Quality Grounding
The Cell Site
A Brief Overview
Developed by Ted J. Pappas
2
National Electric Code (NEC)
National Fire Protection Association (NFPA 70)
The NEC is a regionally adoptable standard for the safe
installation of electrical wiring and equipment in
the United States.
The NEC, while having no legally binding regulation as
written, can be and often is adopted by states,
municipalities and cities in an effort to standardize
their enforcement of safe electrical practices within
their respective jurisdiction. The Law……….
In some cases, the NEC is amended, altered and may
even be rejected in lieu of regional regulations as voted
on by the governing bodies of any given locale.
“Code Compliance”
Ted J. Pappas
3
A Ground, or Earth, is the reference point in an electrical
circuit from which voltages are measured and is a common return
path for electric current as well as a direct physical connection to
the Earth.
What is a GROUND?
Effects of a poor ground connection
 Indictors (alarms) not operating properly
 Motor issues
 Cooling fans not turning to speed resulting in
improper design cooling
 Increased power consumption on site
Electrical shock Hazard-----Death
Ted J. Pappas
4
Ground Rings
• The ring ground will usually encircle the entire cell
site / building that it is trying to protect.
• The ring ground is used as the base of the entire cell
site’s / building's ground system, and all components
of the building's ground system, including the cell site
/ building structure, are connected to the ground ring.
• The National Electrical Code specifies that ring
grounds must be constructed from #2 or thicker wire,
must be buried at least 2 1/2 feet underground, and
must have at least 20 feet of exposed copper to
ensure good electrical contact with the earth
Ted J. Pappas
5
Halo Grounds
• A halo ground is a type of ring ground that, instead of
being installed outside and underground, is installed
inside, near the top of a building or structure.
• The ground reference for all equipment inside the
area being protected is separate from the halo. The
halo is connected to the main building ground, which
may include an underground ring ground outside the
building, with vertical conductors especially in the
corners of the building.
• The halo may be connected to structural metallic
elements such as door frames, building steel, window
frames, and air conditioning vents.
• A typical halo ground is constructed of #2 insulated
copper wire and is installed six inches below the
ceiling, and entirely encircles the area that it is
protecting.
Ted J. Pappas
6
 Exothermic Welding is known by several naming conventions such
as CADWELD , Exothermic bonding, and thermite welding (TW).
 It is a welding process for joining materials that employs molten
metal to permanently join the conductors.
 The process employs an exothermic reaction of
a thermite composition to heat the metal, and requires no external
source of heat or current.
Exothermic Welding
CADWELD is a Registered Trademark
The Graphite Mold
Ted J. Pappas
7
Do I Have The Correct Exothermic Mold?
Inspect the mold ID tag to ensure that it
corresponds to the application, indicated
by the:
1. mold part number
2. conductor size
3. welding material required
4. other materials required
The mold must be correct for the
conductor size and application. DO NOT
MODIFY MOLDS.
Ted J. Pappas
8
Cold Welds, also know as “Correct
Compaction” or the Number of
Crimps, are required to prevent
overheating and joint failure.
The FIRST crimp for lugs requiring
multiple crimps MUST be applied at
the “Palm” end of the lug working
towards the end of the Barrel. As it is
crimped the barrel lengthens and is
known as Cold Flow.
On a lug that requires only one (1)
crimp the die is centered on the
Barrel
Cold Welds and Lugs
Incorrect Compaction also can result in “shiners”
Ted J. Pappas
9
Under and Over Crimping
The cut cross-section of a properly crimped lug to the
left illustrates that all the “Air Voids” have been
removed to form one (1) Mass of Material.
Correct Compaction
The cut cross-section of an Over Crimped lug, also
known as Winging or Flashing, is illustrated to the left.
The common cause of this problem is using a “Die”
that is too small
The resultant is overheating and terminal equipment
failure (under crimping also has the same resultant)
Ted J. Pappas
10
An Accurate Crimp?
The ONLY way to truly identify whether a crimp is accurate is to
employ a Vernier Caliper
The measurement is done across the Flats of the Hexagonal Crimp
Note---If the measurement
does not match the
requirement when employing
the correct Die---the crimper
may require calibration
Ted J. Pappas
11
Proper Cable Lugging
Step One
Strip the Insulation carefully
not to nick of cut conductors.
Ensure the exact amount of
insulator material is striped
based upon the Lug being
employed
Note a depth gauge tool may be employed
Ted J. Pappas
12
Proper Cable Lugging
Step Two
Determine the proper Color-
Keyed Connector for the cable
size being used.
• Connectors marked with just cable size or
CU should be used on copper conductors only.
• Connectors marked “AL9”* with the cable size
should be used on aluminum conductors only.
• Connectors marked “AL9CU” with the cable size
may be used on the aluminum or copper
conductors
13
Proper Cable Lugging
Step Three
Select the proper installation die and appropriate tool
 Connectors have colored bands or colored dots that correspond
to color markings on the dies.
 Connectors and dies also have a die code number marked or stamped
on them. Dies have a code number engraved in the crimp surface.
Ted J. Pappas
14
Proper Cable Lugging
Step Four
 Locate tool with correct die in proper position on connector and activate
tool.
 Remember when making multiple crimps, make the first crimp nearest the
tongue and work towards the barrel end.
 When properly crimped, the die code number will be embossed on the
connector for easy inspection to determine if correct die and connector
combination were used.
15
Thank You

More Related Content

What's hot

ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...
ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...
ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...Thorne & Derrick International
 
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...Yamuna Infra & Technology Pvt. Ltd.
 
H07RN-F cables to a few different products
H07RN-F cables to a few different productsH07RN-F cables to a few different products
H07RN-F cables to a few different productsParamlakani
 
Jmv lps ltd wish india very happy independence to all Citizen of India
Jmv lps ltd wish india very happy independence to all Citizen of IndiaJmv lps ltd wish india very happy independence to all Citizen of India
Jmv lps ltd wish india very happy independence to all Citizen of IndiaMahesh Chandra Manav
 
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueThorne & Derrick International
 
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...Gabriel Onyeuka
 
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Mahesh Chandra Manav
 
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo Centre
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo CentrePlz Visit us ELECRAMA 2020 Place Greator Noida Expo Centre
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo CentreMahesh Chandra Manav
 

What's hot (8)

ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...
ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...
ABB Kabeldon - HV High Voltage Cable Joints, Cable Terminations & Separable C...
 
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...
Yamuna Infra & Technology Pvt. Ltd. is a leading manufacturer of Heat Shrinka...
 
H07RN-F cables to a few different products
H07RN-F cables to a few different productsH07RN-F cables to a few different products
H07RN-F cables to a few different products
 
Jmv lps ltd wish india very happy independence to all Citizen of India
Jmv lps ltd wish india very happy independence to all Citizen of IndiaJmv lps ltd wish india very happy independence to all Citizen of India
Jmv lps ltd wish india very happy independence to all Citizen of India
 
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
 
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...
prevention of crevice corrosion in duplex ss flanges using carbon steel bolts...
 
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
 
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo Centre
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo CentrePlz Visit us ELECRAMA 2020 Place Greator Noida Expo Centre
Plz Visit us ELECRAMA 2020 Place Greator Noida Expo Centre
 

Similar to Quality Grounding-The Cell Site

VG Railway S & T wiring check list rev 00
VG  Railway S & T wiring check list rev 00VG  Railway S & T wiring check list rev 00
VG Railway S & T wiring check list rev 00Varadharajalu Gopal
 
Reliability of Copper PTH for High Current Applications
Reliability of Copper PTH for High Current ApplicationsReliability of Copper PTH for High Current Applications
Reliability of Copper PTH for High Current ApplicationsEpec Engineered Technologies
 
Chapter 35
Chapter 35Chapter 35
Chapter 35mcfalltj
 
Soldering and desoldering electronic components
Soldering and desoldering electronic componentsSoldering and desoldering electronic components
Soldering and desoldering electronic componentsG-one Paisones
 
Overview of Temperature Measurement.ppt
Overview of Temperature Measurement.pptOverview of Temperature Measurement.ppt
Overview of Temperature Measurement.pptHarshwardhanPhatak1
 
Structured Ground BICSI Approved
Structured Ground   BICSI ApprovedStructured Ground   BICSI Approved
Structured Ground BICSI ApprovedTim Hurley
 
Hamari metro rail and electrical safety
Hamari metro rail and electrical safetyHamari metro rail and electrical safety
Hamari metro rail and electrical safetyMahesh Chandra Manav
 
Belco Electric Residential
Belco Electric ResidentialBelco Electric Residential
Belco Electric ResidentialGWatts2617
 
Fundamentals of Manual Metal Arc (MMA) Welding
Fundamentals of Manual Metal Arc (MMA) WeldingFundamentals of Manual Metal Arc (MMA) Welding
Fundamentals of Manual Metal Arc (MMA) WeldingThomas Riggleman
 
RTD-RESISTANCE TEMPERATURE DETECTOR
RTD-RESISTANCE TEMPERATURE DETECTORRTD-RESISTANCE TEMPERATURE DETECTOR
RTD-RESISTANCE TEMPERATURE DETECTORkaroline Enoch
 
Brief introduction to server power cords
Brief introduction to server power cordsBrief introduction to server power cords
Brief introduction to server power cordsKerry Zhang
 
QCI_KESCO_SIR005.pdf
QCI_KESCO_SIR005.pdfQCI_KESCO_SIR005.pdf
QCI_KESCO_SIR005.pdfsandeepimsec
 
Coaxial cable installation
Coaxial cable installationCoaxial cable installation
Coaxial cable installationVinod Jadhav
 
Burndy YA6CL3BOX
Burndy YA6CL3BOXBurndy YA6CL3BOX
Burndy YA6CL3BOXsavomir
 
Ground or earthing is word for safety of equpments and human let apply properly
Ground or earthing is word for safety of equpments and human let apply properlyGround or earthing is word for safety of equpments and human let apply properly
Ground or earthing is word for safety of equpments and human let apply properlyMahesh Chandra Manav
 
Epp 0317-4 08 solder less(2)
Epp 0317-4 08 solder less(2)Epp 0317-4 08 solder less(2)
Epp 0317-4 08 solder less(2)AKBAR TRADING
 

Similar to Quality Grounding-The Cell Site (20)

VG Railway S & T wiring check list rev 00
VG  Railway S & T wiring check list rev 00VG  Railway S & T wiring check list rev 00
VG Railway S & T wiring check list rev 00
 
Reliability of Copper PTH for High Current Applications
Reliability of Copper PTH for High Current ApplicationsReliability of Copper PTH for High Current Applications
Reliability of Copper PTH for High Current Applications
 
En and asme welding guide
En and asme welding guideEn and asme welding guide
En and asme welding guide
 
Instalaciones avionicas
Instalaciones avionicasInstalaciones avionicas
Instalaciones avionicas
 
Chapter 35
Chapter 35Chapter 35
Chapter 35
 
Soldering and desoldering electronic components
Soldering and desoldering electronic componentsSoldering and desoldering electronic components
Soldering and desoldering electronic components
 
Overview of Temperature Measurement.ppt
Overview of Temperature Measurement.pptOverview of Temperature Measurement.ppt
Overview of Temperature Measurement.ppt
 
Structured Ground BICSI Approved
Structured Ground   BICSI ApprovedStructured Ground   BICSI Approved
Structured Ground BICSI Approved
 
Hamari metro rail and electrical safety
Hamari metro rail and electrical safetyHamari metro rail and electrical safety
Hamari metro rail and electrical safety
 
Belco Electric Residential
Belco Electric ResidentialBelco Electric Residential
Belco Electric Residential
 
Fundamentals of Manual Metal Arc (MMA) Welding
Fundamentals of Manual Metal Arc (MMA) WeldingFundamentals of Manual Metal Arc (MMA) Welding
Fundamentals of Manual Metal Arc (MMA) Welding
 
RTD-RESISTANCE TEMPERATURE DETECTOR
RTD-RESISTANCE TEMPERATURE DETECTORRTD-RESISTANCE TEMPERATURE DETECTOR
RTD-RESISTANCE TEMPERATURE DETECTOR
 
PCB
PCBPCB
PCB
 
Brief introduction to server power cords
Brief introduction to server power cordsBrief introduction to server power cords
Brief introduction to server power cords
 
The Elektro Tipp - Terminal Connection
The Elektro Tipp - Terminal ConnectionThe Elektro Tipp - Terminal Connection
The Elektro Tipp - Terminal Connection
 
QCI_KESCO_SIR005.pdf
QCI_KESCO_SIR005.pdfQCI_KESCO_SIR005.pdf
QCI_KESCO_SIR005.pdf
 
Coaxial cable installation
Coaxial cable installationCoaxial cable installation
Coaxial cable installation
 
Burndy YA6CL3BOX
Burndy YA6CL3BOXBurndy YA6CL3BOX
Burndy YA6CL3BOX
 
Ground or earthing is word for safety of equpments and human let apply properly
Ground or earthing is word for safety of equpments and human let apply properlyGround or earthing is word for safety of equpments and human let apply properly
Ground or earthing is word for safety of equpments and human let apply properly
 
Epp 0317-4 08 solder less(2)
Epp 0317-4 08 solder less(2)Epp 0317-4 08 solder less(2)
Epp 0317-4 08 solder less(2)
 

Quality Grounding-The Cell Site

  • 1. 1 Quality Grounding The Cell Site A Brief Overview Developed by Ted J. Pappas
  • 2. 2 National Electric Code (NEC) National Fire Protection Association (NFPA 70) The NEC is a regionally adoptable standard for the safe installation of electrical wiring and equipment in the United States. The NEC, while having no legally binding regulation as written, can be and often is adopted by states, municipalities and cities in an effort to standardize their enforcement of safe electrical practices within their respective jurisdiction. The Law………. In some cases, the NEC is amended, altered and may even be rejected in lieu of regional regulations as voted on by the governing bodies of any given locale. “Code Compliance” Ted J. Pappas
  • 3. 3 A Ground, or Earth, is the reference point in an electrical circuit from which voltages are measured and is a common return path for electric current as well as a direct physical connection to the Earth. What is a GROUND? Effects of a poor ground connection  Indictors (alarms) not operating properly  Motor issues  Cooling fans not turning to speed resulting in improper design cooling  Increased power consumption on site Electrical shock Hazard-----Death Ted J. Pappas
  • 4. 4 Ground Rings • The ring ground will usually encircle the entire cell site / building that it is trying to protect. • The ring ground is used as the base of the entire cell site’s / building's ground system, and all components of the building's ground system, including the cell site / building structure, are connected to the ground ring. • The National Electrical Code specifies that ring grounds must be constructed from #2 or thicker wire, must be buried at least 2 1/2 feet underground, and must have at least 20 feet of exposed copper to ensure good electrical contact with the earth Ted J. Pappas
  • 5. 5 Halo Grounds • A halo ground is a type of ring ground that, instead of being installed outside and underground, is installed inside, near the top of a building or structure. • The ground reference for all equipment inside the area being protected is separate from the halo. The halo is connected to the main building ground, which may include an underground ring ground outside the building, with vertical conductors especially in the corners of the building. • The halo may be connected to structural metallic elements such as door frames, building steel, window frames, and air conditioning vents. • A typical halo ground is constructed of #2 insulated copper wire and is installed six inches below the ceiling, and entirely encircles the area that it is protecting. Ted J. Pappas
  • 6. 6  Exothermic Welding is known by several naming conventions such as CADWELD , Exothermic bonding, and thermite welding (TW).  It is a welding process for joining materials that employs molten metal to permanently join the conductors.  The process employs an exothermic reaction of a thermite composition to heat the metal, and requires no external source of heat or current. Exothermic Welding CADWELD is a Registered Trademark The Graphite Mold Ted J. Pappas
  • 7. 7 Do I Have The Correct Exothermic Mold? Inspect the mold ID tag to ensure that it corresponds to the application, indicated by the: 1. mold part number 2. conductor size 3. welding material required 4. other materials required The mold must be correct for the conductor size and application. DO NOT MODIFY MOLDS. Ted J. Pappas
  • 8. 8 Cold Welds, also know as “Correct Compaction” or the Number of Crimps, are required to prevent overheating and joint failure. The FIRST crimp for lugs requiring multiple crimps MUST be applied at the “Palm” end of the lug working towards the end of the Barrel. As it is crimped the barrel lengthens and is known as Cold Flow. On a lug that requires only one (1) crimp the die is centered on the Barrel Cold Welds and Lugs Incorrect Compaction also can result in “shiners” Ted J. Pappas
  • 9. 9 Under and Over Crimping The cut cross-section of a properly crimped lug to the left illustrates that all the “Air Voids” have been removed to form one (1) Mass of Material. Correct Compaction The cut cross-section of an Over Crimped lug, also known as Winging or Flashing, is illustrated to the left. The common cause of this problem is using a “Die” that is too small The resultant is overheating and terminal equipment failure (under crimping also has the same resultant) Ted J. Pappas
  • 10. 10 An Accurate Crimp? The ONLY way to truly identify whether a crimp is accurate is to employ a Vernier Caliper The measurement is done across the Flats of the Hexagonal Crimp Note---If the measurement does not match the requirement when employing the correct Die---the crimper may require calibration Ted J. Pappas
  • 11. 11 Proper Cable Lugging Step One Strip the Insulation carefully not to nick of cut conductors. Ensure the exact amount of insulator material is striped based upon the Lug being employed Note a depth gauge tool may be employed Ted J. Pappas
  • 12. 12 Proper Cable Lugging Step Two Determine the proper Color- Keyed Connector for the cable size being used. • Connectors marked with just cable size or CU should be used on copper conductors only. • Connectors marked “AL9”* with the cable size should be used on aluminum conductors only. • Connectors marked “AL9CU” with the cable size may be used on the aluminum or copper conductors
  • 13. 13 Proper Cable Lugging Step Three Select the proper installation die and appropriate tool  Connectors have colored bands or colored dots that correspond to color markings on the dies.  Connectors and dies also have a die code number marked or stamped on them. Dies have a code number engraved in the crimp surface. Ted J. Pappas
  • 14. 14 Proper Cable Lugging Step Four  Locate tool with correct die in proper position on connector and activate tool.  Remember when making multiple crimps, make the first crimp nearest the tongue and work towards the barrel end.  When properly crimped, the die code number will be embossed on the connector for easy inspection to determine if correct die and connector combination were used.