80 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Single-Pole SPD
SLP40-XXX/1(S)
Technical Data
SLP40-XXX/1(S) 75 150 275 320 385 440
IEC Electrical
Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V
Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V
Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA
230 V
230 V
275 V
20 kA
40 kA
120 V
150 V
60 V
75 V
Class II • Type 2 •Type 1CA
Location of Use: Sub-Distribution Boards
Network Systems: TN-S, TN-C, TT (only L-N)
Mode of Protection: L-PE, N-PE (only TN-S), L-PEN, L-N
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V
Response Time tA < 25ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA
TOV Withstand 5s UT 90V 180V 335V 580V
TOV 120min UT 115V 230V 440V
mode Withstand Safe Fail Safe Fail Safe Fail Safe Fail
Number of Ports 1
765V
335V
440V
335V
440V
400 V
125 A gL / gG
Withstand
Mechanical & Environmental
Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity RH 5%...95%
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2 (Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC) Optional
RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Order Information
Order Code 75 150 275 320 385 440
SLP40-XXX/1 4007511
(with remote contacts)
Yes
SLP40-XXX/1S
4015011 4027511 4032011 4038511 4044011
4007512 4015012 4027512 4032012 4038512 4044012
SLP40-XXX/0 4007501 4015001 4027501 4032001 4038501 4044001
( )
spare modules
For further information and full technical data, visit: www.lsp-international.com LSP | 81
12
18
90
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/1(S) 75 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL) [270 × 230 × 330 mm]
Minimum Order Quantity 72 Units
SLP40-XXX/1(S)
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Internal Configuration
Plug Internal Configuration SLP40-XXX/0
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/0 75 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
S
Line
Neutral
PE
[270 × 230 × 330 mm]
18
NO COM NC
L/N
N/PE
L/N
N/PE
9
50
67
46
46
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S, TN-C, TT (Single-phase, 1+0)
F1
PE
L L'
L
PE
F2
82 Low wer Systems Series 2019
| LSP Voltage Po
SLP40-XXX/2(S)
Technical Data
SLP40-XXX/2(S) 75 150 275 320 385 440
IEC Electrical
Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V
Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V
Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA
230 V
230 V
275 V
20 kA
40 kA
120 V
150 V
60 V
75 V
Class II • Type 2 •Type 1CA
Location of Use: Sub-Distribution Boards
Network Systems: TN-S
Mode of Protection: L-PE, N-PE
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V
Response Time tA < 25ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA
TOV Withstand 5s UT 90V 180V 335V 580V
TOV 120min UT 115V 230V 440V
mode Withstand Safe Fail Safe Fail Safe Fail Safe Fail
Number of Ports 1
765V
335V
440V
335V
440V
400 V
125 A gL / gG
Withstand
Pluggable Multi-Pole SPD
Mechanical & Environmental
Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity RH 5%...95%
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2 (Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC) Optional
RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Order Information
Order Code 75 150 275 320 385 440
SLP40-XXX/2 4007521
(with remote contacts)
Yes
SLP40-XXX/2S
4015021 4027521 4032021 4038521 4044021
4007522 4015022 4027522 4032022 4038522 4044022
SLP40-XXX/0 4007501 4015001 4027501 4032001 4038501 4044001
( )
spare modules
For further information and full technical data, visit: www.lsp-international.com LSP | 83
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/2(S) 75 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL) [270 × 230 × 330 mm]
Minimum Order Quantity 42 Units
SLP40-XXX/2(S)
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Internal Configuration
Plug Internal Configuration SLP40-XXX/0
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/0 75 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
S
Line
Neutral
PE
[270 × 230 × 330 mm]
18 46
NO
COM
NC
L N
PE
L N
PE
12
36
90
9
50
67
46
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S (Single-phase, 2+0)
F1
PE
L
N
L'
N'
PE
L N
F2
84 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Multi-Pole SPD
SLP40-XXX/3(S)
Technical Data
SLP40-XXX/3(S) 275 320 385 440
IEC Electrical
Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V
Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V
Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA
230 V
230 V
275 V
120 V
150 V
Class II • Type 2 •Type 1CA
Location of Use: Sub-Distribution Boards
Network Systems: TN-C
Mode of Protection: L-PEN
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V
Response Time tA < 25ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA
TOV Withstand 5s UT 180V 335V 580V
TOV 120min UT 230V 440V
mode Safe Fail Safe Fail Safe Fail Safe Fail
Number of Ports 1
765V
335V
440V
335V
440V
125 A gL / gG
Withstand
150
Mechanical & Environmental
Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity RH 5%...95%
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2 (Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC) Optional
RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Order Information
Order Code 150 275 320 385 440
SLP40-XXX/3
(with remote contacts)
Yes
SLP40-XXX/3S
4015031 4027531 4032031 4038531 4044031
4015032 4027532 4032032 4038532 4044032
SLP40-XXX/0 4015001 4027501 4032001 4038501 4044001
( )
spare modules
For further information and full technical data, visit: www.lsp-international.com LSP | 85
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/3(S) 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL) [270 × 230 × 330 mm]
Minimum Order Quantity 30 Units
SLP40-XXX/3(S)
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Internal Configuration
Plug Internal Configuration SLP40-XXX/0
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/0 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
S
Line
Neutral
PE
[270 × 230 × 330 mm]
18 46
NO
COM
NC
L2
L1 L3
PEN
L2
L1 L3
PEN
9
50
67
46
12
54
90
TÜVRheinland
R
CERTIFIED
RoHS
F1
L1
L2
L3
F2
L2'
L3'
L1 L2 L3
PEN
PEN
L1'
TN-C (Three-phase, 3+0)
Connection Diagram
86 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Multi-Pole SPD
SLP40-XXX/4(S)
Technical Data
SLP40-XXX/4(S) 275 320 385 440
IEC Electrical
Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V
Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V
Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA
230 V
230 V
275 V
120 V
150 V
Class II • Type 2 •Type 1CA
Location of Use: Sub-Distribution Boards
Network Systems: TN-S
Mode of Protection: L-PE, N-PE
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V
Response Time tA < 25ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA
TOV Withstand 5s UT 180V 335V 580V
TOV 120min UT 230V 440V
mode Safe Fail Safe Fail Safe Fail Safe Fail
Number of Ports 1
765V
335V
440V
335V
440V
125 A gL / gG
Withstand
150
Mechanical & Environmental
Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity RH 5%...95%
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2 (Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC) Optional
RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Order Information
Order Code 150 275 320 385 440
SLP40-XXX/4
(with remote contacts)
Yes
SLP40-XXX/4S
4015041 4027541 4032041 4038541 4044041
4015042 4027542 4032042 4038542 4044042
SLP40-XXX/0 4015001 4027501 4032001 4038501 4044001
( )
spare modules
For further information and full technical data, visit: www.lsp-international.com LSP | 87
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/4(S) 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL) [270 × 230 × 330 mm]
Minimum Order Quantity 24 Units
SLP40-XXX/4(S)
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Internal Configuration
Plug Internal Configuration SLP40-XXX/0
Dimensions & Packaging
Dimensions & Packaging
SLP40-XXX/0 150 275 320 385 440
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
S
Line
Neutral
PE
[270 × 230 × 330 mm]
18 46
PE
L3
L1 L2 N
NO
COM
NC
PE
L3
L1 L2 N
9
50
67
46
12
72
90
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S (Three-phase, 4+0)
F1
N
L1 L2 L3
PE
L1'
L2'
L3'
N'
PE'
F2
L1
L2
L3
N
PE
88 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Multi-Pole SPD
Location of Use:
Network Systems: TT, TN-S
Mode of Protection: L-N, N-PE
Technical Data
Nominal AC Voltage (50/60Hz)
Maximum Continuous Operating Voltage
Nominal Discharge Current (8/20 µs) 20kA / 20kA
Maximum Discharge Current (8/20 µs) 40kA / 40kA
SLP40-XXX/1(S)+1
SLP40-XXX/1(S)+1
IEC Electrical
Voltage Protection Level
Follow Current Interrupt Rating 100ARMS
Response Time < 25 ns / < 100 ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) 25kA / 50kA
TOV Withstand 5s
TOV 120min
Withstand Safe Fail Safe Fail
TOV Withstand 200ms 1200V
Number of Ports 1
90V 180V 335V
115V 230V 440V
335V
440V
Class II • Type 2 •Type 1CA
Sub-Distribution Boards
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV and GDT
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
125 A gL / gG
Withstand
Mechanical & Environmental
Operating Temperature Range
Permissible Operating Humidity
Terminal Screw Torque
(L - N) Uc
(N - PE) Uc
(L - N) / (N - PE) In
(L - N) / (N - PE) Imax
(L - N) / (N - PE) Up
(N-PE) Ifi
(L-N)/(N-PE) tA
(L - N) ISCCR
(L - N) UT
(L - N) UT
mode
(N-PE) UT
Ta
RH
Mmax
Conductor Cross Section (max)
Mounting
Degree of Protection
Housing Material
Thermal Protection
Operating State / Fault Indication
Remote Contacts (RC)
RC Switching Capacity
RC Conductor Cross Section (max)
Order Information
Order Code 75 150 275 320
Atmospheric pressure and altitude
-40 ºF to +158 ºF [-40 ºC to +70 ºC]
5%...95%
[
39.9 Ibf·in 4.5Nm]
2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2(Flexible)
35 mm DIN Rail, EN 60715
IP 20 (built-in)
Thermoplastic: Extinguishing Degree UL 94 V-0
Optional
16 AWG (Solid) / 1.5 mm2(Solid)
80k Pa ... 106k Pa / -500 m ... 2000 m
Yes
Green ok / Red defect
AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
SLP40-XXX/1+1
(with remote contacts)
SLP40-XXX/1S+1
SLP40-XXX/0
SLP40-NPE/0
4007513
4007514
4007501
4025501
4015013
4015014
4015001
4025501
4027513
4027514
4027501
4025501
4032013
4032014
4032001
4025501
( )
spare modules
( )
spare modules
75 150 275 320 385 440
230 V
230 V
120 V
60 V
320 V
275 V
150 V
75 V
230 V
385 V
400 V
440 V
255 V
0.4kV / 1.5kV 1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV
Safe Fail
335V
440V
Safe Fail
580V
765V
385
4038513
4038514
4038501
4025501
440
4044013
4044014
4044001
4025501
For further information and full technical data, visit: www.lsp-international.com LSP | 89
Dimensions & Packaging
Internal Configuration
Plug Internal Configuration
Dimensions & Packaging
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Line
Neutral
PE
SLP40-XXX/1(S)+1
Dimensions & Packaging
SLP40-XXX/1(S)+1
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 42 Units
SLP40-NPE/0
Dimensions & Packaging
SLP40-XXX/0
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
SLP40-NPE/0 40
[270 × 230 × 330 mm]
SLP40-XXX/0
[270 × 230 × 330 mm]
18 46
L
PE
N
NO
COM
NC
L
PE
N
S
9
50
67
46
12
36
90
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S,TT (Single-phase, 1+1)
N
L L'
N'
F1
L
F2
PE
PE
N
75 150 275 320 385 440
75 150 275 320 385 440
90 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Multi-Pole SPD
Location of Use:
Network Systems: TT, TN-S
Mode of Protection: L-N, N-PE
Technical Data
Nominal AC Voltage (50/60Hz)
Maximum Continuous Operating Voltage
Nominal Discharge Current (8/20 µs) 20kA / 20kA
Maximum Discharge Current (8/20 µs) 40kA / 40kA
SLP40-XXX/2(S)+1
SLP40-XXX/2(S)+1
IEC Electrical
Voltage Protection Level
Follow Current Interrupt Rating 100ARMS
Response Time < 25 ns / < 100 ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) 25kA / 50kA
TOV Withstand 5s
TOV 120min
Safe Fail Safe Fail
TOV Withstand 200ms 1200V
Number of Ports 1
180V 335V
230V 440V
335V
440V
Class II • Type 2 •Type 1CA
Sub-Distribution Boards
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV and GDT
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
125 A gL / gG
Withstand Safe Fail
580V
765V
255 V
Mechanical & Environmental
Operating Temperature Range -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity 5%...95%
Terminal Screw Torque [
39.9 Ibf·in 4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2(Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication
Remote Contacts (RC) Optional
RC Switching Capacity
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Order Information
Order Code 150 275 320
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Yes
Green ok / Red defect
AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
SLP40-XXX/2+1
(with remote contacts)
SLP40-XXX/2S+1
SLP40-XXX/0
SLP40-NPE/0
4015023
4015024
4015001
4025501
4027523
4027524
4027501
4025501
4032023
4032024
4032001
4025501
385
4038523
4038524
4038501
4025501
( )
spare modules
( )
spare modules
(L - N) Uc
(N - PE) Uc
(L - N) / (N - PE) In
(L - N) / (N - PE) Imax
(L - N) / (N - PE) Up
(N-PE) Ifi
(L-N)/(N-PE) tA
(L - N) ISCCR
(L - N) UT
(L - N) UT
mode
(N-PE) UT
Ta
RH
Mmax
150 275 320 385 440
230 V
230 V
120 V
320 V
275 V
150 V
230 V
385 V
400 V
440 V
Safe Fail
335V
440V
1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV
440
4044023
4044024
4044001
4025501
For further information and full technical data, visit: www.lsp-international.com LSP | 91
Dimensions & Packaging
Internal Configuration
Plug Internal Configuration
Dimensions & Packaging
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Line
Neutral
PE
SLP40-XXX/2(S)+1
Dimensions & Packaging
SLP40-XXX/2(S)+1
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 30 Units
SLP40-NPE/0
Dimensions & Packaging
SLP40-XXX/0
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
SLP40-NPE/0 40
[270 × 230 × 330 mm]
SLP40-XXX/0
[270 × 230 × 330 mm]
18 46
S
NO
COM
NC
L1
N L2
PE
L1
N L2
PE
9
50
67
46
12
54
90
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S, TT (Three-phase, 2+1)
F1
L1
L2
F2
L2'
L1 L2
L1'
PE'
N
N
PE
PE
150 275 320 385 440
150 275 320 385 440
92 Low wer Systems Series 2019
| LSP Voltage Po
Pluggable Multi-Pole SPD
Location of Use:
Network Systems: TT, TN-S
Mode of Protection: L-N, N-PE
SLP40-XXX/3(S)+1
Class II • Type 2 •Type 1CA
Sub-Distribution Boards
Surge Ratings: In = 20kA (8/20µs)
IEC/EN/UL Category: Class II / Type 2 / Type 1CA
Protective Elements: High Energy MOV and GDT
Housing: Pluggable Design
Compliance: IEC 61643-11:2011
EN 61643-11:2012
Order Information
Order Code 150 275 320
SLP40-XXX/3+1
(with remote contacts)
SLP40-XXX/3S+1
SLP40-XXX/0
SLP40-NPE/0
4015033
4015034
4015001
4025501
4027533
4027534
4027501
4025501
4032033
4032034
4032001
4025501
385
4038533
4038534
4038501
4025501
( )
spare modules
( )
spare modules
Technical Data
Nominal AC Voltage (50/60Hz)
Maximum Continuous Operating Voltage
Nominal Discharge Current (8/20 µs) 20kA / 20kA
Maximum Discharge Current (8/20 µs) 40kA / 40kA
SLP40-XXX/3(S)+1
IEC Electrical
Voltage Protection Level
Follow Current Interrupt Rating 100ARMS
Response Time < 25 ns / < 100 ns
Back-Up Fuse (max)
Short-Circuit Current Rating (AC) 25kA / 50kA
TOV Withstand 5s
TOV 120min
Safe Fail Safe Fail
TOV Withstand 200ms 1200V
Number of Ports 1
180V 335V
230V 440V
335V
440V
125 A gL / gG
Withstand Safe Fail
580V
765V
255 V
Mechanical & Environmental
Operating Temperature Range -40 ºF to +158 ºF [-40 ºC to +70 ºC]
Permissible Operating Humidity 5%...95%
Terminal Screw Torque [
39.9 Ibf·in 4.5Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25 mm2(Flexible)
Mounting 35 mm DIN Rail, EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection
Operating State / Fault Indication
Remote Contacts (RC) Optional
RC Switching Capacity
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m
Yes
Green ok / Red defect
AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A
(L - N) Uc
(N - PE) Uc
(L - N) / (N - PE) In
(L - N) / (N - PE) Imax
(L - N) / (N - PE) Up
(N-PE) Ifi
(L-N)/(N-PE) tA
(L - N) ISCCR
(L - N) UT
(L - N) UT
mode
(N-PE) UT
Ta
RH
Mmax
150 275 320 385 440
230 V
230 V
120 V
320 V
275 V
150 V
230 V
385 V
400 V
440 V
Safe Fail
335V
440V
1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV
440
4044033
4044034
4044001
4025501
For further information and full technical data, visit: www.lsp-international.com LSP | 93
Dimensions & Packaging
Internal Configuration
Plug Internal Configuration
Dimensions & Packaging
Legend
L
N
Protective Earth
S Signalling Contacts Optional
Line
Neutral
PE
SLP40-XXX/3(S)+1
Dimensions & Packaging
SLP40-XXX/3(S)+1
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 24 Units
SLP40-NPE/0
Dimensions & Packaging
SLP40-XXX/0
Single Unit DIN 43880 Dimension 1 CTN
Packaging Dimensions (HxWxL)
Minimum Order Quantity 96 Units
SLP40-NPE/0 40
[270 × 230 × 330 mm]
SLP40-XXX/0
[270 × 230 × 330 mm]
18 46
9
50
67
46
12
72
90
S
NO
COM
NC
L1 L2 L3
PE
N L1 L2 L3
PE
N
TÜVRheinland
R
CERTIFIED
RoHS
Connection Diagram
TN-S, TT (Three-phase, 3+1)
F1
L1
L2
L3
N
F2
L1'
L2'
L3'
N'
N L1 L2 L3
PE
PE
150 275 320 385 440
150 275 320 385 440

More Related Content

Similar to T2 AC Surge Protection

SETfuse All Product and Application ENG Version Jun 2 2015
SETfuse All Product and Application ENG Version Jun 2 2015SETfuse All Product and Application ENG Version Jun 2 2015
SETfuse All Product and Application ENG Version Jun 2 2015
Apple Yu
 
Switchtec Din Rail Terminal Brochure
Switchtec Din Rail Terminal BrochureSwitchtec Din Rail Terminal Brochure
Switchtec Din Rail Terminal Brochure
Andy Birdsall
 

Similar to T2 AC Surge Protection (20)

Ls catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vnLs catalog thiet bi dien electric products e 1108_dienhathe.vn
Ls catalog thiet bi dien electric products e 1108_dienhathe.vn
 
SETfuse All Product and Application ENG Version Jun 2 2015
SETfuse All Product and Application ENG Version Jun 2 2015SETfuse All Product and Application ENG Version Jun 2 2015
SETfuse All Product and Application ENG Version Jun 2 2015
 
LS Circuit Breaker Catalogue
LS Circuit Breaker CatalogueLS Circuit Breaker Catalogue
LS Circuit Breaker Catalogue
 
Stp17000 tl den130517w
Stp17000 tl den130517wStp17000 tl den130517w
Stp17000 tl den130517w
 
HAW56x
HAW56xHAW56x
HAW56x
 
RK Engineering ATS (2).pdf
RK Engineering ATS (2).pdfRK Engineering ATS (2).pdf
RK Engineering ATS (2).pdf
 
Original Opto TLP141G TLP141 P141 141G SOP-5 New
Original Opto TLP141G TLP141 P141 141G SOP-5 NewOriginal Opto TLP141G TLP141 P141 141G SOP-5 New
Original Opto TLP141G TLP141 P141 141G SOP-5 New
 
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
 
Molded Case Circuit Breakers BX Series
Molded Case Circuit Breakers BX SeriesMolded Case Circuit Breakers BX Series
Molded Case Circuit Breakers BX Series
 
Abtech ABJB 125 HV Hazardous Area (ATEX & IECEx) Electrical Enclosure Data Sheet
Abtech ABJB 125 HV Hazardous Area (ATEX & IECEx) Electrical Enclosure Data SheetAbtech ABJB 125 HV Hazardous Area (ATEX & IECEx) Electrical Enclosure Data Sheet
Abtech ABJB 125 HV Hazardous Area (ATEX & IECEx) Electrical Enclosure Data Sheet
 
Original Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 NewOriginal Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 New
 
Dc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installationsDc circuit supplementary protectors for photovoltaic installations
Dc circuit supplementary protectors for photovoltaic installations
 
Catalog ACB (Air Circuit Breakers) BT3 sereis
Catalog ACB (Air Circuit Breakers) BT3 sereisCatalog ACB (Air Circuit Breakers) BT3 sereis
Catalog ACB (Air Circuit Breakers) BT3 sereis
 
Air Circuit Breakers BT2 Series
Air Circuit Breakers BT2 SeriesAir Circuit Breakers BT2 Series
Air Circuit Breakers BT2 Series
 
Original Opto TLP421 P421 421 DIP-4 New Toshiba
Original Opto TLP421 P421 421 DIP-4 New ToshibaOriginal Opto TLP421 P421 421 DIP-4 New Toshiba
Original Opto TLP421 P421 421 DIP-4 New Toshiba
 
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
Fuji thiet bi dien-acbbt3fuji-160413041525 dienhathe.org
Fuji thiet bi dien-acbbt3fuji-160413041525 dienhathe.orgFuji thiet bi dien-acbbt3fuji-160413041525 dienhathe.org
Fuji thiet bi dien-acbbt3fuji-160413041525 dienhathe.org
 
Fuji thiet bi dien-acbbt3fuji-160413041525
Fuji thiet bi dien-acbbt3fuji-160413041525Fuji thiet bi dien-acbbt3fuji-160413041525
Fuji thiet bi dien-acbbt3fuji-160413041525
 
Switchtec Din Rail Terminal Brochure
Switchtec Din Rail Terminal BrochureSwitchtec Din Rail Terminal Brochure
Switchtec Din Rail Terminal Brochure
 

Recently uploaded

Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 
Architecting Cloud Native Applications
Architecting Cloud Native ApplicationsArchitecting Cloud Native Applications
Architecting Cloud Native Applications
WSO2
 

Recently uploaded (20)

Corporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptxCorporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptx
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdf
 
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu SubbuApidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
Apidays Singapore 2024 - Modernizing Securities Finance by Madhu Subbu
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
 
A Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source MilvusA Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source Milvus
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Architecting Cloud Native Applications
Architecting Cloud Native ApplicationsArchitecting Cloud Native Applications
Architecting Cloud Native Applications
 
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodPolkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
Navi Mumbai Call Girls 🥰 8617370543 Service Offer VIP Hot Model
Navi Mumbai Call Girls 🥰 8617370543 Service Offer VIP Hot ModelNavi Mumbai Call Girls 🥰 8617370543 Service Offer VIP Hot Model
Navi Mumbai Call Girls 🥰 8617370543 Service Offer VIP Hot Model
 
Emergent Methods: Multi-lingual narrative tracking in the news - real-time ex...
Emergent Methods: Multi-lingual narrative tracking in the news - real-time ex...Emergent Methods: Multi-lingual narrative tracking in the news - real-time ex...
Emergent Methods: Multi-lingual narrative tracking in the news - real-time ex...
 

T2 AC Surge Protection

  • 1. 80 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Single-Pole SPD SLP40-XXX/1(S) Technical Data SLP40-XXX/1(S) 75 150 275 320 385 440 IEC Electrical Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 230 V 230 V 275 V 20 kA 40 kA 120 V 150 V 60 V 75 V Class II • Type 2 •Type 1CA Location of Use: Sub-Distribution Boards Network Systems: TN-S, TN-C, TT (only L-N) Mode of Protection: L-PE, N-PE (only TN-S), L-PEN, L-N Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V Response Time tA < 25ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA TOV Withstand 5s UT 90V 180V 335V 580V TOV 120min UT 115V 230V 440V mode Withstand Safe Fail Safe Fail Safe Fail Safe Fail Number of Ports 1 765V 335V 440V 335V 440V 400 V 125 A gL / gG Withstand Mechanical & Environmental Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity RH 5%...95% Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2 (Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Green ok / Red defect Remote Contacts (RC) Optional RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Order Information Order Code 75 150 275 320 385 440 SLP40-XXX/1 4007511 (with remote contacts) Yes SLP40-XXX/1S 4015011 4027511 4032011 4038511 4044011 4007512 4015012 4027512 4032012 4038512 4044012 SLP40-XXX/0 4007501 4015001 4027501 4032001 4038501 4044001 ( ) spare modules
  • 2. For further information and full technical data, visit: www.lsp-international.com LSP | 81 12 18 90 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/1(S) 75 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) [270 × 230 × 330 mm] Minimum Order Quantity 72 Units SLP40-XXX/1(S) Legend L N Protective Earth S Signalling Contacts Optional Internal Configuration Plug Internal Configuration SLP40-XXX/0 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/0 75 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units S Line Neutral PE [270 × 230 × 330 mm] 18 NO COM NC L/N N/PE L/N N/PE 9 50 67 46 46 TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S, TN-C, TT (Single-phase, 1+0) F1 PE L L' L PE F2
  • 3. 82 Low wer Systems Series 2019 | LSP Voltage Po SLP40-XXX/2(S) Technical Data SLP40-XXX/2(S) 75 150 275 320 385 440 IEC Electrical Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 230 V 230 V 275 V 20 kA 40 kA 120 V 150 V 60 V 75 V Class II • Type 2 •Type 1CA Location of Use: Sub-Distribution Boards Network Systems: TN-S Mode of Protection: L-PE, N-PE Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V Response Time tA < 25ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA TOV Withstand 5s UT 90V 180V 335V 580V TOV 120min UT 115V 230V 440V mode Withstand Safe Fail Safe Fail Safe Fail Safe Fail Number of Ports 1 765V 335V 440V 335V 440V 400 V 125 A gL / gG Withstand Pluggable Multi-Pole SPD Mechanical & Environmental Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity RH 5%...95% Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2 (Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Green ok / Red defect Remote Contacts (RC) Optional RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Order Information Order Code 75 150 275 320 385 440 SLP40-XXX/2 4007521 (with remote contacts) Yes SLP40-XXX/2S 4015021 4027521 4032021 4038521 4044021 4007522 4015022 4027522 4032022 4038522 4044022 SLP40-XXX/0 4007501 4015001 4027501 4032001 4038501 4044001 ( ) spare modules
  • 4. For further information and full technical data, visit: www.lsp-international.com LSP | 83 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/2(S) 75 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) [270 × 230 × 330 mm] Minimum Order Quantity 42 Units SLP40-XXX/2(S) Legend L N Protective Earth S Signalling Contacts Optional Internal Configuration Plug Internal Configuration SLP40-XXX/0 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/0 75 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units S Line Neutral PE [270 × 230 × 330 mm] 18 46 NO COM NC L N PE L N PE 12 36 90 9 50 67 46 TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S (Single-phase, 2+0) F1 PE L N L' N' PE L N F2
  • 5. 84 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Multi-Pole SPD SLP40-XXX/3(S) Technical Data SLP40-XXX/3(S) 275 320 385 440 IEC Electrical Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 230 V 230 V 275 V 120 V 150 V Class II • Type 2 •Type 1CA Location of Use: Sub-Distribution Boards Network Systems: TN-C Mode of Protection: L-PEN Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V Response Time tA < 25ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA TOV Withstand 5s UT 180V 335V 580V TOV 120min UT 230V 440V mode Safe Fail Safe Fail Safe Fail Safe Fail Number of Ports 1 765V 335V 440V 335V 440V 125 A gL / gG Withstand 150 Mechanical & Environmental Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity RH 5%...95% Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2 (Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Green ok / Red defect Remote Contacts (RC) Optional RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Order Information Order Code 150 275 320 385 440 SLP40-XXX/3 (with remote contacts) Yes SLP40-XXX/3S 4015031 4027531 4032031 4038531 4044031 4015032 4027532 4032032 4038532 4044032 SLP40-XXX/0 4015001 4027501 4032001 4038501 4044001 ( ) spare modules
  • 6. For further information and full technical data, visit: www.lsp-international.com LSP | 85 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/3(S) 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) [270 × 230 × 330 mm] Minimum Order Quantity 30 Units SLP40-XXX/3(S) Legend L N Protective Earth S Signalling Contacts Optional Internal Configuration Plug Internal Configuration SLP40-XXX/0 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/0 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units S Line Neutral PE [270 × 230 × 330 mm] 18 46 NO COM NC L2 L1 L3 PEN L2 L1 L3 PEN 9 50 67 46 12 54 90 TÜVRheinland R CERTIFIED RoHS F1 L1 L2 L3 F2 L2' L3' L1 L2 L3 PEN PEN L1' TN-C (Three-phase, 3+0) Connection Diagram
  • 7. 86 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Multi-Pole SPD SLP40-XXX/4(S) Technical Data SLP40-XXX/4(S) 275 320 385 440 IEC Electrical Nominal AC Voltage (50/60Hz) Uo/Un 230 V 400 V Maximum Continuous Operating Voltage (AC) Uc 320 V 385 V 440 V Nominal Discharge Current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 230 V 230 V 275 V 120 V 150 V Class II • Type 2 •Type 1CA Location of Use: Sub-Distribution Boards Network Systems: TN-S Mode of Protection: L-PE, N-PE Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 Voltage Protection Level Up 1000 V 1500 V 1600 V 1800 V 2000 V Response Time tA < 25ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) ISCCR 25kA / 50kA TOV Withstand 5s UT 180V 335V 580V TOV 120min UT 230V 440V mode Safe Fail Safe Fail Safe Fail Safe Fail Number of Ports 1 765V 335V 440V 335V 440V 125 A gL / gG Withstand 150 Mechanical & Environmental Operating Temperature Range Ta -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity RH 5%...95% Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Terminal Screw Torque Mmax 39.9 Ibf·in [4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2 (Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Green ok / Red defect Remote Contacts (RC) Optional RC Switching Capacity AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Order Information Order Code 150 275 320 385 440 SLP40-XXX/4 (with remote contacts) Yes SLP40-XXX/4S 4015041 4027541 4032041 4038541 4044041 4015042 4027542 4032042 4038542 4044042 SLP40-XXX/0 4015001 4027501 4032001 4038501 4044001 ( ) spare modules
  • 8. For further information and full technical data, visit: www.lsp-international.com LSP | 87 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/4(S) 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) [270 × 230 × 330 mm] Minimum Order Quantity 24 Units SLP40-XXX/4(S) Legend L N Protective Earth S Signalling Contacts Optional Internal Configuration Plug Internal Configuration SLP40-XXX/0 Dimensions & Packaging Dimensions & Packaging SLP40-XXX/0 150 275 320 385 440 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units S Line Neutral PE [270 × 230 × 330 mm] 18 46 PE L3 L1 L2 N NO COM NC PE L3 L1 L2 N 9 50 67 46 12 72 90 TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S (Three-phase, 4+0) F1 N L1 L2 L3 PE L1' L2' L3' N' PE' F2 L1 L2 L3 N PE
  • 9. 88 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Multi-Pole SPD Location of Use: Network Systems: TT, TN-S Mode of Protection: L-N, N-PE Technical Data Nominal AC Voltage (50/60Hz) Maximum Continuous Operating Voltage Nominal Discharge Current (8/20 µs) 20kA / 20kA Maximum Discharge Current (8/20 µs) 40kA / 40kA SLP40-XXX/1(S)+1 SLP40-XXX/1(S)+1 IEC Electrical Voltage Protection Level Follow Current Interrupt Rating 100ARMS Response Time < 25 ns / < 100 ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) 25kA / 50kA TOV Withstand 5s TOV 120min Withstand Safe Fail Safe Fail TOV Withstand 200ms 1200V Number of Ports 1 90V 180V 335V 115V 230V 440V 335V 440V Class II • Type 2 •Type 1CA Sub-Distribution Boards Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV and GDT Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 125 A gL / gG Withstand Mechanical & Environmental Operating Temperature Range Permissible Operating Humidity Terminal Screw Torque (L - N) Uc (N - PE) Uc (L - N) / (N - PE) In (L - N) / (N - PE) Imax (L - N) / (N - PE) Up (N-PE) Ifi (L-N)/(N-PE) tA (L - N) ISCCR (L - N) UT (L - N) UT mode (N-PE) UT Ta RH Mmax Conductor Cross Section (max) Mounting Degree of Protection Housing Material Thermal Protection Operating State / Fault Indication Remote Contacts (RC) RC Switching Capacity RC Conductor Cross Section (max) Order Information Order Code 75 150 275 320 Atmospheric pressure and altitude -40 ºF to +158 ºF [-40 ºC to +70 ºC] 5%...95% [ 39.9 Ibf·in 4.5Nm] 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2(Flexible) 35 mm DIN Rail, EN 60715 IP 20 (built-in) Thermoplastic: Extinguishing Degree UL 94 V-0 Optional 16 AWG (Solid) / 1.5 mm2(Solid) 80k Pa ... 106k Pa / -500 m ... 2000 m Yes Green ok / Red defect AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A SLP40-XXX/1+1 (with remote contacts) SLP40-XXX/1S+1 SLP40-XXX/0 SLP40-NPE/0 4007513 4007514 4007501 4025501 4015013 4015014 4015001 4025501 4027513 4027514 4027501 4025501 4032013 4032014 4032001 4025501 ( ) spare modules ( ) spare modules 75 150 275 320 385 440 230 V 230 V 120 V 60 V 320 V 275 V 150 V 75 V 230 V 385 V 400 V 440 V 255 V 0.4kV / 1.5kV 1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV Safe Fail 335V 440V Safe Fail 580V 765V 385 4038513 4038514 4038501 4025501 440 4044013 4044014 4044001 4025501
  • 10. For further information and full technical data, visit: www.lsp-international.com LSP | 89 Dimensions & Packaging Internal Configuration Plug Internal Configuration Dimensions & Packaging Legend L N Protective Earth S Signalling Contacts Optional Line Neutral PE SLP40-XXX/1(S)+1 Dimensions & Packaging SLP40-XXX/1(S)+1 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 42 Units SLP40-NPE/0 Dimensions & Packaging SLP40-XXX/0 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units SLP40-NPE/0 40 [270 × 230 × 330 mm] SLP40-XXX/0 [270 × 230 × 330 mm] 18 46 L PE N NO COM NC L PE N S 9 50 67 46 12 36 90 TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S,TT (Single-phase, 1+1) N L L' N' F1 L F2 PE PE N 75 150 275 320 385 440 75 150 275 320 385 440
  • 11. 90 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Multi-Pole SPD Location of Use: Network Systems: TT, TN-S Mode of Protection: L-N, N-PE Technical Data Nominal AC Voltage (50/60Hz) Maximum Continuous Operating Voltage Nominal Discharge Current (8/20 µs) 20kA / 20kA Maximum Discharge Current (8/20 µs) 40kA / 40kA SLP40-XXX/2(S)+1 SLP40-XXX/2(S)+1 IEC Electrical Voltage Protection Level Follow Current Interrupt Rating 100ARMS Response Time < 25 ns / < 100 ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) 25kA / 50kA TOV Withstand 5s TOV 120min Safe Fail Safe Fail TOV Withstand 200ms 1200V Number of Ports 1 180V 335V 230V 440V 335V 440V Class II • Type 2 •Type 1CA Sub-Distribution Boards Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV and GDT Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 125 A gL / gG Withstand Safe Fail 580V 765V 255 V Mechanical & Environmental Operating Temperature Range -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity 5%...95% Terminal Screw Torque [ 39.9 Ibf·in 4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2(Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Remote Contacts (RC) Optional RC Switching Capacity RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Order Information Order Code 150 275 320 Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Yes Green ok / Red defect AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A SLP40-XXX/2+1 (with remote contacts) SLP40-XXX/2S+1 SLP40-XXX/0 SLP40-NPE/0 4015023 4015024 4015001 4025501 4027523 4027524 4027501 4025501 4032023 4032024 4032001 4025501 385 4038523 4038524 4038501 4025501 ( ) spare modules ( ) spare modules (L - N) Uc (N - PE) Uc (L - N) / (N - PE) In (L - N) / (N - PE) Imax (L - N) / (N - PE) Up (N-PE) Ifi (L-N)/(N-PE) tA (L - N) ISCCR (L - N) UT (L - N) UT mode (N-PE) UT Ta RH Mmax 150 275 320 385 440 230 V 230 V 120 V 320 V 275 V 150 V 230 V 385 V 400 V 440 V Safe Fail 335V 440V 1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV 440 4044023 4044024 4044001 4025501
  • 12. For further information and full technical data, visit: www.lsp-international.com LSP | 91 Dimensions & Packaging Internal Configuration Plug Internal Configuration Dimensions & Packaging Legend L N Protective Earth S Signalling Contacts Optional Line Neutral PE SLP40-XXX/2(S)+1 Dimensions & Packaging SLP40-XXX/2(S)+1 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 30 Units SLP40-NPE/0 Dimensions & Packaging SLP40-XXX/0 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units SLP40-NPE/0 40 [270 × 230 × 330 mm] SLP40-XXX/0 [270 × 230 × 330 mm] 18 46 S NO COM NC L1 N L2 PE L1 N L2 PE 9 50 67 46 12 54 90 TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S, TT (Three-phase, 2+1) F1 L1 L2 F2 L2' L1 L2 L1' PE' N N PE PE 150 275 320 385 440 150 275 320 385 440
  • 13. 92 Low wer Systems Series 2019 | LSP Voltage Po Pluggable Multi-Pole SPD Location of Use: Network Systems: TT, TN-S Mode of Protection: L-N, N-PE SLP40-XXX/3(S)+1 Class II • Type 2 •Type 1CA Sub-Distribution Boards Surge Ratings: In = 20kA (8/20µs) IEC/EN/UL Category: Class II / Type 2 / Type 1CA Protective Elements: High Energy MOV and GDT Housing: Pluggable Design Compliance: IEC 61643-11:2011 EN 61643-11:2012 Order Information Order Code 150 275 320 SLP40-XXX/3+1 (with remote contacts) SLP40-XXX/3S+1 SLP40-XXX/0 SLP40-NPE/0 4015033 4015034 4015001 4025501 4027533 4027534 4027501 4025501 4032033 4032034 4032001 4025501 385 4038533 4038534 4038501 4025501 ( ) spare modules ( ) spare modules Technical Data Nominal AC Voltage (50/60Hz) Maximum Continuous Operating Voltage Nominal Discharge Current (8/20 µs) 20kA / 20kA Maximum Discharge Current (8/20 µs) 40kA / 40kA SLP40-XXX/3(S)+1 IEC Electrical Voltage Protection Level Follow Current Interrupt Rating 100ARMS Response Time < 25 ns / < 100 ns Back-Up Fuse (max) Short-Circuit Current Rating (AC) 25kA / 50kA TOV Withstand 5s TOV 120min Safe Fail Safe Fail TOV Withstand 200ms 1200V Number of Ports 1 180V 335V 230V 440V 335V 440V 125 A gL / gG Withstand Safe Fail 580V 765V 255 V Mechanical & Environmental Operating Temperature Range -40 ºF to +158 ºF [-40 ºC to +70 ºC] Permissible Operating Humidity 5%...95% Terminal Screw Torque [ 39.9 Ibf·in 4.5Nm] Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35mm2 (Solid, Stranded) / 25 mm2(Flexible) Mounting 35 mm DIN Rail, EN 60715 Degree of Protection IP 20 (built-in) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Remote Contacts (RC) Optional RC Switching Capacity RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid) Atmospheric pressure and altitude 80k Pa ... 106k Pa / -500 m ... 2000 m Yes Green ok / Red defect AC: 250V/0.5A; DC: 250V/0.1A;125V/0.2A;75V/0.5A (L - N) Uc (N - PE) Uc (L - N) / (N - PE) In (L - N) / (N - PE) Imax (L - N) / (N - PE) Up (N-PE) Ifi (L-N)/(N-PE) tA (L - N) ISCCR (L - N) UT (L - N) UT mode (N-PE) UT Ta RH Mmax 150 275 320 385 440 230 V 230 V 120 V 320 V 275 V 150 V 230 V 385 V 400 V 440 V Safe Fail 335V 440V 1.0kV / 1.5kV 1.5kV / 1.5kV 1.6kV / 1.5kV 1.8kV / 1.5kV 2.0kV / 1.5kV 440 4044033 4044034 4044001 4025501
  • 14. For further information and full technical data, visit: www.lsp-international.com LSP | 93 Dimensions & Packaging Internal Configuration Plug Internal Configuration Dimensions & Packaging Legend L N Protective Earth S Signalling Contacts Optional Line Neutral PE SLP40-XXX/3(S)+1 Dimensions & Packaging SLP40-XXX/3(S)+1 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 24 Units SLP40-NPE/0 Dimensions & Packaging SLP40-XXX/0 Single Unit DIN 43880 Dimension 1 CTN Packaging Dimensions (HxWxL) Minimum Order Quantity 96 Units SLP40-NPE/0 40 [270 × 230 × 330 mm] SLP40-XXX/0 [270 × 230 × 330 mm] 18 46 9 50 67 46 12 72 90 S NO COM NC L1 L2 L3 PE N L1 L2 L3 PE N TÜVRheinland R CERTIFIED RoHS Connection Diagram TN-S, TT (Three-phase, 3+1) F1 L1 L2 L3 N F2 L1' L2' L3' N' N L1 L2 L3 PE PE 150 275 320 385 440 150 275 320 385 440