ABB Power Products - Medium & High Voltage Transformers
Cast Resin Transformers
ABB Power Products
ABB TJC is a single phase voltage transformer which is intended to have one end of its primary winding directly earthed. Indoor dry type, cast resin insulated medium voltage transformer for measuring and protection with up to 2 secondary windings. With or without fuses. Most electrical standards available. Reconnectable MV medium voltage versions available.
Cast Resin Transformers are constructed with their HV high voltage windings encapsulated in resin and are an excellent alternative to traditional oil immersed transformers. Cast resin transformers encase the windings in epoxy resin : these HV high voltage cast resin transformers simplify installation since they are dry, without cooling oil, and so require no fire-proof vault for indoor installations. The epoxy resin protects the high voltage transformer windings from dust and corrosive atmospheres.
ABB TJC Single Phase Voltage Transformer
ABB MV Medium Voltage Transformers - Voltage Transformer Features
Indoor dry type, cast resin insulated transformers for medium voltages (MV). ABB transformers are suitable for measuring and protection of MV medium voltages with up to 2 secondary windings. ABB offers a full range of medium voltage (MV) and high voltage (HV) transformer products and solutions for ANSI, IEC and other local standards. ABB is a major transformer manufacturer throughout the world and offers both liquid-filled and dry-type transfomers for medium and high voltage power distribution, measurement and protection.
T&D distribute ABB fuses, vacuum contactors, surge arresters, capacitors, plugs and sockets for LV, MV and HV electrical distribution and cable systems.
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
ABB TJC MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer Single Pole Transformer
1. Medium Voltage Product
TJC 4
Indoor voltage transformers
Highest voltage for equipment
[kV]
[kV]
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
3.6 - 12
Power frequency test voltage, 1 min.
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
10 -
Lightning impulse test voltage
[kV]
Max. rated burden, classes
[VA/cl]
25/0.2 - 50/0.5 - 100/1
40 - 75
Residual winding
[VA/cl]
50 - 200/6P
Description
The TJC 4 single-pole insulated voltage transformers are cast
in epoxi resin and designed mostly for insulation voltages of
3.6 kV to 12 kV.
If no other value is required the transformers are
manufactured with a overvoltage factor of 1.9 x Un/8 hrs.
One outlet of the primary winding, including the respective
terminal is insulated from the earth to a level which
corresponds to the rated insulation value. The transformer is
mostly equipped with two secondary windings, the first one
for either measuring or protection purposes, the other for
being connected into an open-delta connection in a threephase system. One terminal of each secondary winding
and one of the open-delta connected terminals have to be
earthed during the transformer operation. When not required
otherwise, the secondary windings are lead out into a casttype secondary terminal board.
The transformer can be mounted in any position. The
transformer ore fixed by four screws, the M8 bolted earthing
clamp is located on the transformer base plate. The
secondary terminal board is covered with a transparent and
sealable cover made of plastic material.
Rated primary voltages ... 3/√3 kV; 3,3/√3 kV; 6/√3 kV;
6,6/√3 kV; 10/√3 kV; 11/√3 kV
Other primary voltages can also be supplied on request.
Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy
classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection
winding).
Other secondary voltages can also be supplied on request.
Rated voltages for open-delta connection: ... 100/3 V; 110/3
V- class 6P
Other voltages for open-delta connection can also be
supplied based on customer requirement.
Rated frequency ... 50 Hz; 60 Hz
Based on a discussion with the manufacturer the transformer
can also be designed for two primary voltage levels (with
change over secondary side).
The transformers are manufactured conformably to the
requirements and recommendations of the following
standards and regulations: IEC, VDE, ANSI, BS, GOST and
CSN.
2. Dimensions
197
174
220
8
M10x15
Pg16
14
4
20
22
M8
338
280
125
148
130
11
96
140
30
11
WEIGHT: appr. 20kg
CREEPAGE DISTANCE: 280mm
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
4. PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.:
+420 547 152 602
Fax:
+420 547 152 626
E-mail:
info.ejf@cz.abb.com
+420 547 152 614
www.abb.com
The data and ilustrations in this
WWW.CABLEJOINTS.CO.UKto catalogue are not the
binding. We reserve the right
make changes of
content, in the course of technical development of the
product.
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
1VLC000520 - Rev 1, en 2011, 01.15
ABB s.r.o.
5. Medium Voltage Product
TJC 5
Indoor voltage transformers
Highest voltage for equipment
[kV]
[kV]
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
12 – 17,5
Power frequency test voltage, 1 min.
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
28 - 38
Lightning impulse test voltage
[kV]
Max. rated burden, classes
[VA/cl]
25/0.2 - 50/0.5 - 100/1
75 - 95
Residual winding
[VA/cl]
50 - 200/6P
Description
The TJC 5 single-pole insulated voltage transformers are
casted in epox resin and designed mostly for insulation
voltages of 12 kV to 17,5 kV.
If no other value is required the transformers are
manufactured with a overvoltage factor of 1.9 x Un/8 hrs.
One outlet of the primary winding, including the respective
terminal is insulated from the earth to a level which
corresponds to the rated insulation value. The transformer is
mostly equipped with two secondary windings, the first one
for either measuring or protection purposes, the other for
being connected into an open-delta connection in a threephase system. One terminal of each secondary winding
and one of the open-delta connected terminals have to be
earthed during the transformer operation. When not required
otherwise, the secondary windings are lead out into a casttype secondary terminal board.
The transformer can be mounted in any position. The
transformer re fixed by four screws, the M8 bolted earthing
clamp is located on the transformer base plate. The
secondary terminal board is covered with a transparent and
sealable cover made of plastic material.
Rated primary voltages ... 10/√3 kV; 11/√3 kV; 13,8/√3 kV;
15/√3 kV;
Other primary voltages can also be supplied on request.
Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy
classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection
winding).
Other secondary voltages can also be supplied on request.
Rated voltages for open-delta connection: ... 100/3 V; 110/3
V- class 6P
Other voltages for open-delta connection can also be
supplied based on customer requirement.
Rated frequency ... 50 Hz; 60 Hz
Based on a discussion with the manufacturer the transformer
can also be designed for two primary voltage levels (with
change over secondary side).
The transformers are manufactured conformably to the
requirements and recommendations of the following
standards and regulations: IEC, VDE, ANSI, BS, GOST and
CSN.
6. Dimensions
197
174
220
8
M10x15
Pg16
14
4
20
22
M8
338
280
125
148
130
11
96
140
30
11
WEIGHT: appr. 20kg
CREEPAGE DISTANCE: 280mm
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
8. PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.:
+420 547 152 602
Fax:
+420 547 152 626
E-mail:
info.ejf@cz.abb.com
+420 547 152 614
www.abb.com
The data and ilustrations in this catalogue are not
binding. We reserve the right to make changes
WWW.CABLEJOINTS.CO.UK developmentofofthe
content, in the course of technical
the
THORNE & DERRICK UK
product.
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
1VLC000532 - Rev -, en 2011. 01.15
ABB s.r.o.
9. Medium Voltage Product
TJC 6
Indoor voltage transformers
Highest voltage for equipment
[kV]
[kV]
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
17.5 - 24 (25)
Power frequency test voltage, 1 min.
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
38 - 50 (55)
Lightning impulse test voltage
[kV]
Max. rated burden, classes
[VA/cl]
25/0.2 - 100/0.5 - 150/1
95 - 125
Residual winding
[VA/cl]
50 - 200/6P
Description
The TJC 6 single-pole insulated voltage transformers are
casted in epox resin and designed mostly for insulation
voltages of 17,5 to 25 kV.
Insulation voltages different from the above are to be the
subject of an agreement between the manufacturer and the
customer.
If no other value is required the transformers are
manufactured with a overvoltage factor of 1.9 x Un/8 hrs. One
outlet of the primary winding, including the respective terminal
is insulated from the earth to a level which corresponds to the
rated insulation value. The other outlet of primary winding
with terminal is earthed during the operation.
The transformer is mostly equipped with two secondary
windings, the first one for either measuring or protection
purposes, the other for being connected into an open-delta
connection in a three-phase system. One terminal of each
secondary winding and one of the open-delta connected
terminals have to be earthed during the transformer operation.
When not required otherwise the secondary windings are
lead out into a casted-type secondary terminal board.
The transformer can be mounted in any position. The
transformers are fixed by four screws, the M8 bolted
earthing clamp is located on the transformer base plate. The
secondary terminal board is covered with voltages sealable
cover made of plastic material.
Rated primary voltages ... 11/√3 kV; 15/√3 kV; 20/√3 kV;
22/√3 kV;
Other primary voltages can also be supplied on request.
Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy
classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection
winding).
Other secondary voltages can also be supplied on request.
Rated voltages for open-delta connection: ... 100/3 V; 110/3
V- class 6P
Other voltages for open-delta connection can also be
supplied based on customer requirement.
Rated frequency ... 50 Hz; 60 Hz
Based on a discussion with the manufacturer the transformer
can also be provided with primary winding designed for two
different primary voltages (with change over secondary side).
The transformers are manufactured conformably to the
requirements and recommendations of the following
standards and regulations: IEC, VDE, ANSI, BS, GOST and
ČSN.
10. Dimensions
201
179
280
8
M10x15
22
20
Pg16 ‡14
ZEM M8
EARTH
352
285
178
14
U
150
140
A
96
135
‡30
‡14
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
12. PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.:
+420 547 152 602
Fax:
+420 547 152 626
E-mail:
info.ejf@cz.abb.com
+420 547 152 614
www.abb.com
The data and ilustrations in this catalogue are not
binding. We reserve the right
WWW.CABLEJOINTS.CO.UKto make changes ofofthe
content, in the course of technical development the
THORNE & DERRICK UK
product.
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
1VLC000521 - Rev 2, en 2011, 01.15.
ABB s.r.o.
13. WWW.CABLEJOINTS.CO.UK
Medium Voltage Product
TJC 7
Indoor voltage transformers
Highest voltage for equipment
[kV]
[kV]
70 - 95
Lightning impulse test voltage
[kV]
Max. rated burden, classes
[VA/cl]
50/0.2 - 150/0.5 - 250/1
Residual winding
[VA/cl]
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
36 - 40.5
Power frequency test voltage, 1 min.
THORNE & DERRICK UK
50 - 200/6P
170 - 200
Description
The TJC 7 single-pole insulated voltage transformers are
casted in epox resin and designed mostly for insulation
voltages of 36 kV to 40.5 kV.
Insulation voltages differ t from the above are to be the
subject of an agreement between the manufacturer and the
customer.
If no a different value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs.
One outlet of the primary winding, including the respective
terminal is insulated from the earth to a level which corresponds to the rated insulation value.The other outlet of
primary winding with terminal is earthed during the operation.Most of the transformers are equipped with two secondary
windings, the first one for either measuring or protection
purposes, the other for being connected into an open-delta
connection in a three-phase system. One terminal of each
secondary winding and one of the open-delta connected
terminals have to be earthed during the transformer operation.
The transformer can be mounted in any position.The transformer are fixed by four screws.The secondary terminal board is
covered with sealable cover made of plastic material.
Rated primary voltages ...30/√3 kV;33/√3 kV;35/√3 kV
Other primary voltages can also be supplied on request.
Rated secondary voltages...100/√3 V;110/√3 V – accuracy
classes 0.2;0.5;1 (measuring winding) or 3P;6P (protection
winding).
Other secondary voltages can also be supplied on request.
Rated voltages for open-delta connection:...100/3 V;110/3
V- class 6P
Other voltages for open-delta connection can also be
supplied based on customer requirement.
Rated frequency ...50 Hz;60 Hz
Based on a discussion with the manufacturer the transformer
can also be provided with primary winding designed for two
different primary voltages (with changeover secondary side).
The transformers are manufactured according to the requirements and recommendations of the following
standards and regulations:IEC, ANSI, VDE, BS, GOST and
ČSN.
14. Dimensions
Marking of the voltage transformer outlets
a) Single-pole insulated transformer
b) Single-pole insulated transformer with a tap
c) Double-pole insulated transformer
d) Double-pole insulated transformer with a tap
2
e) Single-pole insulated transformer with two secondary windings
f) Single-pole insulated transformer with two secondary windings, with
one of which being the auxiliary (residual) winding
g) Single-pole insulated transformer with two secondary, tapped
windings, with one which being the auxiliary (residual) winding.
16. Videnska 11 7
619 00 B rno, Cz ech R epublic
Tel.:
+420 547 152 602
Fax:
+420 5 47 152 626
E -mail:
info.ejf@cz.a bb.co m
+420 547 152 614
ww w.a bb .co m
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
ev 1, en 20 11, 01.15.
PP MV B rno
The data and ilustrations in this catalogue a re not
binding. We reser ve the right to make chan ges of th e
content, in the course of technical development of the
product.
A 3440-527-I/2000 - R
WWW.CABLEJOINTS.CO.UK
ABB s . r.o .
17. Medium Voltage Product
TJC 7.1
Indoor voltage transformers
Highest voltage for equipment
[kV]
[kV]
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
36
Power frequency test voltage, 1 min.
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
70
Lightning impulse test voltage
[kV]
Max. rated burden, classes
[VA/cl]
50/0.2 - 150/0.5 - 250/1
170
Residual winding
[VA/cl]
50-200/6P
Description
The TJC 7 single-pole insulated voltage transformers are
casted in epox resin and designed mostly for insulation
voltages of 36 kV.
Insulation voltages different from the above are to be the
subject of an agreement between the manufacturer and the
customer.
If no a different value is required the transformers are
manufactured with a overvoltage factor of 1.9 x Un/8 hrs.
One outlet of the primary winding, including the respective
terminal is insulated from the earth to a level which
corresponds to the rated insulation value. The other outlet of
primary winding with terminal is earthed during the operation.
Most of the transformers are equipped with two secondary
windings, the first one for either measuring or protection
purposes, the other for being connected into an open-delta
connection in a three-phase system. One terminal of each
secondary winding and one of the open-delta connected
terminals have to be earthed during the transformer operation.
The transformer can be mounted in any position. The
transformer are fixed by four screws. The secondary terminal
board is covered with sealable cover made of plastic material.
Rated primary voltages ... 30/√3 kV; 33/√3 kV; 35/√3 kV
Other primary voltages can also be supplied on request.
Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy
classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection
winding).
Other secondary voltages can also be supplied on request.
Rated voltages for open-delta connection: ... 100/3 V; 110/3
V- class 6P
Other voltages for open-delta connection can also be
supplied based on customer requirement.
Rated frequency ... 50 Hz; 60 Hz
Based on a discussion with the manufacturer the transformer
can also be provided with primary winding designed for two
different primary voltages (with changeover secondary side).
The transformers are manufactured according to the
requirements and recommendations of the following
standards and regulations: IEC, ANSI, VDE, BS, GOST and
ČSN.
18. Dimensions
300
M10
6
g1
-P
14
‡
323
22
40
74
4
M8
314
308
60
°
45
182
180
55
250
20
203
180
A
300
383
‡1
4
250
225
96
225
150
WEIGHT: appr. 48kg
CREP. DISTANCE: 398mm
Drawing n. 44204010
Marking of the voltage transformer outlets
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
20. PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.:
+420 547 152 602
Fax:
+420 547 152 626
E-mail:
info.ejf@cz.abb.com
+420 547 152 614
www.abb.com
The data and ilustrations in this catalogue are not
binding. We reserve the right
WWW.CABLEJOINTS.CO.UK to make changes ofofthe
content, in the course of technical development the
THORNE & DERRICK UK
product.
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
1VLC000535 - Rev -, en 2011, 01.15.