  1. 1. A PROJECT ONENHANCEMENT OF POWER QUALITY INDISTRIBUTION SYSTEM USING D-STATCOM
  2. 2. •Power Quality is a term used to broadly encompass the entire scope ofinteraction among electrical suppliers, the environment, the system sandproducts energized, and the users of those system sand products. It is morethan the delivery of "clean“ electric power that complies with industrystandards. It involves them a attainability of that power, thedesign, selection, and the installation of every piece of hard ware andsoftware in the electrical energy system. Stretching from the generation plantto the utility customer, power quality is a measure of how the elements affectthe system as a whole.POWER QUALITY
  3. 3. POWERQUALITYTHE COMMON POWER QUALITYPROBLEMS voltage sags harmonic distortion low power factor
  4. 4. Voltage sags are one of the most occurringpower quality problems. For an industry voltage sags occurmore often and cause severe problems and economical losses.Utilities often focus on disturbances from end-user equipmentas the main power quality problemsTotal Harmonic Distortion, or THD is an amplifieror pre-amplifier specification that compares the outputsignal of the amplifier with the input signal andmeasures the level differences in harmonic frequenciesbetween the two. The difference is called total harmonicdistortion
  5. 5. KEY WORDS• D-STATCOM• Methodology• results and causes• Conclusion
  6. 6. D-STATCOM VOLTAGE SOURCE CONVERTER CONTROLLER ENERGY STORAGE CIRCUIT LCL PASSSIVE FILTER
  7. 7. D-STATCOMSTATCOM is a managing system used on ac power indication system. It isbased on energy gadgets present resource inverter and can act as either aresource or mess up of sensitive ac energy to power system.If linked with a power resource. It can also provide effective ac energy. It isparticipant of the FACTS family.STATCOM is set up to back up power systems that have a bad energyaspect and often inadequate present control.Its most common use is for present balance
  8. 8. D-STATCOM
  9. 9. A voltage-source converter is a power electronic devicethat connected in shunt or parallel to the system. It can generate a sinusoidalvoltage with any required magnitude, frequency and phase angle. The VSCused to either completely replace the voltage or to inject the ‘missingvoltage’. The ‘missing voltage’ is the difference between the nominalvoltage and the actual.Voltage Source Converter (VSC)Suitable adjustment of the phase and magnitude of theD-STATCOM output voltages allows effectives control of active andreactive power exchanges between D-STATCOM and AC system. Inaddition, the converter is normally based on some kind of energystorage, which will supply the converter with a DC voltage
  10. 10. CONTROLLER
  11. 11. ENERGY STORAGE CIRCUITDC source is connected in parallel with the DC capacitor. It carries theinput ripple current of the converter and it is the main reactive energystorage element. This DC capacitor could be charged by a battery sourceor could be recharged by the converter itself.
  12. 12. LCL Passive Filter
  13. 13. METHODOLOGYTEST SYSTEMSIMULINK MODEL FOR THE TESTSYSTEM
  14. 14. TEST SYSTEMSingle line diagram of the test system
  15. 15. SIMULINK MODEL OF THE TEST SYSTEM
  16. 16. CASES IN D-STATCOMWithout insertion of D-STATCOMWith insertion of D-STATCOMD-STATCOM without LCL Passive FilterD-STATCOM with LCL Passive Filter
  17. 17. Three phase to ground faultDouble line to ground faultSingle line to ground faultLine to line faultTYPES OF FAULTS IN THE D-STATCOM
  18. 18. Without insertion of D-STATCOMTPG DPGa) voltage at load point is 0.6600 p.u b) voltage at load point is 0.7070 p.u
  19. 19. LLC) voltage at load point is 0.7487 p.uSLGD) voltage at load point is 0.8259 p.u
  20. 20. With insertion of D-STATCOMTPG(a).voltage at load point is 0.9367 p.uDLG(b).voltage at load point is 0.9800 p.u
  21. 21. LLc).voltage at load point is 1.068 p.uLGd).voltage at load point is 0.9837 p.u
  22. 22. D-STATCOM with out LCL filterharmonic spectrum of distortion output current without LCLPassive Filter
  23. 23. D-STATCOM WITH FILTERharmonic spectrum of output current with LCL Passive Filter
  24. 24. CONCLUSIONThe simulation results show that the voltagesags can be mitigate by inserting D-STATCOM to thedistribution system. By adding LCL Passive filter to D-STATCOM, The power factors also increase close to unity.Thus, it can be concluded that by adding D-STATCOMwith LCL filter the power quality isimproved.