1. <br /> Corrente de curto-circuito máxima a jusante de um transformador MT/BT Os valores indicados no quadro abaixo correspondem a um cc trifásico nos bornes de BT <br /> de um transfo MT/BT ligado a uma rede cuja potência de cc é de 500 MVA<br /> <br />POTÊNCIA DO TRANSFORMADOR EM kVA1625405063801001251602002503154005006308001000125016002000230VIn (A) 40621001261572002503134005006257891001250157520002500312540005000Icc (A)1000156024903110392049706210775099001235015400193402450031200382003835040350------Ucc (%)4444444444444445,565,56--Perdas cobre (kW)700--1100----1750--235028503250390048105950695012000139001750021300--400VIn (A)233658729111514518023229036045658072091011551445180523002890Icc (A)580900145018002270287035904480572071408900112001415017650221002480027800314003660039100Ucc (%)4444444444444444,555,567Perdas cobre (kW)700--1100----1750--23502850325039004600550065001020012100150001810022500<br />ESCOLHA DOS DISJUNTORES DE ENTRADA E DE SAÍDA EM FUNÇÃO DO NÚMERO <br />E DA POTÊNCIA DOS TRANSFORMADORES DE ALIMENTAÇÃO<br />A escolha do disjuntor de protecção de um circuito depende principalmente de dois critérios:<br />A corrente nominal da fonte ou de utilização é que determina o calibre do aparelho.<br />A corrente de curto-circuito máxima no ponto considerado é que determina o <br /> poder de corte mínimo que o aparelho deve ter<br />