SlideShare a Scribd company logo
1 of 48
Download to read offline
PRODUCT SELECTION GUIDE
PerfectSense
®
Intelligent Building Occupancy Sensors
BENEFITS OF PERFECTSENSE
Whether the goal is cost and time-saving installation, building energy efficiency,
certification to national energy code regulation, retrofitting, flexibility, or building
automation, NexLight’s PerfectSense Intelligent Building Occupancy Sensors
meets any application need.
EASY TO DESIGN
Either installed to work independently, or connected to work with a building
network lighting control system, PerfectSense products offer many ways to control
area lighting.
EASY TO INSTALL
All PerfectSense products come with easy to understand installation instructions
and wiring guides to quickly complete the line and low voltage connections. Intelli-
gent out of the box presets provide accurate sensing and detection sensitivities for
most applications, making the installation process even faster.
EASY ENERGY SAVINGS
Cost-effectively save 20-80% of area lighting costs by installing occupancy sensors
throughout a facility. Perhaps the most cost effective controls strategy, occupancy
sensors begin saving energy the day they are installed.
EASY CODE COMPLIANCE
Meet and exceed today’s stringent energy codes and performance requirements
such as ASHRAE 90.1 2010, IECC 2012 and California Title 24 quickly and easily.
EASY SAFETY & SATISFACTION
PerfectSense employs the latest sensing technologies and manufacturing methods
to provide customers with a superior performing product. Backed by a 5-year
limited warranty all products are designed to provide a solution which increases
energy savings while delivering occupant satisfaction.
EASY TO RETROFIT
All PerfectSense products work with every standard commercial lighting load type
from all lighting manufacturers, enabling you to bring savings to every building
application.
VALUABLE TO:
BUILDING PROFESSIONALS, ARCHITECTS, SPECIFIERS, SYSTEM INTEGRATORS, ENGINEERS, AND INSTALLERS.
Flexibility, simplicity, code compliant, environmentally friendly.
BUILDING OWNERS, FACILITY MANAGERS AND PRIVATE CONSUMERS.
Energy savings, cost benefits, flexibility and comfort, simplicity, security.
1
2
PRODUCT SELECTION MATRIX
Model # Pages
Operating
Voltage Description Typical Applications
PS-PWS1277W 11 120/277 PIR Wall Switch 1-Button
Small o ces, small and medium conference rooms,
utility / storage rooms
PS-PWD1277W 11 120/277 PIR Wall Switch 2-Button
Small o ces, small and medium conference rooms,
lunch/ breakrooms, utility / storage rooms
PS-UWS1277W 13 120/277 Ultrasonic Wall Switch 1-Button
Individual restrooms, two-stall restrooms, utility /
storage rooms
PS-UWD1277W 13 120/277 Ultrasonic Wall Switch 2-Button
Individual restrooms, two-stall restrooms, utility /
storage rooms
PS-DWS1277W 15 120/277 Dual Tech Wall Switch 1-Button
Small and executive o ces, small and medium
conference rooms, lunch break rooms
PS-DWD1277W 15 120/277 Dual Tech Wall Switch 2-Button
Small and executive o ces, small and medium
conference rooms, lunch break rooms
PIR
PS-CPS1000 17 24 1000 sq. ft PIR w/ Relay
Small o ces, copy rooms, break rooms, library book
stacks, aisleways, small classrooms
PS-CUS800 19 24 1000 sq. ft 180° view w/ Relay
Open o ces, restrooms, conference rooms,
hallways, end of aisle
PS-CUS2000 21 24 2000 sq. ft w/ Relay
Open o ces, restrooms, conference rooms, large
o ces, hallways
PS-DTC24 23 24 1000 sq. ft
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
PS-DTC24-R 25 24 1000 sq. ft w/ Relay
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
PS-CDS800 27 24 1000 sq. ft 180° view w/ Relay
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
PS-CDS2000 29 24 2000 sq. ft w/ Relay
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
PIR
PS-WPS1500 31 24 Multi-Lens PIR w/ Relay
O ces, classrooms, hallways, warehouses, aisleways,
conference rooms
Ultrasonic
PS-WUS1500 33 24 Ultrasonic w/ Relay
Open o ces, classrooms, restrooms, conference
rooms, large o ces
DualTech
PS-WDS1500 35 24 Dual Tech w/ Relay
Classrooms, conference rooms, training rooms, large
o ces, computer rooms
PS-PP1277 37 120/277 Basic Power Pack Auto On, Auto O
PS-SP24 39 120/277 Auxiliary Power Pack Allows for added loads
PS-PP7000X 41 120/277 Heavy Duty Power Pack
Auto On, Auto O , Manual On, Light Hold On, Light
Hold O
Power Packs Page 37-42
UltrasonicDualTech
Wall Mount Occupancy Sensors Page 31-36
Wall Switch Occupancy Sensors Page 11-18
PIRUltrasonicDualTech
Ceiling Mount Occupancy Sensors Page17-30
Low Voltage Switches Page 43-44
PS-LVSX 43 24 Low Voltage Series of Switches Manual On / Off control in any location
Common Stand Alone Control Strategies Page 45
General Information and Product Design Guide Page 3-10
WallSwitch Occupancy Sensors Page17-30
ENERGY SAVINGS
Occupancy sensors deliver maximum energy savings,
exceeding the savings provided by other control solutions
(i.e. scheduling), by ensuring that lighting is only on when
people are present. NexLight, the world’s top producer of
design built and easy to use lighting control systems,
continues its mission by providing new sensors that save
energy and assist in achieving additional design goals.
EFFICIENCY INCENTIVES
The use of occupancy sensors can assist building owners in
earning Corporate Tax Incentives including credits, deduc-
tions, exemptions and rebates based on the equipment
installed. To qualify, a building must meet or exceed the
energy performance required. Visit www.dsireusa.org for
more information and updates for your local area.
SUSTAINABLE BUILDINGS
By designing beyond the requirements of codes, design
teams can provide even greater energy savings and work
toward sustainable building practices. LEED certification
points are awarded with correct application and use of
sensors. The result is another way of providing the commu-
nity with green and energy efficient buildings.
ENERGY CODE COMPLIANCE
PerfectSense products provide convenient code compliant
Automatic-ON or Manual-ON control and are full of innova-
tive features. Our sensors use Passive Infrared (PIR),
Ultrasonic, and a combination of the two, commonly
referred to as Dual-Technology. Both Automatic-ON and
Manual-ON sensors meet the Automatic-OFF requirement
of all major energy codes, including ASHRAE 90.1 (2007 and
earlier), IECC and California’s Title 24.
ASHRAE 90.1-2010 is now including the requirement for
many spaces to be Manual-ON. A space may use
Automatic-ON control, however the Automatic-ON func-
tion cannot turn on more than 50% of the space lighting.
Whichever method your space requires, PerfectSense
offers a complete selection of compliant solutions.
AUTOMATIC-ON + BI-LEVEL CONTROL
Bi-level switching has the potential to save energy by
enabling occupants to use just as much lighting as they
want, and is a requirement by EPAct, California’s Title 24
and ASHRAE 90.1 2010. Bi-level Auto-on control is when
one zone is turned on automatically (by the sensor) and the
other zone must be turned on manually (local switch).
This method of control has been shown to use 52% less
energy* than Automatic-on only. Additionally, many occu-
pants are comfortable working in lower lighting levels. The
result are dramatic energy savings and enhancing occu-
pant comfort. (*BasedonCaliforniaLightingTechnologyCenterresearch2009.)
AUTO-ON TO 50% EXAMPLE
ENERGY CONSERVATION
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0
Classroom Conference
Room
Private Restroom Storage
Actual Energy Savings By Application
20-80%EnergySavings*
(*Sources:U.S.EPA,LightingResearchCenter&CaliforniaEnergyCommissionpublications)
Office
3
PerfectSense gives engineers and facility managers more control
options than ever before, offering sensors that are the best fit for
any application. Sensors featuring Passive Infrared, Ultrasonic or
Dual Technology are ideally suited for different applications. Let’s
take a closer look at each type.
PASSIVE INFRARED
Passive Infrared (PIR) technology detects occupancy in the space
by sensing the difference between temperatures of a human body
in motion and the background space. Requiring a line of sight for
detection, PIR sensors feature accurate area coverage cut-offs.
ULTRASONIC
Ultrasonic (US) technology operates by transmitting an ultrasonic
sound wave into the space and measuring the speed at which they
return back to the sensor. Occupant movements change the
frequency of the waves. This means ultrasonic sensors can detect
movement around partitions or indirect line of sight.
DUAL TECHNOLOGY
Dual Technology operates by combining PIR and ultrasonic detec-
tion into a single device. This technology increases the accuracy of
detection while decreasing the potential of false ON or false OFF
triggers.
SENSOR TECHNOLOGIES
DUAL TECHNOLOGY
BEST APPLICATIONS:
+ Classrooms
+ Large conference rooms
+ Large offices
+ Lecture halls
+ Cafeterias
ULTRASONIC BEST
APPLICATIONS:
+ Restrooms
+ Open office spaces
+ Enclosed hallways
+ Stairways
PIR BEST APPLICATIONS:
+ Small offices
+ Warehouses
+ High ceiling locations
+ Library book stacks/aisles
+ Lobby / common areas
+ Computer rooms
4
APPLICATION EXAMPLES
Large conference rooms require detection that will account for
occupants that may be still for long periods of time. Dual technol-
ogy sensors will be able to detect minor motion to keep lights on
as long as the space is occupied.
Copy rooms, IT rooms, and janitor’s closets are ideal for occu-
pancy based controls. With a wall or switch mounted PIR sensor,
lights can be shut off just minutes after the occupant leaves
saving hours of wasted lighting energy each day.
Classrooms large and small require the ability to detect minor
motion. Ceiling mounted dual technology sensor models are
preferred to get complete room detection. In larger rooms a
second sensor and power pack could be added for multizone
control.
In private offices, use a PIR or dual tech sensor depending on
room layout and field of view. Take advantage of the integrated
light level feature to keep lights off when sufficient daylight is
present.
Lighting in restrooms is best controlled with ultrasonic sensors to
eliminate hundreds or even thousands of hours of unneeded
on-time during a year. A ceiling-mounted ultrasonic senses
motion around restroom stalls for greater coverage area.
For the open or partitioned office spaces, either the dual tech or
ultrasonic type may be appropriate. Wall mounted or on the
ceiling, expand coverage of large spaces by linking multiple
sensors together to control lighting in a coordinated way. Use
these sensors to cover the area in zones with 10-20% overlap as
illustrated above.
PRIVATE OFFICES CONFERENCE ROOMS
5
REST ROOMS CLOSETS / STORAGE
OPEN OFFICES
CLASSROOMS
Understanding daily space usage patterns are essential to
properly apply occupancy sensing in a commercial building
space. If you are able to answer “YES” to some of the following
questions, adding occupancy sensors are a viable control
option.
+ Are there periods of time when the space is unoccupied?
+ Is energy wasted due to lights being left on when no one is
in the space?
+ Are lights left on after business hours?
+ Is the space used only intermittently?
+ Could some or all area lights be turned off during the day?
DESIGNING WITH OCCUPANCY SENSORS
4 STEP DESIGN PROCESS
Evaluate Space
Needs
Match with Best
Technology
Layout & Specify
Install &
Con gure
“Are Occupancy Sensors The Correct Control Strategy For Your Space?”
1. EVALUATE SPACE NEEDS
The following space characteristics are of particular
importance because of the influence they have when
making a sensor selection:
+ Room / Space dimensions and shape
+ Location of main occupant activity
+ Location of walls, doors, windows and drapes
+ Location of desks / workspaces and orientation with
regard to walls and partitions
+ Ceiling heights, partition heights and locations
+ Location of file cabinets, large furniture, large
equipment or shelves
+ Large objects that could block or alter a sensor
coverage area
+ Available daylight for added light level sensing
+ Make note of high levels of air flow or vibrations
noting the location of HVAC ducts and fans
PerfectSense
®
6
2. MATCH SENSING TECHNOLOGY
Tip: Choose the sensing technology that best meets space needs and characteristics
Location
Passive
Infrared (PIR)
Ultrasonic
Dual
Technology
Sensor Type
Classroom X C
Hallway X C
Private O ce X X C,WS
Conference Room X X C,WS
Open O ces X X C,WM
Lecture Hall X C,WM
Library X C
Rest Room X X C,WS
Lobby X X C,WM,WS
Storage X X C,WM,WS
Warehouse X WS
Closet X X WS
Cafeteria X X C
Coverage Type
Acceptable Application
Qualities
Unacceptable Application
Qualities
Wall Switches
Line of sight with
clear cuto
smaller enclosed spaces
Very low motion levels by
occupants or obstacles
blocking sensor view
Ceiling / Wall
Sensors
Line of sight with
clear cuto
spaces where a sensor has
a view of activity
Very low motion levels by
occupants or obstacles
blocking sensor view
Wall Switches No clear cuto smaller enclosed spaces High level of air ow
Ceiling / Wall
Sensors
Volumetric in space
with no clear cuto
open spaces, and spaces
with obstacles
High ceilings and high levels
of vibration or air ow
Wall Switches Complete Coverage
spaces with low or variable
motion levels by occupants
High level of air ow
Ceiling / Wall
Sensors
Complete Coverage
spaces with low or variable
motion levels by occupants
High level of air ow
PIRUltrasonicDualTech
Occupancy Sensor Technology Selection Matrix
Technology /
Product Type
Common Locations
TIP: Use this reference list to identify the commonly used products for your applications
7
C= Ceiling Mount
WM= Wall Mount
WS= Wall Switch
X
3. LAYOUT & SPECIFICATION
COVERAGE PATTERNS
Once the technology is chosen, the next step is to select
the correct coverage size and shape. A typical design
guideline will call for a minimum of 90% coverage area of
the square footage in a room. Each product cut sheet
includes specific coverage area specifications.
It’s important to know the typical use of space. Will occu-
pants be engaged in major motions (walking, using a
forklift) or minor motion (reading, typing). Coverage
changes depending on motion type.
NEMA TESTING
PerfectSense understands the importance in producing
the highest quality products. When it comes to occupancy
sensors, that means producing sensors with consistent
detection while reducing False Triggers. All PerfectSense
products are designed to meet and exceed the quality and
consistency standards set forth in the National Electrical
Manufacturers Association guide publication. The NEMA
guide establishes two testing parameters as major and
minor motion detection. It defines minor motion as the
movement of a person sitting at a desk reaching for a
telephone, turning the pages of a book, opening a file
folder, or picking up a coffee cup. Major motion is defined
as the movement of a person walking in or through a
space.
CHOOSE POWER PACKS
Power packs are a necessary component providing
three core purposes to most occupancy sensor projects.
Power packs provide power to low voltage sensors and
other control devices, respond to signals from those
devices and switch their internal relays to control the
connected loads.
Power packs can also provide advanced features such as
switch inputs, inputs for scheduling, and dimming
control. Before selecting a power pack, consider the
following factors.
Voltage: Pay attention to the input ratings of each
power pack model.
Low voltage output needs: Typically listed in (mA) be
sure the power pack provides enough current to power
all of the connected devices for that zone.
Relay ratings: Power Packs have specific ratings for
different load types (i.e., incandescent, fluorescent,
motor). Make sure the relay is rated for the type of load
to be controlled and the load being switched does not
exceed the load rating of the power pack.
To protect against the potentially damaging effects of
high inrush current common in newer electronic
ballasts, select power packs with zero crossing circuitry
technology.
Feature Bene t
Isolated Relay Enables interfacing with facility HVAC, BMS or monitoring systems
Light Level Sensing Increased energy savings in areas with signi cant natural light
Terminal Wiring Simpli ed installation
Manual-ON/Auto-ON Options to meet code and maximize energy savings in di erent applications
Dual Relays Enables bi-level switching for increased energy savings and code compliance
Zero Crossing Reduces stress on sensor relays and increases sensor life
LED Operation LED indicators will ash when motion is detected with each technology
Low Voltage Flexibility for installation location and wiring
Line Voltage No need for power pack device
Adaptive Technology Monitors activity patterns over time to auto adjust o time for maximized energy savings
Walk-Through Mode Additional energy savings by turning lights o after brief occupancy
Alerts Audible warning of impending shuto
Multi-way Capability Facilitates control in spaces with multiple entrances
Lamp Saver For bi-level lighting: alternates the load that turns on each time the lights turn on.
Test Mode Temporary setting used to test coverage area typically expires after 15 minutes
Common Features
TIP: Use this reference list to identify the desired features for your applications
DESIGNING WITH OCCUPANCY SENSORS
Note: not all sensors contain all features, refer to specification for complete details
8
4. INSTALL & CONFIGURE
INSTALL THE SENSOR
During installation contractors should position the sensor
so it has the best view of the entire coverage area, while
minimizing the possibility of false ON and OFF triggers.
Wire sensors according to instructions. This will eliminate
any functional problems or sensor damage. If necessary,
adjust sensor settings such as the sensitivity, time delay or
daylight sensing to match the activity levels of the space
being controlled.
Be sure to increase the off time delay setting for spaces
where minor motion and limited activity will be taking
place to further reduce the risk of false offs. For increased
energy efficiency shorten off time delay settings especially
for areas of high traffic. For restrooms, stairwells or areas
with limited or no natural lighting use caution and set
longer off time delays to ensure occupant safety and secu-
rity.
MOUNTING SENSORS
PerfectSense products fall into three categories of
mounting: Ceiling, Wall, and Wall Switch types. Only
wall mount types may be mounted on both the wall
or the ceiling. This is important for applications where
one of the surfaces may be unsuitable for sensor
installation.
MOUNTING POWERPACKS
Power packs are often mounted to the outside of a
junction box, placing them in the plenum space, so
make sure the power pack is plenum rated. Smaller
power packs can be installed inside a standard junc-
tion box.
WIRING POWERPACKS
Intelligent power packs provide inputs so that multiple
control devices can be connected. This enables customiza-
tion of control scenarios for different applications and end
user preferences. Use intelligent power packs when
multi-device, manual switching, and dimming applica-
tions are desired.
PHOTOCELL CONTROLS
Most occupancy sensors include an integrated daylight
sensor to be used in building spaces that receive daylight.
This function is designed to ensure the occupancy sensors
will keep lights off in occupied spaces, when the natural
daylight coming into the space exceeds the set threshold.
If a space has inadequate natural daylight the occupancy
sensor will turn lighting on.
PROGRAMMING AND TESTING
Make post-installation adjustment as needed. This is not
uncommon and is often due to last minute changes in
placement of furniture or fixtures. A walk test of the detec-
tion area is a common method of ensuring the sensor is
located and configured properly for the space.
TIP: Double check
specified sensor
location prior
to installation
TIP: Wire according
to instructions for
proper power pack
and sensor function
9
DESIGNING WITH OCCUPANCY SENSORS
10
INTEGRATING SENSORS WITH CONTROLS
Occupancy sensors that operate independently in a space,
are referred to as “stand alone” sensors providing no infor-
mation of occupancy status to other building systems. To
increase control and energy savings, PerfectSense low
voltage occupancy sensors include isolated Form C relays
to seamlessly integrate with Building Management
Systems (BMS), HVAC (VAV controllers) or NexLight 2-Wire
Lighting Controls Systems. These relays providing real
time occupancy status “intelligence” to other systems,
adding signifcantly to a building wide control strategy and
potential savings. PerfectSense has the industries only
sensor with multiple relay outputs for greater connectivity
to building controls.
MULTILAYERED CONTROL STRATEGY
For the next level of efficiency, consider combining occu-
pancy sensors with other controls such as lighting control
panels or daylight harvesting controls. A multilayered
control strategy can assist in meeting energy codes and
green sustainability guidelines as well as provide maxi-
mized energy savings.
The images below illustrate an example of how a low
voltage sensor could be networked to a building BMS or
2-Wire lighting control system.
See page 45 for Stand-Alone Control Scenarios.
PerfectSense
®
Room Control with
Manual-On + BMS Status
Networked Room
Control with Manual-On
Extreme Reliability
TM
Lighting Control Systems
Your Source for Design Built Systems
PANELS | SWITCHES | SENSORS
NexLight 2-Wire Networked
Lighting Control System
STAND ALONE VS. NETWORKED SYSTEMS
E FA
Line Voltage Class 1 Low Voltage Class 2
(16awg 3-wire)
Low Voltage Class 2
(16awg 2-wire)
WIRING KEY
A
E
A
F
Power Pack
Ceiling Sensor
1-Button
Low Voltage Switch
2-Wire Panel
2-Wire Switch
CBA
Line Voltage Class 1 Low Voltage Class 2
(16awg 4-wire*)
Low Voltage Class 2
(NexLight 2-wire Bus)
WIRING KEY
A
C A
A
B
Occupancy / Vacancy
Sensor
* for 50%on/all off commands add one additional wire
A
To CPU
or Panel
To CPU
or Panel
to BMS or HVAC
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PWS1277 | PS-PWD1277
Commercial Grade Occupancy Sensor
Passive Infrared (PIR) | Wall Switch | Line Voltage
Specifications
Coverage Area: 1000 sq. ft.
Input: 120–277Vac +/-10% 50/60Hz
Output: 120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0% to 90% RH non-condensing
Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
Compliances: UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
Light level Adjustment: 0.5 to 250 footcandles (FC)
Detection: 180° passive infrared (PIR)
Audible alert: Selectable
Service Switch: OFF/Auto/ON
Manual operation: Pushbutton ON/OFF
Lens: Impact resistant
Relay Switching: 0° +/- 500uS
Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
PS-PWS1277W
PS-PWD1277W
Overview
•
•
•
•
•
•
•
•
The Commercial Grade PIR Wall Switch Occupancy Sensor provides automatic control
of loads by detecting motion and ambient light within the detection area.
Sensor features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF.
180° motion detection using passive infrared (PIR) technology.
Superior lens design to provide high resolution for detecting major and
minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbuttons for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON).
Audible alert 10 seconds before sensor turns loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level
lighting applications (2 Circuit model only).
•
•
11 Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Detection Range and Coverage Area
Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PS - P W S 1277 X
Technology
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
Mounting
W= Wall Switch
Power
1277= Line Voltage
Color
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
Circuits
S= Single (1)
D= Dual (2)
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
12
Wiring Diagram- 1 Circuit Order Information- Wall Switch Series
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-UWS1277 | PS-UWD1277
Commercial Grade Occupancy Sensor
Ultrasonic Technology | Wall Switch | Line Voltage
Overview
•
•
•
•
•
•
•
•
Specifications
Coverage Area: 500 sq. ft.
Input: 120–277Vac +/-10% 50/60Hz
Output: 120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0% to 90% RH non-condensing
Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
Compliances: UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
Light level Adjustment: 0.5 to 250 footcandles (FC)
Detection: 180° ultrasonic (US)
Audible alert: Selectable
Service Switch: OFF/Auto/ON
Manual operation: Pushbutton ON/OFF
Lens: Impact resistant
Ultrasonic Transducer: 40kHz
Relay Switching: 0° +/- 500uS
Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
PS-UWS1277W
PS-UWD1277W
The Ultrasonic Wall Switch Occupancy Sensor provides automatic control of
lighting by detecting motion and ambient light within the detection area. Sensor
features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF
180° motion detection using ultrasonic (US) technology.
Superior ultrasonic transducers provide high resolution for detecting major and
minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbutton for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy
savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns
loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting
applications (2 Circuit model only).
•
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.156813
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Detection Range and Coverage Area
Wiring Diagram- 1 Circuit Order Information- Wall Switch Series
PS - U W S 1277 X
Technology
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
Mounting
W= Wall Switch
Power
1277= Line Voltage
Color
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
Circuits
S= Single (1)
D= Dual (2)
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
Both models provide major motion detection up to 500 sq. ft., and minor motion detection up to 300 sq. ft.
14
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-DWS1277 | PS-DWD1277
Commercial Grade Occupancy Sensor
Dual Technology | Wall Switch | Line Voltage
Overview
•
•
•
•
•
•
•
•
Specifications
Coverage Area: 1000 sq. ft.
Input: 120–277Vac +/-10% 50/60Hz
Output: 120Vac
- 1000W max. tungsten incandescent load
- 1000VA max. ballast load
- 1/4 hp max. motor load
- No minimum load required
277Vac
- 1800 VA max. ballast load
- No minimum load required
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0% to 90% RH non-condensing
Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes
Test mode: 15 seconds
Walk through mode: 2 minutes if no activity is
detected after 30 seconds
Compliances: UL and cUL Listed
Title 24 Compliant
FCC part 15 (Class B)
Light level Adjustment: 0.5 to 250 footcandles (FC)
Detection: 180° passive infrared (PIR)
Audible alert: Selectable
Service Switch: OFF/Auto/ON
Manual operation: Pushbutton ON/OFF
Lens: Impact resistant
Ultrasonic Transducer: 40kHz
Relay Switching: 0° +/- 500uS
Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in.
(104 x 44 x 49mm)
PS-DWS1277W
PS-DWD1277W
The Dual Technology Wall Switch Occupancy Sensor provides automatic control
of lighting by detecting motion and ambient light within the detection area.
Sensor features include:
One or Two separate relay circuits for independently switching loads
(typically lighting loads) ON or OFF
180° motion detection using passive infrared (PIR) and ultrasonic technology.
Superior lens design and ultrasonic transducers to provide high resolution for
detecting major and minor motion.
Advanced logic enhances energy savings and user convenience.
Convenient pushbutton for manual control.
Automatic adaptive technology adjusts the time delay for maximum energy
savings.
Automatic 15 second test mode.
Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns
loads OFF.
Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting
applications (2 Circuit model only).
•
15
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
Detection Range and Coverage Area
Wiring Diagram- 1 Circuit Order Information- Wall Switch Series
PS - D W S 1277 X
Technology
D= Dual Tech
U= Ultrasonic
P= Passive Infrared (PIR)
Mounting
W= Wall Switch
Power
1277= Line Voltage
Color
W= White
I= Ivory
L= Light Almond
G= Gray
B= Black
Circuits
S= Single (1)
D= Dual (2)
Wiring Diagrams- 2 Circuits
Color Reference:
BK = Black
GN = Green
R = Red
BL = Blue
BR = Brown
Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft.
16
Specifications
Features
Overview
PS-CPS1000
Standard Range 360˚ Sensor
PIR Detection | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 21mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
Passive Infrared Sensitivity: 600-1000 sq. ft
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
The Ceiling-mounted Passive Infrared (PIR) Occupancy
Sensor accurately detects occupancy and automatically
switches lighting on and off as needed.
This low profile sensor is ceiling mounted for superior
motion detection. With a 360 degree field of view and up
to 1000 square feet of coverage area, the Ceiling-mounted
PIR Occupancy Sensor is ideal for offices, conference rooms
and hallways.
Ceiling-mount sensors also incorporate an integral light
level sensor to prevent lighting from switching On when
sufficient ambient light is present, such as is commonly
found in windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjust-
ments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security
and HVAC systems.
• 1000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• Red LED motion indicator blinks to indicate motion
detection
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
PerfectSense
®
Intelligent Building Occupancy Sensors
17
Wiring Diagrams
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor PS-CUS800 40kHz 180˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
PIR Sensor Field of View
Detection Range and Coverage Area
Ordering Information
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
SENSOR
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
GREEN(N.C.)
YELLOW
(COMMON)
ORANGE(N.O)
18
Specifications
Features
Overview
PS-CUS800
Standard Range 180˚ Sensor
Ultrasonic Technology | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
Passive Infrared Sensitivity: 600-1000 sq. ft
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
The 180 Degree Ceiling-Mounted Occupancy Sensors
are ideal for use in business and office settings to
accurately detect occupancy and automatically control
lighting.
The ceiling-mount design of these low-profile sensors
allows the greatest possible motion sensitivity. An
adjustment panel is conveniently located on the front of
the sensor, providing ready access to setting controls
after the sensor is installed.
These occupancy sensors are available in the ultrasonic
and dual technology models. The dual technology
model employs passive infrared (PIR) and ultrasonic
technology.
Installation and configuration is simple. The sensor
readily mounts to drop ceilings and features front
located adjustments for setting sensitivity and time
delay. Features an isolated relay for use with building
automation, security and HVAC systems.
• 1000 sq. ft. coverage area
• 180° degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
•LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
PerfectSense
®
Intelligent Building Occupancy Sensors
19
Detection Range and Coverage Area
Ordering Information
Ultrasonic Sensor Field of View
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor PS-CUS800 40kHz 180˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
SENSOR
GREEN(N.C.)
YELLOW
(COMMON)
ORANGE(N.O)
20
Wiring Diagrams
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 34mA Nominal (125mA max)
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.25 in
PerfectSense
®
Intelligent Building Occupancy Sensors
The Ceiling-mounted Ultrasonic Occupancy Sensor
accurately detects occupancy and automatically switches
lighting on and off as needed.
This low profile sensor is ceiling mounted for superior motion
detection. With a 360 degree field of view and up to 2000
square feet of coverage area, the Ceiling-mounted Ultrasonic
Occupancy Sensor is ideal for storage rooms, bathrooms,
conference rooms, classrooms, hallways, and open office
areas.
Ceiling-mount sensors also incorporate an integral light level
sensor to prevent lighting from switching On when sufficient
ambient light is present, such as is commonly found in
windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjust-
ments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security and
HVAC systems.
• 2000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15 seconds
to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• Red LED motion indicator blinks to indicate motion detec-
tion
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
21
Specifications
Features
Overview
PS-CUS2000
Standard Range 360˚ Sensor
Ultrasonic Detection | Ceiling Mount | Low Voltage
Wiring Diagrams
Detection Range and Coverage Area
Ordering Information
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Field of View (Top)
SENSOR
22
PS-DTC24
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Specifications
Features
360˚ Coverage Pattern
100% Digital Multiview
TM
PIR
Dual technology uses PIR + U/S
Superior RF immunity
Adjustable Time Delay (30 sec-30 min)
Single Technology Mode
SmartSense
TM
Adapt Mode
Walk Through Mode
Daylight Override Mode
Simple Test Mode
Mounts in drop ceilings and solid ceilings
LED’s provide indication of occupancy sensing
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Output: 24VDC active high logic control signal
with short circuit protection
Wiring Diagram: See Fig. 2
Controls:
Passive Infrared Sensitivity: 0-100% (Factory Set 50%)
Ultrasonic Sensitivity: 0-100% (Factory Set 50%)
Light Sensor: 20-320 LUX (Factory Disables)
Detection Range: See Fig. 1
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 14ºF to 122ºF
Humidity: 0-95% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.33 in
Height 2.2 in
Supported with a limited 5-year warranty
Title 24 Compliant
Meets ASHRAE 90.1 requirements
PerfectSense
®
Intelligent Building Occupancy Sensors
Overview:
The PS-DTC24 increases area lighting energy efficiency quickly
and easily by combining industry leading Passive Infrared (PIR)
technology with Ultrasonic for superior detection. Factory
preset to deliver significant savings out of the box, this sensor
has additional options to further increase energy savings if
desired. The PerfectSense PS-DTC24 is a low-voltage sensor
that works with PerfectSense class 2 power supply (PSPP1277),
to automatically control lighting. The sensor turns the lights
on and keeps them on when occupancy is detected and will
turn the lights off after the delayed-off time has expired.
Operation:
The sensor first sees motion using the PIR detection and then
activates Ultrasonic to confirm and indicate continued occu-
pancy. The standard factory programming is set to meet the
standards of most common area applications with a 10 minute
off delay time.
Additional Operational Features:
Walk-Through Mode: useful when a room is momentarily
occupied, like a storage area. When a person enters the room,
the lights turn on. If the person leaves the room before the 2.5
minute walk-through timer expires the sensor will turn the
lights off. If the person stays in the room longer than 2.5
minutes the sensor will proceed to standard operation.
Single-Tech Mode: Only one technology is active in this mode.
Dip switch selectable, a user may determine that the space
may only require one technology to properly detect the area.
One sensor model can now act as a PIR only, Ultrasonic only or
Dual-tech sensor.
Daylight Sensor: The integrated daylight sensor allows for
ambient light override functionality. If this setting is enabled,
the controlled lighting load will only turn on if the ambient
light present is less than the preset level.
Adaptive Learning: Patented adaptive learning technology will
automatically increase or decrease the off delay time in
response to the occupancy and environmental conditions of
the area over a period of time. For example, if there is
frequent motion detection, the sensor will automatically
shorten the off delay time to better meet the conditions of the
room. This technology also detects false off conditions. If this
happens, the off delay time duration will immediately be
lengthened to avoid future false off conditions.
23
Wiring Diagrams
Detection Range and Coverage Area
Ordering Information
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PIR Major Motion
Ultrasonic Minor Motion
Ultrasonic Major Motion
0ft 0m
8 2.4
10 3
12 3.7
0ft
0m
6 12 18 246121824
1.8 3.7 5.5 7.31.83.75.57.3
SIDE VIEW
DETECTION AREA
PIR Minor Motion
TOP VIEW
26 ft.12 ft.
32 ft.
26 ft.
24 ft.
38 ft.
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Field of View (Top)
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
SENSOR
24
PS-DTC24-R
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Specifications
Features
360˚ Coverage Pattern
100% Digital Multiview
TM
PIR
Dual technology uses PIR + U/S
Superior RF immunity
Adjustable Time Delay (30 sec-30 min)
Single Technology Mode
SmartSense
TM
Adapt Mode
Walk Through Mode
Daylight Override Mode
Simple Test Mode
Mounts in drop ceilings and solid ceilings
LED’s provide indication of occupancy sensing
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 30mA
Output: 24VDC active high logic control signal
with short circuit protection
Isolated Relays: 2 SPDT 1 Amp, 30 VDC Form C
Wiring Diagram: See Fig. 2
Controls:
Passive Infrared Sensitivity: 0-100% (Factory Set 50%)
Ultrasonic Sensitivity: 0-100% (Factory Set 50%)
Light Sensor: 20-320 LUX (Factory Disables)
Detection Range: See Fig. 1
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 14ºF to 122ºF
Humidity: 0-95% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.33 in
Height 2.2 in
Supported with a limited 5-year warranty
Title 24 Compliant
Meets ASHRAE 90.1 requirements
PerfectSense
®
Intelligent Building Occupancy Sensors
Overview:
The PS-DTC24-R increases area lighting energy efficiency quickly
and easily by combining industry leading Passive Infrared (PIR)
technology with Ultrasonic for superior detection. Provides 2
SPDT 1 Amp, 30 VDC Form C relay contacts for integration with
Nexlight Full 2-Way system and BMS systems. Factory preset to
deliver significant savings out of the box, this sensor has
additional options to further increase energy savings if desired.
The PerfectSense PS-DTC24-R is a low-voltage sensor that works
with PerfectSense class 2 power supply (PSPP1277), to automati-
cally control lighting. The sensor turns the lights on and keeps
them on when occupancy is detected and will turn the lights off
after the delayed-off time has expired.
Operation:
The sensor first sees motion using the PIR detection and then
activates Ultrasonic to confirm and indicate continued occu-
pancy. The standard factory programming is set to meet the
standards of most common area applications with a 10 minute
off delay time.
Additional Operational Features:
Walk-Through Mode: useful when a room is momentarily occu-
pied, like a storage area. When a person enters the room, the
lights turn on. If the person leaves the room before the 2.5
minute walk-through timer expires the sensor will turn the lights
off. If the person stays in the room longer than 2.5 minutes the
sensor will proceed to standard operation.
Single-Tech Mode: Only one technology is active in this mode.
Dip switch selectable, a user may determine that the space may
only require one technology to properly detect the area. One
sensor model can now act as a PIR only, Ultrasonic only or Dual-
tech sensor.
Daylight Sensor: The integrated daylight sensor allows for ambi-
ent light override functionality. If this setting is enabled, the
controlled lighting load will only turn on if the ambient light
present is less than the preset level.
Adaptive Learning: Patented adaptive learning technology will
automatically increase or decrease the off delay time in response
to the occupancy and environmental conditions of the area over
a period of time. For example, if there is frequent motion detec-
tion, the sensor will automatically shorten the off delay time to
better meet the conditions of the room. This technology also
detects false off conditions. If this happens, the off delay time
duration will immediately be lengthened to avoid future false off
conditions.
25
Wiring Diagrams
Detection Range and Coverage Area
Ordering Information
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
NORMALLY
CLOSED
COMMON
NORMALLY
OPEN
NORMALLY
OPEN
COMMON
NORMALLY
CLOSED
PIR Major Motion
Ultrasonic Minor Motion
Ultrasonic Major Motion
0ft 0m
8 2.4
10 3
12 3.7
0ft
0m
6 12 18 246121824
1.8 3.7 5.5 7.31.83.75.57.3
SIDE VIEW
DETECTION AREA
PIR Minor Motion
TOP VIEW
26 ft.12 ft.
32 ft.
26 ft.
24 ft.
38 ft.
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Field of View (Top)
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
SENSOR
26
Specifications
Features
Overview
PS-CDS800
Standard Range 180˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 33mA
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
Passive Infrared Sensitivity: 600-1000 sq. ft
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.75 in
The 180 Degree Ceiling-Mounted Occupancy Sensors are
ideal for use in business and office settings to accurately
detect occupancy and automatically control lighting.
The ceiling-mount design of these low-profile sensors
allows the greatest possible motion sensitivity. An adjust-
ment panel is conveniently located on the front of the
sensor, providing ready access to setting controls after the
sensor is installed.
These occupancy sensors are available in the ultrasonic
and dual technology models. The dual technology model
employs passive infrared (PIR) and ultrasonic technology.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjust-
ments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security and
HVAC systems.
• 1000 sq. ft. coverage area
• 180° degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15 seconds
to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
•LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
PerfectSense
®
Intelligent Building Occupancy Sensors
27
Wiring Diagrams
Detection Range and Coverage Area
Ordering Information
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Dual Technology Sensor Field of View
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
SENSOR
GREEN(N.C.)
YELLOW
(COMMON)
ORANGE(N.O)
28
Specifications
Features
Overview
PS-CDS2000
Standard Range 360˚ Sensor
Dual Technology | Ceiling Mount | Low Voltage
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Electrical:
Power Requirements: 24VDC, from powerpack
Current Consumption: 37mA Nominal (125mA max)
Isolated Relay: Form C Contacts for Class 2 signaling
1A @24VDC Resistive
Output: 24VDC active high logic control signal
with short circuit protection
Controls:
Adjustable Sensitivity of (60-100% of Max. Coverage)
Time Delay: 15 sec. - 30 min.
Light Sensor: 0.5-250 foot candles
Load Rating: Controls Class 2 Power Pack
Housing Material: High-Impact ABS
Color: White
Environment Temperature: 32ºF to 122ºF
Humidity: 0-90% Non Condensing
Installation: See Install Instructions
Dimensions: Diameter 4.5 in
Height 1.25 in
PerfectSense
®
Intelligent Building Occupancy Sensors
The Ceiling-mounted Dual Tech Occupancy Sensor
accurately detects occupancy and automatically switches
lighting on and off as needed.
This low profile sensor is ceiling mounted for superior
motion detection. With a 360 degree field of view and up
to 2000 square feet of coverage area, the Ceiling-mounted
Occupancy Sensor is ideal for storage rooms, bathrooms,
conference rooms, classrooms, hallways, and open office
areas.
Ceiling-mount sensors also incorporate an integral light
level sensor to prevent lighting from switching On when
sufficient ambient light is present, such as is commonly
found in windowed areas.
Installation and configuration is simple. The sensor readily
mounts to drop ceilings and features front located adjust-
ments for setting sensitivity and time delay. Features an
isolated relay for use with building automation, security
and HVAC systems.
• 2000 sq. ft. coverage area
• 360 degree field of view
• Light level sensing (from 0.5 to 250 foot-candles)
• Adjustable time delay (pre-set time delays from 15
seconds to 30 minutes)
• Automatic adaptive technology adjusts the time delay for
maximum energy savings.
• Adjustable sensitivity (from 60 to 100%)
• Isolated relay
• LED motion indicator
• Adjustment compartment cover equipped with retention
feature
• Manual bypass
• UL®/cUL Listed
• Title 24 Certified
• Meets ASHRAE 90.1 requirements
• Five-year warranty
29
Wiring Diagrams
Detection Range and Coverage Area
Ordering Information
DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR
FREQUENCY
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White
Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White
Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White
PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White
Power Pack (Required for operation)
*all coverage areas are based on a standard 9 ft mounting height
Neutral
Hot
RED
BLACK
BLUE
BLACK
WHITE
RED
LOAD
+24v
COMMON
CONTROL Power
Pack
PS-PP1277
120V
277V
* Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Field of View (Top)
SENSOR
GREEN(N.C.)
YELLOW
(COMMON)
ORANGE(N.O)
30
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WPS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Passive Infrared
Coverage Areas: Wide Angle: 2500 sq. ft. @ 8 ft. high
(All 3 lenses included) Long Range: 102 linear ft. @ 10 ft. high
High Bay: 54 linear ft. @ 30 ft. high
Field of view: 110°
Ambient light level sensing: 0.5 to 250 foot-candles
Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes
Adjustable sensitivity: 60%-100% independent adjustment for US and PIR
Adaptive Technology: Automatically adjusts the time delay for maximum energy savings
LED Motion Indicators: Red=PIR motion indicator
Current Consumption @ 24Vdc*: 21mA Nominal
Isolated Relay: 1A @ 24 Vdc Resistive
Operating Temperature: 32 - 122° F (0 - 50° C)
Maximum Humidity: 90% RH Non-condensing
Standards: UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
Specifications
Wall-Mounted Passive Infrared (PIR) Occupancy Sensor accurately detects occu-
pancy and automatically switches lighting on and off as needed. This sensor is
wall- or ceiling-mounted for superior motion detection.
The PIR Occupancy Sensor has three interchangeable lenses included for custom
coverage patterns. The Wide Angle lens has a 2500 square foot coverage area
when the sensor is mounted 8 feet high, the Long Range lens has a 102 linear foot
coverage area at 10 ft. high and the High Bay lens has a 54 linear foot coverage
area at 30 ft. high. With a 110 degree field of view the Wall-Mounted PIR Occu-
pancy Sensor is ideal for warehouse, business, and office settings.
Wall-mount sensors also incorporate an integral light level sensor to prevent
lighting from switching On when sufficient ambient light is present, such as is
commonly found in windowed areas.
Installation and configuration is simple. The sensor readily mounts to walls as well
as drop ceilings and features front located adjustments for setting sensitivity and
time delay. Features an isolated relay for use with building automation, security,
and HVAC systems.
31
Overview
Detection Range and Coverage Area
Wiring Color Table
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
CLASS 2 DEVICE WIRING ONLY
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
Wire Color Function
Black 0 VDC
Red +24 VDC
Green Isolated contact NC
Yellow Isolated contact common
Orange Isolated contact NO
Blue Control output
*Confirm the Sensor is connected to the Class 2 side of the Power Pack.
Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information.
Wiring the Sensor
•
•
•
PS-PP1277
Ordering Information
Description Catalog Number
Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500
Power Pack (required) PS-PP1277
PIR (PS-WPS1500)
Wide Angle Lens Long Range Lens High Bay Lens
PerfectSense
®
Intelligent Building Occupancy Sensors
32
Wall Mount Type
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WUS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Ultrasonic Type
Coverage Areas: 1000 sq. ft. major motion 500 sq. ft. minor motion
Field of view: NA
Ambient light level sensing: 0.5 to 250 foot-candles
Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes
Adjustable sensitivity: 60%-100% independent adjusment for US and PIR
Adaptive Technology: Automatically adjusts the time delay for maximum energy savings
LED Motion Indicators: Red=PIR motion indicator
Current Consumption @ 24Vdc*: 34mA Nominal
Isolated Relay: 1A @ 24 Vdc Resistive
Operating Temperature: 32 - 122ºF (0 - 50ºC)
Maximum Humidity: 90% RH Non-condensing
Standards: UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
Specifications
Overview
Wall-mounted Ultrasonic Occupancy Sensor accurately detects occupancy and
automatically switches lighting on and off as needed. This low profile sensor is
wall- or ceiling- mounted for superior motion detection over partitions and other
common obstructions.
With 1000 square feet of coverage area, the Wall-Mounted Ultrasonic Occupancy
Sensor is ideal for storage rooms, hallways, bathrooms, conference rooms,
classrooms and open office areas.
Wall-mount sensors also incorporate an integral light level sensor to prevent
lighting from switching on when sufficient ambient light is present, such as is
commonly found in windowed areas.
Installation and configuration is simple. The sensor readily mounts to walls or drop
ceilings and features front located adjustments for setting sensitivity and time
delay. Features an isolated relay for use with building automation, security and
HVAC systems.
33
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Detection Range and Coverage Area
Ultrasonic (PS-WUS1500)
CLASS 2 DEVICE WIRING ONLY
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
Wire Color Function
Black 0 VDC
Red +24 VDC
Green Isolated contact NC
Yellow Isolated contact common
Orange Isolated contact NO
Blue Control output
*Confirm the Sensor is connected to the Class 2 side of the Power Pack.
Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information.
Wiring Color Table
•
•
•
PS-PP1277
Ordering Information
Description Catalog Number
Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500
Power Pack (required) PS-PP1277
NOTE: Coverage area may vary depending upon the shape,
size, and absorbent properties of the room.
PerfectSense
®
Intelligent Building Occupancy Sensors
34
Wiring the Sensor
Wall Mount Type
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-WDS1500
Commercial Grade Occupancy Sensor
Wall Mounted | Low Voltage | Dual Technology
Coverage Area: 2500 sq. ft. @ 8 ft. high
Field of view: 110°
Ambient light level sensing: 0.5 to 250 foot-candles
Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes
Adjustable sensitivity: 60%-100% independent adjusment for US and PIR
LED Motion Indicators: Red=PIR Green= Ultrasonic
Manual Bypass: Switch selectable
Adjusment cover: Front located
Current Consumption @ 24Vdc*: 37mA Nominal
Isolated Relay: 1A @ 24 Vdc Resistive
Operating Temperature: 32 - 122ºF (0 - 50ºC)
Maximum Humidity: 90% RH Non-condensing
Standards: UL®/cUL Listed
FCC: Part 15, Class B
Title 24 Certified
Specifications
Overview
The Wall-Mounted Dual Technology Occupancy Sensor employs both passive
infrared (PIR) and ultrasonic technology to accurately detect occupancy and
automatically turn on lighting.
To reduce the occurrence of false on events, this sensor employs PIR technology to detect
major motion. Once lighting has been turned on, it employs highly sensitive PIR and ultrasonic
technology to detect minor motion and keep lighting on while areas remain occupied. When the
room or area is no longer occupied, the sensor turns off lighting after a pre-set time delay.
The low profile sensor is wall-mounted for greatest sensitivity to motion in large areas with
obstructions. With a 110º degree field of view and up to 2500 square feet of coverage area when
mounted at 8 ft. off the ground, the Wall-mounted Dual Technology Occupancy Sensor is ideal
for conference rooms, classrooms, bathrooms, and large office areas.
These wall-mount sensors also incorporate an integral light level sensor to prevent lighting from
switching On when sufficient ambient light is present, such as is commonly found in windowed
areas.
Installation and configuration is simple. The sensor readily mounts to walls and drop ceilings and
features front located adjustments for setting sensitivity and time delay. The sensor also features
an isolated relay for use with building automation and HVAC systems.
35
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Detection Range and Coverage Area
Dual Technology (PS-WDS1500)
CLASS 2 DEVICE WIRING ONLY
Do not reclassify and install as Class
1, 3, or Power and Lighting wiring.
To be connected to a Class 2 power
source only.
Wiring connections shall be rated
suitable for the wire size employed.
Failure to follow this instruction can
result in personal injury or equipment
or property damage.
Wire Color Function
Black 0 VDC
Red +24 VDC
Green Isolated contact NC
Yellow Isolated contact common
Orange Isolated contact NO
Blue Control output
*Confirm the Sensor is connected to the Class 2 side of the Power Pack. Refer to the Power Pack
PS-PP1277 Instruction Bulletin for additional information.
Wiring the Sensor
Wiring Color Table
•
•
•
PS-PP1277
Ordering Information
Description Catalog Number
Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500
Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500
Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500
Power Pack (required) PS-PP1277
PerfectSense
®
Intelligent Building Occupancy Sensors
36
Wall Mount Type
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PP1277
Commercial Grade Power Pack
• 100 mA power output can supply up to three sensors
• Single-pole, normally open relay
• Rated for plenum use
• Relay rated for maximum 15 A tungsten and 20 A ballast loads
• Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple
Overview
Features
120V
277V
Relay
White
Line voltage
120/277 Vac
Neutral
Blue
(Control)
Black
(Common)
Red
(+24 Vdc)
Control
Load
TransformerVoltage selector Voltage selector
Load
Neutral
Black
Line voltage
120/277 Vac
Control input
+24 Vdc
Blue Blk Red
Common
Hot
White
Red
BlackHot
Sensor
Override OFF
Red
Storage Temperature: -20°F to 150°F (-29°C to 65°C)
Operating Temperature: 32°F to 104°F (0°C to 40°C)
Maximum Humidity: 90% non-condensing
AC Power Input: 120 or 277 Vac ± 10%, 60 Hz
Output Voltage: 24 Vdc
Specifications
The PerfectSense Power Pack has a line input of 120 or 277 Vac, and a
single-pole, single-throw, relay output for the load. A full wave rectifier
converts the AC line voltage to 24 Vdc to power a low-voltage sensor via
Class 2, plenum-rated wire. The power pack can be mounted inside or
outside of an electrical junction box. Be sure to observe all local codes
when mounting and wiring a powerpack.
Schematic Diagram System Diagram
Output Current: 100 mA nominal
Horsepower Rating: 1 hp @ 120 V
Switching Capacity: 120 Vac, 60 Hz
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz
20 A ballast
37
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
To
sensor
120V
277V
To
sensor
Line voltage
Inside
Installation Instructions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The power pack must be installed and serviced only by qualified
electrical personnel.
• Turn off power at the circuit breaker before beginning installation.
• Always use a properly rated voltage sensing device to confirm power is off.
Failure to follow these instructions will result in death or serious injury.
Mounting Examples
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Set the voltage selector on the front of the unit to either 120 or 277
V, depending on your application. The unit is shipped with the
selector set to 277 V.
5. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
6. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
120V
277V
To
sensor
Line voltage
Outside
PerfectSense
®
Intelligent Building Occupancy Sensors
38
Power Packs
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PS-SP24
Auxiliary Relay Power Pack
• Single-pole, normally open relay
• Rated for plenum use
• Relay rated for maximum 15 A tungsten and 20 A ballast loads
• Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple
Features
Storage Temperature: -20°F to 150°F (-29°C to 65°C)
Operating Temperature: 32°F to 104°F (0°C to 40°C)
Maximum Humidity: 90% non-condensing
AC Power Input: 24Vdc / 36mA
Output Voltage: No Power Supply
Standards: UL and cUL listed
FCC: Part 15, Home and Office use Class B
Specifications
The PerfectSense auxiliary relay is similar to the power pack. The auxiliary
relay does not supply power, but switches lighting and HVAC loads based
on a control signal from the occupancy sensor. Both the power pack and
auxiliary relay are housed in a rugged plenum rated enclosure, and rated
for lighting and HVAC loads, including electronic ballasts. Flexible
mounting scheme allows for installation inside or outside a standard
4”x4”junction box
Schematic DiagramSystem Diagram
Horsepower Rating: 1 hp @ 120 V
Switching Capacity: 120 Vac, 60 Hz
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz
20 A ballast
PerfectSense
®
Intelligent Building Occupancy Sensors
39
Overview
PerfectSense
®
Intelligent Building Occupancy Sensors
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
To
sensor
Line voltage
Inside
Installation Instructions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The power pack must be installed and serviced only by qualified
electrical personnel.
• Turn off power at the circuit breaker before beginning installation.
• Always use a properly rated voltage sensing device to confirm power is off.
Failure to follow these instructions will result in death or serious injury.
Mounting Examples
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
5. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
To
sensor
Line voltage
Outside
40
Power Packs
41 Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-PP7000X
Heavy Duty Power Pack
Overview
Features
Storage Temperature: -20°F to 150°F (-29°C to 65°C)
Operating Temperature: 32°F to 104°F (0°C to 40°C)
Maximum Humidity: 90% non-condensing
AC Power Input: 120 or 277 Vac ± 10%, 60 Hz
Output Voltage: 24 Vdc
Specifications
Combines transformer relay functions, occupancy sensor control, and
manual/automatic operation into a single high performance unit. The
PerfectSense Power Pack provides a wide array of switching solutions into a
single unit. With high inrush stability circuitry specifically designed to
handle today’s demanding inrush from electronic ballast loads and offer
unmatched durability. A full wave rectifier converts the AC line voltage to
24 Vdc to power a low-voltage sensor via Class 2, plenum-rated wire. The
power pack can be mounted inside or outside of an electrical junction box.
Be sure to observe all local codes when mounting and wiring a powerpack.
Output Current: 225 mA nominal
Horsepower Rating: 1 hp @ 120 V
Switching Capacity: 120 Vac, 60 Hz;
15 A tungsten 1800 W
20 A ballast
277 Vac, 60 Hz;
20 A ballast
• Extreme durability: exceeds WS-896 Federal Specification duty cycle
requirements for specification grade toggle switches.
• High Inrush Stability circuit designed to handle high inrush electronic
ballast loads, including the latest T5HO and T4 ballasts.
• Zero crossing design for reliability and extended life.
• Mechanical latching relay for dependability and robust for all load types
• Return-to-on design provides fail safe operation in the event of power
loss or malfunction.
• Transformer Relay Function: replaces traditional transformer relays and
provides occupancy sensors control. Ideal for use where code
requirements/jurisdictions prohibit the use of 277V switch legs.
• Manual-ON or Automatic-ON functionality for use in bi-level lighting
control per CEC Title 24 requirements.
• UL 2043 Plenum Rated
• Endurance tested to over 1,000,000 cycles at full load.
• Integrates with low voltage momentary and maintained switches to
control occupancy sensors.
• Conduit adaptor included for low voltage connections.
42Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Installation Instructions
Bi-Level Switching Diagram
PerfectSense
®
Intelligent Building Occupancy Sensors
N H
Green
Brown
Brown/White
Yellow
White/Blue
Blue
Blue
White
Black
LOAD 1
LOAD 2
Yellow
Orange
Green
Brown
Brown/White
Blue
Red
White
Blue
Blue
Black
Orange/Yellow
White/Blue
Black
Red
Orange
Blue
Zone 1 – Auto ON
Zone 2 – Manual ON
Local SW 1
Auto ON
+24VDC
Com
Local SW 2
Manual ON
Com
Black
Orange/Yellow
Occupancy
Sensor
Momentary or
Maintained Switches
1. Provide separate overcurrent protection in accordance with the
National Electrical Code® and applicable local codes.
2. Use copper wire only.
3. Confirm that the device rating is proper for your application.
4. Mount the power pack to a suitable junction box using the 1/2-in.,
threaded nipple and lock. The power pack is plenum-rated, and can
be mounted to the inside or the outside of a junction box or fixture
in a ceiling plenum.
5. Connect the power pack as shown on previous page. Use approved
wire nuts for electrical connections.
Power Packs
Ordering Information
Features
 Provide simple momentary push
button control.
 LED models provide pilot lights or status
outputs.
 Operate on voltage ranges from 5-36 VDC.
 Certain models are designed for use with
NexLight 2-Wire relay panels.
 Switches fit standard NEMA wall boxes.
 Decorator-style enclosure; wall plate
included.
Part Number Description
PS-LVS1x 1-button, low voltage switch
PS-LVS1Lx 1-button, low voltage switch with LED
PS-LVS2x 2-button, low voltage switch
PS-LVS2Lx 2-button, low voltage switch with LED
PS-LVS1Rx 1-button NexLight 2-Wire relay panel switch with LED
PS-LVS2Rx 2-button NexLight 2-Wire relay panel switch with LED
x = color code; W for White, L for Light Almond, and I for Ivory.
The PerfectSense™ Low Voltage Switches are a series of decorator style push button wall switches that can
be mounted in commercial or residential applications. The low voltage switches are designed to operate with
PerfectSense Occupancy Sensors and NexLight 2-Wire relay panels. All switch models are available in white,
almond, and ivory.
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
PerfectSense
®
Intelligent Building Occupancy Sensors
PS-LVSX Series
Low Voltage Switches
Overview
43
Specifications
Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
Low Voltage Switch Wiring
One Switch
PS-LVS1
SW1
V OUT
V IN
One Switch with LED
SW1
V OUT
V IN
(+) Anode
(-) Cathode
Two Switches
SW1
SW2
V OUT SW1
V OUT SW2
V IN
Two Switches with LEDs
SW1
SW2
V OUT SW1
V OUT SW2
V IN
(+) Anode LED1
(-) Cathode LED1
(+) Anode LED2
(-) Cathode LED2
Connection type External wires
Gauge: #22 AWG stranded
Number of conductors/switch: PS-LVS1: 2
PS-LVS1L: 4
PS-LVS2: 3
PS-LVS2L: 7
PS-LVS1R: 2
PS-LVS2R: 3
Switch Operating Range 5-36VDC
Max current of 50mA @ 36VDC
LED Operating Range 5-36 VDC
Min operating current .150ma @ 5VDC
Min operating current .275ma @ 12VDC
Min operating current .385ma @ 24VDC
Min operating current .470ma @ 36VDC
Conductor temperature rating: Not specified, select to meet UL Class 2 requirements
Conductor voltage rating: 5 to 36 Volt DC
Conductor length: 6 inches from housing
Temperature 0 – 50 degrees C.
Humidity Maximum 90% RH non-condensing
Low Voltage Relay Panel Switch Wiring
One Switch
Reverse
Polarity
Switch
V OUT
V IN
Two Switches
Reverse
Polarity
Switch
V OUT SW2
Reverse
Polarity
Switch
V OUT SW1
V IN
PS-LVS1L
PS-LVS2
PS-LVS2L
PS-LVS1R PS-LVS2R
Low Voltage Switches
44
PerfectSense
®
Intelligent Building Occupancy Sensors
E FA
Line Voltage Class 1 Low Voltage Class 2
(16awg 3-wire)
Low Voltage Class 2
(16awg 2-wire)
WIRING KEY
A
E A
A
F
2- Button
Low Voltage Switch
EA
Line Voltage Class 1
(3-conductor)
Low Voltage Class 2
(16awg 3-wire)
WIRING KEY
E
E
Manual On / Auto Off
50% Manual On / Auto Off
Power Pack
Ceiling Sensor
1-Button
Low Voltage Switch
A1
a
b
A1
a
b
A1
a
b
a
b
a
b
A
E
A
A
Manual On / Auto Off +
Dimming + Daylight Sensor
B
Daylight Sensor
Low Voltage Switch
EA
Line Voltage Class 1WIRING KEY Low Voltage Class 2
(0-10V control wires)
G
Low Voltage Class 2
(16awg 3-wire)
B
Occupancy / Vacancy
Sensor
Occupancy / Vacancy
Sensor
F
Low Voltage Class 2
(16awg 2-wire)
EA
Line Voltage Class 1 Low Voltage Class 2
(16awg 3-wire)
WIRING KEY
A
E A
A
Auto On / Auto Off
Power Pack
Ceiling Sensor
Common Stand Alone Control Strategies
PerfectSense
®
Intelligent Building Occupancy Sensors
45
Auto On / Auto Off is the most basic occupancy control strategy.
Requiring only a standard power pack and low voltage sensor,
the space is controlled based on occupnacy with no manual
override control. Line voltage wall switch sensors may also be
configured to work in this manner. Consult local codes for using
this scenario in approved locations.
50% Manual On / Auto Off requires one lighting load to be
switched on automatically when occupancy is detected by an
occupancy sensor, while a second lighting load can be turned
on manually by the occupant if desired. Both loads can then
be turned off manually or via the occupancy sensor timing
out. Commonly required by building codes (such as California
Title 24), this is an easy and convenient method of delivering
extra energy savings without inconveniencing the occupant.
Manual On / Auto Off is the commonly used method for areas
using a single lighting load. Occupants manually turn lights
onBe sure to use a PS-PP7000X power pack designed to work
with low voltage switches.
Going above and beyond Manual On / Auto Off can be done
in a number of ways. The addition of photocells for daylight
harvesting and or 0-10v dimming are two of the most
popular choices for enahnced levels of control and energy
savings in locations with large windows, conference rooms, or
open office areas.
OUR COMMITMENT TO YOU
We take great pride in designing each of our products with the goal of providing the
highest accuracy detection performance possible in the price range of that product. We
strive to reproduce the consistent performance across all of our products. And we strive
to avoid flashy features and promises of auto-commissioning. While that may sound
initially attractive to the novice, they are not real and not enduring. In addition, we use
only the highest-quality parts and the latest assembly and quality control techniques to
ensure the reliability and long life of our products.
Our reputation rests on our steadfast pursuit of this policy in sensors and lighting control
systems for educational, commercial and industrial applications. At NexLight, we are
committed to investing in research that continually gives rise to new technologies for
improving energy savings and occupant comfort.
When you purchase any product from PerfectSense, we encourage you to compare it, as
we do, to competitive products for long-term performance accuracy. We believe that this
process will enhance your appreciation of the product you select.
With best wishes from all of us at PerfectSense for many years of consistent performance.
HOW TO PURCHASE PERFECTSENSE PRODUCTS
In order to serve you better, PerfectSense products are available through a number of
different sales channels. To get you connected with the right products for your applica-
tion please contact us directly either by telephone at 218-828-3700, or visit us on the web
at www.NexLight.com for more information.
PerfectSense is a trademarked brand of NexLight TEL.: 218-828-3700 FAX: 218-824-1568 WWW.NEXLIGHT.COM
PerfectSense
®
Intelligent Building Occupancy Sensors
PerfectSense
®
Intelligent Building Occupancy Sensors
NexLight Lighting Controls
7877 College Road, Suite 105
Baxter, MN, 56425
1-218-828-3700
www.nexlight.com
Electrical equipment should be installed, operated, serviced and maintained
only by qualified personnel. No responsibility is assumed by NexLight for
any consequences arising out of the use of this material.
© 2013 NexLight Lighting Controls, All Rights Reserved.
Cat# PS.4.13
PerfectSense
®
Intelligent Building Occupancy Sensors

More Related Content

What's hot

Motion Sensor Presentation
Motion Sensor PresentationMotion Sensor Presentation
Motion Sensor PresentationFibaro USA
 
Arduino based home automation using tv remote
Arduino based home automation using tv remoteArduino based home automation using tv remote
Arduino based home automation using tv remoteMahbub Alam Himel
 
Design of alarm using pir sensor for
Design of alarm using pir sensor forDesign of alarm using pir sensor for
Design of alarm using pir sensor forAkshay Dhole
 
Home automation using arduino
Home automation using arduinoHome automation using arduino
Home automation using arduinoIkram Arshad
 
Fibaro Product Brochure - US
Fibaro Product Brochure - USFibaro Product Brochure - US
Fibaro Product Brochure - USFibaro USA
 
Ir remote control dimmer..
Ir remote control dimmer..Ir remote control dimmer..
Ir remote control dimmer..Akshay Mishra
 
InterAct Pro viedie risinājumu uzņēmumu apgaismojumā
InterAct Pro viedie risinājumu uzņēmumu apgaismojumāInterAct Pro viedie risinājumu uzņēmumu apgaismojumā
InterAct Pro viedie risinājumu uzņēmumu apgaismojumāElektrumlv
 
Srr automation smart home presentation
Srr automation smart home presentationSrr automation smart home presentation
Srr automation smart home presentationVijaykumar swaminathan
 
PIR sensors day
PIR sensors day PIR sensors day
PIR sensors day sivagamitec
 
Home automation Using Arduino Uno and Bluetooth
Home automation Using Arduino Uno and BluetoothHome automation Using Arduino Uno and Bluetooth
Home automation Using Arduino Uno and BluetoothSOURAV ROY
 
Super sensitive industrial security system ppt
Super sensitive industrial security system pptSuper sensitive industrial security system ppt
Super sensitive industrial security system pptMohammed Siraj
 
Thesis - Voice Control Home Automation
Thesis - Voice Control Home AutomationThesis - Voice Control Home Automation
Thesis - Voice Control Home AutomationAbhishek Neb
 
Automatic Room Light Controller Using Arduinom & PIR Sensor
Automatic Room Light Controller Using Arduinom & PIR SensorAutomatic Room Light Controller Using Arduinom & PIR Sensor
Automatic Room Light Controller Using Arduinom & PIR SensorAnkit Chaudhary
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationDomotica daVinci
 

What's hot (18)

Motion Sensor Presentation
Motion Sensor PresentationMotion Sensor Presentation
Motion Sensor Presentation
 
Arduino based home automation using tv remote
Arduino based home automation using tv remoteArduino based home automation using tv remote
Arduino based home automation using tv remote
 
Buildtrack Wireless Occupancy Sensors
Buildtrack Wireless Occupancy SensorsBuildtrack Wireless Occupancy Sensors
Buildtrack Wireless Occupancy Sensors
 
Design of alarm using pir sensor for
Design of alarm using pir sensor forDesign of alarm using pir sensor for
Design of alarm using pir sensor for
 
Home automation using arduino
Home automation using arduinoHome automation using arduino
Home automation using arduino
 
Home automation
Home automationHome automation
Home automation
 
Fibaro Product Brochure - US
Fibaro Product Brochure - USFibaro Product Brochure - US
Fibaro Product Brochure - US
 
Buildtrack Apartment automaton
Buildtrack Apartment automatonBuildtrack Apartment automaton
Buildtrack Apartment automaton
 
Ir remote control dimmer..
Ir remote control dimmer..Ir remote control dimmer..
Ir remote control dimmer..
 
InterAct Pro viedie risinājumu uzņēmumu apgaismojumā
InterAct Pro viedie risinājumu uzņēmumu apgaismojumāInterAct Pro viedie risinājumu uzņēmumu apgaismojumā
InterAct Pro viedie risinājumu uzņēmumu apgaismojumā
 
Smart control v3
Smart control v3Smart control v3
Smart control v3
 
Srr automation smart home presentation
Srr automation smart home presentationSrr automation smart home presentation
Srr automation smart home presentation
 
PIR sensors day
PIR sensors day PIR sensors day
PIR sensors day
 
Home automation Using Arduino Uno and Bluetooth
Home automation Using Arduino Uno and BluetoothHome automation Using Arduino Uno and Bluetooth
Home automation Using Arduino Uno and Bluetooth
 
Super sensitive industrial security system ppt
Super sensitive industrial security system pptSuper sensitive industrial security system ppt
Super sensitive industrial security system ppt
 
Thesis - Voice Control Home Automation
Thesis - Voice Control Home AutomationThesis - Voice Control Home Automation
Thesis - Voice Control Home Automation
 
Automatic Room Light Controller Using Arduinom & PIR Sensor
Automatic Room Light Controller Using Arduinom & PIR SensorAutomatic Room Light Controller Using Arduinom & PIR Sensor
Automatic Room Light Controller Using Arduinom & PIR Sensor
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentation
 

Viewers also liked

Carrer de dones a terrassa
Carrer de dones a terrassaCarrer de dones a terrassa
Carrer de dones a terrassajmilanpu
 
Loi constitutionnelle n° 2007-001 du 27 avril 2007
Loi constitutionnelle n° 2007-001 du 27 avril 2007Loi constitutionnelle n° 2007-001 du 27 avril 2007
Loi constitutionnelle n° 2007-001 du 27 avril 2007smemanager
 
2015.2016.HK2.IEE.nhom23.bai1
2015.2016.HK2.IEE.nhom23.bai12015.2016.HK2.IEE.nhom23.bai1
2015.2016.HK2.IEE.nhom23.bai1Ba Marcelo
 
What's New in Literature for Young Readers
What's New in Literature for Young ReadersWhat's New in Literature for Young Readers
What's New in Literature for Young ReadersRobin L. Gibson
 
Svt evaluation
Svt evaluationSvt evaluation
Svt evaluationVivek Rana
 

Viewers also liked (11)

Carrer de dones a terrassa
Carrer de dones a terrassaCarrer de dones a terrassa
Carrer de dones a terrassa
 
ResuméSpring2016v2
ResuméSpring2016v2ResuméSpring2016v2
ResuméSpring2016v2
 
The MoneyShow
The MoneyShowThe MoneyShow
The MoneyShow
 
Base de participante
Base de participanteBase de participante
Base de participante
 
Loi constitutionnelle n° 2007-001 du 27 avril 2007
Loi constitutionnelle n° 2007-001 du 27 avril 2007Loi constitutionnelle n° 2007-001 du 27 avril 2007
Loi constitutionnelle n° 2007-001 du 27 avril 2007
 
2015.2016.HK2.IEE.nhom23.bai1
2015.2016.HK2.IEE.nhom23.bai12015.2016.HK2.IEE.nhom23.bai1
2015.2016.HK2.IEE.nhom23.bai1
 
Circuitul apei in natura
Circuitul apei in naturaCircuitul apei in natura
Circuitul apei in natura
 
What's New in Literature for Young Readers
What's New in Literature for Young ReadersWhat's New in Literature for Young Readers
What's New in Literature for Young Readers
 
Filme
FilmeFilme
Filme
 
Svt evaluation
Svt evaluationSvt evaluation
Svt evaluation
 
Linx Ibèric
Linx IbèricLinx Ibèric
Linx Ibèric
 

Similar to PerfectSenseCatalog

Apex specialized luminaires for imaging therapy centres
Apex   specialized luminaires for imaging therapy centresApex   specialized luminaires for imaging therapy centres
Apex specialized luminaires for imaging therapy centresVivek Mehrotra
 
MRI lighting Solutions from Innowave
MRI lighting Solutions from InnowaveMRI lighting Solutions from Innowave
MRI lighting Solutions from InnowaveInnoWave Healthcare
 
Innowave Freedom ambient Lighting System MRI rooms
Innowave Freedom ambient  Lighting System MRI rooms Innowave Freedom ambient  Lighting System MRI rooms
Innowave Freedom ambient Lighting System MRI rooms Vivek Mehrotra
 
The science of light sensors
The science of light   sensorsThe science of light   sensors
The science of light sensorsJozhe Fonseca
 
Prozess Technologie REVEAL Platform
Prozess Technologie REVEAL PlatformProzess Technologie REVEAL Platform
Prozess Technologie REVEAL PlatformArjay Automation
 
Blaze Occupancy Sensors
Blaze Occupancy SensorsBlaze Occupancy Sensors
Blaze Occupancy Sensorshomeautomation
 
Dmx512 lightng contrl design
Dmx512 lightng contrl designDmx512 lightng contrl design
Dmx512 lightng contrl designajsatienza
 
ATI_Q46PR.pdf
ATI_Q46PR.pdfATI_Q46PR.pdf
ATI_Q46PR.pdfENVIMART
 
VEGA Pressure & Level Measurement - Renewable Energy Industry Applications
VEGA Pressure & Level Measurement  - Renewable Energy Industry ApplicationsVEGA Pressure & Level Measurement  - Renewable Energy Industry Applications
VEGA Pressure & Level Measurement - Renewable Energy Industry ApplicationsThorne & Derrick UK
 
Alarm Annunciator
Alarm AnnunciatorAlarm Annunciator
Alarm AnnunciatorESD India
 
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...Thorne & Derrick UK
 
Ara smart homes catalog
Ara smart homes catalogAra smart homes catalog
Ara smart homes catalogARA TECH Works
 
Dewesoft product overview | Dewesoft
Dewesoft product overview | DewesoftDewesoft product overview | Dewesoft
Dewesoft product overview | DewesoftDewesoft
 
Vega A Multitude Of Solutions With Plics Plus
Vega A Multitude Of Solutions With Plics PlusVega A Multitude Of Solutions With Plics Plus
Vega A Multitude Of Solutions With Plics PlusThorne & Derrick UK
 
Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Soumya Sharma
 
Room Energy Management.pdf
Room Energy Management.pdfRoom Energy Management.pdf
Room Energy Management.pdfJoniGarcia9
 
Aerospace solutions | Dewesoft
Aerospace solutions | DewesoftAerospace solutions | Dewesoft
Aerospace solutions | DewesoftDewesoft
 

Similar to PerfectSenseCatalog (20)

Apex specialized luminaires for imaging therapy centres
Apex   specialized luminaires for imaging therapy centresApex   specialized luminaires for imaging therapy centres
Apex specialized luminaires for imaging therapy centres
 
MRI lighting Solutions from Innowave
MRI lighting Solutions from InnowaveMRI lighting Solutions from Innowave
MRI lighting Solutions from Innowave
 
Innowave Freedom ambient Lighting System MRI rooms
Innowave Freedom ambient  Lighting System MRI rooms Innowave Freedom ambient  Lighting System MRI rooms
Innowave Freedom ambient Lighting System MRI rooms
 
The science of light sensors
The science of light   sensorsThe science of light   sensors
The science of light sensors
 
Prozess Technologie REVEAL Platform
Prozess Technologie REVEAL PlatformProzess Technologie REVEAL Platform
Prozess Technologie REVEAL Platform
 
Blaze Occupancy Sensors
Blaze Occupancy SensorsBlaze Occupancy Sensors
Blaze Occupancy Sensors
 
Blaze Occupancy Sensors
Blaze Occupancy SensorsBlaze Occupancy Sensors
Blaze Occupancy Sensors
 
Dmx512 lightng contrl design
Dmx512 lightng contrl designDmx512 lightng contrl design
Dmx512 lightng contrl design
 
ATI_Q46PR.pdf
ATI_Q46PR.pdfATI_Q46PR.pdf
ATI_Q46PR.pdf
 
VEGA Pressure & Level Measurement - Renewable Energy Industry Applications
VEGA Pressure & Level Measurement  - Renewable Energy Industry ApplicationsVEGA Pressure & Level Measurement  - Renewable Energy Industry Applications
VEGA Pressure & Level Measurement - Renewable Energy Industry Applications
 
Central Grid Tie Solar Inverter - InPhase Power
Central Grid Tie Solar Inverter - InPhase PowerCentral Grid Tie Solar Inverter - InPhase Power
Central Grid Tie Solar Inverter - InPhase Power
 
Alarm Annunciator
Alarm AnnunciatorAlarm Annunciator
Alarm Annunciator
 
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...
VEGA Pressure & Level Measurement - Environment and Recycling Industry Applic...
 
Ara smart homes catalog
Ara smart homes catalogAra smart homes catalog
Ara smart homes catalog
 
Dewesoft product overview | Dewesoft
Dewesoft product overview | DewesoftDewesoft product overview | Dewesoft
Dewesoft product overview | Dewesoft
 
Vega A Multitude Of Solutions With Plics Plus
Vega A Multitude Of Solutions With Plics PlusVega A Multitude Of Solutions With Plics Plus
Vega A Multitude Of Solutions With Plics Plus
 
Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems Fire Safety Devices , Fire detection systems
Fire Safety Devices , Fire detection systems
 
Room Energy Management.pdf
Room Energy Management.pdfRoom Energy Management.pdf
Room Energy Management.pdf
 
Envoirment
EnvoirmentEnvoirment
Envoirment
 
Aerospace solutions | Dewesoft
Aerospace solutions | DewesoftAerospace solutions | Dewesoft
Aerospace solutions | Dewesoft
 

PerfectSenseCatalog

  • 2. BENEFITS OF PERFECTSENSE Whether the goal is cost and time-saving installation, building energy efficiency, certification to national energy code regulation, retrofitting, flexibility, or building automation, NexLight’s PerfectSense Intelligent Building Occupancy Sensors meets any application need. EASY TO DESIGN Either installed to work independently, or connected to work with a building network lighting control system, PerfectSense products offer many ways to control area lighting. EASY TO INSTALL All PerfectSense products come with easy to understand installation instructions and wiring guides to quickly complete the line and low voltage connections. Intelli- gent out of the box presets provide accurate sensing and detection sensitivities for most applications, making the installation process even faster. EASY ENERGY SAVINGS Cost-effectively save 20-80% of area lighting costs by installing occupancy sensors throughout a facility. Perhaps the most cost effective controls strategy, occupancy sensors begin saving energy the day they are installed. EASY CODE COMPLIANCE Meet and exceed today’s stringent energy codes and performance requirements such as ASHRAE 90.1 2010, IECC 2012 and California Title 24 quickly and easily. EASY SAFETY & SATISFACTION PerfectSense employs the latest sensing technologies and manufacturing methods to provide customers with a superior performing product. Backed by a 5-year limited warranty all products are designed to provide a solution which increases energy savings while delivering occupant satisfaction. EASY TO RETROFIT All PerfectSense products work with every standard commercial lighting load type from all lighting manufacturers, enabling you to bring savings to every building application. VALUABLE TO: BUILDING PROFESSIONALS, ARCHITECTS, SPECIFIERS, SYSTEM INTEGRATORS, ENGINEERS, AND INSTALLERS. Flexibility, simplicity, code compliant, environmentally friendly. BUILDING OWNERS, FACILITY MANAGERS AND PRIVATE CONSUMERS. Energy savings, cost benefits, flexibility and comfort, simplicity, security. 1
  • 3. 2 PRODUCT SELECTION MATRIX Model # Pages Operating Voltage Description Typical Applications PS-PWS1277W 11 120/277 PIR Wall Switch 1-Button Small o ces, small and medium conference rooms, utility / storage rooms PS-PWD1277W 11 120/277 PIR Wall Switch 2-Button Small o ces, small and medium conference rooms, lunch/ breakrooms, utility / storage rooms PS-UWS1277W 13 120/277 Ultrasonic Wall Switch 1-Button Individual restrooms, two-stall restrooms, utility / storage rooms PS-UWD1277W 13 120/277 Ultrasonic Wall Switch 2-Button Individual restrooms, two-stall restrooms, utility / storage rooms PS-DWS1277W 15 120/277 Dual Tech Wall Switch 1-Button Small and executive o ces, small and medium conference rooms, lunch break rooms PS-DWD1277W 15 120/277 Dual Tech Wall Switch 2-Button Small and executive o ces, small and medium conference rooms, lunch break rooms PIR PS-CPS1000 17 24 1000 sq. ft PIR w/ Relay Small o ces, copy rooms, break rooms, library book stacks, aisleways, small classrooms PS-CUS800 19 24 1000 sq. ft 180° view w/ Relay Open o ces, restrooms, conference rooms, hallways, end of aisle PS-CUS2000 21 24 2000 sq. ft w/ Relay Open o ces, restrooms, conference rooms, large o ces, hallways PS-DTC24 23 24 1000 sq. ft Classrooms, conference rooms, training rooms, large o ces, computer rooms PS-DTC24-R 25 24 1000 sq. ft w/ Relay Classrooms, conference rooms, training rooms, large o ces, computer rooms PS-CDS800 27 24 1000 sq. ft 180° view w/ Relay Classrooms, conference rooms, training rooms, large o ces, computer rooms PS-CDS2000 29 24 2000 sq. ft w/ Relay Classrooms, conference rooms, training rooms, large o ces, computer rooms PIR PS-WPS1500 31 24 Multi-Lens PIR w/ Relay O ces, classrooms, hallways, warehouses, aisleways, conference rooms Ultrasonic PS-WUS1500 33 24 Ultrasonic w/ Relay Open o ces, classrooms, restrooms, conference rooms, large o ces DualTech PS-WDS1500 35 24 Dual Tech w/ Relay Classrooms, conference rooms, training rooms, large o ces, computer rooms PS-PP1277 37 120/277 Basic Power Pack Auto On, Auto O PS-SP24 39 120/277 Auxiliary Power Pack Allows for added loads PS-PP7000X 41 120/277 Heavy Duty Power Pack Auto On, Auto O , Manual On, Light Hold On, Light Hold O Power Packs Page 37-42 UltrasonicDualTech Wall Mount Occupancy Sensors Page 31-36 Wall Switch Occupancy Sensors Page 11-18 PIRUltrasonicDualTech Ceiling Mount Occupancy Sensors Page17-30 Low Voltage Switches Page 43-44 PS-LVSX 43 24 Low Voltage Series of Switches Manual On / Off control in any location Common Stand Alone Control Strategies Page 45 General Information and Product Design Guide Page 3-10 WallSwitch Occupancy Sensors Page17-30
  • 4. ENERGY SAVINGS Occupancy sensors deliver maximum energy savings, exceeding the savings provided by other control solutions (i.e. scheduling), by ensuring that lighting is only on when people are present. NexLight, the world’s top producer of design built and easy to use lighting control systems, continues its mission by providing new sensors that save energy and assist in achieving additional design goals. EFFICIENCY INCENTIVES The use of occupancy sensors can assist building owners in earning Corporate Tax Incentives including credits, deduc- tions, exemptions and rebates based on the equipment installed. To qualify, a building must meet or exceed the energy performance required. Visit www.dsireusa.org for more information and updates for your local area. SUSTAINABLE BUILDINGS By designing beyond the requirements of codes, design teams can provide even greater energy savings and work toward sustainable building practices. LEED certification points are awarded with correct application and use of sensors. The result is another way of providing the commu- nity with green and energy efficient buildings. ENERGY CODE COMPLIANCE PerfectSense products provide convenient code compliant Automatic-ON or Manual-ON control and are full of innova- tive features. Our sensors use Passive Infrared (PIR), Ultrasonic, and a combination of the two, commonly referred to as Dual-Technology. Both Automatic-ON and Manual-ON sensors meet the Automatic-OFF requirement of all major energy codes, including ASHRAE 90.1 (2007 and earlier), IECC and California’s Title 24. ASHRAE 90.1-2010 is now including the requirement for many spaces to be Manual-ON. A space may use Automatic-ON control, however the Automatic-ON func- tion cannot turn on more than 50% of the space lighting. Whichever method your space requires, PerfectSense offers a complete selection of compliant solutions. AUTOMATIC-ON + BI-LEVEL CONTROL Bi-level switching has the potential to save energy by enabling occupants to use just as much lighting as they want, and is a requirement by EPAct, California’s Title 24 and ASHRAE 90.1 2010. Bi-level Auto-on control is when one zone is turned on automatically (by the sensor) and the other zone must be turned on manually (local switch). This method of control has been shown to use 52% less energy* than Automatic-on only. Additionally, many occu- pants are comfortable working in lower lighting levels. The result are dramatic energy savings and enhancing occu- pant comfort. (*BasedonCaliforniaLightingTechnologyCenterresearch2009.) AUTO-ON TO 50% EXAMPLE ENERGY CONSERVATION 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0 Classroom Conference Room Private Restroom Storage Actual Energy Savings By Application 20-80%EnergySavings* (*Sources:U.S.EPA,LightingResearchCenter&CaliforniaEnergyCommissionpublications) Office 3
  • 5. PerfectSense gives engineers and facility managers more control options than ever before, offering sensors that are the best fit for any application. Sensors featuring Passive Infrared, Ultrasonic or Dual Technology are ideally suited for different applications. Let’s take a closer look at each type. PASSIVE INFRARED Passive Infrared (PIR) technology detects occupancy in the space by sensing the difference between temperatures of a human body in motion and the background space. Requiring a line of sight for detection, PIR sensors feature accurate area coverage cut-offs. ULTRASONIC Ultrasonic (US) technology operates by transmitting an ultrasonic sound wave into the space and measuring the speed at which they return back to the sensor. Occupant movements change the frequency of the waves. This means ultrasonic sensors can detect movement around partitions or indirect line of sight. DUAL TECHNOLOGY Dual Technology operates by combining PIR and ultrasonic detec- tion into a single device. This technology increases the accuracy of detection while decreasing the potential of false ON or false OFF triggers. SENSOR TECHNOLOGIES DUAL TECHNOLOGY BEST APPLICATIONS: + Classrooms + Large conference rooms + Large offices + Lecture halls + Cafeterias ULTRASONIC BEST APPLICATIONS: + Restrooms + Open office spaces + Enclosed hallways + Stairways PIR BEST APPLICATIONS: + Small offices + Warehouses + High ceiling locations + Library book stacks/aisles + Lobby / common areas + Computer rooms 4
  • 6. APPLICATION EXAMPLES Large conference rooms require detection that will account for occupants that may be still for long periods of time. Dual technol- ogy sensors will be able to detect minor motion to keep lights on as long as the space is occupied. Copy rooms, IT rooms, and janitor’s closets are ideal for occu- pancy based controls. With a wall or switch mounted PIR sensor, lights can be shut off just minutes after the occupant leaves saving hours of wasted lighting energy each day. Classrooms large and small require the ability to detect minor motion. Ceiling mounted dual technology sensor models are preferred to get complete room detection. In larger rooms a second sensor and power pack could be added for multizone control. In private offices, use a PIR or dual tech sensor depending on room layout and field of view. Take advantage of the integrated light level feature to keep lights off when sufficient daylight is present. Lighting in restrooms is best controlled with ultrasonic sensors to eliminate hundreds or even thousands of hours of unneeded on-time during a year. A ceiling-mounted ultrasonic senses motion around restroom stalls for greater coverage area. For the open or partitioned office spaces, either the dual tech or ultrasonic type may be appropriate. Wall mounted or on the ceiling, expand coverage of large spaces by linking multiple sensors together to control lighting in a coordinated way. Use these sensors to cover the area in zones with 10-20% overlap as illustrated above. PRIVATE OFFICES CONFERENCE ROOMS 5 REST ROOMS CLOSETS / STORAGE OPEN OFFICES CLASSROOMS
  • 7. Understanding daily space usage patterns are essential to properly apply occupancy sensing in a commercial building space. If you are able to answer “YES” to some of the following questions, adding occupancy sensors are a viable control option. + Are there periods of time when the space is unoccupied? + Is energy wasted due to lights being left on when no one is in the space? + Are lights left on after business hours? + Is the space used only intermittently? + Could some or all area lights be turned off during the day? DESIGNING WITH OCCUPANCY SENSORS 4 STEP DESIGN PROCESS Evaluate Space Needs Match with Best Technology Layout & Specify Install & Con gure “Are Occupancy Sensors The Correct Control Strategy For Your Space?” 1. EVALUATE SPACE NEEDS The following space characteristics are of particular importance because of the influence they have when making a sensor selection: + Room / Space dimensions and shape + Location of main occupant activity + Location of walls, doors, windows and drapes + Location of desks / workspaces and orientation with regard to walls and partitions + Ceiling heights, partition heights and locations + Location of file cabinets, large furniture, large equipment or shelves + Large objects that could block or alter a sensor coverage area + Available daylight for added light level sensing + Make note of high levels of air flow or vibrations noting the location of HVAC ducts and fans PerfectSense ® 6
  • 8. 2. MATCH SENSING TECHNOLOGY Tip: Choose the sensing technology that best meets space needs and characteristics Location Passive Infrared (PIR) Ultrasonic Dual Technology Sensor Type Classroom X C Hallway X C Private O ce X X C,WS Conference Room X X C,WS Open O ces X X C,WM Lecture Hall X C,WM Library X C Rest Room X X C,WS Lobby X X C,WM,WS Storage X X C,WM,WS Warehouse X WS Closet X X WS Cafeteria X X C Coverage Type Acceptable Application Qualities Unacceptable Application Qualities Wall Switches Line of sight with clear cuto smaller enclosed spaces Very low motion levels by occupants or obstacles blocking sensor view Ceiling / Wall Sensors Line of sight with clear cuto spaces where a sensor has a view of activity Very low motion levels by occupants or obstacles blocking sensor view Wall Switches No clear cuto smaller enclosed spaces High level of air ow Ceiling / Wall Sensors Volumetric in space with no clear cuto open spaces, and spaces with obstacles High ceilings and high levels of vibration or air ow Wall Switches Complete Coverage spaces with low or variable motion levels by occupants High level of air ow Ceiling / Wall Sensors Complete Coverage spaces with low or variable motion levels by occupants High level of air ow PIRUltrasonicDualTech Occupancy Sensor Technology Selection Matrix Technology / Product Type Common Locations TIP: Use this reference list to identify the commonly used products for your applications 7 C= Ceiling Mount WM= Wall Mount WS= Wall Switch X
  • 9. 3. LAYOUT & SPECIFICATION COVERAGE PATTERNS Once the technology is chosen, the next step is to select the correct coverage size and shape. A typical design guideline will call for a minimum of 90% coverage area of the square footage in a room. Each product cut sheet includes specific coverage area specifications. It’s important to know the typical use of space. Will occu- pants be engaged in major motions (walking, using a forklift) or minor motion (reading, typing). Coverage changes depending on motion type. NEMA TESTING PerfectSense understands the importance in producing the highest quality products. When it comes to occupancy sensors, that means producing sensors with consistent detection while reducing False Triggers. All PerfectSense products are designed to meet and exceed the quality and consistency standards set forth in the National Electrical Manufacturers Association guide publication. The NEMA guide establishes two testing parameters as major and minor motion detection. It defines minor motion as the movement of a person sitting at a desk reaching for a telephone, turning the pages of a book, opening a file folder, or picking up a coffee cup. Major motion is defined as the movement of a person walking in or through a space. CHOOSE POWER PACKS Power packs are a necessary component providing three core purposes to most occupancy sensor projects. Power packs provide power to low voltage sensors and other control devices, respond to signals from those devices and switch their internal relays to control the connected loads. Power packs can also provide advanced features such as switch inputs, inputs for scheduling, and dimming control. Before selecting a power pack, consider the following factors. Voltage: Pay attention to the input ratings of each power pack model. Low voltage output needs: Typically listed in (mA) be sure the power pack provides enough current to power all of the connected devices for that zone. Relay ratings: Power Packs have specific ratings for different load types (i.e., incandescent, fluorescent, motor). Make sure the relay is rated for the type of load to be controlled and the load being switched does not exceed the load rating of the power pack. To protect against the potentially damaging effects of high inrush current common in newer electronic ballasts, select power packs with zero crossing circuitry technology. Feature Bene t Isolated Relay Enables interfacing with facility HVAC, BMS or monitoring systems Light Level Sensing Increased energy savings in areas with signi cant natural light Terminal Wiring Simpli ed installation Manual-ON/Auto-ON Options to meet code and maximize energy savings in di erent applications Dual Relays Enables bi-level switching for increased energy savings and code compliance Zero Crossing Reduces stress on sensor relays and increases sensor life LED Operation LED indicators will ash when motion is detected with each technology Low Voltage Flexibility for installation location and wiring Line Voltage No need for power pack device Adaptive Technology Monitors activity patterns over time to auto adjust o time for maximized energy savings Walk-Through Mode Additional energy savings by turning lights o after brief occupancy Alerts Audible warning of impending shuto Multi-way Capability Facilitates control in spaces with multiple entrances Lamp Saver For bi-level lighting: alternates the load that turns on each time the lights turn on. Test Mode Temporary setting used to test coverage area typically expires after 15 minutes Common Features TIP: Use this reference list to identify the desired features for your applications DESIGNING WITH OCCUPANCY SENSORS Note: not all sensors contain all features, refer to specification for complete details 8
  • 10. 4. INSTALL & CONFIGURE INSTALL THE SENSOR During installation contractors should position the sensor so it has the best view of the entire coverage area, while minimizing the possibility of false ON and OFF triggers. Wire sensors according to instructions. This will eliminate any functional problems or sensor damage. If necessary, adjust sensor settings such as the sensitivity, time delay or daylight sensing to match the activity levels of the space being controlled. Be sure to increase the off time delay setting for spaces where minor motion and limited activity will be taking place to further reduce the risk of false offs. For increased energy efficiency shorten off time delay settings especially for areas of high traffic. For restrooms, stairwells or areas with limited or no natural lighting use caution and set longer off time delays to ensure occupant safety and secu- rity. MOUNTING SENSORS PerfectSense products fall into three categories of mounting: Ceiling, Wall, and Wall Switch types. Only wall mount types may be mounted on both the wall or the ceiling. This is important for applications where one of the surfaces may be unsuitable for sensor installation. MOUNTING POWERPACKS Power packs are often mounted to the outside of a junction box, placing them in the plenum space, so make sure the power pack is plenum rated. Smaller power packs can be installed inside a standard junc- tion box. WIRING POWERPACKS Intelligent power packs provide inputs so that multiple control devices can be connected. This enables customiza- tion of control scenarios for different applications and end user preferences. Use intelligent power packs when multi-device, manual switching, and dimming applica- tions are desired. PHOTOCELL CONTROLS Most occupancy sensors include an integrated daylight sensor to be used in building spaces that receive daylight. This function is designed to ensure the occupancy sensors will keep lights off in occupied spaces, when the natural daylight coming into the space exceeds the set threshold. If a space has inadequate natural daylight the occupancy sensor will turn lighting on. PROGRAMMING AND TESTING Make post-installation adjustment as needed. This is not uncommon and is often due to last minute changes in placement of furniture or fixtures. A walk test of the detec- tion area is a common method of ensuring the sensor is located and configured properly for the space. TIP: Double check specified sensor location prior to installation TIP: Wire according to instructions for proper power pack and sensor function 9 DESIGNING WITH OCCUPANCY SENSORS
  • 11. 10 INTEGRATING SENSORS WITH CONTROLS Occupancy sensors that operate independently in a space, are referred to as “stand alone” sensors providing no infor- mation of occupancy status to other building systems. To increase control and energy savings, PerfectSense low voltage occupancy sensors include isolated Form C relays to seamlessly integrate with Building Management Systems (BMS), HVAC (VAV controllers) or NexLight 2-Wire Lighting Controls Systems. These relays providing real time occupancy status “intelligence” to other systems, adding signifcantly to a building wide control strategy and potential savings. PerfectSense has the industries only sensor with multiple relay outputs for greater connectivity to building controls. MULTILAYERED CONTROL STRATEGY For the next level of efficiency, consider combining occu- pancy sensors with other controls such as lighting control panels or daylight harvesting controls. A multilayered control strategy can assist in meeting energy codes and green sustainability guidelines as well as provide maxi- mized energy savings. The images below illustrate an example of how a low voltage sensor could be networked to a building BMS or 2-Wire lighting control system. See page 45 for Stand-Alone Control Scenarios. PerfectSense ® Room Control with Manual-On + BMS Status Networked Room Control with Manual-On Extreme Reliability TM Lighting Control Systems Your Source for Design Built Systems PANELS | SWITCHES | SENSORS NexLight 2-Wire Networked Lighting Control System STAND ALONE VS. NETWORKED SYSTEMS E FA Line Voltage Class 1 Low Voltage Class 2 (16awg 3-wire) Low Voltage Class 2 (16awg 2-wire) WIRING KEY A E A F Power Pack Ceiling Sensor 1-Button Low Voltage Switch 2-Wire Panel 2-Wire Switch CBA Line Voltage Class 1 Low Voltage Class 2 (16awg 4-wire*) Low Voltage Class 2 (NexLight 2-wire Bus) WIRING KEY A C A A B Occupancy / Vacancy Sensor * for 50%on/all off commands add one additional wire A To CPU or Panel To CPU or Panel to BMS or HVAC
  • 12. PerfectSense ® Intelligent Building Occupancy Sensors PS-PWS1277 | PS-PWD1277 Commercial Grade Occupancy Sensor Passive Infrared (PIR) | Wall Switch | Line Voltage Specifications Coverage Area: 1000 sq. ft. Input: 120–277Vac +/-10% 50/60Hz Output: 120Vac - 1000W max. tungsten incandescent load - 1000VA max. ballast load - 1/4 hp max. motor load - No minimum load required 277Vac - 1800 VA max. ballast load - No minimum load required Temperature: 32 to 122°F (0 to 50°C) Humidity: 0% to 90% RH non-condensing Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes Test mode: 15 seconds Walk through mode: 2 minutes if no activity is detected after 30 seconds Compliances: UL and cUL Listed Title 24 Compliant FCC part 15 (Class B) Light level Adjustment: 0.5 to 250 footcandles (FC) Detection: 180° passive infrared (PIR) Audible alert: Selectable Service Switch: OFF/Auto/ON Manual operation: Pushbutton ON/OFF Lens: Impact resistant Relay Switching: 0° +/- 500uS Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in. (104 x 44 x 49mm) PS-PWS1277W PS-PWD1277W Overview • • • • • • • • The Commercial Grade PIR Wall Switch Occupancy Sensor provides automatic control of loads by detecting motion and ambient light within the detection area. Sensor features include: One or Two separate relay circuits for independently switching loads (typically lighting loads) ON or OFF. 180° motion detection using passive infrared (PIR) technology. Superior lens design to provide high resolution for detecting major and minor motion. Advanced logic enhances energy savings and user convenience. Convenient pushbuttons for manual control. Automatic adaptive technology adjusts the time delay for maximum energy savings. Automatic 15 second test mode. Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns loads OFF. Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting applications (2 Circuit model only). • • 11 Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568
  • 13. NOTE: Coverage area may vary depending upon the shape, size, and absorbent properties of the room. Detection Range and Coverage Area Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PS - P W S 1277 X Technology D= Dual Tech U= Ultrasonic P= Passive Infrared (PIR) Mounting W= Wall Switch Power 1277= Line Voltage Color W= White I= Ivory L= Light Almond G= Gray B= Black Circuits S= Single (1) D= Dual (2) Wiring Diagrams- 2 Circuits Color Reference: BK = Black GN = Green R = Red BL = Blue BR = Brown 12 Wiring Diagram- 1 Circuit Order Information- Wall Switch Series
  • 14. PerfectSense ® Intelligent Building Occupancy Sensors PS-UWS1277 | PS-UWD1277 Commercial Grade Occupancy Sensor Ultrasonic Technology | Wall Switch | Line Voltage Overview • • • • • • • • Specifications Coverage Area: 500 sq. ft. Input: 120–277Vac +/-10% 50/60Hz Output: 120Vac - 1000W max. tungsten incandescent load - 1000VA max. ballast load - 1/4 hp max. motor load - No minimum load required 277Vac - 1800 VA max. ballast load - No minimum load required Temperature: 32 to 122°F (0 to 50°C) Humidity: 0% to 90% RH non-condensing Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes Test mode: 15 seconds Walk through mode: 2 minutes if no activity is detected after 30 seconds Compliances: UL and cUL Listed Title 24 Compliant FCC part 15 (Class B) Light level Adjustment: 0.5 to 250 footcandles (FC) Detection: 180° ultrasonic (US) Audible alert: Selectable Service Switch: OFF/Auto/ON Manual operation: Pushbutton ON/OFF Lens: Impact resistant Ultrasonic Transducer: 40kHz Relay Switching: 0° +/- 500uS Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in. (104 x 44 x 49mm) PS-UWS1277W PS-UWD1277W The Ultrasonic Wall Switch Occupancy Sensor provides automatic control of lighting by detecting motion and ambient light within the detection area. Sensor features include: One or Two separate relay circuits for independently switching loads (typically lighting loads) ON or OFF 180° motion detection using ultrasonic (US) technology. Superior ultrasonic transducers provide high resolution for detecting major and minor motion. Advanced logic enhances energy savings and user convenience. Convenient pushbutton for manual control. Automatic adaptive technology adjusts the time delay for maximum energy savings. Automatic 15 second test mode. Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns loads OFF. Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting applications (2 Circuit model only). • Phone: 218.828.3700 www.nexlight.com Fax: 218.824.156813
  • 15. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 NOTE: Coverage area may vary depending upon the shape, size, and absorbent properties of the room. Detection Range and Coverage Area Wiring Diagram- 1 Circuit Order Information- Wall Switch Series PS - U W S 1277 X Technology D= Dual Tech U= Ultrasonic P= Passive Infrared (PIR) Mounting W= Wall Switch Power 1277= Line Voltage Color W= White I= Ivory L= Light Almond G= Gray B= Black Circuits S= Single (1) D= Dual (2) Wiring Diagrams- 2 Circuits Color Reference: BK = Black GN = Green R = Red BL = Blue BR = Brown Both models provide major motion detection up to 500 sq. ft., and minor motion detection up to 300 sq. ft. 14
  • 16. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-DWS1277 | PS-DWD1277 Commercial Grade Occupancy Sensor Dual Technology | Wall Switch | Line Voltage Overview • • • • • • • • Specifications Coverage Area: 1000 sq. ft. Input: 120–277Vac +/-10% 50/60Hz Output: 120Vac - 1000W max. tungsten incandescent load - 1000VA max. ballast load - 1/4 hp max. motor load - No minimum load required 277Vac - 1800 VA max. ballast load - No minimum load required Temperature: 32 to 122°F (0 to 50°C) Humidity: 0% to 90% RH non-condensing Time Delay: Initial Minimum: 5, 10, 15, or 30 minutes Test mode: 15 seconds Walk through mode: 2 minutes if no activity is detected after 30 seconds Compliances: UL and cUL Listed Title 24 Compliant FCC part 15 (Class B) Light level Adjustment: 0.5 to 250 footcandles (FC) Detection: 180° passive infrared (PIR) Audible alert: Selectable Service Switch: OFF/Auto/ON Manual operation: Pushbutton ON/OFF Lens: Impact resistant Ultrasonic Transducer: 40kHz Relay Switching: 0° +/- 500uS Dimensions: (H x W x D): 4.1 x 1.7 x 1.9in. (104 x 44 x 49mm) PS-DWS1277W PS-DWD1277W The Dual Technology Wall Switch Occupancy Sensor provides automatic control of lighting by detecting motion and ambient light within the detection area. Sensor features include: One or Two separate relay circuits for independently switching loads (typically lighting loads) ON or OFF 180° motion detection using passive infrared (PIR) and ultrasonic technology. Superior lens design and ultrasonic transducers to provide high resolution for detecting major and minor motion. Advanced logic enhances energy savings and user convenience. Convenient pushbutton for manual control. Automatic adaptive technology adjusts the time delay for maximum energy savings. Automatic 15 second test mode. Service Switch (OFF/Auto/ON). Audible alert 10 seconds before sensor turns loads OFF. Advanced Lamp Saver mode extends the lamp life in 50/50 bi-level lighting applications (2 Circuit model only). • 15
  • 17. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 NOTE: Coverage area may vary depending upon the shape, size, and absorbent properties of the room. Detection Range and Coverage Area Wiring Diagram- 1 Circuit Order Information- Wall Switch Series PS - D W S 1277 X Technology D= Dual Tech U= Ultrasonic P= Passive Infrared (PIR) Mounting W= Wall Switch Power 1277= Line Voltage Color W= White I= Ivory L= Light Almond G= Gray B= Black Circuits S= Single (1) D= Dual (2) Wiring Diagrams- 2 Circuits Color Reference: BK = Black GN = Green R = Red BL = Blue BR = Brown Both models provide major motion detection up to 1000 sq. ft., and minor motion detection up to 300 sq. ft. 16
  • 18. Specifications Features Overview PS-CPS1000 Standard Range 360˚ Sensor PIR Detection | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 21mA Isolated Relay: Form C Contacts for Class 2 signaling 1A @24VDC Resistive Output: 24VDC active high logic control signal with short circuit protection Controls: Passive Infrared Sensitivity: 600-1000 sq. ft Adjustable Sensitivity of (60-100% of Max. Coverage) Time Delay: 15 sec. - 30 min. Light Sensor: 0.5-250 foot candles Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 32ºF to 122ºF Humidity: 0-90% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.5 in Height 1.75 in The Ceiling-mounted Passive Infrared (PIR) Occupancy Sensor accurately detects occupancy and automatically switches lighting on and off as needed. This low profile sensor is ceiling mounted for superior motion detection. With a 360 degree field of view and up to 1000 square feet of coverage area, the Ceiling-mounted PIR Occupancy Sensor is ideal for offices, conference rooms and hallways. Ceiling-mount sensors also incorporate an integral light level sensor to prevent lighting from switching On when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to drop ceilings and features front located adjust- ments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. • 1000 sq. ft. coverage area • 360 degree field of view • Light level sensing (from 0.5 to 250 foot-candles) • Adjustable time delay (pre-set time delays from 15 seconds to 30 minutes) • Automatic adaptive technology adjusts the time delay for maximum energy savings. • Adjustable sensitivity (from 60 to 100%) • Isolated relay • Red LED motion indicator blinks to indicate motion detection • Adjustment compartment cover equipped with retention feature • Manual bypass • UL®/cUL Listed • Title 24 Certified • Meets ASHRAE 90.1 requirements • Five-year warranty PerfectSense ® Intelligent Building Occupancy Sensors 17
  • 19. Wiring Diagrams DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor PS-CUS800 40kHz 180˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height PIR Sensor Field of View Detection Range and Coverage Area Ordering Information Neutral Hot RED BLACK BLUE BLACK WHITE RED SENSOR LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V * Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 GREEN(N.C.) YELLOW (COMMON) ORANGE(N.O) 18
  • 20. Specifications Features Overview PS-CUS800 Standard Range 180˚ Sensor Ultrasonic Technology | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 30mA Isolated Relay: Form C Contacts for Class 2 signaling 1A @24VDC Resistive Output: 24VDC active high logic control signal with short circuit protection Controls: Passive Infrared Sensitivity: 600-1000 sq. ft Adjustable Sensitivity of (60-100% of Max. Coverage) Time Delay: 15 sec. - 30 min. Light Sensor: 0.5-250 foot candles Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 32ºF to 122ºF Humidity: 0-90% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.5 in Height 1.75 in The 180 Degree Ceiling-Mounted Occupancy Sensors are ideal for use in business and office settings to accurately detect occupancy and automatically control lighting. The ceiling-mount design of these low-profile sensors allows the greatest possible motion sensitivity. An adjustment panel is conveniently located on the front of the sensor, providing ready access to setting controls after the sensor is installed. These occupancy sensors are available in the ultrasonic and dual technology models. The dual technology model employs passive infrared (PIR) and ultrasonic technology. Installation and configuration is simple. The sensor readily mounts to drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. • 1000 sq. ft. coverage area • 180° degree field of view • Light level sensing (from 0.5 to 250 foot-candles) • Adjustable time delay (pre-set time delays from 15 seconds to 30 minutes) • Automatic adaptive technology adjusts the time delay for maximum energy savings. • Adjustable sensitivity (from 60 to 100%) • Isolated relay •LED motion indicator • Adjustment compartment cover equipped with retention feature • Manual bypass • UL®/cUL Listed • Title 24 Certified • Meets ASHRAE 90.1 requirements • Five-year warranty PerfectSense ® Intelligent Building Occupancy Sensors 19
  • 21. Detection Range and Coverage Area Ordering Information Ultrasonic Sensor Field of View DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor PS-CUS800 40kHz 180˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White PIR Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V * Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 SENSOR GREEN(N.C.) YELLOW (COMMON) ORANGE(N.O) 20 Wiring Diagrams
  • 22. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 34mA Nominal (125mA max) Isolated Relay: Form C Contacts for Class 2 signaling 1A @24VDC Resistive Output: 24VDC active high logic control signal with short circuit protection Controls: Adjustable Sensitivity of (60-100% of Max. Coverage) Time Delay: 15 sec. - 30 min. Light Sensor: 0.5-250 foot candles Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 32ºF to 122ºF Humidity: 0-90% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.5 in Height 1.25 in PerfectSense ® Intelligent Building Occupancy Sensors The Ceiling-mounted Ultrasonic Occupancy Sensor accurately detects occupancy and automatically switches lighting on and off as needed. This low profile sensor is ceiling mounted for superior motion detection. With a 360 degree field of view and up to 2000 square feet of coverage area, the Ceiling-mounted Ultrasonic Occupancy Sensor is ideal for storage rooms, bathrooms, conference rooms, classrooms, hallways, and open office areas. Ceiling-mount sensors also incorporate an integral light level sensor to prevent lighting from switching On when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to drop ceilings and features front located adjust- ments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. • 2000 sq. ft. coverage area • 360 degree field of view • Light level sensing (from 0.5 to 250 foot-candles) • Adjustable time delay (pre-set time delays from 15 seconds to 30 minutes) • Automatic adaptive technology adjusts the time delay for maximum energy savings. • Adjustable sensitivity (from 60 to 100%) • Isolated relay • Red LED motion indicator blinks to indicate motion detec- tion • Adjustment compartment cover equipped with retention feature • Manual bypass • UL®/cUL Listed • Title 24 Certified • Meets ASHRAE 90.1 requirements • Five-year warranty 21 Specifications Features Overview PS-CUS2000 Standard Range 360˚ Sensor Ultrasonic Detection | Ceiling Mount | Low Voltage
  • 23. Wiring Diagrams Detection Range and Coverage Area Ordering Information DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V * Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Field of View (Top) SENSOR 22
  • 24. PS-DTC24 Standard Range 360˚ Sensor Dual Technology | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Specifications Features 360˚ Coverage Pattern 100% Digital Multiview TM PIR Dual technology uses PIR + U/S Superior RF immunity Adjustable Time Delay (30 sec-30 min) Single Technology Mode SmartSense TM Adapt Mode Walk Through Mode Daylight Override Mode Simple Test Mode Mounts in drop ceilings and solid ceilings LED’s provide indication of occupancy sensing Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 30mA Output: 24VDC active high logic control signal with short circuit protection Wiring Diagram: See Fig. 2 Controls: Passive Infrared Sensitivity: 0-100% (Factory Set 50%) Ultrasonic Sensitivity: 0-100% (Factory Set 50%) Light Sensor: 20-320 LUX (Factory Disables) Detection Range: See Fig. 1 Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 14ºF to 122ºF Humidity: 0-95% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.33 in Height 2.2 in Supported with a limited 5-year warranty Title 24 Compliant Meets ASHRAE 90.1 requirements PerfectSense ® Intelligent Building Occupancy Sensors Overview: The PS-DTC24 increases area lighting energy efficiency quickly and easily by combining industry leading Passive Infrared (PIR) technology with Ultrasonic for superior detection. Factory preset to deliver significant savings out of the box, this sensor has additional options to further increase energy savings if desired. The PerfectSense PS-DTC24 is a low-voltage sensor that works with PerfectSense class 2 power supply (PSPP1277), to automatically control lighting. The sensor turns the lights on and keeps them on when occupancy is detected and will turn the lights off after the delayed-off time has expired. Operation: The sensor first sees motion using the PIR detection and then activates Ultrasonic to confirm and indicate continued occu- pancy. The standard factory programming is set to meet the standards of most common area applications with a 10 minute off delay time. Additional Operational Features: Walk-Through Mode: useful when a room is momentarily occupied, like a storage area. When a person enters the room, the lights turn on. If the person leaves the room before the 2.5 minute walk-through timer expires the sensor will turn the lights off. If the person stays in the room longer than 2.5 minutes the sensor will proceed to standard operation. Single-Tech Mode: Only one technology is active in this mode. Dip switch selectable, a user may determine that the space may only require one technology to properly detect the area. One sensor model can now act as a PIR only, Ultrasonic only or Dual-tech sensor. Daylight Sensor: The integrated daylight sensor allows for ambient light override functionality. If this setting is enabled, the controlled lighting load will only turn on if the ambient light present is less than the preset level. Adaptive Learning: Patented adaptive learning technology will automatically increase or decrease the off delay time in response to the occupancy and environmental conditions of the area over a period of time. For example, if there is frequent motion detection, the sensor will automatically shorten the off delay time to better meet the conditions of the room. This technology also detects false off conditions. If this happens, the off delay time duration will immediately be lengthened to avoid future false off conditions. 23
  • 25. Wiring Diagrams Detection Range and Coverage Area Ordering Information Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PIR Major Motion Ultrasonic Minor Motion Ultrasonic Major Motion 0ft 0m 8 2.4 10 3 12 3.7 0ft 0m 6 12 18 246121824 1.8 3.7 5.5 7.31.83.75.57.3 SIDE VIEW DETECTION AREA PIR Minor Motion TOP VIEW 26 ft.12 ft. 32 ft. 26 ft. 24 ft. 38 ft. DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Field of View (Top) Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V SENSOR 24
  • 26. PS-DTC24-R Standard Range 360˚ Sensor Dual Technology | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Specifications Features 360˚ Coverage Pattern 100% Digital Multiview TM PIR Dual technology uses PIR + U/S Superior RF immunity Adjustable Time Delay (30 sec-30 min) Single Technology Mode SmartSense TM Adapt Mode Walk Through Mode Daylight Override Mode Simple Test Mode Mounts in drop ceilings and solid ceilings LED’s provide indication of occupancy sensing Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 30mA Output: 24VDC active high logic control signal with short circuit protection Isolated Relays: 2 SPDT 1 Amp, 30 VDC Form C Wiring Diagram: See Fig. 2 Controls: Passive Infrared Sensitivity: 0-100% (Factory Set 50%) Ultrasonic Sensitivity: 0-100% (Factory Set 50%) Light Sensor: 20-320 LUX (Factory Disables) Detection Range: See Fig. 1 Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 14ºF to 122ºF Humidity: 0-95% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.33 in Height 2.2 in Supported with a limited 5-year warranty Title 24 Compliant Meets ASHRAE 90.1 requirements PerfectSense ® Intelligent Building Occupancy Sensors Overview: The PS-DTC24-R increases area lighting energy efficiency quickly and easily by combining industry leading Passive Infrared (PIR) technology with Ultrasonic for superior detection. Provides 2 SPDT 1 Amp, 30 VDC Form C relay contacts for integration with Nexlight Full 2-Way system and BMS systems. Factory preset to deliver significant savings out of the box, this sensor has additional options to further increase energy savings if desired. The PerfectSense PS-DTC24-R is a low-voltage sensor that works with PerfectSense class 2 power supply (PSPP1277), to automati- cally control lighting. The sensor turns the lights on and keeps them on when occupancy is detected and will turn the lights off after the delayed-off time has expired. Operation: The sensor first sees motion using the PIR detection and then activates Ultrasonic to confirm and indicate continued occu- pancy. The standard factory programming is set to meet the standards of most common area applications with a 10 minute off delay time. Additional Operational Features: Walk-Through Mode: useful when a room is momentarily occu- pied, like a storage area. When a person enters the room, the lights turn on. If the person leaves the room before the 2.5 minute walk-through timer expires the sensor will turn the lights off. If the person stays in the room longer than 2.5 minutes the sensor will proceed to standard operation. Single-Tech Mode: Only one technology is active in this mode. Dip switch selectable, a user may determine that the space may only require one technology to properly detect the area. One sensor model can now act as a PIR only, Ultrasonic only or Dual- tech sensor. Daylight Sensor: The integrated daylight sensor allows for ambi- ent light override functionality. If this setting is enabled, the controlled lighting load will only turn on if the ambient light present is less than the preset level. Adaptive Learning: Patented adaptive learning technology will automatically increase or decrease the off delay time in response to the occupancy and environmental conditions of the area over a period of time. For example, if there is frequent motion detec- tion, the sensor will automatically shorten the off delay time to better meet the conditions of the room. This technology also detects false off conditions. If this happens, the off delay time duration will immediately be lengthened to avoid future false off conditions. 25
  • 27. Wiring Diagrams Detection Range and Coverage Area Ordering Information Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 NORMALLY CLOSED COMMON NORMALLY OPEN NORMALLY OPEN COMMON NORMALLY CLOSED PIR Major Motion Ultrasonic Minor Motion Ultrasonic Major Motion 0ft 0m 8 2.4 10 3 12 3.7 0ft 0m 6 12 18 246121824 1.8 3.7 5.5 7.31.83.75.57.3 SIDE VIEW DETECTION AREA PIR Minor Motion TOP VIEW 26 ft.12 ft. 32 ft. 26 ft. 24 ft. 38 ft. DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Field of View (Top) Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V SENSOR 26
  • 28. Specifications Features Overview PS-CDS800 Standard Range 180˚ Sensor Dual Technology | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 33mA Isolated Relay: Form C Contacts for Class 2 signaling 1A @24VDC Resistive Output: 24VDC active high logic control signal with short circuit protection Controls: Passive Infrared Sensitivity: 600-1000 sq. ft Adjustable Sensitivity of (60-100% of Max. Coverage) Time Delay: 15 sec. - 30 min. Light Sensor: 0.5-250 foot candles Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 32ºF to 122ºF Humidity: 0-90% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.5 in Height 1.75 in The 180 Degree Ceiling-Mounted Occupancy Sensors are ideal for use in business and office settings to accurately detect occupancy and automatically control lighting. The ceiling-mount design of these low-profile sensors allows the greatest possible motion sensitivity. An adjust- ment panel is conveniently located on the front of the sensor, providing ready access to setting controls after the sensor is installed. These occupancy sensors are available in the ultrasonic and dual technology models. The dual technology model employs passive infrared (PIR) and ultrasonic technology. Installation and configuration is simple. The sensor readily mounts to drop ceilings and features front located adjust- ments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. • 1000 sq. ft. coverage area • 180° degree field of view • Light level sensing (from 0.5 to 250 foot-candles) • Adjustable time delay (pre-set time delays from 15 seconds to 30 minutes) • Automatic adaptive technology adjusts the time delay for maximum energy savings. • Adjustable sensitivity (from 60 to 100%) • Isolated relay •LED motion indicator • Adjustment compartment cover equipped with retention feature • Manual bypass • UL®/cUL Listed • Title 24 Certified • Meets ASHRAE 90.1 requirements • Five-year warranty PerfectSense ® Intelligent Building Occupancy Sensors 27
  • 29. Wiring Diagrams Detection Range and Coverage Area Ordering Information DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Dual Technology Sensor Field of View Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V * Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 SENSOR GREEN(N.C.) YELLOW (COMMON) ORANGE(N.O) 28
  • 30. Specifications Features Overview PS-CDS2000 Standard Range 360˚ Sensor Dual Technology | Ceiling Mount | Low Voltage Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Electrical: Power Requirements: 24VDC, from powerpack Current Consumption: 37mA Nominal (125mA max) Isolated Relay: Form C Contacts for Class 2 signaling 1A @24VDC Resistive Output: 24VDC active high logic control signal with short circuit protection Controls: Adjustable Sensitivity of (60-100% of Max. Coverage) Time Delay: 15 sec. - 30 min. Light Sensor: 0.5-250 foot candles Load Rating: Controls Class 2 Power Pack Housing Material: High-Impact ABS Color: White Environment Temperature: 32ºF to 122ºF Humidity: 0-90% Non Condensing Installation: See Install Instructions Dimensions: Diameter 4.5 in Height 1.25 in PerfectSense ® Intelligent Building Occupancy Sensors The Ceiling-mounted Dual Tech Occupancy Sensor accurately detects occupancy and automatically switches lighting on and off as needed. This low profile sensor is ceiling mounted for superior motion detection. With a 360 degree field of view and up to 2000 square feet of coverage area, the Ceiling-mounted Occupancy Sensor is ideal for storage rooms, bathrooms, conference rooms, classrooms, hallways, and open office areas. Ceiling-mount sensors also incorporate an integral light level sensor to prevent lighting from switching On when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to drop ceilings and features front located adjust- ments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. • 2000 sq. ft. coverage area • 360 degree field of view • Light level sensing (from 0.5 to 250 foot-candles) • Adjustable time delay (pre-set time delays from 15 seconds to 30 minutes) • Automatic adaptive technology adjusts the time delay for maximum energy savings. • Adjustable sensitivity (from 60 to 100%) • Isolated relay • LED motion indicator • Adjustment compartment cover equipped with retention feature • Manual bypass • UL®/cUL Listed • Title 24 Certified • Meets ASHRAE 90.1 requirements • Five-year warranty 29
  • 31. Wiring Diagrams Detection Range and Coverage Area Ordering Information DESCRIPTION CATALOG # OPERATING COVERAGE* COLOR FREQUENCY Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS2000 40kHz 360˚ 2000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS2000 40kHz 360˚ 2000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor PS-DTC24 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-DTC24-R 40kHz 360˚ 1000sf White Dual Tech Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CDS800 40kHz 180˚ 1000sf White Ultrasonic Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CUS800 40kHz 180˚ 1000sf White PIR Ceiling Mounted Low Voltage Occupancy Sensor w/Relay PS-CPS1000 NA 360˚ 1000sf White Power Pack (Required for operation) *all coverage areas are based on a standard 9 ft mounting height Neutral Hot RED BLACK BLUE BLACK WHITE RED LOAD +24v COMMON CONTROL Power Pack PS-PP1277 120V 277V * Control power must be provided by PerfectSense Power Pack PS-PP1277 or an approved equivalent. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Field of View (Top) SENSOR GREEN(N.C.) YELLOW (COMMON) ORANGE(N.O) 30
  • 32. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-WPS1500 Commercial Grade Occupancy Sensor Wall Mounted | Low Voltage | Passive Infrared Coverage Areas: Wide Angle: 2500 sq. ft. @ 8 ft. high (All 3 lenses included) Long Range: 102 linear ft. @ 10 ft. high High Bay: 54 linear ft. @ 30 ft. high Field of view: 110° Ambient light level sensing: 0.5 to 250 foot-candles Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes Adjustable sensitivity: 60%-100% independent adjustment for US and PIR Adaptive Technology: Automatically adjusts the time delay for maximum energy savings LED Motion Indicators: Red=PIR motion indicator Current Consumption @ 24Vdc*: 21mA Nominal Isolated Relay: 1A @ 24 Vdc Resistive Operating Temperature: 32 - 122° F (0 - 50° C) Maximum Humidity: 90% RH Non-condensing Standards: UL®/cUL Listed FCC: Part 15, Class B Title 24 Certified Specifications Wall-Mounted Passive Infrared (PIR) Occupancy Sensor accurately detects occu- pancy and automatically switches lighting on and off as needed. This sensor is wall- or ceiling-mounted for superior motion detection. The PIR Occupancy Sensor has three interchangeable lenses included for custom coverage patterns. The Wide Angle lens has a 2500 square foot coverage area when the sensor is mounted 8 feet high, the Long Range lens has a 102 linear foot coverage area at 10 ft. high and the High Bay lens has a 54 linear foot coverage area at 30 ft. high. With a 110 degree field of view the Wall-Mounted PIR Occu- pancy Sensor is ideal for warehouse, business, and office settings. Wall-mount sensors also incorporate an integral light level sensor to prevent lighting from switching On when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to walls as well as drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security, and HVAC systems. 31 Overview
  • 33. Detection Range and Coverage Area Wiring Color Table Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 CLASS 2 DEVICE WIRING ONLY Do not reclassify and install as Class 1, 3, or Power and Lighting wiring. To be connected to a Class 2 power source only. Wiring connections shall be rated suitable for the wire size employed. Failure to follow this instruction can result in personal injury or equipment or property damage. Wire Color Function Black 0 VDC Red +24 VDC Green Isolated contact NC Yellow Isolated contact common Orange Isolated contact NO Blue Control output *Confirm the Sensor is connected to the Class 2 side of the Power Pack. Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information. Wiring the Sensor • • • PS-PP1277 Ordering Information Description Catalog Number Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500 Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500 Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500 Power Pack (required) PS-PP1277 PIR (PS-WPS1500) Wide Angle Lens Long Range Lens High Bay Lens PerfectSense ® Intelligent Building Occupancy Sensors 32 Wall Mount Type
  • 34. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-WUS1500 Commercial Grade Occupancy Sensor Wall Mounted | Low Voltage | Ultrasonic Type Coverage Areas: 1000 sq. ft. major motion 500 sq. ft. minor motion Field of view: NA Ambient light level sensing: 0.5 to 250 foot-candles Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes Adjustable sensitivity: 60%-100% independent adjusment for US and PIR Adaptive Technology: Automatically adjusts the time delay for maximum energy savings LED Motion Indicators: Red=PIR motion indicator Current Consumption @ 24Vdc*: 34mA Nominal Isolated Relay: 1A @ 24 Vdc Resistive Operating Temperature: 32 - 122ºF (0 - 50ºC) Maximum Humidity: 90% RH Non-condensing Standards: UL®/cUL Listed FCC: Part 15, Class B Title 24 Certified Specifications Overview Wall-mounted Ultrasonic Occupancy Sensor accurately detects occupancy and automatically switches lighting on and off as needed. This low profile sensor is wall- or ceiling- mounted for superior motion detection over partitions and other common obstructions. With 1000 square feet of coverage area, the Wall-Mounted Ultrasonic Occupancy Sensor is ideal for storage rooms, hallways, bathrooms, conference rooms, classrooms and open office areas. Wall-mount sensors also incorporate an integral light level sensor to prevent lighting from switching on when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to walls or drop ceilings and features front located adjustments for setting sensitivity and time delay. Features an isolated relay for use with building automation, security and HVAC systems. 33
  • 35. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Detection Range and Coverage Area Ultrasonic (PS-WUS1500) CLASS 2 DEVICE WIRING ONLY Do not reclassify and install as Class 1, 3, or Power and Lighting wiring. To be connected to a Class 2 power source only. Wiring connections shall be rated suitable for the wire size employed. Failure to follow this instruction can result in personal injury or equipment or property damage. Wire Color Function Black 0 VDC Red +24 VDC Green Isolated contact NC Yellow Isolated contact common Orange Isolated contact NO Blue Control output *Confirm the Sensor is connected to the Class 2 side of the Power Pack. Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information. Wiring Color Table • • • PS-PP1277 Ordering Information Description Catalog Number Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500 Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500 Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500 Power Pack (required) PS-PP1277 NOTE: Coverage area may vary depending upon the shape, size, and absorbent properties of the room. PerfectSense ® Intelligent Building Occupancy Sensors 34 Wiring the Sensor Wall Mount Type
  • 36. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-WDS1500 Commercial Grade Occupancy Sensor Wall Mounted | Low Voltage | Dual Technology Coverage Area: 2500 sq. ft. @ 8 ft. high Field of view: 110° Ambient light level sensing: 0.5 to 250 foot-candles Adjustable Time Delay: Pre-set time delays from 15 seconds to 30 minutes Adjustable sensitivity: 60%-100% independent adjusment for US and PIR LED Motion Indicators: Red=PIR Green= Ultrasonic Manual Bypass: Switch selectable Adjusment cover: Front located Current Consumption @ 24Vdc*: 37mA Nominal Isolated Relay: 1A @ 24 Vdc Resistive Operating Temperature: 32 - 122ºF (0 - 50ºC) Maximum Humidity: 90% RH Non-condensing Standards: UL®/cUL Listed FCC: Part 15, Class B Title 24 Certified Specifications Overview The Wall-Mounted Dual Technology Occupancy Sensor employs both passive infrared (PIR) and ultrasonic technology to accurately detect occupancy and automatically turn on lighting. To reduce the occurrence of false on events, this sensor employs PIR technology to detect major motion. Once lighting has been turned on, it employs highly sensitive PIR and ultrasonic technology to detect minor motion and keep lighting on while areas remain occupied. When the room or area is no longer occupied, the sensor turns off lighting after a pre-set time delay. The low profile sensor is wall-mounted for greatest sensitivity to motion in large areas with obstructions. With a 110º degree field of view and up to 2500 square feet of coverage area when mounted at 8 ft. off the ground, the Wall-mounted Dual Technology Occupancy Sensor is ideal for conference rooms, classrooms, bathrooms, and large office areas. These wall-mount sensors also incorporate an integral light level sensor to prevent lighting from switching On when sufficient ambient light is present, such as is commonly found in windowed areas. Installation and configuration is simple. The sensor readily mounts to walls and drop ceilings and features front located adjustments for setting sensitivity and time delay. The sensor also features an isolated relay for use with building automation and HVAC systems. 35
  • 37. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Detection Range and Coverage Area Dual Technology (PS-WDS1500) CLASS 2 DEVICE WIRING ONLY Do not reclassify and install as Class 1, 3, or Power and Lighting wiring. To be connected to a Class 2 power source only. Wiring connections shall be rated suitable for the wire size employed. Failure to follow this instruction can result in personal injury or equipment or property damage. Wire Color Function Black 0 VDC Red +24 VDC Green Isolated contact NC Yellow Isolated contact common Orange Isolated contact NO Blue Control output *Confirm the Sensor is connected to the Class 2 side of the Power Pack. Refer to the Power Pack PS-PP1277 Instruction Bulletin for additional information. Wiring the Sensor Wiring Color Table • • • PS-PP1277 Ordering Information Description Catalog Number Wall Mounted Dual Technology Occupancy Sensor PS-WDS1500 Wall Mounted PIR Technology Occupancy Sensor PS-WPS1500 Wall Mounted Ultrasonic Technology Occupancy Sensor PS-WUS1500 Power Pack (required) PS-PP1277 PerfectSense ® Intelligent Building Occupancy Sensors 36 Wall Mount Type
  • 38. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-PP1277 Commercial Grade Power Pack • 100 mA power output can supply up to three sensors • Single-pole, normally open relay • Rated for plenum use • Relay rated for maximum 15 A tungsten and 20 A ballast loads • Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple Overview Features 120V 277V Relay White Line voltage 120/277 Vac Neutral Blue (Control) Black (Common) Red (+24 Vdc) Control Load TransformerVoltage selector Voltage selector Load Neutral Black Line voltage 120/277 Vac Control input +24 Vdc Blue Blk Red Common Hot White Red BlackHot Sensor Override OFF Red Storage Temperature: -20°F to 150°F (-29°C to 65°C) Operating Temperature: 32°F to 104°F (0°C to 40°C) Maximum Humidity: 90% non-condensing AC Power Input: 120 or 277 Vac ± 10%, 60 Hz Output Voltage: 24 Vdc Specifications The PerfectSense Power Pack has a line input of 120 or 277 Vac, and a single-pole, single-throw, relay output for the load. A full wave rectifier converts the AC line voltage to 24 Vdc to power a low-voltage sensor via Class 2, plenum-rated wire. The power pack can be mounted inside or outside of an electrical junction box. Be sure to observe all local codes when mounting and wiring a powerpack. Schematic Diagram System Diagram Output Current: 100 mA nominal Horsepower Rating: 1 hp @ 120 V Switching Capacity: 120 Vac, 60 Hz 15 A tungsten 1800 W 20 A ballast 277 Vac, 60 Hz 20 A ballast 37
  • 39. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 To sensor 120V 277V To sensor Line voltage Inside Installation Instructions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • The power pack must be installed and serviced only by qualified electrical personnel. • Turn off power at the circuit breaker before beginning installation. • Always use a properly rated voltage sensing device to confirm power is off. Failure to follow these instructions will result in death or serious injury. Mounting Examples 1. Provide separate overcurrent protection in accordance with the National Electrical Code® and applicable local codes. 2. Use copper wire only. 3. Confirm that the device rating is proper for your application. 4. Set the voltage selector on the front of the unit to either 120 or 277 V, depending on your application. The unit is shipped with the selector set to 277 V. 5. Mount the power pack to a suitable junction box using the 1/2-in., threaded nipple and lock. The power pack is plenum-rated, and can be mounted to the inside or the outside of a junction box or fixture in a ceiling plenum. 6. Connect the power pack as shown on previous page. Use approved wire nuts for electrical connections. 120V 277V To sensor Line voltage Outside PerfectSense ® Intelligent Building Occupancy Sensors 38 Power Packs
  • 40. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PS-SP24 Auxiliary Relay Power Pack • Single-pole, normally open relay • Rated for plenum use • Relay rated for maximum 15 A tungsten and 20 A ballast loads • Mounts to a standard 4-in. x 4-in. junction box using a 1/2-in., threaded EMT nipple Features Storage Temperature: -20°F to 150°F (-29°C to 65°C) Operating Temperature: 32°F to 104°F (0°C to 40°C) Maximum Humidity: 90% non-condensing AC Power Input: 24Vdc / 36mA Output Voltage: No Power Supply Standards: UL and cUL listed FCC: Part 15, Home and Office use Class B Specifications The PerfectSense auxiliary relay is similar to the power pack. The auxiliary relay does not supply power, but switches lighting and HVAC loads based on a control signal from the occupancy sensor. Both the power pack and auxiliary relay are housed in a rugged plenum rated enclosure, and rated for lighting and HVAC loads, including electronic ballasts. Flexible mounting scheme allows for installation inside or outside a standard 4”x4”junction box Schematic DiagramSystem Diagram Horsepower Rating: 1 hp @ 120 V Switching Capacity: 120 Vac, 60 Hz 15 A tungsten 1800 W 20 A ballast 277 Vac, 60 Hz 20 A ballast PerfectSense ® Intelligent Building Occupancy Sensors 39 Overview
  • 41. PerfectSense ® Intelligent Building Occupancy Sensors Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 To sensor Line voltage Inside Installation Instructions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • The power pack must be installed and serviced only by qualified electrical personnel. • Turn off power at the circuit breaker before beginning installation. • Always use a properly rated voltage sensing device to confirm power is off. Failure to follow these instructions will result in death or serious injury. Mounting Examples 1. Provide separate overcurrent protection in accordance with the National Electrical Code® and applicable local codes. 2. Use copper wire only. 3. Confirm that the device rating is proper for your application. 4. Mount the power pack to a suitable junction box using the 1/2-in., threaded nipple and lock. The power pack is plenum-rated, and can be mounted to the inside or the outside of a junction box or fixture in a ceiling plenum. 5. Connect the power pack as shown on previous page. Use approved wire nuts for electrical connections. To sensor Line voltage Outside 40 Power Packs
  • 42. 41 Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-PP7000X Heavy Duty Power Pack Overview Features Storage Temperature: -20°F to 150°F (-29°C to 65°C) Operating Temperature: 32°F to 104°F (0°C to 40°C) Maximum Humidity: 90% non-condensing AC Power Input: 120 or 277 Vac ± 10%, 60 Hz Output Voltage: 24 Vdc Specifications Combines transformer relay functions, occupancy sensor control, and manual/automatic operation into a single high performance unit. The PerfectSense Power Pack provides a wide array of switching solutions into a single unit. With high inrush stability circuitry specifically designed to handle today’s demanding inrush from electronic ballast loads and offer unmatched durability. A full wave rectifier converts the AC line voltage to 24 Vdc to power a low-voltage sensor via Class 2, plenum-rated wire. The power pack can be mounted inside or outside of an electrical junction box. Be sure to observe all local codes when mounting and wiring a powerpack. Output Current: 225 mA nominal Horsepower Rating: 1 hp @ 120 V Switching Capacity: 120 Vac, 60 Hz; 15 A tungsten 1800 W 20 A ballast 277 Vac, 60 Hz; 20 A ballast • Extreme durability: exceeds WS-896 Federal Specification duty cycle requirements for specification grade toggle switches. • High Inrush Stability circuit designed to handle high inrush electronic ballast loads, including the latest T5HO and T4 ballasts. • Zero crossing design for reliability and extended life. • Mechanical latching relay for dependability and robust for all load types • Return-to-on design provides fail safe operation in the event of power loss or malfunction. • Transformer Relay Function: replaces traditional transformer relays and provides occupancy sensors control. Ideal for use where code requirements/jurisdictions prohibit the use of 277V switch legs. • Manual-ON or Automatic-ON functionality for use in bi-level lighting control per CEC Title 24 requirements. • UL 2043 Plenum Rated • Endurance tested to over 1,000,000 cycles at full load. • Integrates with low voltage momentary and maintained switches to control occupancy sensors. • Conduit adaptor included for low voltage connections.
  • 43. 42Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Installation Instructions Bi-Level Switching Diagram PerfectSense ® Intelligent Building Occupancy Sensors N H Green Brown Brown/White Yellow White/Blue Blue Blue White Black LOAD 1 LOAD 2 Yellow Orange Green Brown Brown/White Blue Red White Blue Blue Black Orange/Yellow White/Blue Black Red Orange Blue Zone 1 – Auto ON Zone 2 – Manual ON Local SW 1 Auto ON +24VDC Com Local SW 2 Manual ON Com Black Orange/Yellow Occupancy Sensor Momentary or Maintained Switches 1. Provide separate overcurrent protection in accordance with the National Electrical Code® and applicable local codes. 2. Use copper wire only. 3. Confirm that the device rating is proper for your application. 4. Mount the power pack to a suitable junction box using the 1/2-in., threaded nipple and lock. The power pack is plenum-rated, and can be mounted to the inside or the outside of a junction box or fixture in a ceiling plenum. 5. Connect the power pack as shown on previous page. Use approved wire nuts for electrical connections. Power Packs
  • 44. Ordering Information Features  Provide simple momentary push button control.  LED models provide pilot lights or status outputs.  Operate on voltage ranges from 5-36 VDC.  Certain models are designed for use with NexLight 2-Wire relay panels.  Switches fit standard NEMA wall boxes.  Decorator-style enclosure; wall plate included. Part Number Description PS-LVS1x 1-button, low voltage switch PS-LVS1Lx 1-button, low voltage switch with LED PS-LVS2x 2-button, low voltage switch PS-LVS2Lx 2-button, low voltage switch with LED PS-LVS1Rx 1-button NexLight 2-Wire relay panel switch with LED PS-LVS2Rx 2-button NexLight 2-Wire relay panel switch with LED x = color code; W for White, L for Light Almond, and I for Ivory. The PerfectSense™ Low Voltage Switches are a series of decorator style push button wall switches that can be mounted in commercial or residential applications. The low voltage switches are designed to operate with PerfectSense Occupancy Sensors and NexLight 2-Wire relay panels. All switch models are available in white, almond, and ivory. Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 PerfectSense ® Intelligent Building Occupancy Sensors PS-LVSX Series Low Voltage Switches Overview 43
  • 45. Specifications Phone: 218.828.3700 www.nexlight.com Fax: 218.824.1568 Low Voltage Switch Wiring One Switch PS-LVS1 SW1 V OUT V IN One Switch with LED SW1 V OUT V IN (+) Anode (-) Cathode Two Switches SW1 SW2 V OUT SW1 V OUT SW2 V IN Two Switches with LEDs SW1 SW2 V OUT SW1 V OUT SW2 V IN (+) Anode LED1 (-) Cathode LED1 (+) Anode LED2 (-) Cathode LED2 Connection type External wires Gauge: #22 AWG stranded Number of conductors/switch: PS-LVS1: 2 PS-LVS1L: 4 PS-LVS2: 3 PS-LVS2L: 7 PS-LVS1R: 2 PS-LVS2R: 3 Switch Operating Range 5-36VDC Max current of 50mA @ 36VDC LED Operating Range 5-36 VDC Min operating current .150ma @ 5VDC Min operating current .275ma @ 12VDC Min operating current .385ma @ 24VDC Min operating current .470ma @ 36VDC Conductor temperature rating: Not specified, select to meet UL Class 2 requirements Conductor voltage rating: 5 to 36 Volt DC Conductor length: 6 inches from housing Temperature 0 – 50 degrees C. Humidity Maximum 90% RH non-condensing Low Voltage Relay Panel Switch Wiring One Switch Reverse Polarity Switch V OUT V IN Two Switches Reverse Polarity Switch V OUT SW2 Reverse Polarity Switch V OUT SW1 V IN PS-LVS1L PS-LVS2 PS-LVS2L PS-LVS1R PS-LVS2R Low Voltage Switches 44 PerfectSense ® Intelligent Building Occupancy Sensors
  • 46. E FA Line Voltage Class 1 Low Voltage Class 2 (16awg 3-wire) Low Voltage Class 2 (16awg 2-wire) WIRING KEY A E A A F 2- Button Low Voltage Switch EA Line Voltage Class 1 (3-conductor) Low Voltage Class 2 (16awg 3-wire) WIRING KEY E E Manual On / Auto Off 50% Manual On / Auto Off Power Pack Ceiling Sensor 1-Button Low Voltage Switch A1 a b A1 a b A1 a b a b a b A E A A Manual On / Auto Off + Dimming + Daylight Sensor B Daylight Sensor Low Voltage Switch EA Line Voltage Class 1WIRING KEY Low Voltage Class 2 (0-10V control wires) G Low Voltage Class 2 (16awg 3-wire) B Occupancy / Vacancy Sensor Occupancy / Vacancy Sensor F Low Voltage Class 2 (16awg 2-wire) EA Line Voltage Class 1 Low Voltage Class 2 (16awg 3-wire) WIRING KEY A E A A Auto On / Auto Off Power Pack Ceiling Sensor Common Stand Alone Control Strategies PerfectSense ® Intelligent Building Occupancy Sensors 45 Auto On / Auto Off is the most basic occupancy control strategy. Requiring only a standard power pack and low voltage sensor, the space is controlled based on occupnacy with no manual override control. Line voltage wall switch sensors may also be configured to work in this manner. Consult local codes for using this scenario in approved locations. 50% Manual On / Auto Off requires one lighting load to be switched on automatically when occupancy is detected by an occupancy sensor, while a second lighting load can be turned on manually by the occupant if desired. Both loads can then be turned off manually or via the occupancy sensor timing out. Commonly required by building codes (such as California Title 24), this is an easy and convenient method of delivering extra energy savings without inconveniencing the occupant. Manual On / Auto Off is the commonly used method for areas using a single lighting load. Occupants manually turn lights onBe sure to use a PS-PP7000X power pack designed to work with low voltage switches. Going above and beyond Manual On / Auto Off can be done in a number of ways. The addition of photocells for daylight harvesting and or 0-10v dimming are two of the most popular choices for enahnced levels of control and energy savings in locations with large windows, conference rooms, or open office areas.
  • 47. OUR COMMITMENT TO YOU We take great pride in designing each of our products with the goal of providing the highest accuracy detection performance possible in the price range of that product. We strive to reproduce the consistent performance across all of our products. And we strive to avoid flashy features and promises of auto-commissioning. While that may sound initially attractive to the novice, they are not real and not enduring. In addition, we use only the highest-quality parts and the latest assembly and quality control techniques to ensure the reliability and long life of our products. Our reputation rests on our steadfast pursuit of this policy in sensors and lighting control systems for educational, commercial and industrial applications. At NexLight, we are committed to investing in research that continually gives rise to new technologies for improving energy savings and occupant comfort. When you purchase any product from PerfectSense, we encourage you to compare it, as we do, to competitive products for long-term performance accuracy. We believe that this process will enhance your appreciation of the product you select. With best wishes from all of us at PerfectSense for many years of consistent performance. HOW TO PURCHASE PERFECTSENSE PRODUCTS In order to serve you better, PerfectSense products are available through a number of different sales channels. To get you connected with the right products for your applica- tion please contact us directly either by telephone at 218-828-3700, or visit us on the web at www.NexLight.com for more information. PerfectSense is a trademarked brand of NexLight TEL.: 218-828-3700 FAX: 218-824-1568 WWW.NEXLIGHT.COM PerfectSense ® Intelligent Building Occupancy Sensors PerfectSense ® Intelligent Building Occupancy Sensors
  • 48. NexLight Lighting Controls 7877 College Road, Suite 105 Baxter, MN, 56425 1-218-828-3700 www.nexlight.com Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by NexLight for any consequences arising out of the use of this material. © 2013 NexLight Lighting Controls, All Rights Reserved. Cat# PS.4.13 PerfectSense ® Intelligent Building Occupancy Sensors