Service Manual
English – Original Instructions 1-2010
Generator Set
PowerStart 0500 Control
C8 D5
C11 D5
C12 D6
C16 D6
C17 D5
C20 D6
C22 D5
C28 D5
A029U889 (Issue 2)
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
© Copyright Cummins Power Generation page 3
Table of Contents
SECTION TITLE PAGE
1 IMPORTANT SAFETY INSTRUCTIONS 5
2 INTRODUCTION 7
2.1 About this Manual 7
2.2 System Overview 7
2.3 Test Equipment 7
2.4 How to Obtain Service 7
3 CONTROL PANEL OPERATION 8
3.1 General 8
3.2 Alternator Connections 9
3.3 Control Operation 11
3.4 Control Panel 12
3.5 Mode of Operation 14
4 CIRCUIT BOARD 19
4.1 Control Input and Outputs 21
5 TROUBLESHOOTING 24
5.1 Safety Considerations 24
5.2 Troubleshooting Procedure 24
6 Setup and Calibration 34
7 SERVICING THE GENERATOR 39
7.1 Testing the Generator 39
7.2 Generator Baseboard Isolation Procedure 40
7.3 Excitor Stator 41
7.4 Excitor Rectifier Bridge 42
7.5 Main Stator 45
7.6 Generator Disassembly 47
8 WITHDRAWING ROTOR 49
8.1 Generator Reassembly 49
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
page 4 © Copyright Cummins Power Generation
SECTION TITLE PAGE
9 WIRING DIAGRAMS 53
9.1 General Information 53
9.2 Wiring Diagram 57
9.3 Battery Charger and Coolant Heater 59
9.4 Customer Connections 62
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
© Copyright Cummins Power Generation page 5
SECTION 1 – IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual
contains important instructions that should be followed
during installation and maintenance of the generator
and batteries.
Before operating the generator set (genset), read the
Operator’s Manual and become familiar with it and the
equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the
operator, service personnel, or the equipment.
This symbol warns of
immediate hazards which will result in
severe personal injury or death.
This symbol refers to a
hazard or unsafe practice which can
result in severe personal injury or death.
This symbol refers to a
hazard or unsafe practice which can
result in personal injury or product or
property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result
from improper practices.
• DO NOT fill fuel tanks while engine is running,
unless tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a
potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use
zinc coated or copper fuel lines with diesel fuel
• Be sure all fuel supplies have a positive shutoff
valve.
• Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a
highly explosive hydrogen gas that can be ignited
by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
• Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
likely to congregate. Visually and audibly inspect
the exhaust daily for leaks per the maintenance
schedule. Make sure that exhaust manifolds are
secured and not warped. Do not use exhaust
gases to heat a compartment.
• Be sure the unit is well ventilated.
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
moving parts.
• Before starting work on the generator set,
disconnect battery charger from its AC source,
then disconnect starting batteries, negative (–)
cable first. This will prevent accidental starting.
• Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity
of moving parts, or while working on electrical
equipment. Loose clothing and jewelry can
become caught in moving parts.
• If adjustment must be made while the unit is
running, use extreme caution around hot
manifolds, moving parts, etc.
DO NOT OPERATE INFLAMMABLE AND
EXPLOSIVE ENVIRONMENTS.
Flammable vapor can cause an engine to overspeed
and become difficult to stop, resulting in possible fire,
explosion, severe personal injury and death. Do not
operate a genset where a flammable vapor
environment can be created by fuel spill, leak, etc.,
unless the genset is equipped with an automatic
safety device to block the air intake and stop the
engine. The owners and operators of the genset are
solely responsible for operating the genset safely.
Contact your authorized Cummins Power
Generation distributor for more information.
DANGER
WARNING
CAUTION
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
page 6 © Copyright Cummins Power Generation
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
• Remove electric power before removing
protective shields or touching electrical
equipment. Use rubber insulative mats placed
on dry wood platforms over floors that are metal
or concrete when around electrical equipment.
Do not wear damp clothing (particularly wet
shoes) or allow skin surface to be damp when
handling electrical equipment. Do not wear
jewelry. Jewelry can short out electrical contacts
and cause shock or burning.
• Use extreme caution when working on electrical
components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical
codes. Have all electrical installations performed
by a qualified licensed electrician. Tag and lock
open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DI-
RECTLY TO ANY BUILDING ELECTRICAL
SYSTEM. Hazardous voltages can flow from the
generator set into the utility line. This creates a
potential for electrocution or property damage.
Connect only through an approved isolation
switch or an approved paralleling device.
GENERAL SAFETY PRECAUTIONS
• Coolants sunder pressure have a higher boiling
point than water. DO NOT open a radiator or
heat ex-changer pressure cap while the engine
is running. To prevent severe scalding, let
engine cool down before removing coolant
pressure cap. Turn cap slowly, and do not open
it fully until the pressure has been relieved.
• Used engine oils have been identified by some
state or federal agencies as causing cancer or
reproductive toxicity. When checking or
changing engine oil, take care not to ingest,
breathe the fumes, or con-tact used oil.
• Keep multi-class ABC fire extinguishers
handy. Class A fires involve ordinary
combustible materials such as wood and
cloth; Class B fires, combustible and
flammable liquid fuels and gaseous fuels;
Class C fires, live electrical equipment. (ref.
NFPA No. 10).
• Make sure that rags are not left on or near
the generator set.
• Make sure generator set is mounted in a
manner to prevent combustible materials
from accumulating under or near the unit.
• Remove all unnecessary grease and oil from
the unit. Accumulated grease and oil can
cause over-heating and engine damage
which present a potential fire hazard.
• Keep the generator set and the surrounding
area clean and free from obstructions.
Remove any debris from the set and keep
the floor clean and dry.
• Do not work on this equipment when
mentally or physically fatigued, or after
consuming any alcohol or drug that makes
the operation of equipment unsafe.
• Substances in exhaust gases have been
identified by some state or federal agencies
as causing cancer or reproductive toxicity.
Take care not to breath or ingest or come
into contact with exhaust gases.
• Do not store any flammable liquids, such as
fuel, cleaners, oil, etc., near the generator
set. A fire or explosion could result.
• Wear hearing protection when going near an
operating generator set.
• To prevent serious burns, avoid contact with
hot metal parts such as radiator system,
turbo charger system and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
Power Start 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
© Copyright Cummins Power Generation page 7
SECTION 2 – INTRODUCTION
2.1 ABOUT THIS MANUAL
This manual provides troubleshooting and repair
information regarding the PowerCommand®
1302Control (PCC) and generators for the
generator sets (gensets) listed on the front cover.
Engine service instructions are in the applicable
engine service manual. Operating and maintenance
instructions are in the applicable Operator’s
Manual.
This manual does not have instructions for
servicing printed circuit board assemblies. After
determining that a printed circuit board assembly is
faulty, replace it, do not repair it. Attempts to repair
a printed circuit board can lead to costly damage to
the equipment.
This manual contains basic (generic) wiring
diagrams and schematics that are included to help
in troubleshooting. Service personnel must use the
actual wiring diagram and schematic shipped with
each unit. The wiring diagrams and schematics that
are maintained with the unit should be updated
when modifications are made to the unit.
Read Important Safety Instructions and carefully
observe all instructions and precautions in this
manual.
2.2 SYSTEM OVERVIEW
The PCC is a microprocessor-based control for
Cummins Power Generation generator sets. All
generator set control functions are contained on
one circuit board (Base board). The Base board
provides fuel control, main alternator voltage output
regulation and complete generator set control and
monitoring.
The operating software provides control of the
generator set and its performance characteristics,
and displays performance information on a digital
display panel. It accepts menu-driven control and
set-up input from the push button switches on the
front panel.
2.3 TEST EQUIPMENT
To perform the test procedures in this manual, the
following test equipment must be available
True RMS meter for accurate measurement of
small AC and DC voltages. Fluke models 87 or
8060A are good choices.
Grounding wrist strap to prevent circuit board
damage due to electrostatic discharge (ESD).
Battery Hydrometer.
Jumper Leads.
Tachometer or Frequency Meter.
Wheatstone Bridge or Digital Ohmmeter.
Variac.
Load Test Panel.
Megger or Insulation Resistance Meter.
InPower™ Service Tool (PC based genset
service tool).
PCC1302 Interface Kit (Used with InPower
Service Tool)
2.4 HOW TO OBTAIN SERVICE
Always give the complete Model, Specification and
Serial number of the generator set as shown on the
nameplate when seeking additional service
information or replacement parts. The nameplate is
located on the front of the control panel.
Incorrect service or
replacement of parts can result in severe
personal injury or death, and/or equipment
damage. Service personnel must be trained and
experienced to perform electrical and
mechanical service. Read and follow Important
Safety Instructions on pages iii and iv.
WARNING
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
page 8 © Copyright Cummins Power Generation
SECTION 3 – OPERATOR PANEL OPERATION
FIGURE 3-1. PS0500 - CONTROLLER
3.1 GENERAL
The PS0500 is a microprocessor-based controller
that has these abilities.
• Start and stop the genset.
• Monitor the status of the genset.
• Warn the operator when unsafe conditions
are occurring
• Shut down the genset to prevent damage
• Adjust settings that affect genset behavior.
• Provide a way for other devices to remotely
start / Stop the genset
This is the Operator Manual for the PowerStart 0500
control. It is not the Operator Manual for the
generator set (“genset”) or any accessories.
The third digit is flashed, followed by a half-second
pause, and then the fourth digit is flashed, followed
by a two-second pause. The PowerStart 0500 is
suitable for non-paralleling generator sets
(“gensets”) in standby or
Prime power applications.
Note: Other devices that can remotely start / Stop
the genset might be as simple as a switch or a push
button or as sophisticated as other controllers or
computers. This manual introduces the ways the
Control can interact with other devices, but this
manual cannot identify all of the devices that might
be used in every application.
Power Start 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
© Copyright Cummins Power Generation page 9
3.2 ALTERNATOR CONNECTIONS
This section introduces the connections between the
PS0500 and the alternator.
Main Alternator Output
The PS0500 is connected to the main alternator
output to measure genset voltage and genset
frequency.
The PS0500 is also connected to current
transformers (CTs) which reduce the genset current
by a known ratio for measuring main alternator
output current.
Engine Connections
This section introduces the connections between the
PS0500 and the engine.
Battery Connections
The battery provides power for the PS0500 and the
PS0500 monitors the battery voltage.
Starter
The PS0500 is connected to the starter control relay
in order to control the starter.
See Sequences of Operation for more information
about the behavior of this output.
Fuel Shutoff (FSO) Relay
The PS0500 is connected to the fuel shutoff control
(FSO) in order to control the fuel shutoff solenoid in
the fuel supply line.
See Sequences of Operation for more information
about the behavior of this output.
Genset Connections
This section introduces the connections betweent he
PS0500 and other parts of the genset. Some of
these connections are flexible and might be made to
many types of devices.
Customer Input
The PS0500 has one customer input that can be
configured to invoke a shutdown or Warning
response
Battery Charger Failed Switch
The PS0500’s Customer Input may be connected to
a battery charger’s status output (discrete) to
monitor the battery charger operation.
Emergency Stop Buttons
The PS0500 may be connected to a push button
that shuts the genset down immediately when
pressed.
FIGURE 3-2. EMERGENCY STOP BUTTON
(EXAMPLE)
Customer Output
The PS0500 has one customer output that can be
configured to become active when either a shutdown
or Warning fault occurs.
PowerStart 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
page 10 © Copyright Cummins Power Generation
PC-based Service Tools
The PS0500 or the Operator Panel may be
connected to a PC-based service tool, such
as InPower.
Note: See the PC-based service tool documentation
for more information.
The PC-based service tool harness (Figure 3-3) is used
to connect the PS0500 to a PC-based service tool.
FIGURE 3-3. PC-BASED SERVICE TOOL HARNESS
Ready to Load
The PS0500 may notify a device when event 1465 (Ready to
Load) is active. Typically, the device is a programmable logic
controller
Remote Start
The PS0500 may be connected to a device that can
generate a remote start signal. Typically, the device is a
transfer switch.
Certifications
The PS0500 meets or exceeds the requirements of the
following codes and standards.
• UL 508
• CSA
• C282 compliant
• 22.2 compliant
• NFPA 99 compliant
• MS 202C, Method 101 compliant
• IEEE C62.41 compliant
• IEEE C37.90 compliant
• BS ISO 8528−4:2005
• BS EN 50081−1:1992
• BS EN 61000−6−2:2001
• BS EN 61000−6−3:2001
• BS EN 61000−6−4:2001CE Marking: The control
system is suitable for use on generator sets to be CE
− marked.
• BS EN 61000−6−4:2001CE Marking: The control
system is suitable for use on generator sets to be CE
− marked.
Power Start 0500 Publication A029U889
Models C8 D5 – C28 D5 Issue 2 - 1-2010
© Copyright Cummins Power Generation page 11
3.3 CONTROL OPERATION
In this section, italics are used to identify a specific
parameter by name.
Safety Considerations
AC power is present when the genset is running. Do not
open the generator output box while the genset is
running.
Contacting high-voltage
components can cause electrocution, resulting in
severe personal injury or death. Do not open the
generator output box while the set is running. Read
and observe all WARNINGS and CAUTIONS in your
genset manuals.
The PS0500 cabinet must be opened only by technically
qualified personnel.
The PS0500 cabinet must be
opened only by qualified personnel. High-level
voltages (up to 600 VAC) are present in the PS0500
cabinet. These voltages can cause electrical shock,
resulting in personal injury or death.
Even with the power removed,
improper handling of components can cause
electrostatic discharge and damage to circuit
components.
Read Safety Precautions, and carefully observe all of the
instructions and precautions in this manual.
Starting and Stopping the Genset
The buttons related to changing mode of operation are
highlighted in figure 3.4 and described in
Table 3.1
FIGURE 3-4. CONTROL PANEL BUTTONS
TABLE 3-1 CONTROL PANEL BUTTONS
BUTTON(S) DESCRIPTION
Manual
Puts the control in Manual Mode to Start
the genset Manually.
You have to push the Start button in
less than ten seconds after you push
the Manual button.
Auto
Puts the control in Auto Mode. The
genset starts and stops when it
is told by other devices (such as a
transfer switch)
Stop Stops the genset
When the genset starts and stops, it follows a series of
steps, called a sequence of operation that is intended to
maximize the life of the genset. The genset might not
start or stop immediately.
The genset might not start or
stop immediately. Do not attempt to service the
genset if it does not appear to respond immediately.
Accidental starting of the genset during
troubleshooting can cause severe personal injury or
death.
WARNING
WARNING
CAUTION
WARNING
Thank you very much
for your reading.
Please Click Here
Then Get More
Information.

More Related Content

More from fjkfksmemm

Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...fjkfksmemm
 
Cummins onan c250 d6 generator set with power command 1302 controller service...
Cummins onan c250 d6 generator set with power command 1302 controller service...Cummins onan c250 d6 generator set with power command 1302 controller service...
Cummins onan c250 d6 generator set with power command 1302 controller service...fjkfksmemm
 
Cummins onan c150 d5 generator set with power command 1301 controller service...
Cummins onan c150 d5 generator set with power command 1301 controller service...Cummins onan c150 d5 generator set with power command 1301 controller service...
Cummins onan c150 d5 generator set with power command 1301 controller service...fjkfksmemm
 
Cummins onan c140 d6 generator set with power command 1301 controller service...
Cummins onan c140 d6 generator set with power command 1301 controller service...Cummins onan c140 d6 generator set with power command 1301 controller service...
Cummins onan c140 d6 generator set with power command 1301 controller service...fjkfksmemm
 
Cummins onan c125 d5 generator set with power command 1301 controller service...
Cummins onan c125 d5 generator set with power command 1301 controller service...Cummins onan c125 d5 generator set with power command 1301 controller service...
Cummins onan c125 d5 generator set with power command 1301 controller service...fjkfksmemm
 
Cummins onan c110 d6 generator set with power command 1301 controller service...
Cummins onan c110 d6 generator set with power command 1301 controller service...Cummins onan c110 d6 generator set with power command 1301 controller service...
Cummins onan c110 d6 generator set with power command 1301 controller service...fjkfksmemm
 
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...fjkfksmemm
 
Cummins onan c110 d5 generator set with power command 1301 controller service...
Cummins onan c110 d5 generator set with power command 1301 controller service...Cummins onan c110 d5 generator set with power command 1301 controller service...
Cummins onan c110 d5 generator set with power command 1301 controller service...fjkfksmemm
 
Cummins onan c90 d6 generator set with power command 1301 controller service ...
Cummins onan c90 d6 generator set with power command 1301 controller service ...Cummins onan c90 d6 generator set with power command 1301 controller service ...
Cummins onan c90 d6 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c90 d5 generator set with power command 1301 controller service ...
Cummins onan c90 d5 generator set with power command 1301 controller service ...Cummins onan c90 d5 generator set with power command 1301 controller service ...
Cummins onan c90 d5 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c80 d6 generator set with power command 1301 controller service ...
Cummins onan c80 d6 generator set with power command 1301 controller service ...Cummins onan c80 d6 generator set with power command 1301 controller service ...
Cummins onan c80 d6 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c80 d5 generator set with power command 1301 controller service ...
Cummins onan c80 d5 generator set with power command 1301 controller service ...Cummins onan c80 d5 generator set with power command 1301 controller service ...
Cummins onan c80 d5 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c70 d6 generator set with power command 1301 controller service ...
Cummins onan c70 d6 generator set with power command 1301 controller service ...Cummins onan c70 d6 generator set with power command 1301 controller service ...
Cummins onan c70 d6 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c70 d5 generator set with power command 1301 controller service ...
Cummins onan c70 d5 generator set with power command 1301 controller service ...Cummins onan c70 d5 generator set with power command 1301 controller service ...
Cummins onan c70 d5 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c60 d6 generator set with power command 1301 controller service ...
Cummins onan c60 d6 generator set with power command 1301 controller service ...Cummins onan c60 d6 generator set with power command 1301 controller service ...
Cummins onan c60 d6 generator set with power command 1301 controller service ...fjkfksmemm
 
Cummins onan c28 d5 generator set power start 0500 control service repair manual
Cummins onan c28 d5 generator set power start 0500 control service repair manualCummins onan c28 d5 generator set power start 0500 control service repair manual
Cummins onan c28 d5 generator set power start 0500 control service repair manualfjkfksmemm
 
Cummins onan c20 d6 generator set power start 0500 control service repair manual
Cummins onan c20 d6 generator set power start 0500 control service repair manualCummins onan c20 d6 generator set power start 0500 control service repair manual
Cummins onan c20 d6 generator set power start 0500 control service repair manualfjkfksmemm
 
Cummins onan c17 d5 generator set power start 0500 control service repair manual
Cummins onan c17 d5 generator set power start 0500 control service repair manualCummins onan c17 d5 generator set power start 0500 control service repair manual
Cummins onan c17 d5 generator set power start 0500 control service repair manualfjkfksmemm
 
Cummins onan c16 d6 generator set power start 0500 control service repair manual
Cummins onan c16 d6 generator set power start 0500 control service repair manualCummins onan c16 d6 generator set power start 0500 control service repair manual
Cummins onan c16 d6 generator set power start 0500 control service repair manualfjkfksmemm
 
Cummins onan c12 d6 generator set power start 0500 control service repair manual
Cummins onan c12 d6 generator set power start 0500 control service repair manualCummins onan c12 d6 generator set power start 0500 control service repair manual
Cummins onan c12 d6 generator set power start 0500 control service repair manualfjkfksmemm
 

More from fjkfksmemm (20)

Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...
 
Cummins onan c250 d6 generator set with power command 1302 controller service...
Cummins onan c250 d6 generator set with power command 1302 controller service...Cummins onan c250 d6 generator set with power command 1302 controller service...
Cummins onan c250 d6 generator set with power command 1302 controller service...
 
Cummins onan c150 d5 generator set with power command 1301 controller service...
Cummins onan c150 d5 generator set with power command 1301 controller service...Cummins onan c150 d5 generator set with power command 1301 controller service...
Cummins onan c150 d5 generator set with power command 1301 controller service...
 
Cummins onan c140 d6 generator set with power command 1301 controller service...
Cummins onan c140 d6 generator set with power command 1301 controller service...Cummins onan c140 d6 generator set with power command 1301 controller service...
Cummins onan c140 d6 generator set with power command 1301 controller service...
 
Cummins onan c125 d5 generator set with power command 1301 controller service...
Cummins onan c125 d5 generator set with power command 1301 controller service...Cummins onan c125 d5 generator set with power command 1301 controller service...
Cummins onan c125 d5 generator set with power command 1301 controller service...
 
Cummins onan c110 d6 generator set with power command 1301 controller service...
Cummins onan c110 d6 generator set with power command 1301 controller service...Cummins onan c110 d6 generator set with power command 1301 controller service...
Cummins onan c110 d6 generator set with power command 1301 controller service...
 
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
 
Cummins onan c110 d5 generator set with power command 1301 controller service...
Cummins onan c110 d5 generator set with power command 1301 controller service...Cummins onan c110 d5 generator set with power command 1301 controller service...
Cummins onan c110 d5 generator set with power command 1301 controller service...
 
Cummins onan c90 d6 generator set with power command 1301 controller service ...
Cummins onan c90 d6 generator set with power command 1301 controller service ...Cummins onan c90 d6 generator set with power command 1301 controller service ...
Cummins onan c90 d6 generator set with power command 1301 controller service ...
 
Cummins onan c90 d5 generator set with power command 1301 controller service ...
Cummins onan c90 d5 generator set with power command 1301 controller service ...Cummins onan c90 d5 generator set with power command 1301 controller service ...
Cummins onan c90 d5 generator set with power command 1301 controller service ...
 
Cummins onan c80 d6 generator set with power command 1301 controller service ...
Cummins onan c80 d6 generator set with power command 1301 controller service ...Cummins onan c80 d6 generator set with power command 1301 controller service ...
Cummins onan c80 d6 generator set with power command 1301 controller service ...
 
Cummins onan c80 d5 generator set with power command 1301 controller service ...
Cummins onan c80 d5 generator set with power command 1301 controller service ...Cummins onan c80 d5 generator set with power command 1301 controller service ...
Cummins onan c80 d5 generator set with power command 1301 controller service ...
 
Cummins onan c70 d6 generator set with power command 1301 controller service ...
Cummins onan c70 d6 generator set with power command 1301 controller service ...Cummins onan c70 d6 generator set with power command 1301 controller service ...
Cummins onan c70 d6 generator set with power command 1301 controller service ...
 
Cummins onan c70 d5 generator set with power command 1301 controller service ...
Cummins onan c70 d5 generator set with power command 1301 controller service ...Cummins onan c70 d5 generator set with power command 1301 controller service ...
Cummins onan c70 d5 generator set with power command 1301 controller service ...
 
Cummins onan c60 d6 generator set with power command 1301 controller service ...
Cummins onan c60 d6 generator set with power command 1301 controller service ...Cummins onan c60 d6 generator set with power command 1301 controller service ...
Cummins onan c60 d6 generator set with power command 1301 controller service ...
 
Cummins onan c28 d5 generator set power start 0500 control service repair manual
Cummins onan c28 d5 generator set power start 0500 control service repair manualCummins onan c28 d5 generator set power start 0500 control service repair manual
Cummins onan c28 d5 generator set power start 0500 control service repair manual
 
Cummins onan c20 d6 generator set power start 0500 control service repair manual
Cummins onan c20 d6 generator set power start 0500 control service repair manualCummins onan c20 d6 generator set power start 0500 control service repair manual
Cummins onan c20 d6 generator set power start 0500 control service repair manual
 
Cummins onan c17 d5 generator set power start 0500 control service repair manual
Cummins onan c17 d5 generator set power start 0500 control service repair manualCummins onan c17 d5 generator set power start 0500 control service repair manual
Cummins onan c17 d5 generator set power start 0500 control service repair manual
 
Cummins onan c16 d6 generator set power start 0500 control service repair manual
Cummins onan c16 d6 generator set power start 0500 control service repair manualCummins onan c16 d6 generator set power start 0500 control service repair manual
Cummins onan c16 d6 generator set power start 0500 control service repair manual
 
Cummins onan c12 d6 generator set power start 0500 control service repair manual
Cummins onan c12 d6 generator set power start 0500 control service repair manualCummins onan c12 d6 generator set power start 0500 control service repair manual
Cummins onan c12 d6 generator set power start 0500 control service repair manual
 

Recently uploaded

Dubai Call Girls Size E6 (O525547819) Call Girls In Dubai
Dubai Call Girls  Size E6 (O525547819) Call Girls In DubaiDubai Call Girls  Size E6 (O525547819) Call Girls In Dubai
Dubai Call Girls Size E6 (O525547819) Call Girls In Dubaikojalkojal131
 
FULL ENJOY - 9953040155 Call Girls in Sector 61 | Noida
FULL ENJOY - 9953040155 Call Girls in Sector 61 | NoidaFULL ENJOY - 9953040155 Call Girls in Sector 61 | Noida
FULL ENJOY - 9953040155 Call Girls in Sector 61 | NoidaMalviyaNagarCallGirl
 
audience feedback draft 3.pptxxxxxxxxxxx
audience feedback draft 3.pptxxxxxxxxxxxaudience feedback draft 3.pptxxxxxxxxxxx
audience feedback draft 3.pptxxxxxxxxxxxMollyBrown86
 
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...anilsa9823
 
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class Service 100% Saf...
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class  Service 100% Saf...Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class  Service 100% Saf...
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class Service 100% Saf...shivangimorya083
 
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdf
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdfSales & Marketing Alignment_ How to Synergize for Success.pptx.pdf
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdfAggregage
 
How To Fix Mercedes Benz Anti-Theft Protection Activation Issue
How To Fix Mercedes Benz Anti-Theft Protection Activation IssueHow To Fix Mercedes Benz Anti-Theft Protection Activation Issue
How To Fix Mercedes Benz Anti-Theft Protection Activation IssueTerry Sayther Automotive
 
Production documentary.ppt. x
Production documentary.ppt.               xProduction documentary.ppt.               x
Production documentary.ppt. x21005760
 
What Could Cause Your Subaru's Touch Screen To Stop Working
What Could Cause Your Subaru's Touch Screen To Stop WorkingWhat Could Cause Your Subaru's Touch Screen To Stop Working
What Could Cause Your Subaru's Touch Screen To Stop WorkingBruce Cox Imports
 
John deere 425 445 455 Maitenance Manual
John deere 425 445 455 Maitenance ManualJohn deere 425 445 455 Maitenance Manual
John deere 425 445 455 Maitenance ManualExcavator
 
Greenery-Palette Pitch Deck by Slidesgo.pptx
Greenery-Palette Pitch Deck by Slidesgo.pptxGreenery-Palette Pitch Deck by Slidesgo.pptx
Greenery-Palette Pitch Deck by Slidesgo.pptxzohiiimughal286
 
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂Hot Call Girls In Sector 58 (Noida)
 
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...Delhi Call girls
 
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls Services
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls ServicesBandra Escorts, (*Pooja 09892124323), Bandra Call Girls Services
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls ServicesPooja Nehwal
 
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 person
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 personDelhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 person
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 personshivangimorya083
 
What Causes BMW Chassis Stabilization Malfunction Warning To Appear
What Causes BMW Chassis Stabilization Malfunction Warning To AppearWhat Causes BMW Chassis Stabilization Malfunction Warning To Appear
What Causes BMW Chassis Stabilization Malfunction Warning To AppearJCL Automotive
 
John Deere Tractors 6130M 6140M Diagnostic Manual
John Deere Tractors  6130M 6140M Diagnostic ManualJohn Deere Tractors  6130M 6140M Diagnostic Manual
John Deere Tractors 6130M 6140M Diagnostic ManualExcavator
 
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sex
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sexDelhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sex
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sexshivangimorya083
 
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...Hot Call Girls In Sector 58 (Noida)
 

Recently uploaded (20)

Dubai Call Girls Size E6 (O525547819) Call Girls In Dubai
Dubai Call Girls  Size E6 (O525547819) Call Girls In DubaiDubai Call Girls  Size E6 (O525547819) Call Girls In Dubai
Dubai Call Girls Size E6 (O525547819) Call Girls In Dubai
 
FULL ENJOY - 9953040155 Call Girls in Sector 61 | Noida
FULL ENJOY - 9953040155 Call Girls in Sector 61 | NoidaFULL ENJOY - 9953040155 Call Girls in Sector 61 | Noida
FULL ENJOY - 9953040155 Call Girls in Sector 61 | Noida
 
audience feedback draft 3.pptxxxxxxxxxxx
audience feedback draft 3.pptxxxxxxxxxxxaudience feedback draft 3.pptxxxxxxxxxxx
audience feedback draft 3.pptxxxxxxxxxxx
 
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...
Lucknow 💋 (Genuine) Escort Service Lucknow | Service-oriented sexy call girls...
 
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class Service 100% Saf...
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class  Service 100% Saf...Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class  Service 100% Saf...
Hot Modals Call Girls (Delhi) Dwarka9711199171✔️ High Class Service 100% Saf...
 
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdf
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdfSales & Marketing Alignment_ How to Synergize for Success.pptx.pdf
Sales & Marketing Alignment_ How to Synergize for Success.pptx.pdf
 
How To Fix Mercedes Benz Anti-Theft Protection Activation Issue
How To Fix Mercedes Benz Anti-Theft Protection Activation IssueHow To Fix Mercedes Benz Anti-Theft Protection Activation Issue
How To Fix Mercedes Benz Anti-Theft Protection Activation Issue
 
Production documentary.ppt. x
Production documentary.ppt.               xProduction documentary.ppt.               x
Production documentary.ppt. x
 
What Could Cause Your Subaru's Touch Screen To Stop Working
What Could Cause Your Subaru's Touch Screen To Stop WorkingWhat Could Cause Your Subaru's Touch Screen To Stop Working
What Could Cause Your Subaru's Touch Screen To Stop Working
 
John deere 425 445 455 Maitenance Manual
John deere 425 445 455 Maitenance ManualJohn deere 425 445 455 Maitenance Manual
John deere 425 445 455 Maitenance Manual
 
Greenery-Palette Pitch Deck by Slidesgo.pptx
Greenery-Palette Pitch Deck by Slidesgo.pptxGreenery-Palette Pitch Deck by Slidesgo.pptx
Greenery-Palette Pitch Deck by Slidesgo.pptx
 
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂
꧁༒☬ 7042364481 (Call Girl) In Dwarka Delhi Escort Service In Delhi Ncr☬༒꧂
 
Call Girls In Kirti Nagar 📱 9999965857 🤩 Delhi 🫦 HOT AND SEXY VVIP 🍎 SERVICE
Call Girls In Kirti Nagar 📱  9999965857  🤩 Delhi 🫦 HOT AND SEXY VVIP 🍎 SERVICECall Girls In Kirti Nagar 📱  9999965857  🤩 Delhi 🫦 HOT AND SEXY VVIP 🍎 SERVICE
Call Girls In Kirti Nagar 📱 9999965857 🤩 Delhi 🫦 HOT AND SEXY VVIP 🍎 SERVICE
 
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...
Call Girls in Malviya Nagar Delhi 💯 Call Us 🔝9205541914 🔝( Delhi) Escorts Ser...
 
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls Services
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls ServicesBandra Escorts, (*Pooja 09892124323), Bandra Call Girls Services
Bandra Escorts, (*Pooja 09892124323), Bandra Call Girls Services
 
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 person
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 personDelhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 person
Delhi Call Girls Saket 9711199171 ☎✔👌✔ Full night Service for more than 1 person
 
What Causes BMW Chassis Stabilization Malfunction Warning To Appear
What Causes BMW Chassis Stabilization Malfunction Warning To AppearWhat Causes BMW Chassis Stabilization Malfunction Warning To Appear
What Causes BMW Chassis Stabilization Malfunction Warning To Appear
 
John Deere Tractors 6130M 6140M Diagnostic Manual
John Deere Tractors  6130M 6140M Diagnostic ManualJohn Deere Tractors  6130M 6140M Diagnostic Manual
John Deere Tractors 6130M 6140M Diagnostic Manual
 
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sex
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sexDelhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sex
Delhi Call Girls Safdarjung 9711199171 ☎✔👌✔Body to body massage with sex
 
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...
(COD) ̄Young Call Girls In Dwarka , New Delhi꧁❤ 7042364481❤꧂ Escorts Service i...
 

Cummins onan c22 d5 generator set power start 0500 control service repair manual

  • 1. Service Manual English – Original Instructions 1-2010 Generator Set PowerStart 0500 Control C8 D5 C11 D5 C12 D6 C16 D6 C17 D5 C20 D6 C22 D5 C28 D5 A029U889 (Issue 2)
  • 2. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 © Copyright Cummins Power Generation page 3 Table of Contents SECTION TITLE PAGE 1 IMPORTANT SAFETY INSTRUCTIONS 5 2 INTRODUCTION 7 2.1 About this Manual 7 2.2 System Overview 7 2.3 Test Equipment 7 2.4 How to Obtain Service 7 3 CONTROL PANEL OPERATION 8 3.1 General 8 3.2 Alternator Connections 9 3.3 Control Operation 11 3.4 Control Panel 12 3.5 Mode of Operation 14 4 CIRCUIT BOARD 19 4.1 Control Input and Outputs 21 5 TROUBLESHOOTING 24 5.1 Safety Considerations 24 5.2 Troubleshooting Procedure 24 6 Setup and Calibration 34 7 SERVICING THE GENERATOR 39 7.1 Testing the Generator 39 7.2 Generator Baseboard Isolation Procedure 40 7.3 Excitor Stator 41 7.4 Excitor Rectifier Bridge 42 7.5 Main Stator 45 7.6 Generator Disassembly 47 8 WITHDRAWING ROTOR 49 8.1 Generator Reassembly 49
  • 3. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 page 4 © Copyright Cummins Power Generation SECTION TITLE PAGE 9 WIRING DIAGRAMS 53 9.1 General Information 53 9.2 Wiring Diagram 57 9.3 Battery Charger and Coolant Heater 59 9.4 Customer Connections 62
  • 4. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 © Copyright Cummins Power Generation page 5 SECTION 1 – IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure to follow fundamental rules and precautions. The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the operator, service personnel, or the equipment. This symbol warns of immediate hazards which will result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. FUEL AND FUMES ARE FLAMMABLE Fire, explosion, and personal injury or death can result from improper practices. • DO NOT fill fuel tanks while engine is running, unless tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard. • DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the generator set or fuel tank. • Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel • Be sure all fuel supplies have a positive shutoff valve. • Be sure battery area has been well-ventilated prior to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc. EXHAUST GASES ARE DEADLY • Provide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are secured and not warped. Do not use exhaust gases to heat a compartment. • Be sure the unit is well ventilated. • Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm. MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH • Keep your hands, clothing, and jewelry away from moving parts. • Before starting work on the generator set, disconnect battery charger from its AC source, then disconnect starting batteries, negative (–) cable first. This will prevent accidental starting. • Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc. • Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equipment. Loose clothing and jewelry can become caught in moving parts. • If adjustment must be made while the unit is running, use extreme caution around hot manifolds, moving parts, etc. DO NOT OPERATE INFLAMMABLE AND EXPLOSIVE ENVIRONMENTS. Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire, explosion, severe personal injury and death. Do not operate a genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the genset safely. Contact your authorized Cummins Power Generation distributor for more information. DANGER WARNING CAUTION
  • 5. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 page 6 © Copyright Cummins Power Generation ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH • Remove electric power before removing protective shields or touching electrical equipment. Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical contacts and cause shock or burning. • Use extreme caution when working on electrical components. High voltages can cause injury or death. DO NOT tamper with interlocks. • Follow all applicable state and local electrical codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure. • DO NOT CONNECT GENERATOR SET DI- RECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for electrocution or property damage. Connect only through an approved isolation switch or an approved paralleling device. GENERAL SAFETY PRECAUTIONS • Coolants sunder pressure have a higher boiling point than water. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down before removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has been relieved. • Used engine oils have been identified by some state or federal agencies as causing cancer or reproductive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or con-tact used oil. • Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10). • Make sure that rags are not left on or near the generator set. • Make sure generator set is mounted in a manner to prevent combustible materials from accumulating under or near the unit. • Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause over-heating and engine damage which present a potential fire hazard. • Keep the generator set and the surrounding area clean and free from obstructions. Remove any debris from the set and keep the floor clean and dry. • Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment unsafe. • Substances in exhaust gases have been identified by some state or federal agencies as causing cancer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases. • Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explosion could result. • Wear hearing protection when going near an operating generator set. • To prevent serious burns, avoid contact with hot metal parts such as radiator system, turbo charger system and exhaust system. KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
  • 6. Power Start 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 © Copyright Cummins Power Generation page 7 SECTION 2 – INTRODUCTION 2.1 ABOUT THIS MANUAL This manual provides troubleshooting and repair information regarding the PowerCommand® 1302Control (PCC) and generators for the generator sets (gensets) listed on the front cover. Engine service instructions are in the applicable engine service manual. Operating and maintenance instructions are in the applicable Operator’s Manual. This manual does not have instructions for servicing printed circuit board assemblies. After determining that a printed circuit board assembly is faulty, replace it, do not repair it. Attempts to repair a printed circuit board can lead to costly damage to the equipment. This manual contains basic (generic) wiring diagrams and schematics that are included to help in troubleshooting. Service personnel must use the actual wiring diagram and schematic shipped with each unit. The wiring diagrams and schematics that are maintained with the unit should be updated when modifications are made to the unit. Read Important Safety Instructions and carefully observe all instructions and precautions in this manual. 2.2 SYSTEM OVERVIEW The PCC is a microprocessor-based control for Cummins Power Generation generator sets. All generator set control functions are contained on one circuit board (Base board). The Base board provides fuel control, main alternator voltage output regulation and complete generator set control and monitoring. The operating software provides control of the generator set and its performance characteristics, and displays performance information on a digital display panel. It accepts menu-driven control and set-up input from the push button switches on the front panel. 2.3 TEST EQUIPMENT To perform the test procedures in this manual, the following test equipment must be available True RMS meter for accurate measurement of small AC and DC voltages. Fluke models 87 or 8060A are good choices. Grounding wrist strap to prevent circuit board damage due to electrostatic discharge (ESD). Battery Hydrometer. Jumper Leads. Tachometer or Frequency Meter. Wheatstone Bridge or Digital Ohmmeter. Variac. Load Test Panel. Megger or Insulation Resistance Meter. InPower™ Service Tool (PC based genset service tool). PCC1302 Interface Kit (Used with InPower Service Tool) 2.4 HOW TO OBTAIN SERVICE Always give the complete Model, Specification and Serial number of the generator set as shown on the nameplate when seeking additional service information or replacement parts. The nameplate is located on the front of the control panel. Incorrect service or replacement of parts can result in severe personal injury or death, and/or equipment damage. Service personnel must be trained and experienced to perform electrical and mechanical service. Read and follow Important Safety Instructions on pages iii and iv. WARNING
  • 7. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 page 8 © Copyright Cummins Power Generation SECTION 3 – OPERATOR PANEL OPERATION FIGURE 3-1. PS0500 - CONTROLLER 3.1 GENERAL The PS0500 is a microprocessor-based controller that has these abilities. • Start and stop the genset. • Monitor the status of the genset. • Warn the operator when unsafe conditions are occurring • Shut down the genset to prevent damage • Adjust settings that affect genset behavior. • Provide a way for other devices to remotely start / Stop the genset This is the Operator Manual for the PowerStart 0500 control. It is not the Operator Manual for the generator set (“genset”) or any accessories. The third digit is flashed, followed by a half-second pause, and then the fourth digit is flashed, followed by a two-second pause. The PowerStart 0500 is suitable for non-paralleling generator sets (“gensets”) in standby or Prime power applications. Note: Other devices that can remotely start / Stop the genset might be as simple as a switch or a push button or as sophisticated as other controllers or computers. This manual introduces the ways the Control can interact with other devices, but this manual cannot identify all of the devices that might be used in every application.
  • 8. Power Start 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 © Copyright Cummins Power Generation page 9 3.2 ALTERNATOR CONNECTIONS This section introduces the connections between the PS0500 and the alternator. Main Alternator Output The PS0500 is connected to the main alternator output to measure genset voltage and genset frequency. The PS0500 is also connected to current transformers (CTs) which reduce the genset current by a known ratio for measuring main alternator output current. Engine Connections This section introduces the connections between the PS0500 and the engine. Battery Connections The battery provides power for the PS0500 and the PS0500 monitors the battery voltage. Starter The PS0500 is connected to the starter control relay in order to control the starter. See Sequences of Operation for more information about the behavior of this output. Fuel Shutoff (FSO) Relay The PS0500 is connected to the fuel shutoff control (FSO) in order to control the fuel shutoff solenoid in the fuel supply line. See Sequences of Operation for more information about the behavior of this output. Genset Connections This section introduces the connections betweent he PS0500 and other parts of the genset. Some of these connections are flexible and might be made to many types of devices. Customer Input The PS0500 has one customer input that can be configured to invoke a shutdown or Warning response Battery Charger Failed Switch The PS0500’s Customer Input may be connected to a battery charger’s status output (discrete) to monitor the battery charger operation. Emergency Stop Buttons The PS0500 may be connected to a push button that shuts the genset down immediately when pressed. FIGURE 3-2. EMERGENCY STOP BUTTON (EXAMPLE) Customer Output The PS0500 has one customer output that can be configured to become active when either a shutdown or Warning fault occurs.
  • 9. PowerStart 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 page 10 © Copyright Cummins Power Generation PC-based Service Tools The PS0500 or the Operator Panel may be connected to a PC-based service tool, such as InPower. Note: See the PC-based service tool documentation for more information. The PC-based service tool harness (Figure 3-3) is used to connect the PS0500 to a PC-based service tool. FIGURE 3-3. PC-BASED SERVICE TOOL HARNESS Ready to Load The PS0500 may notify a device when event 1465 (Ready to Load) is active. Typically, the device is a programmable logic controller Remote Start The PS0500 may be connected to a device that can generate a remote start signal. Typically, the device is a transfer switch. Certifications The PS0500 meets or exceeds the requirements of the following codes and standards. • UL 508 • CSA • C282 compliant • 22.2 compliant • NFPA 99 compliant • MS 202C, Method 101 compliant • IEEE C62.41 compliant • IEEE C37.90 compliant • BS ISO 8528−4:2005 • BS EN 50081−1:1992 • BS EN 61000−6−2:2001 • BS EN 61000−6−3:2001 • BS EN 61000−6−4:2001CE Marking: The control system is suitable for use on generator sets to be CE − marked. • BS EN 61000−6−4:2001CE Marking: The control system is suitable for use on generator sets to be CE − marked.
  • 10. Power Start 0500 Publication A029U889 Models C8 D5 – C28 D5 Issue 2 - 1-2010 © Copyright Cummins Power Generation page 11 3.3 CONTROL OPERATION In this section, italics are used to identify a specific parameter by name. Safety Considerations AC power is present when the genset is running. Do not open the generator output box while the genset is running. Contacting high-voltage components can cause electrocution, resulting in severe personal injury or death. Do not open the generator output box while the set is running. Read and observe all WARNINGS and CAUTIONS in your genset manuals. The PS0500 cabinet must be opened only by technically qualified personnel. The PS0500 cabinet must be opened only by qualified personnel. High-level voltages (up to 600 VAC) are present in the PS0500 cabinet. These voltages can cause electrical shock, resulting in personal injury or death. Even with the power removed, improper handling of components can cause electrostatic discharge and damage to circuit components. Read Safety Precautions, and carefully observe all of the instructions and precautions in this manual. Starting and Stopping the Genset The buttons related to changing mode of operation are highlighted in figure 3.4 and described in Table 3.1 FIGURE 3-4. CONTROL PANEL BUTTONS TABLE 3-1 CONTROL PANEL BUTTONS BUTTON(S) DESCRIPTION Manual Puts the control in Manual Mode to Start the genset Manually. You have to push the Start button in less than ten seconds after you push the Manual button. Auto Puts the control in Auto Mode. The genset starts and stops when it is told by other devices (such as a transfer switch) Stop Stops the genset When the genset starts and stops, it follows a series of steps, called a sequence of operation that is intended to maximize the life of the genset. The genset might not start or stop immediately. The genset might not start or stop immediately. Do not attempt to service the genset if it does not appear to respond immediately. Accidental starting of the genset during troubleshooting can cause severe personal injury or death. WARNING WARNING CAUTION WARNING