2. PRODUCT FEATURES
20x4 alphanumeric Display with user friendly keypad.
Password Protected panel.
Ac power & battery visual indications.
Battery fault visual & audible warning with indication.
Visual indication & audible warning for individual zone status
All type of Conventional detector can be connected.
Mode of operations: Automatic & Manual.
Zone Isolation facility for disabling of zones.
Programmable Timer delay before gas release.
Manual gas release & abort facility with visual indication.
Main / Standby Cylinder Output Facility with open & short fault
indications.
Programmable input for remote fire with visual & audible indication.
Programmable input for pressure & actuator switches.
Programmable solenoid "on time".
Environmental friendly panel - single battery
Battery backup for 24 hour in normal condition & 2 hours in alarm
condition.
Pulse charging for better battery life.
2 Relay output for fire condition & 1 relay output for fault condition.
24 VDC for alarm condition to connect notification devices (Hooter).
Pre discharge and post discharge relay contact outputs.
Event logs facility
Test mode for complete testing of panel with visual & audible indication.
Programmable cylinder selection- main /stand-by.
Tampering protection with visual and audible alarm.
TECHNICAL SPECIFICATIONS
Supply specification:
Supply Voltage: 230VAC ± 10 % 50 Hz.
Battery specification:
Lead acid battery 12V -7Ah
Battery backup with inbuilt Charging.
Charging Voltage: 15.9 VDC.
Initiating Device Circuits:
All zones are Class B wiring
Normal Operating Voltage: 24 VDC
Loop resistance: 100 ohms Maximum
End-Of-Line Resistor: 4.7KΩ, 1/4watt
Maximum 20 No's of detectors (30mA Max current per
detector in alarm condition) can connect for each zone loop.
Notification Appliance Circuits (Sounder/Hooter Circuit)
Class – B wiring
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output: 0.6A maximum
End-Of-Line Resistor: 4.7KΩ, 1/4watt
Relay Voltage free contact Outputs
Fire Contact (C, NO):125VAC@ 1A /30v DC@ 2A
Fire Contact (C, NO):125VAC@ 1A /30v DC@ 2A
Fault Contact(C, NO): 125VAC@ 1A /30v DC@ 2A
Hooter 2 Contact (C, NO): 125VAC@ 1A /30v DC@ 2A
Hooter 3 Contact (C, NO): 125VAC@ 1A /30v DC@ 2A