1. START PERMISSIVE
August 9, 2015 1
Boiler Feed Pump:
Boiler feed pump suction valve open Feed
Back
Dearator level Normal.
Recirculation Line valve open feed back
2. Condensate Extraction pump:
Pump Feeder Healthy .
No pump trip signal.
Level greater than set point.
August 9, 2015 2
3. ID FANS:
ID Fan O/L Damper close feed back .
ID Fan I/L Damper close feed back.
Guillotine damper open.
ID Fan MCC no trouble.
August 9, 2015 3
4. Boiler trip:
SH#1 Metal temperature Hi-Hi.
SH#2 Metal temperature Hi-Hi.
Drum level less than Low-Low.
Drum Level Greater than Hi-Hi.
Both ID fan Trip/ Stop feedback.
TRIP CONDITION
August 9, 2015 4
5. Turbine trip:
Main steam temperature Low-Low( 480 °c).
Temp. of Turbine thrust pads & bearing liners
Hi-Hi (100 ° C), common.
Return Oil temp. of bearing Hi-Hi (70 °C),
common.
Condenser pressure Hi-Hi(-0.4 kg/cm²).
Main steam pressure Low-Low (60.95 kg/cm²).
Hot well Level Low-Low (20%).
Lube oil pressure Low-Low ((0.3 kg/cm²).
August 9, 2015 5
8. Generator Trip:
Differential Protection (5%).
Generator Rotor Earth Protection(1 stage-
alarm/2nd
stage- trip).
Stator Frame Temperature Operated (80 °c
alarm /100°c trip)
Emergency Trip Push Button Operated .
Reverse Power Protection (0.5%) .
Generator Winding Temperature Operated
(100°C –alarm/110 °C trip).
Backup Impedence Protection.
Incase of air cooler tube leakage.?
August 9, 2015 8
9. Turbine Trip Solenoid:
Low forward power Protection (05%).
Loss of Excitation Protection.
Under voltage protection (Drop out 70%)
Gen. over current protection with time delay
unit (105%, 10 sec.)
PT fuse failure relay (Met-A, Port- Gen. Ckt
closed).
Gen. negative phase sequency protection
(1st=7.5%,
-Alarm , 12t= 10- Trip) .
August 9, 2015 9
10. Over / under frequency port ( 1st
=2 sec-Alarm,
2nd
=2 sec-Trip.
All devices connected for Turbine.
Gen. over current voltage restraint port.
Gen. over voltage protection (105%=0.3 sec.-
Alarm, 110%=2 sec.- Trip.
Under voltage protection (80%= 3 sec- Trip.).
August 9, 2015 10
11. TIE CIRCUIT BREAKER TRIP:
Over /under Frequency (1st
- Alarm+ Trip)
Negative Phase sequence ( 1st
- Alarm+ Trip).
Over voltage / under voltage protection (1st
-
Alarm+ Trip).
Vector surge protection (1st
- Alarm + Trip).
August 9, 2015 11