2. Product Description
1) High grade outdoor type, epoxy resin
insulated, bus bar system
2) Modified, C type bushing, for easy
connection with seperable
connectors, and heat shrink
terminations.
3) Sliding wooden Cable Clamps
4) Twin Earthing Bar, for cables from
both sides.
5) Longitutional Safety doors for easy
Installation and access.
6) Certified steel sheet, stiffener
column
1
2
3 4
5
6
2
Cable Collector Series V-CON® UG-300
4. Wooden Cable Cleats , Sliding on the panel
base, to control electrodynamic forces
4
Product Description
40 x 5 x 150mm Cu Bar
Metric 12mmΦ
Twin Earthing Bar
Twin Earthing Bar
Cable Collector Series V-CON® UG-300
6. Basement Plinth for elevated foundation
6
Front view Rear view
Right view
Left view
12 kV
High
Voltage
12 kV
High
Voltage
Product Description
Cable Collector Series V-CON® UG-300
9. No Particular Specification Requirement
1 Installation Type Outdoor
2 Type of Insulation
Solid insulated bus bar (embedded in
cast resin) with feeder terminals
suitable for Polymeric Heat Shrink
termination and plug in type separable
connectors
3 Bus-bar Scheme and Size Single bus bar, 50x6 =300mm²
4 Mounting Floor Mounting
5 System 3 Phase, 3-wire with Earhted Neutral
6 Nominal System Voltage 11kV phase to Phase
7 System Highest Voltage 12kV phase to phase
8
Rated short duration power frequency
withstand voltage
28kV (rms)
9
Rated Lightning Impulse withstand
voltage
75 kV (peak)
10 Frequency 50 Hz
11
Rated normal current, 11KV incoming,
outgoing feeder, branch feeders.
300A
12 Temperature rise of the joint block 90° C
13
Rated Short-time withstand Current
(Rated short circuit withstand current)
25kA for 3 sec.
14
Degrees of Protection by enclosures (IP) IP 54
15 Dimensions of 11kV Cubicle
W=1000mm, D=600mm, H=1000mm
16 Enclosure Steel Sheet thickness Min. 2.3mm
17 Enclosure Paint Type Static powder paint
18 Ral code of paint 7035
9
Cable Collector Series V-CON® UG-300
Technical Specifications
10. Item
No
Particular
Specification
Requirement
19 Standards
ASTM A1008 /
A1008M - 21
Standard Specification for Steel, Sheet,
Cold-Rolled, Carbon, Structural, High-
Strength Low-Alloy, High-Strength Low-
Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable.
BS HD 629.1 S3:2019
Test requirements for accessories for use
on power cables of rated voltage from 3
,6/6(7,2) kV up to 20,8/36(42) kV.
Accessories for cables with extruded
insulation
EN 50581
Plug-in type bushings above 1kV up to
36kV and from 250A to 1.25kA for
equipment other than liquid filled
transformers.
EN 61238-1
Compression and mechanical connectors
for power cables for rated voltages up to
36kV(Um=42kV) – Part 1: Test Methods
and requirements (IEC61238-1:2003,
Mod.)
EN 61442
Test Methods for accessories for power
cables with rated voltages from 6kV
(Um=7.2kV) up to 36kV (Um=42kV) (IEC
61442)
HD 428.2.2
Three-phase oil immersed distribution
transformers 50hz, from 50 to 2500kVA
with highest voltage for equipment not
exceeding 36kV – Part 2: Distribution
transformers with cable boxes on the
high voltage and/or low voltage side –
Section 2: Cable boxes type 1 for use on
distribution transformers meeting the
requirements of HD 428.2.1 S1.
IEC 61439-5
Low-voltage switchgear and control gear
assemblies –
Part 5: Assemblies for power distribution
in public networks
IEC 60529 (2015)
Degrees of protection provided by
enclosures (IP Code)
IEC/TR 61439-0
Low-voltage switchgear and control gear
assemblies –
Part 0: Guidance to specifying assemblies
IEC 62271-1
High-voltage switchgear and control gear
–
Part 1: Common specifications
IEC 60137
Insulated bushings for alternating
voltages above 1 000 V
10
Cable Collector Series V-CON® UG-300
Technical Specifications
11. Item
No
Particular
Specification
Requirement
19 Standards
EN 60085 Thermal evaluation and classification of
electrical insulation
EN 22063 Metallic and other organic coatings.
Thermal spraying. Zinc, aluminium and
alloys
EN 60137 Insulated bushings for alternating voltages
above 1 kV
IEC 60529 Specification for degrees of protection
provided by enclosures (IP Code)
EN ISO 2063 Thermal spraying. Metallic and other
inorganic coatings. Zinc, aluminium and
their alloys
IEC 60060-1:1989 High-voltage test techniques − Part 1:
General definitions and test
requirements
IEC 62271-200 High-voltage switchgear and controlgear -
Part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above 1
kV and up to and including 52 kV
11
Name Plate
Cable Collector Series V-CON® UG-300
Technical Specifications