One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 1 09:45:15 Jun 23, 2013 Project File: SC
Switchgear 11kV Pabrik-2 11 kV
0% 0
30,05 kA -87,4
MCC-10
0,525 kV
15,71% -18,3SWGR-11
6,9 kV
8,81% -31,7
SWGR-9
6,9 kV
11,35% -30,7
SWGR-8
6,9 kV
10,79% -30,7SWGR-5
6,9 kV
14,13% -36,8MCC-3
0,525 kV
10,42% -20,1
MCC-4
0,525 kV
13,55% -20,4
MCC-7
0,525 kV
5,72% -21
MCC-6
0,4 kV
2,82% -20,8
Sistem Integrasi
LINE 4 2010 U
30,4 MW
12,39
UREA STORAGE
114 kVA
0,698
0,698
TR-6
1 MVA
Cable6
SEAWATER INTAKE MCC7
180 kVA
0,818
0,818
TR-7
0,75 MVA
Cable7
UREA PLANT 525V
925 kVA
3,86
3,86
TR-4
1,5 MVA
Cable4
AMMONIA PLANT 525V
725 kVA
2,97
2,97
TR-3
1,5 MVA
Cable3
UREA PLANT 6,9kV
800 kVA
0,352
0,352
TR-5
1,5 MVA
Cable5
SEAWATER INTAKE MCC8
1942 kVA
0,885
0,885
TR-8
5 MVA
Cable8
SEAWATER INTAKE MCC9
2055 kVA
0,931
0,931
TR-9
5 MVA
Cable9
OFFSITE SWGR 6,6kV
1523 kVA
0,71
0,71
TR-11
5 MVA
Cable11
OFFSITE SWGR 525V
1094 kVA
4,46
4,46
TR-10
1,5 MVA
Cable10
101-JAM
6705 HP
1,9
Cable12
K2-TR-01
35 MVA
AMMONIA PLANT 525V
725 kVA
UREA PLANT 525V
925 kVA UREA PLANT 6,9kV
800 kVA
UREA STORAGE
114 kVA
SEAWATER INTAKE MCC7
180 kVA
SEAWATER INTAKE MCC8
1942 kVA
SEAWATER INTAKE MCC9
2055 kVA
OFFSITE SWGR 525V
1094 kVA
OFFSITE SWGR 6,6kV
1523 kVA
Sistem Integrasi
13,41
2010 U
30,4 MW
Cable3 Cable4 Cable5 Cable6 Cable7 Cable8 Cable9 Cable10 Cable11 Cable12
LINE 4
TR-3
1,5 MVA
TR-4
1,5 MVA
TR-5
1,5 MVA
TR-6
1 MVA
TR-7
0,75 MVA
TR-8
5 MVA
TR-9
5 MVA
TR-10
1,5 MVA
TR-11
5 MVA
K2-TR-01
35 MVA
Switchgear 11kV Pabrik-2 11 kV
MCC-3
0,525 kV
MCC-4
0,525 kV
SWGR-5
6,9 kV
MCC-6
0,4 kV
MCC-7
0,525 kV
SWGR-8
6,9 kV
SWGR-9
6,9 kV
MCC-10
0,525 kV
SWGR-11
6,9 kV
101-JAM
6705 HP
0,142 0,184 0,22 0,025 0,039 0,555 0,584 0,213 0,445 1,9
8,81% -31,7
15,71% -18,3
11,35% -30,7
10,79% -30,7
5,72% -212,82% -20,8
14,13% -36,8
13,55% -20,4
10,42% -20,1
0% 0
30,05 kA -87,4
12,39
0,025 0,0390,1840,142 0,22 0,555 0,584 0,4450,213 1,9
2,97 3,86 0,352 0,698 0,818 0,885 0,931 4,46 0,71
2,97 3,86 0,698 0,818 0,885 0,931 4,46 0,71
0,352
1,9
13,41

More Related Content

Viewers also liked

Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
IJERD Editor
 
Performance Comparison Between the Original Forms of Biogeography-Based Optim...
Performance Comparison Between the Original Forms of Biogeography-Based Optim...Performance Comparison Between the Original Forms of Biogeography-Based Optim...
Performance Comparison Between the Original Forms of Biogeography-Based Optim...
XperiaZ1
 
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
Prashanta Sarkar
 

Viewers also liked (7)

Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
Performance Comparison Between the Original Forms of Biogeography-Based Optim...
Performance Comparison Between the Original Forms of Biogeography-Based Optim...Performance Comparison Between the Original Forms of Biogeography-Based Optim...
Performance Comparison Between the Original Forms of Biogeography-Based Optim...
 
Determination of the Weakest Branch in a Radial Distribution System using Rea...
Determination of the Weakest Branch in a Radial Distribution System using Rea...Determination of the Weakest Branch in a Radial Distribution System using Rea...
Determination of the Weakest Branch in a Radial Distribution System using Rea...
 
Differential Evolution Based Optimization Approach for Power Factor Correction
Differential Evolution Based Optimization Approach for Power Factor CorrectionDifferential Evolution Based Optimization Approach for Power Factor Correction
Differential Evolution Based Optimization Approach for Power Factor Correction
 
Optimal Siting And Sizing Of Distributed Generation For Radial Distribution S...
Optimal Siting And Sizing Of Distributed Generation For Radial Distribution S...Optimal Siting And Sizing Of Distributed Generation For Radial Distribution S...
Optimal Siting And Sizing Of Distributed Generation For Radial Distribution S...
 
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
OPTIMAL PLACEMENT AND SIZING OF CAPACITOR BANKS BASED ON VOLTAGE PROFILE AND ...
 
Calculating Voltage Instability Using Index Analysis in Radial Distribution ...
Calculating Voltage Instability Using Index Analysis in Radial  Distribution ...Calculating Voltage Instability Using Index Analysis in Radial  Distribution ...
Calculating Voltage Instability Using Index Analysis in Radial Distribution ...
 

Olv1 (short circuit analysis)2

  • 1. One-Line Diagram - OLV1 (Short-Circuit Analysis) page 1 09:45:15 Jun 23, 2013 Project File: SC Switchgear 11kV Pabrik-2 11 kV 0% 0 30,05 kA -87,4 MCC-10 0,525 kV 15,71% -18,3SWGR-11 6,9 kV 8,81% -31,7 SWGR-9 6,9 kV 11,35% -30,7 SWGR-8 6,9 kV 10,79% -30,7SWGR-5 6,9 kV 14,13% -36,8MCC-3 0,525 kV 10,42% -20,1 MCC-4 0,525 kV 13,55% -20,4 MCC-7 0,525 kV 5,72% -21 MCC-6 0,4 kV 2,82% -20,8 Sistem Integrasi LINE 4 2010 U 30,4 MW 12,39 UREA STORAGE 114 kVA 0,698 0,698 TR-6 1 MVA Cable6 SEAWATER INTAKE MCC7 180 kVA 0,818 0,818 TR-7 0,75 MVA Cable7 UREA PLANT 525V 925 kVA 3,86 3,86 TR-4 1,5 MVA Cable4 AMMONIA PLANT 525V 725 kVA 2,97 2,97 TR-3 1,5 MVA Cable3 UREA PLANT 6,9kV 800 kVA 0,352 0,352 TR-5 1,5 MVA Cable5 SEAWATER INTAKE MCC8 1942 kVA 0,885 0,885 TR-8 5 MVA Cable8 SEAWATER INTAKE MCC9 2055 kVA 0,931 0,931 TR-9 5 MVA Cable9 OFFSITE SWGR 6,6kV 1523 kVA 0,71 0,71 TR-11 5 MVA Cable11 OFFSITE SWGR 525V 1094 kVA 4,46 4,46 TR-10 1,5 MVA Cable10 101-JAM 6705 HP 1,9 Cable12 K2-TR-01 35 MVA AMMONIA PLANT 525V 725 kVA UREA PLANT 525V 925 kVA UREA PLANT 6,9kV 800 kVA UREA STORAGE 114 kVA SEAWATER INTAKE MCC7 180 kVA SEAWATER INTAKE MCC8 1942 kVA SEAWATER INTAKE MCC9 2055 kVA OFFSITE SWGR 525V 1094 kVA OFFSITE SWGR 6,6kV 1523 kVA Sistem Integrasi 13,41 2010 U 30,4 MW Cable3 Cable4 Cable5 Cable6 Cable7 Cable8 Cable9 Cable10 Cable11 Cable12 LINE 4 TR-3 1,5 MVA TR-4 1,5 MVA TR-5 1,5 MVA TR-6 1 MVA TR-7 0,75 MVA TR-8 5 MVA TR-9 5 MVA TR-10 1,5 MVA TR-11 5 MVA K2-TR-01 35 MVA Switchgear 11kV Pabrik-2 11 kV MCC-3 0,525 kV MCC-4 0,525 kV SWGR-5 6,9 kV MCC-6 0,4 kV MCC-7 0,525 kV SWGR-8 6,9 kV SWGR-9 6,9 kV MCC-10 0,525 kV SWGR-11 6,9 kV 101-JAM 6705 HP 0,142 0,184 0,22 0,025 0,039 0,555 0,584 0,213 0,445 1,9 8,81% -31,7 15,71% -18,3 11,35% -30,7 10,79% -30,7 5,72% -212,82% -20,8 14,13% -36,8 13,55% -20,4 10,42% -20,1 0% 0 30,05 kA -87,4 12,39 0,025 0,0390,1840,142 0,22 0,555 0,584 0,4450,213 1,9 2,97 3,86 0,352 0,698 0,818 0,885 0,931 4,46 0,71 2,97 3,86 0,698 0,818 0,885 0,931 4,46 0,71 0,352 1,9 13,41