EnOcean Equipment Profiles No Wires. No Batteries. No Limits 06 Enero 2010
Standardization of Radio Protocol <ul><li>Bit sampling </li></ul><ul><li>Carrier frequency, modulation, data rate, Tx powe...
EnOcean Protocol. Application Layer
EnOcean Telegrams types – ORG EEP and Data payload Definition The EEP is defined as following: ORG – FUNC (profile) – TYPE...
ORG 7 – 4BS Telegrams Functions - Profiles <ul><li>The LRN bit (DB_0.Bit_3) must be set “0” to signalize a teach-in telegr...
EnOcean Equipment Profiles – ORG 5 –  ORG 6 i.e STM250-Wireless window contact 06-00-01 01-Single Input Contact 00-Contact...
EEP – ORG 7 – 4BS – Function 2 DB_1: Temperature, linear n=255…0 07-02-1B 1B-Range +50ºC to +130ºC DB_1: Temperature, line...
EEP – ORG 7 – 4BS – Functions 4…9 tbd 07-09-0C 0C-Propane Sensor tbd 07-09-08 08-O2 Sensor tbd 07-09-04 04-CO2 Sensor   07...
EEP – ORG 7 – 4BS – Function 10 DB_3: Turn-switch for fan speed DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slid...
EEP – ORG 7 – 4BS – Function 10 DB_2: Rel. Humidity 0…100%, linear n=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 DB_0....
EEP – ORG 7 – 4BS – Functions 11, 30, 38, 3F This profile is intended for manufacturer specific applications. Every manufa...
Upcoming SlideShare
Loading in …5
×

EEP-EnOcean Profiles v02.00

1,363 views

Published on

EnOcean Equipment Profiles v02.00

Published in: Technology, Business
0 Comments
1 Like
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
1,363
On SlideShare
0
From Embeds
0
Number of Embeds
5
Actions
Shares
0
Downloads
29
Comments
0
Likes
1
Embeds 0
No embeds

No notes for slide

EEP-EnOcean Profiles v02.00

  1. 1. EnOcean Equipment Profiles No Wires. No Batteries. No Limits 06 Enero 2010
  2. 2. Standardization of Radio Protocol <ul><li>Bit sampling </li></ul><ul><li>Carrier frequency, modulation, data rate, Tx power, Rx sensitivity, etc. </li></ul>RF SIGNAL Physical <ul><li>Subtelegrams / Acknowledge </li></ul><ul><li>Listen before talk </li></ul><ul><li>Encoding/Decoding telegram (inv-sync bit, checksum, CRC, etc.) </li></ul>ENCODED TELEGRAM (Bits) Data Link <ul><li>Repeating / Routing </li></ul>DECODED TELEGRAM (Bytes: ORG, ID, Data, Status) Transport Network Formal standardization at IEC <ul><li>Encapsulate/Decapsulate </li></ul><ul><li>Encryption / Decryption </li></ul>DATA ENCR./DECR. Presentation Standardization started within EnOcean Alliance Version 2.0 available <ul><li>EnOcean Equipment Profiles </li></ul><ul><li>Custom application </li></ul>DATA INTERPRETATION Application Standardization Task Action Data Unit Layer
  3. 3. EnOcean Protocol. Application Layer
  4. 4. EnOcean Telegrams types – ORG EEP and Data payload Definition The EEP is defined as following: ORG – FUNC (profile) – TYPE Ranges: ORG 0x00 … 0xFF FUNC 0x00 … 0x3F TYPE 0x00 … 0x7F
  5. 5. ORG 7 – 4BS Telegrams Functions - Profiles <ul><li>The LRN bit (DB_0.Bit_3) must be set “0” to signalize a teach-in telegram. </li></ul><ul><li>The LRN Type bit (DB_0.BIT_7) signalizes whether the teach-in telegram contains information on Function-Profile, Type and Manufacturer ID (LRN Type = “1”) or if regular data is sent (LRN Type =”0”). </li></ul>To keep the radio telegram as short as possible the transmitter will inform the receiver only during the teach-in procedure about its characteristics. Sensor 1. Press LRN pushbutton 2. LRN telegramm will be send
  6. 6. EnOcean Equipment Profiles – ORG 5 – ORG 6 i.e STM250-Wireless window contact 06-00-01 01-Single Input Contact 00-Contacts & Switches ORG 6 1BS Telegram   05-10-00 00-Window Handle 10-Mechanical Handle     tbd 05-Position Switch, Industrial Application Insertion of Key Card generates an N-Message, take-out a U-Message 05-04-01 01-Key Card Activated Switch 04-Position Switch, Home and Office application This EEP definition is based on the assumption that a RPS switch module (e.g. PTM200) is installed in an I-STATE up position! Application Style 2 is typically used in US and CAN but may be found in other markets as well. 05-03-02 02-Light and Blind Control-Application Style 2   This EEP definition is based on the assumption that a RPS switch module (e.g. PTM200) is installed in a 0-STATE up position! Application Style 1 is widely used in EU but may be found in other markets as well. 05-03-01 01-Light and Blind Control-Application Style 1 03-Rocker Switch 4 rocker This EEP definition is based on the assumption that a RPS switch module (e.g. PTM200) is installed in an I-STATE up position! Application Style 2 is typically used in US and CAN but may be found in other markets as well. 05-02-02 02-Light and Blind Control-Application Style 2   This EEP definition is based on the assumption that a RPS switch module (e.g. PTM200) is installed in a 0-STATE up position! Application Style 1 is widely used in EU but may be found in other markets as well. 05-02-01 01-Light and Blind Control-Application Style 1 02-Rocker Switch 2 rocker Comments EEP TYPE FUNCTION -PROFILE ORG 5 RPS Telegram
  7. 7. EEP – ORG 7 – 4BS – Function 2 DB_1: Temperature, linear n=255…0 07-02-1B 1B-Range +50ºC to +130ºC DB_1: Temperature, linear n=255…0 07-02-1A 1A-Range +40ºC to +120ºC DB_1: Temperature, linear n=255…0 07-02-19 19-Range +30ºC to +110ºC DB_1: Temperature, linear n=255…0 07-02-18 18-Range +20ºC to +100ºC DB_1: Temperature, linear n=255…0 07-02-17 17-Range +10ºC to +90ºC DB_1: Temperature, linear n=255…0 07-02-16 16-Range 0ºC to +80ºC DB_1: Temperature, linear n=255…0 07-02-15 15-Range -10ºC to +70ºC DB_1: Temperature, linear n=255…0 07-02-14 14-Range -20ºC to +60ºC DB_1: Temperature, linear n=255…0 07-02-13 13-Range -30ºC to +50ºC DB_1: Temperature, linear n=255…0 07-02-12 12-Range -40ºC to +40ºC DB_1: Temperature, linear n=255…0 07-02-11 11-Range -50ºC to +30ºC DB_1: Temperature, linear n=255…0 07-02-10 10-Range -60ºC to +20ºC DB_1: Temperature, linear n=255…0 07-02-0B 0B-Range +60ºC to +100ºC DB_1: Temperature, linear n=255…0 07-02-0A 0A-Range +50ºC to +90ºC DB_1: Temperature, linear n=255…0 07-02-09 09-Range +40ºC to +80ºC DB_1: Temperature, linear n=255…0 07-02-08 08-Range +30ºC to +70ºC DB_1: Temperature, linear n=255…0 07-02-07 07-Range +20ºC to +60ºC DB_1: Temperature, linear n=255…0 07-02-06 06-Range +10ºC to +50ºC DB_1: Temperature, linear n=255…0 07-02-05 05-Range 0ºC to +40ºC DB_1: Temperature, linear n=255…0 07-02-04 04-Range -10ºC to +30ºC DB_1: Temperature, linear n=255…0 07-02-03 03-Range -20ºC to +20ºC DB_1: Temperature, linear n=255…0 07-02-02 02-Range -30ºC to +10ºC DB_1: Temperature, linear n=255…0 07-02-01 01-Range -40ºC to 0ºC 02-Temperature Sensor Comments EEP TYPE FUNCTION -PROFILE ORG 7 4BS Telegram
  8. 8. EEP – ORG 7 – 4BS – Functions 4…9 tbd 07-09-0C 0C-Propane Sensor tbd 07-09-08 08-O2 Sensor tbd 07-09-04 04-CO2 Sensor   07-09-01 01-CO Sensor 09-Gas Sensor DB_3: Supply voltage 0…5,1V, linear n=0…255 DB_2: Illuminance 0…1530lx, linear n=255…0 DB_1: Temperature -30…50ºC, linear n=255…0 07-08-02 02-Range 0lx to 1530lx -30ºC to +50ºC and Occupancy DB_3: Supply voltage 0…5,1V, linear n=0…255 DB_2: Illuminance 0…1020lx, linear n=255…0 DB_1: Temperature 0…51ºC, linear n=255…0 07-08-02 02-Range 0lx to 1020lx 0ºC to +51ºC and Occupancy DB_3: Supply voltage 0…5,1V, linear n=0…255 DB_2: Illuminance 0…510lx, linear n=255…0 DB_1: Temperature 0…51ºC, linear n=255…0 07-08-01 01-Range 0lx to 510lx 0ºC to +51ºC and Occupancy 08-Light, Temperature&Occupancy Sensor DB_1: PIR Status 0…127 PIR off, 127…255 PIR on The transmission of &quot;PIR off&quot; telegrams is optional 07-07-01 01-Occupancy 07-Occupancy Sensor DB_3: Supply voltage 0…5,1V, linear n=0…255 DB_2: Illuminance 0…510lx, linear n=255…0 DB_1: Illuminance 0…1.024lx, linear n=255…0 07-06-02 02-Range 0lx to 1.024lx DB_3: Supply voltage 0…5,1V, linear n=0…255 DB_2: Illuminance 300…30.000lx, linear n=255…0 DB_1: Illuminance 600…60.000lx, linear n=255…0 07-06-01 01-Range 300lx to 60.000lx 06-Light Sensor     tbd 05-Pressure Sensor DB_2: Rel. Humidity 0…100%, linear n=255…0 DB_1: Temperature, 0…40ºC, linear n=255…0 07-04-01 01-Range 0ºC to +40ºC and 0% to 100% 04-Temperature & Humidity Sensor Comments EEP TYPE FUNCTION -PROFILE ORG 7 4BS Telegram
  9. 9. EEP – ORG 7 – 4BS – Function 10 DB_3: Turn-switch for fan speed DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slide switch O/I, Day/Night 07-10-09 09-Temperature Sensor, Fan Speed and Day/Night Control DB_3: Turn-switch for fan speed DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Occupancy button 07-10-08 08-Temperature Sensor, Fan Speed and Ocuppancy Control DB_3: Turn-switch for fan speed DB_1: Temperature, 0…40ºC, linear n=255…0 07-10-07 07-Temperature Sensor, Fan Speed Control DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slide switch O/I, Day/Night 07-10-06 06-Temperature Sensor, set point and Day/Night Control DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slide switch O/I, Day/Night 07-10-05 05-Temperature Sensor, set point and Occupancy Control DB_3: Turn-switch for fan speed DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 07-10-04 04-Temperature Sensor, set point and Fan Speed Control DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 07-10-03 03-Temperature Sensor, set point control DB_3: Turn-switch for fan speed DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slide switch O/I, Day/Night 07-10-02 02-Temperature Sensor, set point, Fan Speed and Day/Night Control DB_3: Turn-switch for fan speed DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Occupancy button 07-10-01 01-Temperature Sensor, set point, Fan Speed and Ocuppancy Control 10-Room Operating Panel Comments EEP TYPE FUNCTION -PROFILE ORG 7 4BS Telegram
  10. 10. EEP – ORG 7 – 4BS – Function 10 DB_2: Rel. Humidity 0…100%, linear n=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 DB_0.bit_0: Slide Switch 0/I or Slide switch Day/Night 07-10-14 14-Temperature and Humidity Sensor, Day/Night Control DB_2: Rel. Humidity 0…100%, linea nr=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 DB_0.bit_0: Occupancy button 07-10-13 13-Temperature and Humidity Sensor, Occupancy Control DB_3: Set point, min…max +, linear n=0…255 DB_2: Rel. Humidity 0…100%, linear n=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 07-10-12 12-Temperature and Humidity Sensor, set point Control DB_3: Set point, min…max +, linear n=0…255 DB_2: Rel. Humidity 0…100%, linear n=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 DB_0.bit_0: Slide Switch 0/I or Slide switch Day/Night 07-10-11 11-Temperature and Humidity Sensor, set point and Day/Night Control DB_3: Set point, min…max +, linear n=0…255 DB_2: Rel. Humidity 0…100%, linear n=0…250 DB_1: Temperature, 0…40ºC, linear n=0…250 DB_0.bit_0: Ocuupancy button 07-10-10 10-Temperature and Humidity Sensor, set point and Occupancy Control DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Slide switch 07-10-0D 0D-Temperature Sensor and Day/Night Control DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Occupancy 07-10-0C 0C-Temperature Sensor and Occupancy Control DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Input State 07-10-0B 0B-Temperature Sensor and Single Input Contact DB_2: Set point, min…max +, linear n=0…255 DB_1: Temperature, 0…40ºC, linear n=255…0 DB_0.bit_0: Contact State 07-10-0A 0A-Temperature Sensor, Set Point Adjust and Single Input Contact 10-Room Operating Panel Comments EEP TYPE FUNCTION -PROFILE ORG 7 4BS Telegram
  11. 11. EEP – ORG 7 – 4BS – Functions 11, 30, 38, 3F This profile is intended for manufacturer specific applications. Every manufacturer may independently define the types within this profile. 07-3F-7F 7F-Universal 3F-Universal Commands 0x8x to 0xFE are not used 07-38-08 08-PHC Gateway DB_3: Command 0h02 dimming value, ramping time, dimming range, store final value…   Dimming DB_3: Command 0h01 time, delay…   Switching 38-Central Command (0h01…0h7F) DB_0.bit0: Input State 07-30-02 02-Single Input Contact DB_2: Supply voltage 0…120 battery LOW, 121…255 battery OK DB_1: Input State, 0…195 contact closed, 196…255 Contact open 07-30-01 01-Single Input, Battery Monitor 30-Digital Input DB_3: Illuminance 0...510lx, linear n=0…255 DB_2: Illuminance set point, min...max, linear n=0…255 DB_1: Dimming output level, min...max, linear n=0…255 DB_0.bit_7: Repeater DB_0.bit_6: Power Relay Timer DB_0.bit_5: Daylight Harvesting DB_0.bit_4: Dimming DB_0.bit_2: Magnet Contact DB_0.bit_1: Occupancy DB_0.bit_0: Power Relay 07-11-01 01-Lighting Controller 11-Controller Status Comments EEP TYPE FUNCTION -PROFILE ORG 7 4BS Telegram

×