2000 lsc for assisted living handout

  1. 1. 4/22/2014 1 2014 THCA LTC/AL Quality Symposium Rebekah Eaddy, Architect Architectural Unit Survey Operations Section 512-438-2535 512-438-4623 FAX becky.eaddy@dads.state.tx.us DADS REGIONAL MAP Facility Totals April 7, 2014 Adult Day Care 470 Assisted Living 1,747 ICF-IID/RC 861 Nursing 1,222 Total Facilities 4,300 HCSSA agencies 6,336
  2. 2. 4/22/2014 2 Assisted Living___________1,747 • Large A 147 ( 139 in 9/06) • Large B 545 (393 in 9/06) • Small A 429 (485 in 9/06) • Small B 582 (298 in 9/06) • Type C 44 (119 in 9/06) • Type E 0 ( 16 in 9/06) LIFE SAFETY CODE (LSC) • The LSC’s purpose is to provide minimum requirements for the design, operation, and maintenance of buildings and structures for safety to life from fire. LIFE SAFETY CODE (LSC) Protection of occupants is achieved by a combination of: • Prevention of ignition • Detection of fire • Control of fire development
  3. 3. 4/22/2014 3 LIFE SAFETY CODE (LSC) Protection of occupants is achieved by a combination of: • Extinguishment of fire • Provision of refuge or evacuation • Staff reaction • Provision of fire safety information JUNE 13, 2013 DADS COUNCIL TEXAS REGISTER EFFECTIVE DATE JANUARY 6, 2014 DADS adopts 2000 edition LSC for ALF 2000 edition of NFPA 101 Chapter 32 for New Residential Board and Care All new ALF’s must have sprinklers Chapter 33 for Existing Residential Board and Care Small Type A’s sprinklers not req’d
  4. 4. 4/22/2014 4 2000 edition of NFPA 101 Chapter 18 for New Healthcare All new ALF’s must have sprinklers Chapter 19 for Existing Healthcare Only conversions of existing NF to Large B would NOT require sprinklers NFPA 101 2000 EDITION CODE BOOK COST $82.50 + S&H http//catalog.nfpa.org 1-800-344-3555 http://www.nfpa.org/
  5. 5. 4/22/2014 5 How sprinklers work I got a great deal on insurance Large Type A ALF’s An existing Large Type A facility may have an NFPA 13 system. In a building not more than four stories high an NFPA 13R system may be permitted.
  6. 6. 4/22/2014 6 Large Type A ALF’s An existing Large Type A facility may have an NFPA 13 system. In a building not more than four stories high an NFPA 13R system may be permitted. A new Large Type A facility must have an NFPA 13 system, however a building not more than four stories high may have an NFPA 13R system Large Type B ALF’s Existing Large Type B ALF’s must have a complete NFPA 13 system Large Type B ALF’s Existing Large Type B ALF’s must have a complete NFPA 13 system New Large Type B ALF’s must have a complete NFPA 13 system
  7. 7. 4/22/2014 7 Large Type B ALF’s Plastic CPVC piping may be used if installed to meet manufacturers’ installation instructions New Large Type B ALF’s must have a complete NFPA 13 system Small Type A ALF’s An existing small Type A facility may have a system that meets NFPA 13, 13D, or 13R requirements. Small Type A ALF’s An existing small Type A facility may have a system that meets NFPA 13, 13D, or 13R requirements. A new small Type A facility must have a system that meets NFPA 13, 13D, or 13R requirements, installed in accordance with §32.2.3.5.2.
  8. 8. 4/22/2014 8 §33.2.3.5.2. Exception No. 2 In existing slow evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered. Bath-rooms <55 sf are exempt. §32.2.3.5.2. Exception No. 2 In new slow evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered. Small Type B ALF’s An existing small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, in accordance with §33.2.3.5.2. .
  9. 9. 4/22/2014 9 Small Type B ALF’s An existing small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, in accordance with §33.2.3.5.2. . A new small Type B facility must have a system that meets NFPA 13, 13D, or 13R requirements, installed in accordance with §32.2.3.5.2. §33.2.3.5.2. Exception No. 2 In existing impractical evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered. Bath-rooms <55 sf are exempt. §32.2.3.5.2. Exception No. 2 In new impractical evacuation capability facilities, an automatic sprinkler system in accordance with NFPA 13D with a 30-minute water supply, shall be permitted. All habitable areas and closets shall be sprinklered.
  10. 10. 4/22/2014 10 Thirty minute water supply NFPA 13D has the minimum design discharge at 4-1.1, but it can be no less than the listing of the sprinkler, and the number of design sprinklers is at 4-1.2. NFPA 13D Sprinkler Systems Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes Only ten minute water supply required No sprinklers required in: • Bathrooms <55 sf, • Closets <24 sf with dimension <3 ft • Garages, porches, carports • Attics, crawl spaces • Entry foyers if not only means of egress Sprinkler Maintenance When installed or required, sprinkler systems must be inspected, tested, and maintained in accordance with NFPA 25.
  11. 11. 4/22/2014 11 Sprinkler Maintenance The facility must have a written contract with a fire protection sprinkler firm that has been issued a Sprinkler Certificate of Registration number (SCR) from the Texas State Fire Marshal's Office to perform the required services semiannually. Sprinkler Maintenance The facility must have documentation available to show that all the requirements of NFPA 25 have been met including the annual inspection, test, and maintenance by the registered fire sprinkler firm. Sprinkler Maintenance The facility must retain one set of the fire sprinkler system plans and hydraulic calculations on the property in accordance with NFPA 25.
  12. 12. 4/22/2014 12 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 10. Failed to provide a written contract for maintaining the fire alarm system semi-annually §92.62(f)(1)(e) Not ranked in FY12 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 9. Type B Large meets Health Care LSC §92.61(b)(4)(B) #6 in FY12 & FY13 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 8. Failed to ensure interior wall and ceilings were sheathed with at least 20-minute fire-rating §92.62(e)(2) Number 10 in FY12
  13. 13. 4/22/2014 13 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 7. Dirty, rubbish, hazards, clean floors, no storage in attic §92.62(h)(8) Top five last ten years TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 6. Fire drills conducted properly §92.62(c)(2) #8 in FY11 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 5. Fire alarm and smoke detection system §92.62(f)(1) # 5 in FY10, F11, & FY12
  14. 14. 4/22/2014 14 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 4. Failed to meet other chapters of the Life Safety Code §92.61(b)(4)(C) Ranked #6 in FY11 and #8 in FY12 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 3. Type A Large & Small must meet LSC §92.61(b)(4)(A) Top three last ten years LSC 21-2.3.5.2 Impractical All impractical facilities shall be protected throughout by an approved supervised automatic sprinkler system (supervised requires signal to sound at panel) TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 2. Sprinkler maintenance and testing §92.62(f)(2) Top 3 last 4 years
  15. 15. 4/22/2014 15 TOP 10 MOST FREQUENTLY CITED A. L. TAGS FY2013 1. Building, heating and air conditioning, electrical systems must be maintained. Use of electrical appliances, devices, and lamps must be such as to not overload circuits.. §92.62(i)(2) Top five last ten years Any questions?

×