The Oil Smart Pump Switch, when combined with a non-auto sump pump, will allow water to be pumped without the risk of pumping oil. The switch is ideal for elevator sumps, transformer containment areas, parking garages, and city underground vaults
Unlocking the Power of ChatGPT and AI in Testing - A Real-World Look, present...
Oil smart pump switch
1. Oil Smart Pump Switch
Installation Manual
Oil Smart® Pump Switch:
The Oil Smart® Pump Switch is a stand-alone pump
Controller; it will operate any pump up to 1HP. It is an
industrial grade switch that differentiates between oil
and water used to control pumps in elevators, transformer
oil containment areas, underground vaults, marine,
and other applications. The Oil Smart Switch can be
an integral part of the pump assembly or a stand alone
component wired to the pump or a control valve. Since
1995, the Oil Smart Switch has been the reliable choice
for safely pumping water. Installation of the unit allows
you to comply with State and Federal regulations while
reducing the risk of adverse publicity, fines and expensive
cleanup costs.
Features:
Directly controls sump pumps 0 to 1 hp(piggyback):
quick installation
Available in 120 VAC, 230 VAC 50/60 Hz., or 12/24
VDC
No expensive electrical panel required
Sensors differentiate between oil and water
Differential between on and off comes in 2.5″or 6″
models
Available with or without a piggyback plug
Helps satisfy elevator code ASME A17.1 and EPA, The
Figure 1: Oil Smart® Pump Switch
Spill Prevention, Control, and Countermeasure Plan
UL Certified File E183129, CE Certified
Includes Complete Mounting Brackets and Hardware
No Moving Parts. Patented Electronic Control.
Solid-state sensing device that differentiates between oil and water. Incorporates two level
sense points, pump ON, pump OFF
121 N. Dillon Street | San Jacinto, CA 92583
Voice: (951) 487-8073 | FAX: (951) 487-0557
http://www.seewaterinc.com
2. Preventive Maintenance:
The Oil Smart® Pump must be kept clean. If the switch
is submerged in water during initial installation, it must
be cleaned. Clean with a rag and household rubbing
alcohol or kerosene. Consistent inspection and
preventive maintenance ensures longevity and proper
operation of component.
Operation:
Oil Smart Switch Installation:
Caution: Remove any float switch that is currently in
use or supplied by pump manufacturer. If pump has
manual/auto set, switch to manual.
1. Branch circuit protection shall be provided by
the installer; it must be sized according to
pump/motor specifications.
2. Mount Oil Smart Pump Control panel with
enclosed mounting hardware to pump discharge
pipe. The off sensor of the Oil Smart Switch
shall be positioned at least 3” above the
impeller of the pump.
When water comes in contact with the short (on)
sensor, the pump will turn on. The pump will remain
on until water clear the long (off) sensor. If oil comes
in contact with the on sensor, the pump will not turn
on; however the pump switch will activate and pump
water from under the oil.
Testing:
Place your thumb on the short sensor of Oil Smart®
Pump Switch and the pump will turn on. While touching
the short sensor, touch the long sensor “off” with your
fingers. Remove your thumb from the on sensor and
begin to move your fingers down the off sensor. Remove
your fingers from off sensor and the pump will turn off.
OR Fill up sump area with water, when water reaches
the on sensor, the pump will turn on and remain on until
water clears the off sensor.
121 N. Dillon Street | San Jacinto, CA 92583
Voice: (951) 487-8073 | FAX: (951) 487-0557
http://www.seewaterinc.com
3. Specifications:
Model
Volts
Assembly
120 60Hz.
120 60Hz.
120 60Hz.
Max.
Load
1HP
1HP
1HP
Bare Leads
Bare Leads
Piggyback Plug
Pumping
Range
2.5”
6″
2.5″
OSS20R
OSS20R6
OSS20PBP
R
OSS20PBP
6
OSS20R6E
120 60Hz.
1HP
Piggyback Plug
6″
230
50/60Hz.
1HP
Bare Leads
6″
Testing Made Easy!
A concept offered only by SeeWater Inc.Contractors have the luxury of testing the Oil Smart switch and
alarm at any common receptacle prior to installation and during critical troubleshooting. Test with your
fingers -no oil or water required!
Applications
Elevator Sump Pumps
Electric Utilities ( Substations, Power Plants, Underground Vaults, and Transformer Barriers
Any Industrial Sump or Marine Application
121 N. Dillon Street | San Jacinto, CA 92583
Voice: (951) 487-8073 | FAX: (951) 487-0557
http://www.seewaterinc.com