To slow or prevent the spread of fire, building
codes require fire-resistant or fire-rated assem-
blies in certain locations, occupancies, and
types of buildings. When fire-rated walls and/
or floor/ceiling assemblies are required, a fire
barrier over the walls is typically necessary
to prevent flames from escaping the confine-
ment provided by the wall or ceiling assembly.
The barrier may be in the form of continuous
rim board on top of the wall and parallel with
the floor joists or as continuous rim board
along the top of the wall and perpendicular to
the joists. A fire barrier can also be made by
inserting individual sections of snugly fit rated
material over the wall and between the floor
joists and carefully sealed against fire passage.
This last method is more labor intensive, particularly when wood I-joists or trusses are used to support the floor.
Because the flammability and ignitability of the adhesive used in the rim boards is less than that of the wood, the
adhesive does not melt prior to ignition. The wood itself determines the flammability of the rim boards.
The assemblies diagrammed in this publication are based on char rates of APA Rim Boards as determined by the United
States Forest Service, Forest Products Laboratory in Madison, Wisconsin.(a)
The Rim Boards in this brochure were
subjected to fire tests that met the requirements of ASTM E119 and CAN/ULC S101.
FIRE-RESISTANT RIM BOARD ASSEMBLIES
The rim board assemblies on the following pages will achieve the fire resistances shown.
(a) White, R. H. 2003. Fire Resistance of Engineered Wood Rim Board Products. Research Paper FPL-RP-610. USDA Forest Service, Forest
Products Laboratory. Madison, WI.
Rim Board® is a registered trademark of APA – The Engineered Wood Association.
APARimBoard®
in
Fire-RatedAssemblies
A gypsum wall board provides fire resistance for rim board assembly
(see “RB1,” next page.)
APA Performance-Rated Rim Boards are manufactured and tested
under the requirements of ANSI/APA PRR 410 or APA PRR 401
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  2
Data File: APA Rim Board in Fire-Rated Assemblies
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB1
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101
RB1
RB2
Load
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Load Load
Load
Gypsum boards (B)
Rim board (A)
Ceiling and wall ratings
as required by Building OfficialsSame as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum boards (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
Jan. 4, 2013
Fire_Assem
Same a
right-ha
side dra
Same a
right-ha
side dra
Same
right-h
side dr
Same
right-h
side dr
END WALL CONFIGURATION BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane
Req. for 1-hr
Ceiling Membrane
Req. for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4
1-1/8
Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4
1-1/4
Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4
1-1/2
Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x6
1-3/4
Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x6
(2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x6
1)	 Rim assembly for fire from inside of structure.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral loads.
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  3
Data File: APA Rim Board in Fire-Rated Assemblies
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB2
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101RB2
Load
Stud (D)
Rated wall assembly
Stud (E)
Rated wall assembly
Load
Gypsum boards (B)
Rim board (A)
Ceiling and wall ratings
as required by Building OfficialsSame as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum boards (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
Jan
Fi
SINGLE WALL CONFIGURATION BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane
Req.for 1-hr
Ceiling Membrane
Req.for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x6
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6
(2) 5/8” Type X No Ceiling Required 1/2" Type X 2x8 2x6
1-1/8
Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6
1-1/4
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6
1-1/2
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x8
1-3/4
Unprotected 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x8 2x8
1)	 Rim assembly for fire from either side of wall.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 Toenailing from the I-joist flange to the rim is permitted. When 2-layer (or more) gypsum wallboards are used, I-joist end nails shall be 16d
box (0.135 inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral loads.
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  4
Data File: APA Rim Board in Fire-Rated Assemblies
RB3
RB4
ficials
Load Load
Load Loadngs
ng Officials
C)
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB3
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101
DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane
Req. for 1-hr
Ceiling Membrane
Req.for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4
1-1/8
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4
1-1/4
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4
1-1/2
Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1-3/4
Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x6
(1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6
(1) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1)	 Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim
board fails.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box
(0.135 inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral loads.
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  5
Data File: APA Rim Board in Fire-Rated Assemblies
RB4
Load Loadgs
ng Officials
C)
Rated wall assembly Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
side drawing
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB4
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101
DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane
Req. for 1-hr
Ceiling Membrane
Req. for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/8
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4
1-1/4
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4
1-1/2
Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(1) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1-3/4
Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1)	 Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim
board fails.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box
(0.135 inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral loads.
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  6
Data File: APA Rim Board in Fire-Rated Assemblies
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB5
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101
RB5
RB6
LoadLoad LoadLoad
LoadLoad LoadLoad
cials
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
ficials
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane Req.
for 1-hr
Ceiling Membrane Req.
for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/8
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/4
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/2
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x6
1-3/4
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1)	 Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire
exposed rim board fails.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 Toenailing from the I-joist flange to the rim is permitted. When 2 layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135
inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral loads.
Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  7
Data File: APA Rim Board in Fire-Rated Assemblies
FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB6
This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101
RB6
LoadLoad LoadLoad
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (D)
Rated wall assembly
Gypsum board (B)
Rim board (A)
Ceiling and wall ratings
as required by Building Officials
Ceiling membrane (C)
Stud (E)
Rated wall assembly
Jan. 4, 2013
Fire_Assembly_Bosie_Rim_Board_2013_v4.eps
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
Same as
right-hand
side drawing
DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY
Rim Board
Thickness, in.
Rim Board
Protection
Ceiling Membrane
Req. for 1-hr
Ceiling Membrane
Req. for 2-hr
Stud
Size
Stud
Size
A B C C D E
1
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/8
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/4
Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4
1-1/2
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1-3/4
Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4
(1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4
(1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4
(2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6
(2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6
1)	 Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire
exposed rim board fails.
2)	 Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated.
3)	 Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c.
4)	 Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c.
5)	 Provide min. 1-3/4-inch bearing for I-joist.
6)	 Use only fire-rated gypsum wallboard. Type C may be substituted for Type X.
7)	 Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted.
8)	 Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box
(0.135 inch x 3-1/2 inches) nails.
9)	 Rim board needs to be sized for vertical and lateral load.
APA Rim Board® in Fire-Rated Assemblies
We have field representatives in many major U.S. cities and in Canada
who can help answer questions involving APA trademarked products.
For additional assistance in specifying engineered wood products, contact us:
APA HEADQUARTERS
7011 So. 19th St. ■
Tacoma, Washington 98466
(253) 565-6600 ■
Fax: (253) 565-7265
PRODUCT SUPPORT HELP DESK
(253) 620-7400 ■
help@apawood.org
DISCLAIMER
The information contained herein is based on APA – The Engineered Wood Association’s
­continuing programs of laboratory testing, product research, and comprehensive field experi-
ence. Neither APA, nor its members make any warranty, expressed or implied, or assume any
legal liability or responsibility for the use, application of, and/or reference to opinions, findings,
conclusions, or recommendations included in this publication. Consult your local jurisdiction or
design professional to assure compliance with code, construction, and performance require-
ments. Because APA has no control over quality of workmanship or the conditions under which
engineered wood products are used, it cannot accept responsibility of product performance or
designs as actually constructed.
Form No. D350B/Revised February 2015

More Related Content

Similar to APA Rim in Fire Rated Assemblies D350

Detailing : Interior Wall Assemblies
Detailing : Interior Wall AssembliesDetailing : Interior Wall Assemblies
Detailing : Interior Wall Assemblies
Todd Wyatt
 
portfolio june 24 finished portfolio
portfolio june 24 finished portfolioportfolio june 24 finished portfolio
portfolio june 24 finished portfolio
Andrew Johnson
 
Supplier's rates updated
Supplier's rates updatedSupplier's rates updated
Supplier's rates updated
Arthur Wilson
 
Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005
Mike Coughlin
 
Comparative performance of residential walls
Comparative performance of residential wallsComparative performance of residential walls
Comparative performance of residential walls
Robert1239
 

Similar to APA Rim in Fire Rated Assemblies D350 (20)

Reboard Presentation 11 4 2009
Reboard Presentation 11 4 2009Reboard Presentation 11 4 2009
Reboard Presentation 11 4 2009
 
Detailing : Interior Wall Assemblies
Detailing : Interior Wall AssembliesDetailing : Interior Wall Assemblies
Detailing : Interior Wall Assemblies
 
Reboard S G I A V1
Reboard  S G I A V1Reboard  S G I A V1
Reboard S G I A V1
 
Inflateaspace Brochure
Inflateaspace BrochureInflateaspace Brochure
Inflateaspace Brochure
 
Fasteners3
Fasteners3Fasteners3
Fasteners3
 
Gypsum Board
Gypsum BoardGypsum Board
Gypsum Board
 
AL-33D
AL-33DAL-33D
AL-33D
 
BlackWood Gate
BlackWood GateBlackWood Gate
BlackWood Gate
 
Types of Roofing and Roofing Materials
Types of Roofing and Roofing MaterialsTypes of Roofing and Roofing Materials
Types of Roofing and Roofing Materials
 
Establishing Intumescent Paint Thickness
Establishing Intumescent Paint ThicknessEstablishing Intumescent Paint Thickness
Establishing Intumescent Paint Thickness
 
portfolio june 24 finished portfolio
portfolio june 24 finished portfolioportfolio june 24 finished portfolio
portfolio june 24 finished portfolio
 
Versaloc - very easy, very quick
Versaloc - very easy, very quickVersaloc - very easy, very quick
Versaloc - very easy, very quick
 
Versaloc
VersalocVersaloc
Versaloc
 
Aac
AacAac
Aac
 
Supplier's rates updated
Supplier's rates updatedSupplier's rates updated
Supplier's rates updated
 
Cement Bonded Particle Board Manufacturer in India -Bison Panel Product Guide...
Cement Bonded Particle Board Manufacturer in India -Bison Panel Product Guide...Cement Bonded Particle Board Manufacturer in India -Bison Panel Product Guide...
Cement Bonded Particle Board Manufacturer in India -Bison Panel Product Guide...
 
Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005
 
DecoRidge Hip and Ridge Shingles
DecoRidge Hip and Ridge ShinglesDecoRidge Hip and Ridge Shingles
DecoRidge Hip and Ridge Shingles
 
Structural glazing
Structural glazingStructural glazing
Structural glazing
 
Comparative performance of residential walls
Comparative performance of residential wallsComparative performance of residential walls
Comparative performance of residential walls
 

APA Rim in Fire Rated Assemblies D350

  • 1. D A T A F I L E To slow or prevent the spread of fire, building codes require fire-resistant or fire-rated assem- blies in certain locations, occupancies, and types of buildings. When fire-rated walls and/ or floor/ceiling assemblies are required, a fire barrier over the walls is typically necessary to prevent flames from escaping the confine- ment provided by the wall or ceiling assembly. The barrier may be in the form of continuous rim board on top of the wall and parallel with the floor joists or as continuous rim board along the top of the wall and perpendicular to the joists. A fire barrier can also be made by inserting individual sections of snugly fit rated material over the wall and between the floor joists and carefully sealed against fire passage. This last method is more labor intensive, particularly when wood I-joists or trusses are used to support the floor. Because the flammability and ignitability of the adhesive used in the rim boards is less than that of the wood, the adhesive does not melt prior to ignition. The wood itself determines the flammability of the rim boards. The assemblies diagrammed in this publication are based on char rates of APA Rim Boards as determined by the United States Forest Service, Forest Products Laboratory in Madison, Wisconsin.(a) The Rim Boards in this brochure were subjected to fire tests that met the requirements of ASTM E119 and CAN/ULC S101. FIRE-RESISTANT RIM BOARD ASSEMBLIES The rim board assemblies on the following pages will achieve the fire resistances shown. (a) White, R. H. 2003. Fire Resistance of Engineered Wood Rim Board Products. Research Paper FPL-RP-610. USDA Forest Service, Forest Products Laboratory. Madison, WI. Rim Board® is a registered trademark of APA – The Engineered Wood Association. APARimBoard® in Fire-RatedAssemblies A gypsum wall board provides fire resistance for rim board assembly (see “RB1,” next page.) APA Performance-Rated Rim Boards are manufactured and tested under the requirements of ANSI/APA PRR 410 or APA PRR 401
  • 2. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  2 Data File: APA Rim Board in Fire-Rated Assemblies FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB1 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101 RB1 RB2 Load Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Load Load Load Gypsum boards (B) Rim board (A) Ceiling and wall ratings as required by Building OfficialsSame as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum boards (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps Jan. 4, 2013 Fire_Assem Same a right-ha side dra Same a right-ha side dra Same right-h side dr Same right-h side dr END WALL CONFIGURATION BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req. for 1-hr Ceiling Membrane Req. for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4 1-1/8 Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4 1-1/4 Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4 1-1/2 Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x6 1-3/4 Unprotected 1-hour Fire-rated Assembly 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x6 (2) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x6 1) Rim assembly for fire from inside of structure. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.
  • 3. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  3 Data File: APA Rim Board in Fire-Rated Assemblies FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB2 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101RB2 Load Stud (D) Rated wall assembly Stud (E) Rated wall assembly Load Gypsum boards (B) Rim board (A) Ceiling and wall ratings as required by Building OfficialsSame as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum boards (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps Jan Fi SINGLE WALL CONFIGURATION BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req.for 1-hr Ceiling Membrane Req.for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x6 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6 (2) 5/8” Type X No Ceiling Required 1/2" Type X 2x8 2x6 1-1/8 Unprotected 45-min Fire-rated Assembly 2-hour Fire-rated Assembly 2x6 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x8 2x6 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6 1-1/4 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x6 1-1/2 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x6 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x8 2x8 1-3/4 Unprotected 5/8" Type X 90-min Fire-rated Assembly 2x6 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x8 2x6 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x8 2x6 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x8 2x6 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x8 2x8 1) Rim assembly for fire from either side of wall. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer (or more) gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.
  • 4. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  4 Data File: APA Rim Board in Fire-Rated Assemblies RB3 RB4 ficials Load Load Load Loadngs ng Officials C) Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB3 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101 DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req. for 1-hr Ceiling Membrane Req.for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4 1-1/8 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4 1-1/4 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 45-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 5/8" Type X 2x4 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4 1-1/2 Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1-3/4 Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x6 (1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6 (1) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1) Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim board fails. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.
  • 5. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  5 Data File: APA Rim Board in Fire-Rated Assemblies RB4 Load Loadgs ng Officials C) Rated wall assembly Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing side drawing FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB4 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101 DOUBLE WALL CONFIGURATION WITH LOAD TRANSFER BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req. for 1-hr Ceiling Membrane Req. for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/8 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4 1-1/4 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x4 1-1/2 Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (1) 5/8" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1-3/4 Unprotected No Ceiling Required 1-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (1) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1) Rim assembly for fire from either side of wall. “With load transfer” assumes load transfers to the adjacent rim board if the fire exposed rim board fails. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.
  • 6. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  6 Data File: APA Rim Board in Fire-Rated Assemblies FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB5 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101 RB5 RB6 LoadLoad LoadLoad LoadLoad LoadLoad cials Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly ficials Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req. for 1-hr Ceiling Membrane Req. for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/8 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/4 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/2 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x6 1-3/4 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x6 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1) Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire exposed rim board fails. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2 layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral loads.
  • 7. Form No. D350B  ■  © 2015 APA – The Engineered Wood Association  ■ www.apawood.org  7 Data File: APA Rim Board in Fire-Rated Assemblies FIRE RESISTANCE R ATED RIM BOARD ASSEMBLY RB6 This fire resistance design is listed in accordance with ASTM E119 and CAN/ULC S101 RB6 LoadLoad LoadLoad Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (D) Rated wall assembly Gypsum board (B) Rim board (A) Ceiling and wall ratings as required by Building Officials Ceiling membrane (C) Stud (E) Rated wall assembly Jan. 4, 2013 Fire_Assembly_Bosie_Rim_Board_2013_v4.eps Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing Same as right-hand side drawing DOUBLE WALL CONFIGURATION WITH NO LOAD TRANSFER BASE ASSEMBLY Rim Board Thickness, in. Rim Board Protection Ceiling Membrane Req. for 1-hr Ceiling Membrane Req. for 2-hr Stud Size Stud Size A B C C D E 1 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 5/8" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/8 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/4 Unprotected 5/8" Type X 2-hour Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required 1/2" Type X 2x6 2x4 1-1/2 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X 1/2" Type X 90-min Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required 1/2" Type X 2x6 2x4 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1-3/4 Unprotected 1/2" Type X 90-min Fire-rated Assembly 2x4 2x4 (1) 1/2" Type X No Ceiling Required 1-hour Fire-rated Assembly 2x6 2x4 (1) 5/8" Type X No Ceiling Required 45-min Fire-rated Assembly 2x6 2x4 (2) 1/2" Type X No Ceiling Required No Ceiling Required 2x6 2x6 (2) 5/8" Type X No Ceiling Required No Ceiling Required 2x6 2x6 1) Rim assembly for fire from either side of wall. “With no load transfer” assumes no load transfers to the adjacent rim board if the fire exposed rim board fails. 2) Gypsum wallboard shown on the ceiling is to protect the rim board only. It does not necessarily cause the floor assembly to be rated. 3) Attach 1-layer Type X (1/2 or 5/8-inch) gypsum wallboard to rim board with 1-1/2-inch Type W drywall screws spaced 12 inches o.c. 4) Attach 2-layer Type X (1/2 or 5/8-inch) gypsum wallboards to rim board with 2-inch Type W drywall screws spaced 12 inches o.c. 5) Provide min. 1-3/4-inch bearing for I-joist. 6) Use only fire-rated gypsum wallboard. Type C may be substituted for Type X. 7) Rim board and gypsum wallboard thicknesses are shown as minimums. Thicker rim board and gypsum wallboard may be substituted. 8) Toenailing from the I-joist flange to the rim is permitted. When 2-layer gypsum wallboards are used, I-joist end nails shall be 16d box (0.135 inch x 3-1/2 inches) nails. 9) Rim board needs to be sized for vertical and lateral load.
  • 8. APA Rim Board® in Fire-Rated Assemblies We have field representatives in many major U.S. cities and in Canada who can help answer questions involving APA trademarked products. For additional assistance in specifying engineered wood products, contact us: APA HEADQUARTERS 7011 So. 19th St. ■ Tacoma, Washington 98466 (253) 565-6600 ■ Fax: (253) 565-7265 PRODUCT SUPPORT HELP DESK (253) 620-7400 ■ help@apawood.org DISCLAIMER The information contained herein is based on APA – The Engineered Wood Association’s ­continuing programs of laboratory testing, product research, and comprehensive field experi- ence. Neither APA, nor its members make any warranty, expressed or implied, or assume any legal liability or responsibility for the use, application of, and/or reference to opinions, findings, conclusions, or recommendations included in this publication. Consult your local jurisdiction or design professional to assure compliance with code, construction, and performance require- ments. Because APA has no control over quality of workmanship or the conditions under which engineered wood products are used, it cannot accept responsibility of product performance or designs as actually constructed. Form No. D350B/Revised February 2015