VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
- 1 -- 1 -
GO WITH THE FLOW 2012
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
- 2 -- 2 -
VA-meters
Verschildruk debietsmeters
Vortex debietsmeters
2
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
- 3 -- 3 -
VA-meters
- 4 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Agenda
Nomenclatuur
Meetprincipe
Toepassingsgebied
Uitvoeringen
Nauwkeurigheid
Voordelen en beperkingen
Speciale uitvoeringen
Installatievoorschriften
Page 4
3
- 5 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nomenclatuur
- 6 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nomenclatuur
Variabele doorlaat-meter
– Vado-meter of VA-meter
Vlotterdebiet-meter
Zweeftol-debietmeter
Rotameter
Peil-meter
….
4
- 7 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Meetprincipe
- 8 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Meetprincipe
5
- 9 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Meetprincipe
Meetprincipe: zwaartekracht
Conische geslepen buis met vlotter
Druk van het fluïdum = gewicht van
de vlotter => Vlotter blijft hangen
Hoogte van vlotter is evenredig met
de stroomsnelheid van gas of
vloeistof (debiet)
Schaalverdeling
- 10 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Toepassingsgebied en
voorwaarden
6
- 11 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Dichteid moet constant zijn
Vaste deeltjes in het medium zijn
niet toegestaan
– aantasting vlotter, meetfouten, blokking
Viscositeit: max. 100 mPa.s
Druk: tot en met 700 bar
Temperatuur:
– RVS : -200 tot + 450°C
– PTFE: -80 tot +130°C
Toepassingsgebieden en voorwaarden
- 12 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
– Low-range limiet 10 : 1
– High-range limiet:
• water: 130 m³/h
• lucht: 1400 m³/h
– Repeatability: 0,1% van full scale
– Installatie: vertikaal
– Meestal voor lokale indicatie
– Drukval over vlotter: constant
– Meet-karakteristieken: lineair
Toepassingsgebieden en voorwaarden
7
- 13 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Uitvoeringen
- 14 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Metalen
Glas
Plastic
Uitvoeringen in verschillende materialen
8
- 15 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nauwkeurigheden
- 16 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nauwkeurigheid bij Rotameters
Bestaande systeem voor classificatie van de nauwkeurigheid is recent herzien om
de begrijpbaarheid ervan te vergroten naar klanten toe.
De voormalige specificaties (gecreëerd in december 1978) maakten gebruik van
onderstaande formule ter berekening van de fout voor de gemeten waarden
Formule: F = (¾ M + ¼ E)*K/100
M = gemeten waarde van de flow met flow-eenheid
E = full scale waarde van de flow met flow-eenheid
K = waarde van de nauwkeurigheidsklasse
=> Nieuw systeem is eenvoudiger en transparant
-> praat niet meer over nauwkeurigheidsklassen
-> bepaalt het maximum toegelaten percentage van afwijking van de
gemeten waarde
9
- 17 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nauwkeurigheid bij Rotameters
De nieuwe specificaties worden gesplit in 2 ranges:
– Lineaire Range van qG tot Qmax (main working range)
– Niet-lineaire Range van Qmin tot qG (low flow range)
De nauwkeurigheidsklasse wordt vervangen door 2 nieuwe parameters:
– Maximum permissible error “G”
– Threshold value “qG”
Vroegere specificatie Nieuwe specificatie
Accuracy class 1.6 G=1.6 qG = 50 %
Accuracy class 2.5 G=2.5 qG = 50 %
Accuracy class 4 G=4 qG = 50 %
- 18 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nauwkeurigheid bij Rotameters
Former specification: accuracy class 1.6
New specification: qG = 50%, G=1.6
Now 8%
Before 5.2%
New specification
less strict more strict
than former specification
qG
Threshold value « qG » is defined by each manufacturer
Range qG to Qmax
with constant error value
Deviation
/ % of
measured
value
Measuring range / % Qmax
10
- 19 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voordelen en beperkingen
- 20 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voordelen
Lage kostprijs
Geen voeding nodig voor lokale indicatie
Geschikt voor gas, vloeistoffen en stoom
Metalen versie
– CIP
– Steriliseerbaar
– PTFE-lining
Verschillende vormen van vlotters beschikbaar
Constante drukval onafhankelijk van het debiet
11
- 21 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Beperking
Vertikale installatie is verplicht
Invloed van wijzigingen in temperatuur en densiteit
Schade aan vlotter door aanwezigheid van vaste deeltjes
– Kan tegengegaan worden door bv. Magneetfilters
Invloed van pulsatie en vibratie
Nood aan exotische materialen (monel, Hastelloy, …)
- 22 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Measuring Range of a Rotameter
Indication
Float reaches the
upper stopper at
105% of max. flow.
Float lifts at 5
to 8% of max.
flow.
Beperkingen
Start, zero en maximum
Zonder flow: vlotter ligt op onderste stopper (rustpunt)
Meting start wanneer de drukval hoog genoeg is om de vlotter te liften
(5 – 8% van de max. flow)
Rotameter heeft dus geen afgelijnd zero-punt
Maximum overrange die kan aangeduid worden vooraleer de bovenste stopper
wordt bereikt is tussen 105 – 110% van de schaal
12
- 23 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Speciale uitvoeringen
- 24 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Float blocking detection
De Zero-fluctuaties worden
geregistreerd onder
No-flow condition wanneer
de vlotter zich op het
rustpunt bevindt.
Er wordt een grens
vastgelegd voor het
minimum aan fluctuaties
met inbegrip van een
safety factor.
13
- 25 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
ATEX: EExd Rota meter
VA-meters
• Met EExd approval (12 mm glass moulded, EEX d wartels M20*1,5)
• Met dust EEx approval (12 mm glass moulded)
• Standaard IP 67
- 26 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
SIL
Safety Integrity Level
– Norm: IEC 61508 en IEC 61511
– SIL 1 : Ondergeschikte (onroerende) goederen- en productiebescherming.
– SIL 2 : Belangrijke (onroerende) goederen- en productiebescherming.
Mogelijke kans op verwonding van werknemers.
– SIL 3 : Werknemers- en gemeenschap-bescherming.
– SIL 4 : Katastrofale impact op de gemeenschap.
14
- 27 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatievoorschriften
- 28 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatie-voorschriften
De VA-meter dient verticaal gemonteerd te worden
met flow-richting opwaarts
Grotere leiding-diameters vragen een rechte lengte
van 5D voor en na voor een ideaal flow-profiel
Vermijd corrosieve omgevingen
Geen blootstelling aan omgeving met sterke vibraties
Om interferentie te vermijden is de minimale afstand
tussen twee flowmeters best > 300mm
Het meetgedeelte is gevoelig aan externe niet-
homogene magnetische velden (bv. Solenoid valves)
Asymmetrische magnetische vormen kunnen een
invloed hebben op de werking van de vlotter
15
- 29 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatie Hints voor Metalen Rotameters
VA-meters
Min. 300 mm
Grotere nominale diameters
(DN80/DN100), vragen ten minste 5D voor
en na de Rotameter
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
- 30 -- 30 -
Verschildruk debietsmeters
16
- 31 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Wet van Bernoulli
Wet van behoud van energie: drukenergie +
statische energie + kinetische energie
= constant
Permanent
Pressure Loss
Final Head After
Pressure
Recovery
Upstream
Initial Head
Maximum
Pressure
Change
Streamlin
e (Typical)
Flow
High Pressure Connection
Low Pressure
Connection
Primary Element
Concentric Orifice
Plate
Secondary Element
DP Transmitter
ρ
ε
p
dmCQV
∆⋅
⋅⋅
Π
⋅⋅⋅=
2
4
2
22
1
tcoefficiendischarge
m
K
C
⋅−
⋅
==
µ
µ
=ε Gas expansion factor (for liquids =1)
2
1
0
1
0






==
d
d
A
A
m
0
2
A
A
=µ
ρ=density
Diameter pipe = D
A0=surface orifice hole
A1=surface pipe
A2=surface after orifice hole
A0A1
A2
Volumetrisch debiet
- 32 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Massadebiet
ρε
β
..2
41
2
4
pd
C
Qm ∆⋅⋅
Π
⋅⋅
−
=
Permanent
Pressure Loss
Final Head After
Pressure
Recovery
Upstream
Initial Head
Maximum
Pressure
Change
Streamlin
e (Typical)
Flow
High Pressure Connection
Low Pressure
Connection
Primary Element
Concentric Orifice
Plate
Secondary Element
DP Transmitter
A0A1
A2
factorapproachofvelocity
1
1
4
=
− β
tcoefficiendischarge=C
1)liquids(forfactorexpansionGas ==ε
D
d
== BetaRatioβ
conditionsflowingatdensity=ρ
d= Bore Diameter primary
element
pressurealDifferenti=∆p
D= Pipe Diameter
Wet van Bernoulli
Wet van behoud van energie:
drukenergie + statische energie +
kinetische energie = constant
Relatie tussen dp en Qm:
17
- 33 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
De berekeningen: de makkelijke manier
P
dC
Qm ∆⋅⋅
⋅
−
= ρε
π
β
2
41
2
4
K-factor
PkQm ∆⋅=
Is dit correct?
- 34 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Binnenin de leiding
Snelheid omhoog (V ⇑⇑⇑⇑ )
Druk daalt (P ⇓⇓⇓⇓ )
Dichtheid daalt (ρρρρ ⇓⇓⇓⇓ )
Snelheid omhoog (V ⇑⇑⇑⇑ )
Punt met laagste druk
(vena contracta) verschuift
T stijging
D en d wijziging
18
- 35 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Larger
beta
Smaller beta
d/Dβ = dD
Wat is de ββββ−−−−ratio
Beta Ratio (ββββ)
– Definitie:
– De verhouding van de orifice bore diameter (d)
en de interne buis diameter (D).
– Definieert hoeveel restrictie (drukval) je in de
leiding/orifice kan hebben.
– Hoe kleiner Beta, hoe groter de restrictie.
- 36 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Discharge coefficiënt (C)
Empirisch bepaalde factor voor een DP flow element
FlowlTheoretica
FlowActual
=C
19
- 37 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Discharge coëfficient: orifice en averaging pitot
Orifice Averaging pitot
- 38 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Discharge coëfficiënt varieert met debiet
Het punt met de laagste druk noemen we de ‘Vena Contracta’.
De exacte positie van de Vena Contracta wijzigt als de flow
verandert. Dit effect heeft impact op de Discharge
coëfficiënt.
High
side
Low
side
Vena Contracta
20
- 39 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
P = 4 bar, abs
Same volume
2x the gas or steam!
P = 8 bar, abs
Dichtheid ρρρρ is afhankelijk van druk en temperatuur
Bij eenzelfde volume neemt de dichtheid toe als de
druk toeneemt
Bij eenzelfde volume neemt de dichtheid toe als de
temperatuur toeneemt
- 40 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Het medium moet door een vernauwing:
Snelheid omhoog
(Statische) druk daalt
Dichtheid daalt
We moeten een correctiefactor invoeren om de
dichtheidswijziging op te vangen
High
side
Low
side
Primary element
Velocity increase (V ⇑⇑⇑⇑ )
Pressure decrease (P ⇓⇓⇓⇓ )
Density decrease (ρρρρ ⇓⇓⇓⇓ )
Flow
Fouten bij primaire elementen: dichtheidswijziging
21
- 41 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Velocity of approach-factor
factorapproachofvelocity
1
1
4
=
− β
High
side
Low
side
Primary element
Flow
Door temperatuurswijzigingen, wijzigen ook afmetingen van
het primair element
- 42 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
De diameter van de buis (D) en van het primair element
(d) verandert door de T. Oorzaak is de thermische
expansie van metalen.
Typische Fouten door T-veranderingen:
Gassen & Stoom: 0.05 - 0.5%
Vloeistoffen: 0.05 - 0.5%
Dit is typisch een redelijk kleine fout, maar in applicaties waar
de T nogal varieert, kan dit belangrijk zijn:
Primair element bore (d) wordt beïnvloed door de T°
d = 10 mm d = 10.03 mm
T = 30 degC T = 200 degC
Steel Stainless (304): 17.3 x 10-6 mm/K
Steel Stainless (316) 16.0 x 10-6 mm/K
22
- 43 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Varieert door debietwijziging
1. C = Discharge Coefficient
2. ε = Gas Expansion Factor
Varieert door druk en T
5. Density Compensation
6. Compressibility Factor
Varieert door temperatuurswijziging
3. Velocity of Approach = 1/(1-ββββ4)1/2
4. d2 = Diameter van primary element
Massadebiet wordt bepaald door continue herberekening
van deze parameters
Wat is de impact van de proceswijzigingen?
ρ
β
ε ..2
1
1
4
2
4
pdCQm ∆⋅⋅
−
⋅
Π
⋅⋅=
<VIK – Go with the flow>
Copyright © Yokogawa Electric Corporation
<October 2012>
- 44 -
ISO 5167 formule
1
2
4
2
41
ρε
π
β
P
dC
Qm ∆
−
=
C =f ( Re D No ) µ =f ( T )
ββββ =f ( D , d )
ε = f ( SP , ∆∆∆∆ P )
Re D No =f ( Q m , µ , D )
d =f ( d 0 , αααα 2 , T )
D =f ( D 0 , αααα 1 , T )
ρρρρ 1 =f ( SP , T )
Q m Mass flow rate
C Discharge coefficient
ββββ Beta Ratio d/D
d Bore of Diffrential Producer
D Pipe inner diameter
ε Gas expansion factor
∆∆∆∆ P Differential pressure
ρρρρ Density
Re D No Reynolds number
SP Static pressure
T Temperature
µµµµ Viscosity
αααα Thermal expansion
23
- 45 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nauwkeurigheid binnen de ISO formule
Nauwkeurigheid:
– ISO5167-2 2003
– Primary device: Orifice; medium: gas
2222
4
22
4
422
m
m
p
p
d
d2
D
D2
C
C
q
q
















































=
ρ
ρ
4
1
+
4
1
+
1-β
+
1-β
β
+
ε
ε
+
δδδδδδδ
(δC / C)2 C
(δε / ε)2 ε
((2β4)/(1-β4))2(δD / D)2 D
(2/(1-β4))2(δd / d)2 d
1/4(δ∆P/∆P)2 P
1/4(δρ /ρ)2 ρ
C
ε
D
d
DP
ρ
0.928 0.563 0.072 0.137 0.086 0.0004 0.0025
- 46 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
De berekeningen: de makkelijke manier
P
dC
Qm ∆⋅⋅
⋅
−
= ρε
π
β
2
41
2
4
K-factor
PkQm ∆⋅=
Is dit correct? Ja, als er geen externe factoren wijzigen
24
- 47 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Single variable flow
Vaste compensatie-factor (k)
Opletten bij gebruik in dynamische condities
Low flow
PkQm ∆⋅=
- 48 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Druktransmitter met zowel verschildruk, statische druk, temperatuurmeting
én flow computer
Flow computer
Temp.
sensor
Four in one = Cost saving
Dynamic flow measurement: Improves flow accuracy
EJX /MV
Mass flow output
Multi-sensing
(DP,SP, temp, density)
Gauge
pressure
transmitter
Differential
pressure
transmitter
Temp.
transmitter
+
Temp.
sensor
Wat is een multivariable transmitter?
25
- 49 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voorbeeld van de intelligentie binnenin een multivariabele druktransmitter
Differential pressure
Resonant
sensor
RTD
((((High accuracy))))
Computation
●●●● Flow calculation
Re No compensation
●●●● Density compensation
・Flow rate
Volume/mass
・Difference pressure
・Static pressure
absolute pressure/(gage
pressure)
・Temperature(density)
Static pressure
Temperature
INPUT SIGNAL
BUS OUTPUT
HART
F-Fieldbus
・Pulse
Volume/mass
Analog
・Difference pressure
・Static pressure
absolute pressure/(gage
pressure)
・Temperature(density)
SIGNAL OUTPUT
Fluid databank 126
most common fluids
Orifice plate data
Orifice Plate RTD
- 50 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Dichtheidsberekeningen in een flow computer
Hou rekening met de mogelijkheden!
– Gebruikmakend van een database (bvb. DIPPR) (AIChE)
• Eigenschappen van 126 verschillende vloeistoffen en gassen
– AGA 8 of ISO12213 aardgas vergelijkingen
• Simplified of full molecular weight composition
– IAPWS-IF97 formules voor water en stoom
– Eigen compensatie-tabel (dichtheid en viscositeit moet
gekend zijn bij verschillende condities)
Page 50
26
- 51 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voorbeeld van de DIPPR database
Page 51
No. Fluid name No. Fluid name No. Fluid name No. Fluid name
1 Acetic Acid 33 Ethylamine 65 n-Decane 97 Vinyl Cyclohexene
2 Acetone 34 Ethylbenzene 66 n-Dodecane 98 Water
3 Acetonitrile 35 Ethylene 67 n-Heptadecane 99 1-Butene
4 Acetylene 36 Ethylene Glycol 68 n-Heptane 100 1-Decene
5 Acrylonitrile 37 Ethylene Oxide 69 n-Hexane 101 1-Decanal
6 Air 38 Fluorene 70 n-nonane 102 1-Decanol
7 Allyl Alcohol 39 Furan 71 n-Octane 103 1-Dodecene
8 Ammonia 40 Helium-4 72 n-Pentane 104 1-Dodecanol
9 Argon 41 Hydrazine 73 Neon 105 1-Heptanol
10 Benzaldehyde 42 Hydrogen 74 Neopentane 106 1-Heptene
11 Benzene 43 Hydrogen Chloride 75 Nitric Acid 107 1-Hexene
12 Benzoic Acid 44 Hydrogen Cyanide 76 Nitric Oxide 108 1-Hexadecanol
13 Benz Alcohol 45 Hydrogen Peroxide 77 Nitrobenzene 109 1-Octanol
14 Biphenyl 46 Hydrogen Sulfide 78 Nitroethane 110 1-Octene
15 Bromine 47 Isobutane 79 Nitrogen 111 1-Nonanal
16 Carbon Dioxide 48 Isobutene 80 Nitromethane 112 1-Nonanol
17 Carbon Monoxide 49 Isobutylbenzene 81 Nitrous Oxide 113 1-Pentadecanol
18 Carbon Tetrachloride 50 Isopentane 82 Oxygen 114 1-Pentanol
19 Chlorine 51 Isoprene 83 Pentafluoroethane 115 1-Pentene
20 Chlorodifluoromethane 52 Isopropanol 84 Phenol 116 1-Undecanol
21 Chloroprene 53 m-chloronitrobenzene 85 Phosphoric Acid 117 1,1,2,2-Tetrafluoroethane
22 Chlorotrifluoroethylene 54 m-dichlorobenzene 86 Propadiene 118 1,1,2-Trichloroethane
23 Citric Acid 55 Methane 87 Propane 119 1,2,4-Trichlorobenzene
24 Cycloheptane 56 Methanol 88 Propylene 120 1,2-Butadiene
25 Cyclohexane 57 Methyl Acrylate 89 Pyrene 121 1,3-Butadiene
26 Cyclopentane 58 Methyl Ethyl Ketone 90 Styrene 122 1,3,5-Trichlorobenzene
27 Cyclopentene 59 Methyl Vinyl ether 91 Sulfur Dioxide 123 1,4-Dioxane
28 Cyclopropane 60 Monochlorobenzene 92 Toluene 124 1,4-Hexadiene
29 Dichlorodifluoromethane 61 n-Butane 93 Trichloroethylene 125 2-Methyl-1-Pentene
30 Divinyl Ether 62 n-Butanol 94 Trichlorofluoromethane 126 2,2-Dimethylbutane
31 Ethane 63 n-Butylaldehyde 95 Vinyl Acetate
32 Ethanol 64 n-Butyronitrile 96 Vinyl Chloride
<VIK – Go with the flow>
Copyright © Yokogawa Electric Corporation
<October 2012>
- 52 -
Primaire elementen
27
- 53 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Pitot Tube
Venturi Tube
Wedge Flow ElementFlow Nozzle
Elbow
Overzicht
Orifice plate
- 54 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Pitot tube
Wat is het?
– Een L-vormige buis met een opening in de stroomrichting (dynamische
drukmeting) met daarin een tweede buis met een opening loodrecht op
de stroomrichting (meet de statische druk). Het debiet is rechtevenredig
met het verschil tussen de dynamische en de statische drukmeting
Nauwkeurigheid
– Van 0.5% to 4%
Voordelen
– Klein
– Draagbare oplossingen
Beperkingen
– Blokkage van de drukopeningen
– De positie(s) van de statische drukopeningen kunnen de meting
beinvloeden
28
- 55 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
De “averaging” pitot tube
Wat?
– Een pitot tube met meerdere dynamische en statische drukopeningen.
De verschildruktransmitter berekent het debiet door het gemiddelde te
nemen van de drukopeningen.
Nauwkeurigheid
– 1%
Voordelen
– Lage drukval
– Bi-directionele oplossingen mogelijk
– Mogelijkheid tot geïntegreerde temperatuursmeting voor
massadebietsmeting
Beperkingen
– Geen berekeningen volgens een standaard
- 56 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Averaging pitot tube: info
Lage installatiekost in vergelijking met andere primaire elementen
Drill Weld Insert Wire
3) Lage permanente drukval leidt
tot kostenbesparing
2) Bi-directionele metingen
mogelijk bij sommige
vormen
4) « Non clogging »
oplossingen mogelijk
29
- 57 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Averaging pitot tube: installatie
Relatief lange upstream en
downstream lengtes zijn echter
noodzakelijk
Gas application
Steam application
Horizontal pipe
(side view)
Vertical pipe
(bottom view)
Horizontal pipe
(side view)
Vertical pipe
(bottom view)
- 58 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Orifice plate
Wat?
– Een vlakke metalen plaat met een opening (al dan niet concentrisch).
De verschildruktransmitter meet de druk voor en na de plaat en
berekent zo het volumetrisch debiet.
Nauwkeurigheid
– Indien volgens de standaard ISO5167: 0.5% - 0.75%
– Indien volgens de standaard AGA: 0.44 - 1%
Voordelen
– Goede nauwkeurigheid
– Installatievoorschriften en documentatie voorhanden in ISO
documentatie
Nadelen
– Relatief grote drukval
– Grote upstream en downstream lengtes noodzakelijk
– Blokkage van de impulsleidingen mogelijk bij sommige vloeistoffen of
gassen
30
- 59 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Pressure tappings:
Flanged tappings (Orifice flange assembly – most
common execution)
Corner tappings: used mostly in monobloc &
wafer executions
Case 1: with annular rings
Case 2: single pressure tappings
Orifice: tappings
- 60 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Pipe tappings (D & D/2)
Pipe tappings (D & D/2)
are mostly used in larger
pipe sizes to save the
flanges cost.
Orifice: tappings
31
- 61 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Steam application,
horizontal line
Compact mass flow including multi-variable
transmitter & temperature compensation
Compact flow
measurement
Gas
Orifice: compact oplossingen
- 62 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatie van de druktransmitter
32
- 63 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Page 63
Installation requirements according to ISO standard
Installatievoorschriften en nauwkeurigheid
- 64 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Meter run
Wat?
– Een orifice plaat met daarbij geinstalleerd een leiding en
flensconstructie. De volledige constructie respecteert de upstream en
downstream lengtes
Nauwkeurigheid
– Conform ISO5167: 0.5%
Voordelen
– Goede nauwkeurigheid
– Geen problemen qua montage
Beperkingen
– Drukval redelijk hoog
– Blokkage van de impulsleidingen mogelijk bij sommige vloeistoffen of
gassen
33
- 65 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Venturi
Wat?
– A leiging met een convergerende ingang en divergerende uitgang. De
verschildruktransmitter meet het drukverschil tussen inlet en
middendeel en berekent op die manier het volumetrisch debiet
Nauwkeurigheid
– 0.7% - 1.5%
Voordelen
– Lagere drukval dan orifice plates
– Practisch geen blokkages mogelijk
Beperkingen
– Duur
- 66 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Nozzle
Wat?
– Een stuk leiding met een zacht inlopende ingang en een scherpe
uitgang. De verschildruktransmitter meet het drukverschil tussen de
ingang en de uitgang en bepaalt op deze manier het volumetrisch
debiet
Nauwkeurigheid
– 2.0%
Voordeel
– Beperkt drukverlies
Beperkingen
– Duurder dan orifice plates
– Slechts beperkte buisdiameters mogelijk
34
- 67 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Venturi nozzle
Wat?
– Een venturi met een nozzle ingang
Nauwkeurigheid
– 1% - 1.5%
Voordelen
– Minder drukval dan orifice plate
– Combineert de sterktes van een venturi en nozzle
Beperkingen/nadelen
– Prijs
- 68 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Selectie primair element
Device Line size (mm) Field of application Specific Advantages Specific disadvantages
Orifice plate flange taps 50 to 1000 General purpose
Orifice plate corner taps 25 to 1200 Lines below 50 mm Economic, simple, flexible, widely
accepted
Pressure loss, upstream pipe
requirements
Orifice plate D & D/2 taps 100 to 1000 Line sizes above 600 mm
Orifice plate quarter circle 25 to 500 Viscous fluids, low Reynolds
number
Viscous fluid, low flow rate Less accurate
Orifice plate conical entrance 25 to 500 Viscous fluids, low Reynolds
number
Viscous fluid, low flow rate Less accurate
Orifice plate eccentric 100 to 1000 Dirty fluids and two phase flow Dirty Fluids Less accurate
Integral orifice plate 15 to 40 Small flowrates, small line size Small flowrates Less accurate
Meter run 15 to 400 Accurate measurement Accuracy Manufacturing costs, handling
length
Venturi tube 50 to 1200 Accurate measurement, low
pressure loss
Accuracy with low pressure loss Handling length
(Venturi) nozzle 65 to 500 High velocity fluids on low
pressure loss
Erosive fluids with low pressure
loss
Less accurate, handling length
Averaging pitot tube 15 to 15000 Large flow rate at low pressure
of clean fluids
Economic, low pressure loss, bi-
directional
Clean fluids, no international
standard
35
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
- 69 -- 69 -
Vortex debietsmeters
- 70 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Agenda
Werkingsprincipe
Eigenschappen & specificaties
Voordelen / beperkingen
Vortex en veiligheidstoepassingen
Installatievoorschriften
Applicaties
Page 70
36
- 71 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Werkingsprincipe
- 72 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Werkingsprincipe
Wat is een Karman Vortex Straat?
Hoe wordt deze gebruikt in debietmeting?
Page 72
37
- 73 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Karmán vortex straat
Theodore von Kármán (1881-1963) is een Hongaars-Amerikaanse
ingenieur en wetenschapper die hoofdzakelijk actief was in
luchtvaart en ruimtevaart.
Hij gaf les aan de universiteit van Göttingen, RWTH Aken,
California Institute of Technology.
Hij is medeoprichter van Jet Propulsion Laboratory, NASA
Theodore von Kármán
Page 73
- 74 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Karmán vortex straat
Vortices zijn een natuurlijk fenomeen.
Page 74
38
- 75 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Karmán vortex straat
Page 75
- 76 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vortex als debietsmeting
Page 76
39
- 77 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
l
17,0≈=
l
d
St
Het Strouhal getal (St):
Vortex als debietsmeting
Page 77
- 78 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Karmán vortex frequentie
f = Karmán vortex frequency
St = Strouhal number (constant in a certain area)
v = fluid velocity
d = width of vortex shedder (constant)
d
vSt
f
⋅
=
Vortex als debietsmeting
Page 78
40
- 79 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
lichte bries - laminaire flow,
no vortices formed
Re < 5000
Stevige bries - transitie flow,
onregelmatige vortices gevormd
5000 < Re < 20000
Sterke wind - turbulente flow,
regelmatig vortex patroon
Re > 20000
Reynolds getal (Re):
Principe
Page 79
- 80 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Relatie tussen St, Re en snelheid
LINEAR RANGE
MEASURING RANGE
5 x 10
3
2 x 10
4
VELOCITY
.2
.1
.3
262 F/S (GAS)
32 F/S (LIQUID)1 F/S (LIQUID)
10 F/S (GAS)
7 x 107
SPECIFICATION RANGE
REYNOLDS NUMBER
StrouhalNumber
Principe
Page 80
41
- 81 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Principe
Page 81
Laminar TurbulentTransitional
Delta geometry { D }
Round geometry { }– Alleen de delta
geometrie geeft
een optimaal
verband tussen
snelheid en vortex
frequentie.
– Verdere
verbeteringen aan
de geometrie
hebben geleid tot
een
nauwkeurigheid
van 0,75%.
Geometrie van de shedder bar
- 82 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Principe
In praktijk vervangt de K-factor het St (Strouhal getal) als de
toonaangevende parameter.
De omzettingsvergelijking wordt dan:
Flow rate = Vortex Frequency
K-factor
De K-factor wordt bepaald door de fabriekskalibratie van de
debietmeter (water kalibratie – “ X “ Pulsen / Liter)
K-factor wordt niet beïnvloed door: T, P, density, ...
Gevolg hiervan is dat alle kalibraties uitgevoerd worden met
water voor alle applicaties.
Page 82
42
- 83 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Eigenschappen & specificaties
- 84 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : pick-up sensor
Sensor posities voor vortex metingen
Page 84
Drukschommelingen
Fluida-beweging
Fluida-kracht op de
shedder-bar
43
- 85 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : pick-up sensor
Page 85
Verschildruk Integraal
Diafragma
Differential Switched
Capacitor
- 86 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor desig : pick-up sensor
Page 86
Massieve
piëzo pick up
Shedder-Bar
Vane achter Shedder-bar
Piëzo vinger
pick up
in de Shedder
44
- 87 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : pick-up sensor
Page 87
Drukschommelingen
Fluida-beweging
Fluida-kracht op de
shedder-bar
- 88 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : bodies
Page 88
Wafer type
Flanged type
Insertion type
45
- 89 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : bodies
Page 89
Reduced bore type
- 90 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Sensor design : hoge & lage temperatuur
Page 90
Extended neck:
*Beschermt de elektronica
tegen hoge/lage temperatuur
*Installatie van elektronica
buiten isolatie
46
- 91 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Convertor design
Page 91
Remote opstelling
Integral opstelling
- 92 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Bidirectional flow
Bidirectionele flow mogelijk gemaakt
Page 92
47
- 93 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Multivariabel
Page 93
RTD
sensor
piezo
sensors
shedder
bar
Druk gecompenseerd Temperatuur gecompenseerd
- 94 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Temperatuur gecompenseerd
Page 94
ingebouwde temperatuur sensor
• beschermd in de shedder bar
• +/- 1 °C (vloeistof), +/- 2 °C
(gas/stoom);
RTD Pt1000
multi-variabele optie
• waarde flow & temperatuur worden
weergegeven
• dubbele output (flow: pulse, temp: 4-20mA)
stoom massadebiet-berekening
• Massadebiet-berekening, gebruik makend
van gemeten T (druk = cte)
• +/- 2% nauwkeurig
Multivariabel
48
- 95 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Druk gecompenseerd
Page 95
Ingebouwde druk sensor
• ±1.5% van de gemeten waarde
(Re ≥ 20000); ±2.5% van de gemeten
waarde (10000 < Re < 20000)
multi-variabele optie
• waardes voor flow & druk worden
weergegeven
• dubbele output (flow, pressure)
steam mass flowrate calculation
• Massadebiet-berekening, gebruik makend
van gemeten P (Temperatuur = cte)
1 Pressure sensor
2 Shut-off valve
3 Fully welded stainless steel design
4 Converter with Intelligent Signal Processing [ISP]
Multivariabel
- 96 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vibratie onderdrukking
Page 96
Vibraties kunnen veroorzaakt
worden door:
•Pompen
•Compressoren
•Wandelende mensen
•Piping
•Wind
•…
Als f(vibration) = f(vortex)
« interferenties »
49
- 97 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vibratie invloeden / onderdrukking
Page 97
Frequency Analyzing/
Intelligent Amplification
Output Waveform
Vortex Signal met ruis
Spectrum Analyzing
Spectral Adaptive
Filtering (SAF)
-Signaal wordt opgesplitst in
individuele frequentie sub-banden
-band splitting filter maakt gebruik van
intelligente demping om de amplitude
vs. snelheid karakteristiek te
lineariseren
-Met als basis de info van de applicatie,
(vloeistof of gas, flow span en
dichtheid) kan een
amplitude/gevoeligheids-curve
berekend worden
-resultaten van de individuele sub-band
analysers worden vergeleken met de
berekende gevoeligheidscurve
- Uiteindelijk wordt een tight band pass
filter gebruikt die de focus legt rond het
vortex flow signaal
SUB6
SUB5
SUB4
SUB3
SUB2
SUB1
Time
Time
SB6 SB5 SB4 SB3 SB2 SB1 Frequency
Noise
Gain
Frequency
[Separation by SAF]
Frequency
Vortex Signal
Sensitivity Curve
- 98 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voordelen & beperkingen
50
- 99 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Voordelen
Geaccepteerd door de industrie
Industriële metingen bestaan reeds sinds late jaren 60
Output proportioneel tot snelheid
Geen invloed van dichtheid, p, T°, geleidbaarheid, …
Hoge nauwkeurigheid over grote range (40:1) voor een redelijke prijs
Weinig mogelijke lekpunten
Sensor aansluiting
Gelaste flenzen , gegoten bodies
Minimum snelheid/debiet nodig (Re>20.000)
Klein permanent drukverlies
Minimale tegendruk nodig om cavitatie te vermijden
Debietmeter normaal 1 maat kleiner dan de nominale diameter van de buis (hogere
snelheid)
Sommige leveranciers kunnen reduced bore types aanbieden
Hoge T° & P ratings mogelijk
Geen bewegende delen
- 100 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Beperkingen
De meeste pick up sensoren zijn gelokaliseerd op 1 punt
Pipe condition/ Flowprofile gevoelig
– Sommige leveranciers zijn minder gevoelig aan deze condities / profiles.
Multivariabele oplossingen
– Meeste leveranciers voorzien een geïntegreerde T°-correctie (verzadigde stoom, dichtheidscompensatie, actieve
K-factor correctie)
– Sommige leveranciers voorzien een geïntegreerde P-correctie (Drukopname is echter op de verkeerde plaats.
Druk zou moeten gemeten worden op 5D na de meter)
Vibratie-gevoelig (alle leveranciers specifiëren in de range van 1G bij flow van water)
Soms moeilijk om onderscheid te maken tussen vortex signaal en vibraties
– Sommige leveranciers voorzien vibratie diagnostiek
51
- 101 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vortex veiligheidstoepassingen
- 102 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vortex en veiligheid
Verklaring van sommige benamingen en afkortingen
IEC 61508
• Algemene standaard over veiligheid
IEC 61511
• Meer gedetailleerde veiligheidsstandaard voor de proces-
industrie
FMEDA Report volgens IEC 61508 en IEC 61511
• Failure Modes, Effects and Diagnostic Analysis
Noodzakelijk om SFF (Safety Failure Fraction) te
vinden/berekenen
Page 102
SIL = Safety Integrity level
52
- 103 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vortex en veiligheid
SFF = Safety Failure Fraction
The magic number is 0.9 or 90%
SFF > 0.9 one unit is suitable for a SIL 2
application
SFF < 0.9 two units are needed for SIL 2
application
Page 103
Application Application Application Application
SFF SIL 1 SIL 2 SIL 3 SIL 4
< 0.9 1 unit 2 units 3 units 4 units
> 0.9 1 unit 1 unit 2 units 3 units
SIL = Safety Integrity level
- 104 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Vortex en veiligheid
Page 104
SIL = Safety Integrity level
Kalibratie samen
53
- 105 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatievoorschriften
- 106 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatievoorschriften
Anders per leverancier!
54
- 107 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatievoorschriften
Positionering converter in alle richtingen
Converter naar boven/beneden/zijdelings gericht
Zijdelingse installatie kan gebruikt worden om invloeden van
vibraties te voorkomen
Volle buis vereist
Vermijden van waterslag of andere obstakels
Goede uitlijning van piping en dichtingen
Page 107
Liquid
Gas / Steam
- 108 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Installatievoorschriften
Page 108
55
- 109 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Applicaties
- 110 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Waar te gebruiken
Propere toepassingen / viscositeit vloeistof (<3cp)
Stoom & Gassen
Lage viscositeit Koolwaterstoffen
Water, laal corrosieve chemicaliën
Niet geleidende vloeistoffen
Hoge-T oliën en bitumen
Page 110
56
- 111 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Waar niet te gebruiken
Minder geschikt voor
– corrosieve chemicaliën
– visceuze vloeistoffen (<7cp)
– Lichte slurries (minder dan 1%)
Niet mogelijk
– Stoffige en vuile processtromen
– 2-fasige stroom
– Pulserende flow
– Hoge omgevingsvibraties (>1G)
Page 111
- 112 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Specificaties
Maten / procesaansluitingen
– Wafer 15-100 mm
– Flenzen 15-400 mm
– Butt weld
– Tri clamp
– Smooth flens-afwerking
– RTJ (Ring Type Joint or nut und feder- DIN 2526/2513) Flenzen
– EN, ANSI, JIS
Sizing toont aan dat de meter telkens 1-2 maten kleiner is dan de nominale
diameter van de buis
Nauwkeurigheid
– +/- 0.75% van de gemeten waarde voor vloeistoffen
– +/- 1% van de gemeten waarde voor gassen
– MV types: +/- 2% van de gemeten waarde voor massa-debiet van verzadigde stoom
Repeatability
– +/- 0.2% va de gemeten waarde
Druk
– Vanaf volledig vacuüm tot EN 250 / ANSI #2500
Temperatuur
– -200°C tot +450 °C
Wetted materials
– SS316, CF8M, ASTM 216 A WCB, 1.4552, Hast C, Gold coating
Page 112
57
- 113 -
VIK – Go with the flow
Copyright © Yokogawa Electric Corporation
October 2012
Specificaties
Wetted parts behandeling
– NACE compliant
– Zuurstof ontvetting mogelijk
Ranges
– Vanaf Re 20.000: tot 10 m/s voor vloeistoffen en 80 m/s voor gassen/stoom
Output
– 2 draad 4-20 mA Hart, Profibus, FF
– EDDL en/of FDT/DTM ready
– Gelijktijdig pulse contact
Remote electronica
– Tot 30m tussen meter en converter
CE MARKING
– PED
– ATEX: Exi, Exd, Exn, FM, JIS
Beschermingsklasse
– IP65 or 67
Certificaten
– 3.1 Materiaal certificaat
– Las-certificaten
– Dye penetration test
– FMEDA report
– ATEX certificaten
– Kalibratie
Page 113
<VIK – Go with the flow>
Copyright © Yokogawa Electric Corporation
<October 2012>
- 114 -
Vragen?

More Related Content

What's hot

Boiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsBoiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsManohar Tatwawadi
 
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670طه محمد
 
SPICE Model of Current Transformer
SPICE Model of Current TransformerSPICE Model of Current Transformer
SPICE Model of Current TransformerTsuyoshi Horigome
 
Level measurement
Level measurementLevel measurement
Level measurementgujjubharat
 
Principle of mass flow meter
Principle of mass flow meterPrinciple of mass flow meter
Principle of mass flow meterPrem Baboo
 
Siemens s7 300 programming
Siemens s7 300 programming Siemens s7 300 programming
Siemens s7 300 programming satyajit patra
 
Initial Conditions
Initial ConditionsInitial Conditions
Initial ConditionsSmit Shah
 
Ravi Shankar_I&C Engineer
Ravi Shankar_I&C EngineerRavi Shankar_I&C Engineer
Ravi Shankar_I&C EngineerRavi Shankar
 
Instrumentation positioner presentation
Instrumentation positioner presentationInstrumentation positioner presentation
Instrumentation positioner presentationSANGRAM PATNAIK
 
Instrumentation And Control Data for Specialist.
Instrumentation And Control Data for Specialist.  Instrumentation And Control Data for Specialist.
Instrumentation And Control Data for Specialist. Instrumentation Knowledge
 
Plc and scada project ppt
Plc and scada project pptPlc and scada project ppt
Plc and scada project pptPriya Hada
 
Split range control system
Split range  control systemSplit range  control system
Split range control systemAshvani Shukla
 
Sag in overhead transmission line, sag calculation &amp; string chart
Sag in overhead transmission line, sag   calculation &amp; string chartSag in overhead transmission line, sag   calculation &amp; string chart
Sag in overhead transmission line, sag calculation &amp; string chartvishalgohel12195
 
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)Thorne & Derrick International
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingAsif Eqbal
 
Introduction to Industrial Instrumentation
Introduction to Industrial InstrumentationIntroduction to Industrial Instrumentation
Introduction to Industrial InstrumentationMaria Romina Angustia
 
PLC applications .pdf
PLC applications .pdfPLC applications .pdf
PLC applications .pdfmohamedm56
 

What's hot (20)

Boiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power StationsBoiler Drum level measurement in Thermal Power Stations
Boiler Drum level measurement in Thermal Power Stations
 
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670
 
SPICE Model of Current Transformer
SPICE Model of Current TransformerSPICE Model of Current Transformer
SPICE Model of Current Transformer
 
Presentation On Ips
Presentation On IpsPresentation On Ips
Presentation On Ips
 
Level measurement
Level measurementLevel measurement
Level measurement
 
Principle of mass flow meter
Principle of mass flow meterPrinciple of mass flow meter
Principle of mass flow meter
 
Siemens s7 300 programming
Siemens s7 300 programming Siemens s7 300 programming
Siemens s7 300 programming
 
IEC60296-2020.pdf
IEC60296-2020.pdfIEC60296-2020.pdf
IEC60296-2020.pdf
 
Initial Conditions
Initial ConditionsInitial Conditions
Initial Conditions
 
Tap Changer
Tap ChangerTap Changer
Tap Changer
 
Ravi Shankar_I&C Engineer
Ravi Shankar_I&C EngineerRavi Shankar_I&C Engineer
Ravi Shankar_I&C Engineer
 
Instrumentation positioner presentation
Instrumentation positioner presentationInstrumentation positioner presentation
Instrumentation positioner presentation
 
Instrumentation And Control Data for Specialist.
Instrumentation And Control Data for Specialist.  Instrumentation And Control Data for Specialist.
Instrumentation And Control Data for Specialist.
 
Plc and scada project ppt
Plc and scada project pptPlc and scada project ppt
Plc and scada project ppt
 
Split range control system
Split range  control systemSplit range  control system
Split range control system
 
Sag in overhead transmission line, sag calculation &amp; string chart
Sag in overhead transmission line, sag   calculation &amp; string chartSag in overhead transmission line, sag   calculation &amp; string chart
Sag in overhead transmission line, sag calculation &amp; string chart
 
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizing
 
Introduction to Industrial Instrumentation
Introduction to Industrial InstrumentationIntroduction to Industrial Instrumentation
Introduction to Industrial Instrumentation
 
PLC applications .pdf
PLC applications .pdfPLC applications .pdf
PLC applications .pdf
 

Similar to VA-meters, Verschildruk / Vortex debietmeters

DC-net for DSO? European Utility Week 2014
DC-net for DSO?  European Utility Week 2014DC-net for DSO?  European Utility Week 2014
DC-net for DSO? European Utility Week 2014Hans Schneider
 
Meten aan E+PV installaties (Solar Event)
Meten aan E+PV installaties (Solar Event)Meten aan E+PV installaties (Solar Event)
Meten aan E+PV installaties (Solar Event)VNUExhibitions
 
Presentatie Workshop Condition Based Maintenance13 En4 Oct12
Presentatie Workshop Condition Based Maintenance13 En4 Oct12Presentatie Workshop Condition Based Maintenance13 En4 Oct12
Presentatie Workshop Condition Based Maintenance13 En4 Oct12GH_Wijnants
 
Sdu middagen nen 3140 Kees Compaan
Sdu middagen nen 3140 Kees CompaanSdu middagen nen 3140 Kees Compaan
Sdu middagen nen 3140 Kees CompaanRaymond Soerodikromo
 
Go with the flow: Basisbegrippen in industrile flowmetingen
Go with the flow: Basisbegrippen in industrile flowmetingenGo with the flow: Basisbegrippen in industrile flowmetingen
Go with the flow: Basisbegrippen in industrile flowmetingenie-net ingenieursvereniging vzw
 
Introductie Yokogawa AQ7280 OTDR Simac
Introductie Yokogawa AQ7280 OTDR SimacIntroductie Yokogawa AQ7280 OTDR Simac
Introductie Yokogawa AQ7280 OTDR SimacSimac Electronics bv
 
Industriële ventilatoren Almeco AVK
Industriële ventilatoren Almeco AVKIndustriële ventilatoren Almeco AVK
Industriële ventilatoren Almeco AVKpieterjantroost
 
Phoenix Contact, Themamiddag Alles over bliksembeveiliging
Phoenix Contact, Themamiddag Alles over bliksembeveiligingPhoenix Contact, Themamiddag Alles over bliksembeveiliging
Phoenix Contact, Themamiddag Alles over bliksembeveiligingCito Benelux
 
1 sermes totaal (nederlands) v1.6-
1  sermes totaal (nederlands) v1.6-1  sermes totaal (nederlands) v1.6-
1 sermes totaal (nederlands) v1.6-SERMES Nederland
 
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water Quality
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water QualityDSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water Quality
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water QualityDeltares
 
Toekomst van afvalwater pomptechnologie - Stefan Abelin
Toekomst van afvalwater pomptechnologie - Stefan AbelinToekomst van afvalwater pomptechnologie - Stefan Abelin
Toekomst van afvalwater pomptechnologie - Stefan AbelinXylem Water Solutions Benelux
 

Similar to VA-meters, Verschildruk / Vortex debietmeters (16)

Sdu middagen nen 1010 keescompaan
Sdu middagen nen 1010 keescompaanSdu middagen nen 1010 keescompaan
Sdu middagen nen 1010 keescompaan
 
DC-net for DSO? European Utility Week 2014
DC-net for DSO?  European Utility Week 2014DC-net for DSO?  European Utility Week 2014
DC-net for DSO? European Utility Week 2014
 
Meten aan E+PV installaties (Solar Event)
Meten aan E+PV installaties (Solar Event)Meten aan E+PV installaties (Solar Event)
Meten aan E+PV installaties (Solar Event)
 
Presentatie Workshop Condition Based Maintenance13 En4 Oct12
Presentatie Workshop Condition Based Maintenance13 En4 Oct12Presentatie Workshop Condition Based Maintenance13 En4 Oct12
Presentatie Workshop Condition Based Maintenance13 En4 Oct12
 
Know your pressure (Koen Hoogstoel | Yokogawa Belgium)
Know your pressure (Koen Hoogstoel | Yokogawa Belgium)Know your pressure (Koen Hoogstoel | Yokogawa Belgium)
Know your pressure (Koen Hoogstoel | Yokogawa Belgium)
 
Sdu middagen nen 3140 Kees Compaan
Sdu middagen nen 3140 Kees CompaanSdu middagen nen 3140 Kees Compaan
Sdu middagen nen 3140 Kees Compaan
 
Total Cost of Ownership / facturatie (KROHNE)
Total Cost of Ownership / facturatie (KROHNE)Total Cost of Ownership / facturatie (KROHNE)
Total Cost of Ownership / facturatie (KROHNE)
 
Go with the flow: Basisbegrippen in industrile flowmetingen
Go with the flow: Basisbegrippen in industrile flowmetingenGo with the flow: Basisbegrippen in industrile flowmetingen
Go with the flow: Basisbegrippen in industrile flowmetingen
 
Introductie Yokogawa AQ7280 OTDR Simac
Introductie Yokogawa AQ7280 OTDR SimacIntroductie Yokogawa AQ7280 OTDR Simac
Introductie Yokogawa AQ7280 OTDR Simac
 
Industriële ventilatoren Almeco AVK
Industriële ventilatoren Almeco AVKIndustriële ventilatoren Almeco AVK
Industriële ventilatoren Almeco AVK
 
Phoenix Contact, Themamiddag Alles over bliksembeveiliging
Phoenix Contact, Themamiddag Alles over bliksembeveiligingPhoenix Contact, Themamiddag Alles over bliksembeveiliging
Phoenix Contact, Themamiddag Alles over bliksembeveiliging
 
1 sermes totaal (nederlands) v1.6-
1  sermes totaal (nederlands) v1.6-1  sermes totaal (nederlands) v1.6-
1 sermes totaal (nederlands) v1.6-
 
Solar panel rec
Solar panel rec Solar panel rec
Solar panel rec
 
Gastcollege Niveaumeten HoGent 2015
Gastcollege Niveaumeten HoGent 2015Gastcollege Niveaumeten HoGent 2015
Gastcollege Niveaumeten HoGent 2015
 
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water Quality
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water QualityDSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water Quality
DSD-NL 2015, SOBEK 3 Gebruikersbijeenkomst, 4 Ontwikkelingen D-Water Quality
 
Toekomst van afvalwater pomptechnologie - Stefan Abelin
Toekomst van afvalwater pomptechnologie - Stefan AbelinToekomst van afvalwater pomptechnologie - Stefan Abelin
Toekomst van afvalwater pomptechnologie - Stefan Abelin
 

More from ie-net ingenieursvereniging vzw

Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)ie-net ingenieursvereniging vzw
 
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
Hoe maak ik de omgeving van mijn opslagtank veilig  efficientHoe maak ik de omgeving van mijn opslagtank veilig  efficient
Hoe maak ik de omgeving van mijn opslagtank veilig efficientie-net ingenieursvereniging vzw
 
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)ie-net ingenieursvereniging vzw
 
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)ie-net ingenieursvereniging vzw
 

More from ie-net ingenieursvereniging vzw (20)

Ultrasoon_Clamp-on.pdf
Ultrasoon_Clamp-on.pdfUltrasoon_Clamp-on.pdf
Ultrasoon_Clamp-on.pdf
 
Elektromagnetische_debietmeters.pdf
Elektromagnetische_debietmeters.pdfElektromagnetische_debietmeters.pdf
Elektromagnetische_debietmeters.pdf
 
SGS Skybase (NL) .pdf
SGS Skybase (NL) .pdfSGS Skybase (NL) .pdf
SGS Skybase (NL) .pdf
 
VEGA-Radar vs US-26APR2022-NL.pdf
VEGA-Radar vs US-26APR2022-NL.pdfVEGA-Radar vs US-26APR2022-NL.pdf
VEGA-Radar vs US-26APR2022-NL.pdf
 
From process to emission
From process to emissionFrom process to emission
From process to emission
 
Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)Contactloos volume flow meting op transportbanden (ENG.)
Contactloos volume flow meting op transportbanden (ENG.)
 
Connecting fieldbus power and knowledge
Connecting fieldbus power and knowledgeConnecting fieldbus power and knowledge
Connecting fieldbus power and knowledge
 
Frequentieregelaars
FrequentieregelaarsFrequentieregelaars
Frequentieregelaars
 
Breekplaten beademingsmachines vlamdover (NED.)
Breekplaten beademingsmachines vlamdover (NED.)Breekplaten beademingsmachines vlamdover (NED.)
Breekplaten beademingsmachines vlamdover (NED.)
 
Veiligheden rond de tank
Veiligheden rond de tankVeiligheden rond de tank
Veiligheden rond de tank
 
Veiligheden rond de tank
Veiligheden rond de tankVeiligheden rond de tank
Veiligheden rond de tank
 
Hima cyber security
Hima cyber securityHima cyber security
Hima cyber security
 
Vik g.haekens-atex risico evaluatie
Vik g.haekens-atex risico evaluatieVik g.haekens-atex risico evaluatie
Vik g.haekens-atex risico evaluatie
 
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
Hoe maak ik de omgeving van mijn opslagtank veilig  efficientHoe maak ik de omgeving van mijn opslagtank veilig  efficient
Hoe maak ik de omgeving van mijn opslagtank veilig efficient
 
Checklist tankcontrole 2018 bacd
Checklist tankcontrole 2018 bacdChecklist tankcontrole 2018 bacd
Checklist tankcontrole 2018 bacd
 
Controle en ingebruikname van uw opslagtank
Controle en ingebruikname van uw opslagtankControle en ingebruikname van uw opslagtank
Controle en ingebruikname van uw opslagtank
 
Certainly not explosive (Eng)
Certainly not explosive (Eng)Certainly not explosive (Eng)
Certainly not explosive (Eng)
 
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (Nl.)
 
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
Elektrische installaties in ruimtes met stofexplosiegevaar (1.3 Mb) (Nl.)
 
Tuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentationTuev sued-drives-and-controls-2014-presentation
Tuev sued-drives-and-controls-2014-presentation
 

VA-meters, Verschildruk / Vortex debietmeters

  • 1. 1 VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 - 1 -- 1 - GO WITH THE FLOW 2012 VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 - 2 -- 2 - VA-meters Verschildruk debietsmeters Vortex debietsmeters
  • 2. 2 VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 - 3 -- 3 - VA-meters - 4 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Agenda Nomenclatuur Meetprincipe Toepassingsgebied Uitvoeringen Nauwkeurigheid Voordelen en beperkingen Speciale uitvoeringen Installatievoorschriften Page 4
  • 3. 3 - 5 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nomenclatuur - 6 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nomenclatuur Variabele doorlaat-meter – Vado-meter of VA-meter Vlotterdebiet-meter Zweeftol-debietmeter Rotameter Peil-meter ….
  • 4. 4 - 7 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Meetprincipe - 8 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Meetprincipe
  • 5. 5 - 9 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Meetprincipe Meetprincipe: zwaartekracht Conische geslepen buis met vlotter Druk van het fluïdum = gewicht van de vlotter => Vlotter blijft hangen Hoogte van vlotter is evenredig met de stroomsnelheid van gas of vloeistof (debiet) Schaalverdeling - 10 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Toepassingsgebied en voorwaarden
  • 6. 6 - 11 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Dichteid moet constant zijn Vaste deeltjes in het medium zijn niet toegestaan – aantasting vlotter, meetfouten, blokking Viscositeit: max. 100 mPa.s Druk: tot en met 700 bar Temperatuur: – RVS : -200 tot + 450°C – PTFE: -80 tot +130°C Toepassingsgebieden en voorwaarden - 12 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 – Low-range limiet 10 : 1 – High-range limiet: • water: 130 m³/h • lucht: 1400 m³/h – Repeatability: 0,1% van full scale – Installatie: vertikaal – Meestal voor lokale indicatie – Drukval over vlotter: constant – Meet-karakteristieken: lineair Toepassingsgebieden en voorwaarden
  • 7. 7 - 13 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Uitvoeringen - 14 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Metalen Glas Plastic Uitvoeringen in verschillende materialen
  • 8. 8 - 15 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nauwkeurigheden - 16 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nauwkeurigheid bij Rotameters Bestaande systeem voor classificatie van de nauwkeurigheid is recent herzien om de begrijpbaarheid ervan te vergroten naar klanten toe. De voormalige specificaties (gecreëerd in december 1978) maakten gebruik van onderstaande formule ter berekening van de fout voor de gemeten waarden Formule: F = (¾ M + ¼ E)*K/100 M = gemeten waarde van de flow met flow-eenheid E = full scale waarde van de flow met flow-eenheid K = waarde van de nauwkeurigheidsklasse => Nieuw systeem is eenvoudiger en transparant -> praat niet meer over nauwkeurigheidsklassen -> bepaalt het maximum toegelaten percentage van afwijking van de gemeten waarde
  • 9. 9 - 17 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nauwkeurigheid bij Rotameters De nieuwe specificaties worden gesplit in 2 ranges: – Lineaire Range van qG tot Qmax (main working range) – Niet-lineaire Range van Qmin tot qG (low flow range) De nauwkeurigheidsklasse wordt vervangen door 2 nieuwe parameters: – Maximum permissible error “G” – Threshold value “qG” Vroegere specificatie Nieuwe specificatie Accuracy class 1.6 G=1.6 qG = 50 % Accuracy class 2.5 G=2.5 qG = 50 % Accuracy class 4 G=4 qG = 50 % - 18 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nauwkeurigheid bij Rotameters Former specification: accuracy class 1.6 New specification: qG = 50%, G=1.6 Now 8% Before 5.2% New specification less strict more strict than former specification qG Threshold value « qG » is defined by each manufacturer Range qG to Qmax with constant error value Deviation / % of measured value Measuring range / % Qmax
  • 10. 10 - 19 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voordelen en beperkingen - 20 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voordelen Lage kostprijs Geen voeding nodig voor lokale indicatie Geschikt voor gas, vloeistoffen en stoom Metalen versie – CIP – Steriliseerbaar – PTFE-lining Verschillende vormen van vlotters beschikbaar Constante drukval onafhankelijk van het debiet
  • 11. 11 - 21 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Beperking Vertikale installatie is verplicht Invloed van wijzigingen in temperatuur en densiteit Schade aan vlotter door aanwezigheid van vaste deeltjes – Kan tegengegaan worden door bv. Magneetfilters Invloed van pulsatie en vibratie Nood aan exotische materialen (monel, Hastelloy, …) - 22 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Measuring Range of a Rotameter Indication Float reaches the upper stopper at 105% of max. flow. Float lifts at 5 to 8% of max. flow. Beperkingen Start, zero en maximum Zonder flow: vlotter ligt op onderste stopper (rustpunt) Meting start wanneer de drukval hoog genoeg is om de vlotter te liften (5 – 8% van de max. flow) Rotameter heeft dus geen afgelijnd zero-punt Maximum overrange die kan aangeduid worden vooraleer de bovenste stopper wordt bereikt is tussen 105 – 110% van de schaal
  • 12. 12 - 23 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Speciale uitvoeringen - 24 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Float blocking detection De Zero-fluctuaties worden geregistreerd onder No-flow condition wanneer de vlotter zich op het rustpunt bevindt. Er wordt een grens vastgelegd voor het minimum aan fluctuaties met inbegrip van een safety factor.
  • 13. 13 - 25 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 ATEX: EExd Rota meter VA-meters • Met EExd approval (12 mm glass moulded, EEX d wartels M20*1,5) • Met dust EEx approval (12 mm glass moulded) • Standaard IP 67 - 26 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 SIL Safety Integrity Level – Norm: IEC 61508 en IEC 61511 – SIL 1 : Ondergeschikte (onroerende) goederen- en productiebescherming. – SIL 2 : Belangrijke (onroerende) goederen- en productiebescherming. Mogelijke kans op verwonding van werknemers. – SIL 3 : Werknemers- en gemeenschap-bescherming. – SIL 4 : Katastrofale impact op de gemeenschap.
  • 14. 14 - 27 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatievoorschriften - 28 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatie-voorschriften De VA-meter dient verticaal gemonteerd te worden met flow-richting opwaarts Grotere leiding-diameters vragen een rechte lengte van 5D voor en na voor een ideaal flow-profiel Vermijd corrosieve omgevingen Geen blootstelling aan omgeving met sterke vibraties Om interferentie te vermijden is de minimale afstand tussen twee flowmeters best > 300mm Het meetgedeelte is gevoelig aan externe niet- homogene magnetische velden (bv. Solenoid valves) Asymmetrische magnetische vormen kunnen een invloed hebben op de werking van de vlotter
  • 15. 15 - 29 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatie Hints voor Metalen Rotameters VA-meters Min. 300 mm Grotere nominale diameters (DN80/DN100), vragen ten minste 5D voor en na de Rotameter VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 - 30 -- 30 - Verschildruk debietsmeters
  • 16. 16 - 31 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Wet van Bernoulli Wet van behoud van energie: drukenergie + statische energie + kinetische energie = constant Permanent Pressure Loss Final Head After Pressure Recovery Upstream Initial Head Maximum Pressure Change Streamlin e (Typical) Flow High Pressure Connection Low Pressure Connection Primary Element Concentric Orifice Plate Secondary Element DP Transmitter ρ ε p dmCQV ∆⋅ ⋅⋅ Π ⋅⋅⋅= 2 4 2 22 1 tcoefficiendischarge m K C ⋅− ⋅ == µ µ =ε Gas expansion factor (for liquids =1) 2 1 0 1 0       == d d A A m 0 2 A A =µ ρ=density Diameter pipe = D A0=surface orifice hole A1=surface pipe A2=surface after orifice hole A0A1 A2 Volumetrisch debiet - 32 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Massadebiet ρε β ..2 41 2 4 pd C Qm ∆⋅⋅ Π ⋅⋅ − = Permanent Pressure Loss Final Head After Pressure Recovery Upstream Initial Head Maximum Pressure Change Streamlin e (Typical) Flow High Pressure Connection Low Pressure Connection Primary Element Concentric Orifice Plate Secondary Element DP Transmitter A0A1 A2 factorapproachofvelocity 1 1 4 = − β tcoefficiendischarge=C 1)liquids(forfactorexpansionGas ==ε D d == BetaRatioβ conditionsflowingatdensity=ρ d= Bore Diameter primary element pressurealDifferenti=∆p D= Pipe Diameter Wet van Bernoulli Wet van behoud van energie: drukenergie + statische energie + kinetische energie = constant Relatie tussen dp en Qm:
  • 17. 17 - 33 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 De berekeningen: de makkelijke manier P dC Qm ∆⋅⋅ ⋅ − = ρε π β 2 41 2 4 K-factor PkQm ∆⋅= Is dit correct? - 34 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Binnenin de leiding Snelheid omhoog (V ⇑⇑⇑⇑ ) Druk daalt (P ⇓⇓⇓⇓ ) Dichtheid daalt (ρρρρ ⇓⇓⇓⇓ ) Snelheid omhoog (V ⇑⇑⇑⇑ ) Punt met laagste druk (vena contracta) verschuift T stijging D en d wijziging
  • 18. 18 - 35 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Larger beta Smaller beta d/Dβ = dD Wat is de ββββ−−−−ratio Beta Ratio (ββββ) – Definitie: – De verhouding van de orifice bore diameter (d) en de interne buis diameter (D). – Definieert hoeveel restrictie (drukval) je in de leiding/orifice kan hebben. – Hoe kleiner Beta, hoe groter de restrictie. - 36 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Discharge coefficiënt (C) Empirisch bepaalde factor voor een DP flow element FlowlTheoretica FlowActual =C
  • 19. 19 - 37 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Discharge coëfficient: orifice en averaging pitot Orifice Averaging pitot - 38 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Discharge coëfficiënt varieert met debiet Het punt met de laagste druk noemen we de ‘Vena Contracta’. De exacte positie van de Vena Contracta wijzigt als de flow verandert. Dit effect heeft impact op de Discharge coëfficiënt. High side Low side Vena Contracta
  • 20. 20 - 39 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 P = 4 bar, abs Same volume 2x the gas or steam! P = 8 bar, abs Dichtheid ρρρρ is afhankelijk van druk en temperatuur Bij eenzelfde volume neemt de dichtheid toe als de druk toeneemt Bij eenzelfde volume neemt de dichtheid toe als de temperatuur toeneemt - 40 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Het medium moet door een vernauwing: Snelheid omhoog (Statische) druk daalt Dichtheid daalt We moeten een correctiefactor invoeren om de dichtheidswijziging op te vangen High side Low side Primary element Velocity increase (V ⇑⇑⇑⇑ ) Pressure decrease (P ⇓⇓⇓⇓ ) Density decrease (ρρρρ ⇓⇓⇓⇓ ) Flow Fouten bij primaire elementen: dichtheidswijziging
  • 21. 21 - 41 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Velocity of approach-factor factorapproachofvelocity 1 1 4 = − β High side Low side Primary element Flow Door temperatuurswijzigingen, wijzigen ook afmetingen van het primair element - 42 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 De diameter van de buis (D) en van het primair element (d) verandert door de T. Oorzaak is de thermische expansie van metalen. Typische Fouten door T-veranderingen: Gassen & Stoom: 0.05 - 0.5% Vloeistoffen: 0.05 - 0.5% Dit is typisch een redelijk kleine fout, maar in applicaties waar de T nogal varieert, kan dit belangrijk zijn: Primair element bore (d) wordt beïnvloed door de T° d = 10 mm d = 10.03 mm T = 30 degC T = 200 degC Steel Stainless (304): 17.3 x 10-6 mm/K Steel Stainless (316) 16.0 x 10-6 mm/K
  • 22. 22 - 43 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Varieert door debietwijziging 1. C = Discharge Coefficient 2. ε = Gas Expansion Factor Varieert door druk en T 5. Density Compensation 6. Compressibility Factor Varieert door temperatuurswijziging 3. Velocity of Approach = 1/(1-ββββ4)1/2 4. d2 = Diameter van primary element Massadebiet wordt bepaald door continue herberekening van deze parameters Wat is de impact van de proceswijzigingen? ρ β ε ..2 1 1 4 2 4 pdCQm ∆⋅⋅ − ⋅ Π ⋅⋅= <VIK – Go with the flow> Copyright © Yokogawa Electric Corporation <October 2012> - 44 - ISO 5167 formule 1 2 4 2 41 ρε π β P dC Qm ∆ − = C =f ( Re D No ) µ =f ( T ) ββββ =f ( D , d ) ε = f ( SP , ∆∆∆∆ P ) Re D No =f ( Q m , µ , D ) d =f ( d 0 , αααα 2 , T ) D =f ( D 0 , αααα 1 , T ) ρρρρ 1 =f ( SP , T ) Q m Mass flow rate C Discharge coefficient ββββ Beta Ratio d/D d Bore of Diffrential Producer D Pipe inner diameter ε Gas expansion factor ∆∆∆∆ P Differential pressure ρρρρ Density Re D No Reynolds number SP Static pressure T Temperature µµµµ Viscosity αααα Thermal expansion
  • 23. 23 - 45 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nauwkeurigheid binnen de ISO formule Nauwkeurigheid: – ISO5167-2 2003 – Primary device: Orifice; medium: gas 2222 4 22 4 422 m m p p d d2 D D2 C C q q                                                 = ρ ρ 4 1 + 4 1 + 1-β + 1-β β + ε ε + δδδδδδδ (δC / C)2 C (δε / ε)2 ε ((2β4)/(1-β4))2(δD / D)2 D (2/(1-β4))2(δd / d)2 d 1/4(δ∆P/∆P)2 P 1/4(δρ /ρ)2 ρ C ε D d DP ρ 0.928 0.563 0.072 0.137 0.086 0.0004 0.0025 - 46 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 De berekeningen: de makkelijke manier P dC Qm ∆⋅⋅ ⋅ − = ρε π β 2 41 2 4 K-factor PkQm ∆⋅= Is dit correct? Ja, als er geen externe factoren wijzigen
  • 24. 24 - 47 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Single variable flow Vaste compensatie-factor (k) Opletten bij gebruik in dynamische condities Low flow PkQm ∆⋅= - 48 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Druktransmitter met zowel verschildruk, statische druk, temperatuurmeting én flow computer Flow computer Temp. sensor Four in one = Cost saving Dynamic flow measurement: Improves flow accuracy EJX /MV Mass flow output Multi-sensing (DP,SP, temp, density) Gauge pressure transmitter Differential pressure transmitter Temp. transmitter + Temp. sensor Wat is een multivariable transmitter?
  • 25. 25 - 49 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voorbeeld van de intelligentie binnenin een multivariabele druktransmitter Differential pressure Resonant sensor RTD ((((High accuracy)))) Computation ●●●● Flow calculation Re No compensation ●●●● Density compensation ・Flow rate Volume/mass ・Difference pressure ・Static pressure absolute pressure/(gage pressure) ・Temperature(density) Static pressure Temperature INPUT SIGNAL BUS OUTPUT HART F-Fieldbus ・Pulse Volume/mass Analog ・Difference pressure ・Static pressure absolute pressure/(gage pressure) ・Temperature(density) SIGNAL OUTPUT Fluid databank 126 most common fluids Orifice plate data Orifice Plate RTD - 50 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Dichtheidsberekeningen in een flow computer Hou rekening met de mogelijkheden! – Gebruikmakend van een database (bvb. DIPPR) (AIChE) • Eigenschappen van 126 verschillende vloeistoffen en gassen – AGA 8 of ISO12213 aardgas vergelijkingen • Simplified of full molecular weight composition – IAPWS-IF97 formules voor water en stoom – Eigen compensatie-tabel (dichtheid en viscositeit moet gekend zijn bij verschillende condities) Page 50
  • 26. 26 - 51 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voorbeeld van de DIPPR database Page 51 No. Fluid name No. Fluid name No. Fluid name No. Fluid name 1 Acetic Acid 33 Ethylamine 65 n-Decane 97 Vinyl Cyclohexene 2 Acetone 34 Ethylbenzene 66 n-Dodecane 98 Water 3 Acetonitrile 35 Ethylene 67 n-Heptadecane 99 1-Butene 4 Acetylene 36 Ethylene Glycol 68 n-Heptane 100 1-Decene 5 Acrylonitrile 37 Ethylene Oxide 69 n-Hexane 101 1-Decanal 6 Air 38 Fluorene 70 n-nonane 102 1-Decanol 7 Allyl Alcohol 39 Furan 71 n-Octane 103 1-Dodecene 8 Ammonia 40 Helium-4 72 n-Pentane 104 1-Dodecanol 9 Argon 41 Hydrazine 73 Neon 105 1-Heptanol 10 Benzaldehyde 42 Hydrogen 74 Neopentane 106 1-Heptene 11 Benzene 43 Hydrogen Chloride 75 Nitric Acid 107 1-Hexene 12 Benzoic Acid 44 Hydrogen Cyanide 76 Nitric Oxide 108 1-Hexadecanol 13 Benz Alcohol 45 Hydrogen Peroxide 77 Nitrobenzene 109 1-Octanol 14 Biphenyl 46 Hydrogen Sulfide 78 Nitroethane 110 1-Octene 15 Bromine 47 Isobutane 79 Nitrogen 111 1-Nonanal 16 Carbon Dioxide 48 Isobutene 80 Nitromethane 112 1-Nonanol 17 Carbon Monoxide 49 Isobutylbenzene 81 Nitrous Oxide 113 1-Pentadecanol 18 Carbon Tetrachloride 50 Isopentane 82 Oxygen 114 1-Pentanol 19 Chlorine 51 Isoprene 83 Pentafluoroethane 115 1-Pentene 20 Chlorodifluoromethane 52 Isopropanol 84 Phenol 116 1-Undecanol 21 Chloroprene 53 m-chloronitrobenzene 85 Phosphoric Acid 117 1,1,2,2-Tetrafluoroethane 22 Chlorotrifluoroethylene 54 m-dichlorobenzene 86 Propadiene 118 1,1,2-Trichloroethane 23 Citric Acid 55 Methane 87 Propane 119 1,2,4-Trichlorobenzene 24 Cycloheptane 56 Methanol 88 Propylene 120 1,2-Butadiene 25 Cyclohexane 57 Methyl Acrylate 89 Pyrene 121 1,3-Butadiene 26 Cyclopentane 58 Methyl Ethyl Ketone 90 Styrene 122 1,3,5-Trichlorobenzene 27 Cyclopentene 59 Methyl Vinyl ether 91 Sulfur Dioxide 123 1,4-Dioxane 28 Cyclopropane 60 Monochlorobenzene 92 Toluene 124 1,4-Hexadiene 29 Dichlorodifluoromethane 61 n-Butane 93 Trichloroethylene 125 2-Methyl-1-Pentene 30 Divinyl Ether 62 n-Butanol 94 Trichlorofluoromethane 126 2,2-Dimethylbutane 31 Ethane 63 n-Butylaldehyde 95 Vinyl Acetate 32 Ethanol 64 n-Butyronitrile 96 Vinyl Chloride <VIK – Go with the flow> Copyright © Yokogawa Electric Corporation <October 2012> - 52 - Primaire elementen
  • 27. 27 - 53 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Pitot Tube Venturi Tube Wedge Flow ElementFlow Nozzle Elbow Overzicht Orifice plate - 54 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Pitot tube Wat is het? – Een L-vormige buis met een opening in de stroomrichting (dynamische drukmeting) met daarin een tweede buis met een opening loodrecht op de stroomrichting (meet de statische druk). Het debiet is rechtevenredig met het verschil tussen de dynamische en de statische drukmeting Nauwkeurigheid – Van 0.5% to 4% Voordelen – Klein – Draagbare oplossingen Beperkingen – Blokkage van de drukopeningen – De positie(s) van de statische drukopeningen kunnen de meting beinvloeden
  • 28. 28 - 55 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 De “averaging” pitot tube Wat? – Een pitot tube met meerdere dynamische en statische drukopeningen. De verschildruktransmitter berekent het debiet door het gemiddelde te nemen van de drukopeningen. Nauwkeurigheid – 1% Voordelen – Lage drukval – Bi-directionele oplossingen mogelijk – Mogelijkheid tot geïntegreerde temperatuursmeting voor massadebietsmeting Beperkingen – Geen berekeningen volgens een standaard - 56 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Averaging pitot tube: info Lage installatiekost in vergelijking met andere primaire elementen Drill Weld Insert Wire 3) Lage permanente drukval leidt tot kostenbesparing 2) Bi-directionele metingen mogelijk bij sommige vormen 4) « Non clogging » oplossingen mogelijk
  • 29. 29 - 57 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Averaging pitot tube: installatie Relatief lange upstream en downstream lengtes zijn echter noodzakelijk Gas application Steam application Horizontal pipe (side view) Vertical pipe (bottom view) Horizontal pipe (side view) Vertical pipe (bottom view) - 58 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Orifice plate Wat? – Een vlakke metalen plaat met een opening (al dan niet concentrisch). De verschildruktransmitter meet de druk voor en na de plaat en berekent zo het volumetrisch debiet. Nauwkeurigheid – Indien volgens de standaard ISO5167: 0.5% - 0.75% – Indien volgens de standaard AGA: 0.44 - 1% Voordelen – Goede nauwkeurigheid – Installatievoorschriften en documentatie voorhanden in ISO documentatie Nadelen – Relatief grote drukval – Grote upstream en downstream lengtes noodzakelijk – Blokkage van de impulsleidingen mogelijk bij sommige vloeistoffen of gassen
  • 30. 30 - 59 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Pressure tappings: Flanged tappings (Orifice flange assembly – most common execution) Corner tappings: used mostly in monobloc & wafer executions Case 1: with annular rings Case 2: single pressure tappings Orifice: tappings - 60 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Pipe tappings (D & D/2) Pipe tappings (D & D/2) are mostly used in larger pipe sizes to save the flanges cost. Orifice: tappings
  • 31. 31 - 61 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Steam application, horizontal line Compact mass flow including multi-variable transmitter & temperature compensation Compact flow measurement Gas Orifice: compact oplossingen - 62 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatie van de druktransmitter
  • 32. 32 - 63 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Page 63 Installation requirements according to ISO standard Installatievoorschriften en nauwkeurigheid - 64 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Meter run Wat? – Een orifice plaat met daarbij geinstalleerd een leiding en flensconstructie. De volledige constructie respecteert de upstream en downstream lengtes Nauwkeurigheid – Conform ISO5167: 0.5% Voordelen – Goede nauwkeurigheid – Geen problemen qua montage Beperkingen – Drukval redelijk hoog – Blokkage van de impulsleidingen mogelijk bij sommige vloeistoffen of gassen
  • 33. 33 - 65 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Venturi Wat? – A leiging met een convergerende ingang en divergerende uitgang. De verschildruktransmitter meet het drukverschil tussen inlet en middendeel en berekent op die manier het volumetrisch debiet Nauwkeurigheid – 0.7% - 1.5% Voordelen – Lagere drukval dan orifice plates – Practisch geen blokkages mogelijk Beperkingen – Duur - 66 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Nozzle Wat? – Een stuk leiding met een zacht inlopende ingang en een scherpe uitgang. De verschildruktransmitter meet het drukverschil tussen de ingang en de uitgang en bepaalt op deze manier het volumetrisch debiet Nauwkeurigheid – 2.0% Voordeel – Beperkt drukverlies Beperkingen – Duurder dan orifice plates – Slechts beperkte buisdiameters mogelijk
  • 34. 34 - 67 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Venturi nozzle Wat? – Een venturi met een nozzle ingang Nauwkeurigheid – 1% - 1.5% Voordelen – Minder drukval dan orifice plate – Combineert de sterktes van een venturi en nozzle Beperkingen/nadelen – Prijs - 68 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Selectie primair element Device Line size (mm) Field of application Specific Advantages Specific disadvantages Orifice plate flange taps 50 to 1000 General purpose Orifice plate corner taps 25 to 1200 Lines below 50 mm Economic, simple, flexible, widely accepted Pressure loss, upstream pipe requirements Orifice plate D & D/2 taps 100 to 1000 Line sizes above 600 mm Orifice plate quarter circle 25 to 500 Viscous fluids, low Reynolds number Viscous fluid, low flow rate Less accurate Orifice plate conical entrance 25 to 500 Viscous fluids, low Reynolds number Viscous fluid, low flow rate Less accurate Orifice plate eccentric 100 to 1000 Dirty fluids and two phase flow Dirty Fluids Less accurate Integral orifice plate 15 to 40 Small flowrates, small line size Small flowrates Less accurate Meter run 15 to 400 Accurate measurement Accuracy Manufacturing costs, handling length Venturi tube 50 to 1200 Accurate measurement, low pressure loss Accuracy with low pressure loss Handling length (Venturi) nozzle 65 to 500 High velocity fluids on low pressure loss Erosive fluids with low pressure loss Less accurate, handling length Averaging pitot tube 15 to 15000 Large flow rate at low pressure of clean fluids Economic, low pressure loss, bi- directional Clean fluids, no international standard
  • 35. 35 VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 - 69 -- 69 - Vortex debietsmeters - 70 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Agenda Werkingsprincipe Eigenschappen & specificaties Voordelen / beperkingen Vortex en veiligheidstoepassingen Installatievoorschriften Applicaties Page 70
  • 36. 36 - 71 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Werkingsprincipe - 72 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Werkingsprincipe Wat is een Karman Vortex Straat? Hoe wordt deze gebruikt in debietmeting? Page 72
  • 37. 37 - 73 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Karmán vortex straat Theodore von Kármán (1881-1963) is een Hongaars-Amerikaanse ingenieur en wetenschapper die hoofdzakelijk actief was in luchtvaart en ruimtevaart. Hij gaf les aan de universiteit van Göttingen, RWTH Aken, California Institute of Technology. Hij is medeoprichter van Jet Propulsion Laboratory, NASA Theodore von Kármán Page 73 - 74 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Karmán vortex straat Vortices zijn een natuurlijk fenomeen. Page 74
  • 38. 38 - 75 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Karmán vortex straat Page 75 - 76 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vortex als debietsmeting Page 76
  • 39. 39 - 77 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 l 17,0≈= l d St Het Strouhal getal (St): Vortex als debietsmeting Page 77 - 78 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Karmán vortex frequentie f = Karmán vortex frequency St = Strouhal number (constant in a certain area) v = fluid velocity d = width of vortex shedder (constant) d vSt f ⋅ = Vortex als debietsmeting Page 78
  • 40. 40 - 79 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 lichte bries - laminaire flow, no vortices formed Re < 5000 Stevige bries - transitie flow, onregelmatige vortices gevormd 5000 < Re < 20000 Sterke wind - turbulente flow, regelmatig vortex patroon Re > 20000 Reynolds getal (Re): Principe Page 79 - 80 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Relatie tussen St, Re en snelheid LINEAR RANGE MEASURING RANGE 5 x 10 3 2 x 10 4 VELOCITY .2 .1 .3 262 F/S (GAS) 32 F/S (LIQUID)1 F/S (LIQUID) 10 F/S (GAS) 7 x 107 SPECIFICATION RANGE REYNOLDS NUMBER StrouhalNumber Principe Page 80
  • 41. 41 - 81 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Principe Page 81 Laminar TurbulentTransitional Delta geometry { D } Round geometry { }– Alleen de delta geometrie geeft een optimaal verband tussen snelheid en vortex frequentie. – Verdere verbeteringen aan de geometrie hebben geleid tot een nauwkeurigheid van 0,75%. Geometrie van de shedder bar - 82 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Principe In praktijk vervangt de K-factor het St (Strouhal getal) als de toonaangevende parameter. De omzettingsvergelijking wordt dan: Flow rate = Vortex Frequency K-factor De K-factor wordt bepaald door de fabriekskalibratie van de debietmeter (water kalibratie – “ X “ Pulsen / Liter) K-factor wordt niet beïnvloed door: T, P, density, ... Gevolg hiervan is dat alle kalibraties uitgevoerd worden met water voor alle applicaties. Page 82
  • 42. 42 - 83 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Eigenschappen & specificaties - 84 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : pick-up sensor Sensor posities voor vortex metingen Page 84 Drukschommelingen Fluida-beweging Fluida-kracht op de shedder-bar
  • 43. 43 - 85 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : pick-up sensor Page 85 Verschildruk Integraal Diafragma Differential Switched Capacitor - 86 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor desig : pick-up sensor Page 86 Massieve piëzo pick up Shedder-Bar Vane achter Shedder-bar Piëzo vinger pick up in de Shedder
  • 44. 44 - 87 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : pick-up sensor Page 87 Drukschommelingen Fluida-beweging Fluida-kracht op de shedder-bar - 88 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : bodies Page 88 Wafer type Flanged type Insertion type
  • 45. 45 - 89 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : bodies Page 89 Reduced bore type - 90 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Sensor design : hoge & lage temperatuur Page 90 Extended neck: *Beschermt de elektronica tegen hoge/lage temperatuur *Installatie van elektronica buiten isolatie
  • 46. 46 - 91 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Convertor design Page 91 Remote opstelling Integral opstelling - 92 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Bidirectional flow Bidirectionele flow mogelijk gemaakt Page 92
  • 47. 47 - 93 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Multivariabel Page 93 RTD sensor piezo sensors shedder bar Druk gecompenseerd Temperatuur gecompenseerd - 94 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Temperatuur gecompenseerd Page 94 ingebouwde temperatuur sensor • beschermd in de shedder bar • +/- 1 °C (vloeistof), +/- 2 °C (gas/stoom); RTD Pt1000 multi-variabele optie • waarde flow & temperatuur worden weergegeven • dubbele output (flow: pulse, temp: 4-20mA) stoom massadebiet-berekening • Massadebiet-berekening, gebruik makend van gemeten T (druk = cte) • +/- 2% nauwkeurig Multivariabel
  • 48. 48 - 95 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Druk gecompenseerd Page 95 Ingebouwde druk sensor • ±1.5% van de gemeten waarde (Re ≥ 20000); ±2.5% van de gemeten waarde (10000 < Re < 20000) multi-variabele optie • waardes voor flow & druk worden weergegeven • dubbele output (flow, pressure) steam mass flowrate calculation • Massadebiet-berekening, gebruik makend van gemeten P (Temperatuur = cte) 1 Pressure sensor 2 Shut-off valve 3 Fully welded stainless steel design 4 Converter with Intelligent Signal Processing [ISP] Multivariabel - 96 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vibratie onderdrukking Page 96 Vibraties kunnen veroorzaakt worden door: •Pompen •Compressoren •Wandelende mensen •Piping •Wind •… Als f(vibration) = f(vortex) « interferenties »
  • 49. 49 - 97 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vibratie invloeden / onderdrukking Page 97 Frequency Analyzing/ Intelligent Amplification Output Waveform Vortex Signal met ruis Spectrum Analyzing Spectral Adaptive Filtering (SAF) -Signaal wordt opgesplitst in individuele frequentie sub-banden -band splitting filter maakt gebruik van intelligente demping om de amplitude vs. snelheid karakteristiek te lineariseren -Met als basis de info van de applicatie, (vloeistof of gas, flow span en dichtheid) kan een amplitude/gevoeligheids-curve berekend worden -resultaten van de individuele sub-band analysers worden vergeleken met de berekende gevoeligheidscurve - Uiteindelijk wordt een tight band pass filter gebruikt die de focus legt rond het vortex flow signaal SUB6 SUB5 SUB4 SUB3 SUB2 SUB1 Time Time SB6 SB5 SB4 SB3 SB2 SB1 Frequency Noise Gain Frequency [Separation by SAF] Frequency Vortex Signal Sensitivity Curve - 98 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voordelen & beperkingen
  • 50. 50 - 99 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Voordelen Geaccepteerd door de industrie Industriële metingen bestaan reeds sinds late jaren 60 Output proportioneel tot snelheid Geen invloed van dichtheid, p, T°, geleidbaarheid, … Hoge nauwkeurigheid over grote range (40:1) voor een redelijke prijs Weinig mogelijke lekpunten Sensor aansluiting Gelaste flenzen , gegoten bodies Minimum snelheid/debiet nodig (Re>20.000) Klein permanent drukverlies Minimale tegendruk nodig om cavitatie te vermijden Debietmeter normaal 1 maat kleiner dan de nominale diameter van de buis (hogere snelheid) Sommige leveranciers kunnen reduced bore types aanbieden Hoge T° & P ratings mogelijk Geen bewegende delen - 100 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Beperkingen De meeste pick up sensoren zijn gelokaliseerd op 1 punt Pipe condition/ Flowprofile gevoelig – Sommige leveranciers zijn minder gevoelig aan deze condities / profiles. Multivariabele oplossingen – Meeste leveranciers voorzien een geïntegreerde T°-correctie (verzadigde stoom, dichtheidscompensatie, actieve K-factor correctie) – Sommige leveranciers voorzien een geïntegreerde P-correctie (Drukopname is echter op de verkeerde plaats. Druk zou moeten gemeten worden op 5D na de meter) Vibratie-gevoelig (alle leveranciers specifiëren in de range van 1G bij flow van water) Soms moeilijk om onderscheid te maken tussen vortex signaal en vibraties – Sommige leveranciers voorzien vibratie diagnostiek
  • 51. 51 - 101 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vortex veiligheidstoepassingen - 102 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vortex en veiligheid Verklaring van sommige benamingen en afkortingen IEC 61508 • Algemene standaard over veiligheid IEC 61511 • Meer gedetailleerde veiligheidsstandaard voor de proces- industrie FMEDA Report volgens IEC 61508 en IEC 61511 • Failure Modes, Effects and Diagnostic Analysis Noodzakelijk om SFF (Safety Failure Fraction) te vinden/berekenen Page 102 SIL = Safety Integrity level
  • 52. 52 - 103 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vortex en veiligheid SFF = Safety Failure Fraction The magic number is 0.9 or 90% SFF > 0.9 one unit is suitable for a SIL 2 application SFF < 0.9 two units are needed for SIL 2 application Page 103 Application Application Application Application SFF SIL 1 SIL 2 SIL 3 SIL 4 < 0.9 1 unit 2 units 3 units 4 units > 0.9 1 unit 1 unit 2 units 3 units SIL = Safety Integrity level - 104 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Vortex en veiligheid Page 104 SIL = Safety Integrity level Kalibratie samen
  • 53. 53 - 105 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatievoorschriften - 106 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatievoorschriften Anders per leverancier!
  • 54. 54 - 107 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatievoorschriften Positionering converter in alle richtingen Converter naar boven/beneden/zijdelings gericht Zijdelingse installatie kan gebruikt worden om invloeden van vibraties te voorkomen Volle buis vereist Vermijden van waterslag of andere obstakels Goede uitlijning van piping en dichtingen Page 107 Liquid Gas / Steam - 108 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Installatievoorschriften Page 108
  • 55. 55 - 109 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Applicaties - 110 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Waar te gebruiken Propere toepassingen / viscositeit vloeistof (<3cp) Stoom & Gassen Lage viscositeit Koolwaterstoffen Water, laal corrosieve chemicaliën Niet geleidende vloeistoffen Hoge-T oliën en bitumen Page 110
  • 56. 56 - 111 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Waar niet te gebruiken Minder geschikt voor – corrosieve chemicaliën – visceuze vloeistoffen (<7cp) – Lichte slurries (minder dan 1%) Niet mogelijk – Stoffige en vuile processtromen – 2-fasige stroom – Pulserende flow – Hoge omgevingsvibraties (>1G) Page 111 - 112 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Specificaties Maten / procesaansluitingen – Wafer 15-100 mm – Flenzen 15-400 mm – Butt weld – Tri clamp – Smooth flens-afwerking – RTJ (Ring Type Joint or nut und feder- DIN 2526/2513) Flenzen – EN, ANSI, JIS Sizing toont aan dat de meter telkens 1-2 maten kleiner is dan de nominale diameter van de buis Nauwkeurigheid – +/- 0.75% van de gemeten waarde voor vloeistoffen – +/- 1% van de gemeten waarde voor gassen – MV types: +/- 2% van de gemeten waarde voor massa-debiet van verzadigde stoom Repeatability – +/- 0.2% va de gemeten waarde Druk – Vanaf volledig vacuüm tot EN 250 / ANSI #2500 Temperatuur – -200°C tot +450 °C Wetted materials – SS316, CF8M, ASTM 216 A WCB, 1.4552, Hast C, Gold coating Page 112
  • 57. 57 - 113 - VIK – Go with the flow Copyright © Yokogawa Electric Corporation October 2012 Specificaties Wetted parts behandeling – NACE compliant – Zuurstof ontvetting mogelijk Ranges – Vanaf Re 20.000: tot 10 m/s voor vloeistoffen en 80 m/s voor gassen/stoom Output – 2 draad 4-20 mA Hart, Profibus, FF – EDDL en/of FDT/DTM ready – Gelijktijdig pulse contact Remote electronica – Tot 30m tussen meter en converter CE MARKING – PED – ATEX: Exi, Exd, Exn, FM, JIS Beschermingsklasse – IP65 or 67 Certificaten – 3.1 Materiaal certificaat – Las-certificaten – Dye penetration test – FMEDA report – ATEX certificaten – Kalibratie Page 113 <VIK – Go with the flow> Copyright © Yokogawa Electric Corporation <October 2012> - 114 - Vragen?