MHRC-AE-060-VS-01
Simultaneous Heating & Cooling (SHC)
Chiller for Solar Applications
5 Ton Nominal Hybrid Heat/Cool Chiller
Primary - DC (380V) / Secondary - AC (208/230-1-50/60)
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
2
HVAC Guide Specifications
Air-Cooled Liquid Chiller
Nominal Size: 5 Tons
Multiaqua Model Number: MHRC-AE-060-VS-01
Part 1-General
1.01 System Description
Multiaqua air-cooled and water to water liquid chillers are designed using variable speed scroll compressors, high volume
condenserfans and motors.
1.02 Quality Assurance
A. ETL safety certified to UL Standard 1995, 4th
edition (U.S.A.).
B. UL performance certified.
C. Third party certified efficiency ratings are at ANSI/AHRI Standard 550/590 with Addendum3-2011 conditions.
D. Manufactured in U.S.A.
E. Fully tested.
F. Damage resistant packaging.
1.03 Delivery, Storage and Handling
A. Packaged and readied for shipment from distribution center.
B. Controls shall be capable of withstanding 150°F storage temperatures in the control compartment.
C. Stored and handled per manufacturer’s recommendations.
Part 2-Product
2.01 Equipment
A. General:
1. Unit shall be a factory assembled and tested.
2. Shall be assembled on heavy gauge steel mounting/lifting rails.
3. Contained within the unit cabinet shall be all factory wiring, piping, controls, refrigerant charge (R410a), POE oil and
special accessories required prior to start up.
4. Brass body strainers with 20 mesh screen and blow down shall be supplied in cabinet as a field installable accessory.
B. Unit Cabinet:
1. Composed of heavy gauge galvanized steelcasing with a baked polyester powder coating.
2. Capable of withstanding 500-hour salt spray test in accordance with the ASTM (U.S.A.) standard.
C. CondenserFans:
1. Five blade glass reinforced polypropylene (PP) petals mounted on a cast aluminum hub construction and shall be
dynamically balanced and corrosion resistant.
2. Discharge air is vertical.
3. Motors and blades shall be protected by coated steel wire safety guards.
D. Fan Motors:
1. Condenser fan motor shall be variable speed,brushless DC type.
2. Condenser fan motors shall be Totally Enclosed Air Over (TEAO), use Class B insulation, and permanently lubricated
ball and/or sleeve bearings.
3. Condenser fan motors shall be internally overload protected with automatic reset.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
3
E. Compressor:
1. Unit shall contain one Emerson/Copeland variable speed DC scroll compressor.
2. Direct current DC, 900-7,200 rpm (15-120Hz).
3. Compressor motor shall be suction gas cooled.
4. External motor protection.
5. Externally protected by low and high pressure cutout devices and discharge temperature sensing thermistor.
6. Individual vibration isolators.
7. Compressor compartment is internally insulated using noise reducing elastomeric foam insulation.
F. Solar Inverter:
1. Unit shall contain one Pika 7601C Power Core Inverter matched with S2501 PV links at solar panels.
G. Pump:
1. Unit shall not be capable of incorporating a field installed chilled liquid solution pump internally. (Space restricted)
2. Unit shall have chilled liquid solution piping to the exterior of the cabinet.
H. Evaporator (Cooling):
1. Evaporator shall have one refrigerant circuit and one liquid solution circuit.
2. Evaporator rated for a refrigerant side working pressure up to 550 psig.
3. Evaporator rated for a water side working pressure up to 150 psig.
4. Single pass,ANSI type 316 stainless steel,brazed plate construction with copper/nickel brazing material.
I. Condenser(Heating):
1. Condenser shall have one refrigerant circuit and one liquid solution circuit.
2. Condenser rated for a refrigerant side working pressure up to 550 psig.
3. Condenser rated for a water side working pressure up to 150 psig.
4. Single pass,ANSI type 316 stainless steel,brazed plate construction with copper/nickel brazing material.
J. Evaporator/Condenser(Cooling/Heating):
1. Condenser coil shall be air-cooled with integral sub-cooler.
2. Constructed of rifled coppertubing mechanically bonded to aluminum fins.
3. Cleaned and dehydrated.
4. Factory leak tested to 650 psig.
K. Refrigerant Circuits:
1. Each circuit shall contain liquid line strainers, electronic expansion valves, solenoid valve, check valve, refrigerant
charge of R410a, and POE compressor oil.
Part 3-Controls and Safeties
3.01 Controls
A. Chiller shall be completely factory wired and tested.
B. Temperature control shall be based on leaving liquid solution temperatures.
1. Temperature accuracy shall be + - 1°F
C. Controls shall be capable of variable speed control.
D. Controls shall include the following components:
1. 24vac transformers to serve all controllers, relays, and control components.
2. Microprocessorbased liquid solution temperature controller.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
4
3. Leaving water temperature thermistors.
4. Chilled liquid solution flow switches.
E. All functions shall be addressable,logic, code, and algorithm controlled.
F. Ethernet port supplied for communication and monitoring.
G. Compatible with Building Automation Systems (BAS) using BACnet protocol.
3.02 Safeties
A. Unit shall be equipped with all necessary components in conjunction with the control systemto provide the following
protection:
1. Low refrigerant pressure.
2. High refrigerant pressure.
3. Water side cold & hot flow.
Part 4-Operating Characteristics
4.01 Temperatures
A. Unit shall be capable of starting and running at outdoortemperatures from 0°F to 120°F.
B. Unit shall be capable of initial startup in cooling mode with a maximum 80°F entering fluid temperature and ambient not
above 95° F.
C. Maximum sustained entering fluid solution temperature to the evaporatorshall not exceed 70°F in cooling mode.
D. Minimum 10% glycol solution is required in all applications. For outdoor temperatures below 32°F, reference the
propylene glycol manufacture’s data table of field installed polypropylene glycol solution concentrations.
4.02 Electrical Requirements
A. Primary DC electrical power supply shall enter the unit at a single location.
B. Secondary AC electrical power supply if used,shall enter the unit at a single location.
C. Electrical power supply shall be rated to withstand 90°C operating ambient temperature.
Part 5- Definitions
5.01 Abbreviations
A. DB = Dry Bulb Temperature
B. EWT = Entering Water Temperature
C. LWT = Leaving Water Temperature
D. EAT = Entering Air Temperature
E. EAT/DB = Entering Air Temperature Dry Bulb
F. EAT/WB = Entering Air Wet Bulb
G. GPM = US Gallons per Minute
H. MBH = BTU X 1000
I. SC = Sensible Cooling
J. TC = Total Cooling = Sensible + Latent
K. dB = Decibel Level
5.02 Measurements
A. All measurements with regard to length, width, and height shall be in inches.
B. All measurements with regard to pipe sizes shall be in outside diameter (OD) unless otherwise noted.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
5
MHRC-AE-060-VS-01 Product Specifications
Simultaneous Heat & Cool (SHC) Mode Electrical Data
Model Number Volts/ Phase/ Hertz
Compressor Condenser Fan Motor
SCCR
Fuse or HACR Circuit
Breaker
(Qty 1) (Qty 1)
(RLA) (LRA) (RLA) (RPM)
Minimum
Amps
(MCA)
Maximum
Amps
(MOCP)
MHRC-AE-060-VS-01
DC (380V) Primary
AC (208/230-1-50/60) Secondary
8 to 25 ~ ~* ~* 10kA 40 50
* Condenserfan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) Mode.
Cooling Mode Electrical Data
Model Number Volts/ Phase/ Hertz
Compressor Condenser Fan Motor
SCCR
Fuse or HACR Circuit
Breaker
(Qty 1) (Qty 1)
(RLA) (LRA) (RLA) (RPM)
Minimum
Amps (MCA)
Maximum
Amps
(MOCP)
MHRC-AE-060-VS-01
DC (380V) Primary
AC (208/230-1-50/60) Secondary
8 to 21 ~ 2.5 1200/VAR* 10kA 40 50
* VAR = Variable Speed
Heating Mode Electrical Data
Model Number Volts/ Phase/ Hertz
Compressor Condenser Fan Motor
SCCR
Fuse or HACR Circuit
Breaker
(Qty 1) (Qty 1)
(RLA) (LRA) (RLA) (RPM)
Minimum
Amps (MCA)
Maximum
Amps
(MOCP)
MHRC-AE-060-VS-01
DC (380V) Primary
AC (208/230-1-50/60) Secondary
8 to 31 ~ 2.5 1200/VAR* 10kA 40 50
* VAR = Variable Speed
Physical Data
Model Number
Chiller Weight (lbs.)
Height
(in)
Length
(in)
Width
(in)
Refrigerant R410a
(1 Circuits)
Net Shipping
MHRC-AE-060-VS-01 63-1/2 33-5/8 52-1/2 13.5 lbs. / 216 oz. 700 900
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
6
MHRC-AE-060-VS-01 Product Specifications
Compressor
Copeland Variable Speed (VS)
Scroll
Refrigerant R410a
Heat Exchanger (Cooling) Brazed Plate
Heat Exchanger (Heating) Brazed Plate
Max. Flow Rate (Cooling) 14.4 gpm
Min. Flow Rate (Cooling) 12 gpm
Max. Flow Rate (Heating) 14.4 gpm
Min. Flow Rate (Heating) 12 gpm
Supply Water Temp (Cooling) 44°F (Adjustable)
Return Water Temp (Cooling) 54°F (Adjustable)
Minimum Supply Water Temp (Cooling) 28°F*
Minimum Return Water Temp (Cooling) 38°F*
Maximum Supply Water Temp (Heating) 130°F*
Maximum Return Water Temp (Heating) 120°F*
Minimum SystemSolution Content (Cold Side) 25 Gallons
Minimum SystemSolution Content (Hot Side) 25 Gallons
Expansion Tank Size 3% of Total System
Water Connections (4) 1.00" MPT Supply & Return
* Compatible with Thermal Storage (TS) systems.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
7
MHRC-AE-060-VS-01 Performance Data
Simultaneous Heat/Cool (SHC) Mode
Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating
LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F)
44 46839 105534 7.76 26.49 58695 105
 Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.
 Compressor runningat 5000 RPMin SHC mode.
Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating
LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F)
44 43080 100383 5.95 20.29 57303 120
 Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.
 Compressor runningat 5000 RPMin SHC mode.
Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating
LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F)
44 41827 98666 5.49 18.73 56839 125
 Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.
 Compressor runningat 5000 RPMin SHC mode.
Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating
LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F)
44 40575 96949 5.08 17.34 56375 130
 Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.
 Compressor runningat 5000 RPMin SHC mode.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
8
MHRC-AE-060-VS-01 Performance Data
Cooling Mode
Entering Air
Temperature
Entering Air
Temperature
Entering Air
Temperature
Entering Air
Temperature
55°F 65°F 80°F 95°F
LWT
(°F)
BTU's COP EER BTU's COP EER BTU's COP EER BTU's COP EER
44 53084 5.94 20.26 54996 4.98 17.00 47314 3.77 12.86 46500 3.00 10.22
IPLV 15.58
 Compressor runningat 5000 RPMin coolingmode.
Heating Mode
Entering Air Temperature Entering Air Temperature
47°F 47°F
LWT (°F) BTU's COP EER BTU's COP EER LWT (°F)
105° 66365 2.91 9.93 64641 2.63 8.96 120°
Entering Air Temperature Entering Air Temperature
LWT (°F) 47°F 47°F LWT (°F)
125° BTU's COP EER BTU's COP EER 130°
64066 2.54 8.66 63492 2.46 8.39
 Compressor runningat 6000 RPMin heatingmode.
Entering Air Temperature Entering Air Temperature
17°F 17°F
LWT (°F) BTU's COP EER BTU's COP EER LWT (°F)
105° 45853 2.11 7.20 43653 1.96 6.70 120°
Entering Air Temperature Entering Air Temperature
LWT (°F) 17°F 17°F LWT (°F)
125° BTU's COP EER BTU's COP EER 130°
42919 1.92 6.54 42186 1.87 6.39
 Compressor runningat 6000 RPMin heatingmode.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
9
MHRC-AE-060-VS-01 Glycol Adjustment Factors
Glycol Solution Concentration Data
Propylene Glycol % Min. Ambient Temp
10% 26°F
20% 18°F
30% 8°F
40% -7°F
50% -29°F
Estimated Propylene Glycol Adjustment Factors:
Percent of Propylene Glycol
Capacity adjustment Pressure Drop adjustment
Multiply TONS by: Multiply PD by:
10% 0.995 1.02
15% 0.992 1.04
20% 0.986 1.08
25% 0.972 1.13
30% 0.96 1.21
35% 0.95 1.26
40% 0.928 1.47
50% 0.878 2.79
Important
Required Use of 10% Minimum Propylene Glycol
Multiaqua Inc. requires a minimum concentration of 10% propylene glycol in the chiller system solution. This
requirement applies to all chiller product models for protection of the brazed plate heat exchanger (BPHE), regardless of
outdoor ambient operating temperature.
The Multiaqua chiller operating at a 44 leaving water temperature (LWT) will have an internal BPHE temperature of 32 F
to 38 F. Without the required MINIMUM 10% concentration of propylene glycol, the unit is susceptible to areas of
freezing within the BPHE which could result in failure of the BPHE.
With any deviation from full flow through the BPHE,the BPHE would also be susceptible to areas of freezing within the
BPHE. This could be caused by, but not limited to, contaminates being caught in the wye strainer, flow switch or pump
failure. Each chiller is supplied from the factory with a Wye strainer that is to be installed on the inlet (suction) side of the
pump on the MAC- 036HE, 048HE, 060HE, 120HE, and MHRC2-060-VS chillers.
Failure to follow this requirement will void the chiller warranty. Failure to comply may result in BPHE failure due to
freezing followed by compressor failure, all of which are not covered under Multiaqua’s warranty policy.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
10
MHRC-AE-060-VS-01 Altitude Adjustment Factors
Important notes about LowAmbient Operation:
If the outside temperature is expected to fall below freezing (32°F) in the area where the Multiaqua chiller is to be
installed; the installer must take the following precautions. Failure to do so will void the warranty.
To not engage in cold ambient mitigation will result in the failure of components such as the heat exchanger,
piping, circulating pump, etc.. and or property damage.
• Keep the liquid solution at a minimum of 10% percent Propylene Glycol even in areas where there is no danger of
freezing.
• The percentage amount of glycol recommended is dependent on the expected ambient temperatures and the solution
makeup recommendation of the glycol manufacturer. For outdoor temperatures below 32°F, reference glycol
manufacture’s data table of field installed polypropylene glycol solution.
• Ensure the system circulating pump is in a constant energized mode to keep a continuous circulation of liquid solution.
The Multiaqua chiller is a self-contained, air-cooled condenser, coupled with brazed plate heat exchangers (evaporator).
The system utilizes a scroll compressor to circulate refrigerant between the condenser and heat exchanger. The refrigerant
is metered into the heat exchanger with a electronic expansion valve. Protecting the system are both high and low pressure
switches as well as a pump flow switch.
Liquid solution (water and propylene glycol; minimum 10 % is required at any ambient) is circulated through the heat
exchangers by externally mounted pumps. The liquid solution flows through the heat exchangers to the system supply
piping and on to the air handlers.
Altitude Tons
1000 ft. .995
2000 ft. .990
3000 ft. .986
4000 ft. .983
5000 ft. .980
6000 ft. .978
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
11
MHRC-AE-060-VS-01 Sound Data
MODEL # MHRC-AE-060-VS-01
(Cooling Mode)
Fan Speed dB(A) @ 3 m
H 62
MODEL # MHRC-AE-060-VS-01
(Heating Mode)
Fan Speed dB(A) @ 3 m
H 62
MODEL # MHRC-AE-060-VS-01
Simultaneous Heating
& Cooling (SHC Mode)
Fan Speed dB(A) @ 3 m
FAN OFF* 60
* Condenser fan does not run in Simultaneous
Heat & Cool (SHC) mode.
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
12
MHRC-AE-060-VS-01 Upper Electrical Panel Layout
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
13
MHRC-AE-060-VS-01 Lower Electrical Panel Layout
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
14
MHRC-AE-060-VS-01 Low Voltage Wiring Diagram
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
15
MHRC-AE-060-VS-01 Low Voltage Wiring Diagram
(Expanded Upper Section of Diagram)
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
16
MHRC-AE-060-VS-01 Low Voltage Wiring Diagram
(Expanded Lower Section of Diagram)
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
17
MHRC-AE-060-VS-01 High Voltage Wiring Diagram
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
18
MHRC-AE-060-VS-01 Dimensional Drawing
Model A B C D E F G H I J
MHRC-AE-060 63.50 52.50 29.00 33.625 27.75 16.75 7.00 18.50 9.50 9.25
Dimensionsare ininches.
All supplyandreturn waterconnectionsare 1.00" (MPT).
These specifications are subject to change without notice. Rev. 1.15
Check www.multiaqua.com for the latest information.
19
306 Hagood Street
Easley, SC 29640
Ph.: 864-850-8990
Fax: 864-850-8995
www.multiaqua.com
For TechnicalAssistance:
1-855-THNK-WTR (1-855-846-5987)

More Related Content

Similar to MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf

#1 Perkins UK Generators Supplier – Dubai
#1 Perkins UK Generators Supplier – Dubai#1 Perkins UK Generators Supplier – Dubai
#1 Perkins UK Generators Supplier – DubaiAdpower FZCO
 
Perkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aePerkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aeAdpower FZCO
 
Specification – Perkins UK Generating Set – Dubai
Specification – Perkins UK Generating Set – DubaiSpecification – Perkins UK Generating Set – Dubai
Specification – Perkins UK Generating Set – DubaiAdpower FZCO
 
Perkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEPerkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEAdpower FZCO
 
42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdfCarrier Singapore
 
Aph operation and emergency handling
Aph operation and emergency handlingAph operation and emergency handling
Aph operation and emergency handlingParag Agrawal
 
Varaible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsVaraible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsJames S Nasby
 
Kohler 125rzg spec_sheet
Kohler 125rzg spec_sheetKohler 125rzg spec_sheet
Kohler 125rzg spec_sheetPooja Kamthe
 
Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) SYED KHURSHID ALAM ARZOO
 
Product training ac fans & blowers
Product training   ac fans & blowersProduct training   ac fans & blowers
Product training ac fans & blowersshagal2007
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentationRamendra Dhiman
 
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfPNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfXmergeKuwait
 
48 tc 04-16-03pd paquete carrier
48 tc 04-16-03pd paquete carrier48 tc 04-16-03pd paquete carrier
48 tc 04-16-03pd paquete carrierRios Luis
 
Adpower FZCO - Perkins Generating Sets Specification
Adpower FZCO - Perkins Generating Sets SpecificationAdpower FZCO - Perkins Generating Sets Specification
Adpower FZCO - Perkins Generating Sets SpecificationAdpower FZCO
 
Heatpulse 8108 rapid thermal processor
Heatpulse 8108 rapid thermal processorHeatpulse 8108 rapid thermal processor
Heatpulse 8108 rapid thermal processorEmily Tan
 

Similar to MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf (20)

#1 Perkins UK Generators Supplier – Dubai
#1 Perkins UK Generators Supplier – Dubai#1 Perkins UK Generators Supplier – Dubai
#1 Perkins UK Generators Supplier – Dubai
 
Ank y na60_00
Ank y na60_00Ank y na60_00
Ank y na60_00
 
CTU MF 26-32-.pdf
CTU  MF 26-32-.pdfCTU  MF 26-32-.pdf
CTU MF 26-32-.pdf
 
Perkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aePerkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.ae
 
Specification – Perkins UK Generating Set – Dubai
Specification – Perkins UK Generating Set – DubaiSpecification – Perkins UK Generating Set – Dubai
Specification – Perkins UK Generating Set – Dubai
 
Perkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEPerkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAE
 
42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf
 
Aph operation and emergency handling
Aph operation and emergency handlingAph operation and emergency handling
Aph operation and emergency handling
 
Varaible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsVaraible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire Pumps
 
1800REOZM_8_12b
1800REOZM_8_12b1800REOZM_8_12b
1800REOZM_8_12b
 
Kohler 125rzg spec_sheet
Kohler 125rzg spec_sheetKohler 125rzg spec_sheet
Kohler 125rzg spec_sheet
 
Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation)
 
Product training ac fans & blowers
Product training   ac fans & blowersProduct training   ac fans & blowers
Product training ac fans & blowers
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentation
 
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdfPNGC-048-400-50-Hz-CPRC20-5-002.pdf
PNGC-048-400-50-Hz-CPRC20-5-002.pdf
 
48 tc 04-16-03pd paquete carrier
48 tc 04-16-03pd paquete carrier48 tc 04-16-03pd paquete carrier
48 tc 04-16-03pd paquete carrier
 
1600REOZM_8_12b
1600REOZM_8_12b1600REOZM_8_12b
1600REOZM_8_12b
 
Adpower FZCO - Perkins Generating Sets Specification
Adpower FZCO - Perkins Generating Sets SpecificationAdpower FZCO - Perkins Generating Sets Specification
Adpower FZCO - Perkins Generating Sets Specification
 
Heatpulse 8108 rapid thermal processor
Heatpulse 8108 rapid thermal processorHeatpulse 8108 rapid thermal processor
Heatpulse 8108 rapid thermal processor
 
Industrial air-cooled water chiller - DC25000-DC30000 - DANA UAE INDIA SAUDI ...
Industrial air-cooled water chiller - DC25000-DC30000 - DANA UAE INDIA SAUDI ...Industrial air-cooled water chiller - DC25000-DC30000 - DANA UAE INDIA SAUDI ...
Industrial air-cooled water chiller - DC25000-DC30000 - DANA UAE INDIA SAUDI ...
 

Recently uploaded

power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 

Recently uploaded (20)

power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

MHRC-AE-060-VS-01_Submittal_Rev._1.15.pdf

  • 1. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 1 MHRC-AE-060-VS-01 Simultaneous Heating & Cooling (SHC) Chiller for Solar Applications 5 Ton Nominal Hybrid Heat/Cool Chiller Primary - DC (380V) / Secondary - AC (208/230-1-50/60)
  • 2. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 2 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 5 Tons Multiaqua Model Number: MHRC-AE-060-VS-01 Part 1-General 1.01 System Description Multiaqua air-cooled and water to water liquid chillers are designed using variable speed scroll compressors, high volume condenserfans and motors. 1.02 Quality Assurance A. ETL safety certified to UL Standard 1995, 4th edition (U.S.A.). B. UL performance certified. C. Third party certified efficiency ratings are at ANSI/AHRI Standard 550/590 with Addendum3-2011 conditions. D. Manufactured in U.S.A. E. Fully tested. F. Damage resistant packaging. 1.03 Delivery, Storage and Handling A. Packaged and readied for shipment from distribution center. B. Controls shall be capable of withstanding 150°F storage temperatures in the control compartment. C. Stored and handled per manufacturer’s recommendations. Part 2-Product 2.01 Equipment A. General: 1. Unit shall be a factory assembled and tested. 2. Shall be assembled on heavy gauge steel mounting/lifting rails. 3. Contained within the unit cabinet shall be all factory wiring, piping, controls, refrigerant charge (R410a), POE oil and special accessories required prior to start up. 4. Brass body strainers with 20 mesh screen and blow down shall be supplied in cabinet as a field installable accessory. B. Unit Cabinet: 1. Composed of heavy gauge galvanized steelcasing with a baked polyester powder coating. 2. Capable of withstanding 500-hour salt spray test in accordance with the ASTM (U.S.A.) standard. C. CondenserFans: 1. Five blade glass reinforced polypropylene (PP) petals mounted on a cast aluminum hub construction and shall be dynamically balanced and corrosion resistant. 2. Discharge air is vertical. 3. Motors and blades shall be protected by coated steel wire safety guards. D. Fan Motors: 1. Condenser fan motor shall be variable speed,brushless DC type. 2. Condenser fan motors shall be Totally Enclosed Air Over (TEAO), use Class B insulation, and permanently lubricated ball and/or sleeve bearings. 3. Condenser fan motors shall be internally overload protected with automatic reset.
  • 3. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 3 E. Compressor: 1. Unit shall contain one Emerson/Copeland variable speed DC scroll compressor. 2. Direct current DC, 900-7,200 rpm (15-120Hz). 3. Compressor motor shall be suction gas cooled. 4. External motor protection. 5. Externally protected by low and high pressure cutout devices and discharge temperature sensing thermistor. 6. Individual vibration isolators. 7. Compressor compartment is internally insulated using noise reducing elastomeric foam insulation. F. Solar Inverter: 1. Unit shall contain one Pika 7601C Power Core Inverter matched with S2501 PV links at solar panels. G. Pump: 1. Unit shall not be capable of incorporating a field installed chilled liquid solution pump internally. (Space restricted) 2. Unit shall have chilled liquid solution piping to the exterior of the cabinet. H. Evaporator (Cooling): 1. Evaporator shall have one refrigerant circuit and one liquid solution circuit. 2. Evaporator rated for a refrigerant side working pressure up to 550 psig. 3. Evaporator rated for a water side working pressure up to 150 psig. 4. Single pass,ANSI type 316 stainless steel,brazed plate construction with copper/nickel brazing material. I. Condenser(Heating): 1. Condenser shall have one refrigerant circuit and one liquid solution circuit. 2. Condenser rated for a refrigerant side working pressure up to 550 psig. 3. Condenser rated for a water side working pressure up to 150 psig. 4. Single pass,ANSI type 316 stainless steel,brazed plate construction with copper/nickel brazing material. J. Evaporator/Condenser(Cooling/Heating): 1. Condenser coil shall be air-cooled with integral sub-cooler. 2. Constructed of rifled coppertubing mechanically bonded to aluminum fins. 3. Cleaned and dehydrated. 4. Factory leak tested to 650 psig. K. Refrigerant Circuits: 1. Each circuit shall contain liquid line strainers, electronic expansion valves, solenoid valve, check valve, refrigerant charge of R410a, and POE compressor oil. Part 3-Controls and Safeties 3.01 Controls A. Chiller shall be completely factory wired and tested. B. Temperature control shall be based on leaving liquid solution temperatures. 1. Temperature accuracy shall be + - 1°F C. Controls shall be capable of variable speed control. D. Controls shall include the following components: 1. 24vac transformers to serve all controllers, relays, and control components. 2. Microprocessorbased liquid solution temperature controller.
  • 4. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 4 3. Leaving water temperature thermistors. 4. Chilled liquid solution flow switches. E. All functions shall be addressable,logic, code, and algorithm controlled. F. Ethernet port supplied for communication and monitoring. G. Compatible with Building Automation Systems (BAS) using BACnet protocol. 3.02 Safeties A. Unit shall be equipped with all necessary components in conjunction with the control systemto provide the following protection: 1. Low refrigerant pressure. 2. High refrigerant pressure. 3. Water side cold & hot flow. Part 4-Operating Characteristics 4.01 Temperatures A. Unit shall be capable of starting and running at outdoortemperatures from 0°F to 120°F. B. Unit shall be capable of initial startup in cooling mode with a maximum 80°F entering fluid temperature and ambient not above 95° F. C. Maximum sustained entering fluid solution temperature to the evaporatorshall not exceed 70°F in cooling mode. D. Minimum 10% glycol solution is required in all applications. For outdoor temperatures below 32°F, reference the propylene glycol manufacture’s data table of field installed polypropylene glycol solution concentrations. 4.02 Electrical Requirements A. Primary DC electrical power supply shall enter the unit at a single location. B. Secondary AC electrical power supply if used,shall enter the unit at a single location. C. Electrical power supply shall be rated to withstand 90°C operating ambient temperature. Part 5- Definitions 5.01 Abbreviations A. DB = Dry Bulb Temperature B. EWT = Entering Water Temperature C. LWT = Leaving Water Temperature D. EAT = Entering Air Temperature E. EAT/DB = Entering Air Temperature Dry Bulb F. EAT/WB = Entering Air Wet Bulb G. GPM = US Gallons per Minute H. MBH = BTU X 1000 I. SC = Sensible Cooling J. TC = Total Cooling = Sensible + Latent K. dB = Decibel Level 5.02 Measurements A. All measurements with regard to length, width, and height shall be in inches. B. All measurements with regard to pipe sizes shall be in outside diameter (OD) unless otherwise noted.
  • 5. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 5 MHRC-AE-060-VS-01 Product Specifications Simultaneous Heat & Cool (SHC) Mode Electrical Data Model Number Volts/ Phase/ Hertz Compressor Condenser Fan Motor SCCR Fuse or HACR Circuit Breaker (Qty 1) (Qty 1) (RLA) (LRA) (RLA) (RPM) Minimum Amps (MCA) Maximum Amps (MOCP) MHRC-AE-060-VS-01 DC (380V) Primary AC (208/230-1-50/60) Secondary 8 to 25 ~ ~* ~* 10kA 40 50 * Condenserfan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) Mode. Cooling Mode Electrical Data Model Number Volts/ Phase/ Hertz Compressor Condenser Fan Motor SCCR Fuse or HACR Circuit Breaker (Qty 1) (Qty 1) (RLA) (LRA) (RLA) (RPM) Minimum Amps (MCA) Maximum Amps (MOCP) MHRC-AE-060-VS-01 DC (380V) Primary AC (208/230-1-50/60) Secondary 8 to 21 ~ 2.5 1200/VAR* 10kA 40 50 * VAR = Variable Speed Heating Mode Electrical Data Model Number Volts/ Phase/ Hertz Compressor Condenser Fan Motor SCCR Fuse or HACR Circuit Breaker (Qty 1) (Qty 1) (RLA) (LRA) (RLA) (RPM) Minimum Amps (MCA) Maximum Amps (MOCP) MHRC-AE-060-VS-01 DC (380V) Primary AC (208/230-1-50/60) Secondary 8 to 31 ~ 2.5 1200/VAR* 10kA 40 50 * VAR = Variable Speed Physical Data Model Number Chiller Weight (lbs.) Height (in) Length (in) Width (in) Refrigerant R410a (1 Circuits) Net Shipping MHRC-AE-060-VS-01 63-1/2 33-5/8 52-1/2 13.5 lbs. / 216 oz. 700 900
  • 6. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 6 MHRC-AE-060-VS-01 Product Specifications Compressor Copeland Variable Speed (VS) Scroll Refrigerant R410a Heat Exchanger (Cooling) Brazed Plate Heat Exchanger (Heating) Brazed Plate Max. Flow Rate (Cooling) 14.4 gpm Min. Flow Rate (Cooling) 12 gpm Max. Flow Rate (Heating) 14.4 gpm Min. Flow Rate (Heating) 12 gpm Supply Water Temp (Cooling) 44°F (Adjustable) Return Water Temp (Cooling) 54°F (Adjustable) Minimum Supply Water Temp (Cooling) 28°F* Minimum Return Water Temp (Cooling) 38°F* Maximum Supply Water Temp (Heating) 130°F* Maximum Return Water Temp (Heating) 120°F* Minimum SystemSolution Content (Cold Side) 25 Gallons Minimum SystemSolution Content (Hot Side) 25 Gallons Expansion Tank Size 3% of Total System Water Connections (4) 1.00" MPT Supply & Return * Compatible with Thermal Storage (TS) systems.
  • 7. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 7 MHRC-AE-060-VS-01 Performance Data Simultaneous Heat/Cool (SHC) Mode Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F) 44 46839 105534 7.76 26.49 58695 105  Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.  Compressor runningat 5000 RPMin SHC mode. Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F) 44 43080 100383 5.95 20.29 57303 120  Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.  Compressor runningat 5000 RPMin SHC mode. Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F) 44 41827 98666 5.49 18.73 56839 125  Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.  Compressor runningat 5000 RPMin SHC mode. Simultaneous Cooling Simultaneous Heat/Cool Simultaneous Heating LWT (°F) BTU's Total BTU's COP EER BTU's LWT (°F) 44 40575 96949 5.08 17.34 56375 130  Condenser fan does not run when MHRC2 is in Simultaneous Heat & Cool (SHC) mode.  Compressor runningat 5000 RPMin SHC mode.
  • 8. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 8 MHRC-AE-060-VS-01 Performance Data Cooling Mode Entering Air Temperature Entering Air Temperature Entering Air Temperature Entering Air Temperature 55°F 65°F 80°F 95°F LWT (°F) BTU's COP EER BTU's COP EER BTU's COP EER BTU's COP EER 44 53084 5.94 20.26 54996 4.98 17.00 47314 3.77 12.86 46500 3.00 10.22 IPLV 15.58  Compressor runningat 5000 RPMin coolingmode. Heating Mode Entering Air Temperature Entering Air Temperature 47°F 47°F LWT (°F) BTU's COP EER BTU's COP EER LWT (°F) 105° 66365 2.91 9.93 64641 2.63 8.96 120° Entering Air Temperature Entering Air Temperature LWT (°F) 47°F 47°F LWT (°F) 125° BTU's COP EER BTU's COP EER 130° 64066 2.54 8.66 63492 2.46 8.39  Compressor runningat 6000 RPMin heatingmode. Entering Air Temperature Entering Air Temperature 17°F 17°F LWT (°F) BTU's COP EER BTU's COP EER LWT (°F) 105° 45853 2.11 7.20 43653 1.96 6.70 120° Entering Air Temperature Entering Air Temperature LWT (°F) 17°F 17°F LWT (°F) 125° BTU's COP EER BTU's COP EER 130° 42919 1.92 6.54 42186 1.87 6.39  Compressor runningat 6000 RPMin heatingmode.
  • 9. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 9 MHRC-AE-060-VS-01 Glycol Adjustment Factors Glycol Solution Concentration Data Propylene Glycol % Min. Ambient Temp 10% 26°F 20% 18°F 30% 8°F 40% -7°F 50% -29°F Estimated Propylene Glycol Adjustment Factors: Percent of Propylene Glycol Capacity adjustment Pressure Drop adjustment Multiply TONS by: Multiply PD by: 10% 0.995 1.02 15% 0.992 1.04 20% 0.986 1.08 25% 0.972 1.13 30% 0.96 1.21 35% 0.95 1.26 40% 0.928 1.47 50% 0.878 2.79 Important Required Use of 10% Minimum Propylene Glycol Multiaqua Inc. requires a minimum concentration of 10% propylene glycol in the chiller system solution. This requirement applies to all chiller product models for protection of the brazed plate heat exchanger (BPHE), regardless of outdoor ambient operating temperature. The Multiaqua chiller operating at a 44 leaving water temperature (LWT) will have an internal BPHE temperature of 32 F to 38 F. Without the required MINIMUM 10% concentration of propylene glycol, the unit is susceptible to areas of freezing within the BPHE which could result in failure of the BPHE. With any deviation from full flow through the BPHE,the BPHE would also be susceptible to areas of freezing within the BPHE. This could be caused by, but not limited to, contaminates being caught in the wye strainer, flow switch or pump failure. Each chiller is supplied from the factory with a Wye strainer that is to be installed on the inlet (suction) side of the pump on the MAC- 036HE, 048HE, 060HE, 120HE, and MHRC2-060-VS chillers. Failure to follow this requirement will void the chiller warranty. Failure to comply may result in BPHE failure due to freezing followed by compressor failure, all of which are not covered under Multiaqua’s warranty policy.
  • 10. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 10 MHRC-AE-060-VS-01 Altitude Adjustment Factors Important notes about LowAmbient Operation: If the outside temperature is expected to fall below freezing (32°F) in the area where the Multiaqua chiller is to be installed; the installer must take the following precautions. Failure to do so will void the warranty. To not engage in cold ambient mitigation will result in the failure of components such as the heat exchanger, piping, circulating pump, etc.. and or property damage. • Keep the liquid solution at a minimum of 10% percent Propylene Glycol even in areas where there is no danger of freezing. • The percentage amount of glycol recommended is dependent on the expected ambient temperatures and the solution makeup recommendation of the glycol manufacturer. For outdoor temperatures below 32°F, reference glycol manufacture’s data table of field installed polypropylene glycol solution. • Ensure the system circulating pump is in a constant energized mode to keep a continuous circulation of liquid solution. The Multiaqua chiller is a self-contained, air-cooled condenser, coupled with brazed plate heat exchangers (evaporator). The system utilizes a scroll compressor to circulate refrigerant between the condenser and heat exchanger. The refrigerant is metered into the heat exchanger with a electronic expansion valve. Protecting the system are both high and low pressure switches as well as a pump flow switch. Liquid solution (water and propylene glycol; minimum 10 % is required at any ambient) is circulated through the heat exchangers by externally mounted pumps. The liquid solution flows through the heat exchangers to the system supply piping and on to the air handlers. Altitude Tons 1000 ft. .995 2000 ft. .990 3000 ft. .986 4000 ft. .983 5000 ft. .980 6000 ft. .978
  • 11. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 11 MHRC-AE-060-VS-01 Sound Data MODEL # MHRC-AE-060-VS-01 (Cooling Mode) Fan Speed dB(A) @ 3 m H 62 MODEL # MHRC-AE-060-VS-01 (Heating Mode) Fan Speed dB(A) @ 3 m H 62 MODEL # MHRC-AE-060-VS-01 Simultaneous Heating & Cooling (SHC Mode) Fan Speed dB(A) @ 3 m FAN OFF* 60 * Condenser fan does not run in Simultaneous Heat & Cool (SHC) mode.
  • 12. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 12 MHRC-AE-060-VS-01 Upper Electrical Panel Layout
  • 13. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 13 MHRC-AE-060-VS-01 Lower Electrical Panel Layout
  • 14. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 14 MHRC-AE-060-VS-01 Low Voltage Wiring Diagram
  • 15. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 15 MHRC-AE-060-VS-01 Low Voltage Wiring Diagram (Expanded Upper Section of Diagram)
  • 16. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 16 MHRC-AE-060-VS-01 Low Voltage Wiring Diagram (Expanded Lower Section of Diagram)
  • 17. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 17 MHRC-AE-060-VS-01 High Voltage Wiring Diagram
  • 18. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 18 MHRC-AE-060-VS-01 Dimensional Drawing Model A B C D E F G H I J MHRC-AE-060 63.50 52.50 29.00 33.625 27.75 16.75 7.00 18.50 9.50 9.25 Dimensionsare ininches. All supplyandreturn waterconnectionsare 1.00" (MPT).
  • 19. These specifications are subject to change without notice. Rev. 1.15 Check www.multiaqua.com for the latest information. 19 306 Hagood Street Easley, SC 29640 Ph.: 864-850-8990 Fax: 864-850-8995 www.multiaqua.com For TechnicalAssistance: 1-855-THNK-WTR (1-855-846-5987)