 for repeater/slave communication (Use shielded or
twisted wire (CAT5E or CAT6)).
!
Lamp test facilities.
!
O n e m a n w a l k t e s t f a c i l i t y.
!
Compatible to all types of conventional detectors.
!
Zone Isolation facility with loop voltage cut off.
!
Real time clock facility.
!
Events of fire and fault can be seen.
!
RS 232 facility (Optional).
TECHNICAL DATA
1. POWER SUPPLY:
2.
3.
4.
5.
6.
7.
8.
9.
(i)
AC Supply
(ii) DC Supply
Operating Conditions
Operating Voltage
Normal Loop Voltage
Open Threshold Current
Short Circuit Threshold Current
Stand by Threshold Current
( EOL Current + detector's Current)
Alarm Current
Quiescent Current
230 V AC, 50 Hz
24 V DC
-10 to 49 oC ,30 - 95 % RH
24 V DC
20.7 DC
4.2 mA
40 mA
8.2 mA
:
:
20 - 35 mA
50 mA Plus 4.2 mA per Zone
:
10. Colour of the Panel
:
:
:
:
:
:
:
:
Broken White (Red, Red texture - Optional).
:
0.2 Amps per Zone.
2. ALARM OUTPUTS:
Standard Common Output
3. REMOTE INDICATION OUTPUTS:
Standard
:
Common Fire Relay Output (2 No's of 230 V 2A contact)
Fault Relay Output (1 No. of 230 V 2A contact)