ENGINEERING LECTURE SERIES
HVAC- FUNDAMENTALS OF AIRFLOW
Airflow, Pressure, Velocity & Duct System Behavior
COURSE HVAC System Design
LECTURE 01 — Fundamentals of Airflow
REFERENCE
STANDARDS
ASHRAE Handbook - Fundamentals
INSTRUCTOR Eng. Ali Uday Harobey
DATE 2026
Content aligned with ASHRAE Handbook — Fundamentals and applicable ASHRAE Standards (55, 62.1, 90.1). ASHRAE® is a registered trademark of the American
Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 2 of 14
Contents
1. Introduction
2. Learning Objectives
3. Mass, Weight, Density, and Specific Volume
4. Hydrostatic Pressure
5. The Continuity Equation
6. Temperature, Density, and Volume Flow
7. Mixing Air Streams
8. Energy and the First Law
9. Static, Velocity, and Total Pressure
10. Bernoulli’s Equation
11. Static Pressure Regain
12. Standard Air and the Psychrometric Chart
13. Duct Friction and Pressure Loss
14. Reynolds Number and Friction Factor
15. Moody Chart and Friction Charts
16. System Constant and System Curve
17. Density and Altitude Effects
18. Integrated Engineering View
19. Practical Example
20. Common Errors
21. Key Equations
22. Summary
23. References
24. Skill Development Exercises
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 3 of 14
1. Introduction
Airflow is the foundation of an HVAC air system. Duct sizing, external static pressure, fan selection, air-terminal
performance, and many system calculations all depend on a basic understanding of how air behaves as a fluid.
This lecture follows ASHRAE chapter 1 of the book and turns its core ideas into a clearer teaching sequence for
new HVAC engineers. The purpose is not to memorize isolated formulas. The goal is to understand what each
equation means physically and when an engineer should use it.
Engineering note: Keep the engineering chain in mind throughout the lecture:
Figure 1 — HVAC Air-System Engineering Chain: From Airflow to Fan Requirement
2. Learning Objectives
• Explain the difference between mass and weight.
• Define density and specific volume and relate them to air temperature.
• Use the Continuity Equation in ducts and understand why velocity changes with duct area.
• Understand how air temperature changes affect density and volume flow.
• Estimate mixed-air temperature for two air streams.
• Identify the main forms of energy present in an air system.
• Distinguish static pressure, velocity pressure, and total pressure.
• Explain Bernoulli’s Equation in a practical duct-system context.
• Understand static pressure regain in an expanding duct.
• Explain why duct friction occurs and how pressure loss is estimated.
• Understand Reynolds number, friction factor, and the purpose of the Moody chart.
• Interpret the relationship between airflow and system pressure drop.
3. Mass, Weight, Density, and Specific Volume
3.1 Mass and Weight
Mass describes how much matter is present. Weight is the gravitational force acting on that mass. In elementary
engineering form:
𝑊 = 𝑚 𝑔
where W is weight, m is mass, and g is gravitational acceleration. The supplied chapter also introduces the unit-
consistency factor gₙ (often written 𝑔𝑐) when mixed engineering units are used.
3.2 Density
𝜌 = 𝑚 / 𝑉
Density is mass per unit volume. For HVAC work, density matters because a given volume of air does not always
contain the same mass. Temperature and pressure change the density of air.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 4 of 14
3.3 Specific Volume
𝑣 = 1 / 𝜌
Specific volume is the volume occupied by a unit mass. It is therefore the inverse of density. If density decreases,
specific volume increases.
Engineering note: For airflow calculations, always know whether a quantity is a mass flow rate (kg/s) or a
volume flow rate (m³/s, m³/h, L/s, CFM). They are related, but they are not the same thing.
4. Hydrostatic Pressure
A fluid at rest exerts pressure because of the weight of the fluid above a point. The pressure difference due to a
vertical liquid or gas column can be expressed as:
𝛥𝑝 = 𝛾 𝛥ℎ
where γ is the weight density of the fluid and Δh is the elevation difference.
At a point in a fluid at rest, static pressure acts in all directions. This same id
-ea helps explain why pressure inside a duct act on all duct surfaces rather
than only on the top or bottom wall.
5. The Continuity Equation
The Continuity Equation is a conservation-of-mass statement. For steady flow, mass entering a control volume
must equal mass leaving it when there is no accumulation.
𝜌₁ 𝐴₁ 𝑉₁ = 𝜌₂ 𝐴₂ 𝑉₂
When density can be treated as approximately constant, the HVAC form becomes:
𝐴₁ 𝑉₁ = 𝐴₂ 𝑉₂
5.1 Physical meaning
If a duct becomes smaller, the same airflow must pass through a smaller area, so the average velocity increases.
If the duct becomes larger, the velocity decreases.
𝐴 ↓ → 𝑉 ↑
𝐴 ↑ → 𝑉 ↓
Figure 3 — Continuity
Equation: Relationship
Between Duct Area and
Air Velocity
Figure 2 — Hydrostatic Pressure
Variation with Fluid Elevation
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 5 of 14
Engineering note: This is one of the most useful mental checks in duct design: if you reduce the duct area
while keeping the same flow, velocity must increase.
6. Temperature, Density, and Volume Flow
For air at approximately constant pressure, density is inversely related to absolute temperature.
𝜌₁ / 𝜌₂ = 𝑇₂ / 𝑇₁
Temperature ratios must use absolute temperature (Kelvin), not Celsius directly.
The engineering meaning is straightforward: heating air lowers its density, while cooling air raises its density.
𝑇 ↑ → 𝜌 ↓ → 𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐 𝑣𝑜𝑙𝑢𝑚𝑒 ↑
𝑇 ↓ → 𝜌 ↑ → 𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐 𝑣𝑜𝑙𝑢𝑚𝑒 ↓
7. Mixing Air Streams
Mixing outdoor air with return air is common in air-handling units. A convenient approximate temperature
relation, using consistent volume-flow units, is:
(𝐿₁ 𝑇₁) + (𝐿₂ 𝑇₂) = (𝐿₁ + 𝐿₂) 𝑇ₘ
𝑇ₘ = [𝐿₁ 𝑇₁ + 𝐿₂ 𝑇₂] / [𝐿₁ + 𝐿₂]
Example: 11,000 L/s at 24°C mixes with 3,000 L/s at 5°C. The total flow is 14,000 L/s, and the weighted-
temperature estimate is obtained from the equation above.
Figure 4 — Effect of Air
Heating on Density and
Volume Flow
Figure 5 — Mixing of Return
Air and Outdoor Air in an Air-
Handling System
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 6 of 14
Engineering note: The chapter explicitly cautions that this mixing formula is useful but not absolutely
exact. Keep the flow units consistent and remember that density changes can matter when temperature
differences become significant.
8. Energy and the First Law
Energy, like mass, is conserved. It can move from one form to another, but it is not created or destroyed.
The complete energy equation presented in the chapter includes heat transfer, work, internal energy, flow work,
potential energy, and kinetic energy. For new HVAC engineers, the important step is to recognize what each
term represents rather than memorize the full expression immediately.
8.1 Main forms of energy
• Work — energy transferred by a force acting through a distance or torque through an angle.
• Heat — energy transferred because of a temperature difference.
• Internal energy — microscopic thermal energy associated with the material.
• Potential energy — energy associated with elevation in a gravitational field.
• Kinetic energy — energy associated with motion.
𝐾𝐸 = 𝑚 𝑉² / 2
Engineering note: A fan adds mechanical energy to the air. That added energy appears in the air system as
pressure and velocity effects, while the system also loses energy through friction and component
resistance.
9. Static, Velocity, and Total Pressure
9.1 Static pressure
Static pressure is the pressure exerted by the fluid independent of the direction of motion. In duct measurement
practice, a pressure tap in the side wall is used to sense static pressure.
9.2 Velocity pressure
Velocity pressure represents the pressure associated with the motion of the air. It is proportional to the square
of velocity:
𝑝ᵥ = 𝜌 𝑉² / 2
For standard air, the supplied chapter gives the useful HVAC relationship:
𝑝ᵥ = 0.602 𝑉² 𝑃𝑎
9.3 Total pressure
𝑝ₜ = 𝑝ₛ + 𝑝ᵥ
Total pressure is therefore the combination of static pressure and velocity pressure.
Engineering note: Never treat static pressure and
total pressure as interchangeable. Their difference
is the velocity pressure (dynamic pressure).
Figure 6 — Static Pressure,
Velocity Pressure, and Total
Pressure Measurement
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 7 of 14
10. Bernoulli’s Equation
Bernoulli’s Equation expresses conservation of mechanical energy for an ideal flow system. In the duct form used
in the chapter:
[ 𝑝/𝛾 + 𝑉²/(2𝑔) ] − ₍𝑑𝑢𝑐𝑡₎ = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
The practical meaning is more useful than the notation: if the air slows down and friction is ignored, velocity
pressure decreases and static pressure increases by the same amount.
𝑉 ↓ → 𝑝ᵥ ↓ → 𝑝ₛ ↑ (𝑖𝑑𝑒𝑎𝑙, 𝑛𝑜 − 𝑙𝑜𝑠𝑠 𝑐𝑎𝑠𝑒)
𝑉 ↑ → 𝑝ᵥ ↑ → 𝑝ₛ ↓ (𝑖𝑑𝑒𝑎𝑙, 𝑛𝑜 − 𝑙𝑜𝑠𝑠 𝑐𝑎𝑠𝑒)
11. Static Pressure Regain
When a duct expands, the cross-sectional area increases. From continuity, velocity decreases. The corresponding
reduction in velocity pressure can be converted partly into static pressure when losses are neglected.
𝐴 ↑ → 𝑉 ↓ → 𝑝ᵥ ↓ → 𝑝ₛ ↑
This recovery is called static pressure regain. Real systems always have losses, so the actual recovery is less than
the ideal amount.
Engineering note: Static pressure regain is not the same as pressure magically appearing. It is an energy
conversion: some kinetic energy is converted into static pressure as the air slows down.
12. Standard Air and the Psychrometric Chart
12.1 Standard air
The chapter uses standard air as a reference condition for air-system calculations and performance data. Under
the stated standard condition, air density is approximately 1.204 kg/m³ at 20°C and 101.325 kPa.
𝜌ₛₜ𝑑 ≈ 1.204 𝑘𝑔/𝑚³
This reference allows engineers to use standardized fan and duct charts. When project conditions differ
significantly from standard conditions, correction may be required.
12.2 Psychrometric chart
The psychrometric chart is introduced as a way of representing the thermodynamic state of moist air. It
organizes quantities such as dry-bulb temperature, humidity ratio, relative humidity, and specific volume on one
graphical field.
Figure 7 — Psychrometric Chart
Engineering note: The chart
becomes much more powerful
later when we analyze heating,
cooling, humidification,
dehumidification, and mixing
processes. In this first lecture,
focus on understanding why air
properties change with
temperature and moisture.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 8 of 14
Figure 8 — Psychrometric Chart: Temperature,
Humidity Ratio, and Specific Volume
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 9 of 14
13. Duct Friction and Pressure Loss
Real duct systems are not frictionless. Air loses mechanical energy because of wall roughness and because of
joints, fittings, equipment, and outlets.
The Darcy-Weisbach equation is introduced in the supplied chapter for frictional pressure loss:
𝛥𝑝𝑓 = 𝑓 (𝐿/𝐷ₕ) (𝜌 𝑉²/2)
where f is the friction factor, L is duct length, Dₕ is hydraulic diameter, ρ is air density, and V is average velocity.
13.1 What the equation tells the engineer
• Longer ducts produce more friction loss.
• Higher velocity produces much greater pressure loss.
• Larger hydraulic diameter generally reduces the friction effect for a given flow condition.
• Surface roughness affects the friction factor.
Engineering note: This is the physical reason that duct sizing is an optimization problem. Very small ducts
may reduce material cost but can create high velocity, high pressure loss, fan energy, and noise.
14. Reynolds Number and Friction Factor
Flow regime affects the friction factor. The chapter introduces Reynolds number as a dimensionless indicator of
the relative importance of inertial and viscous effects:
𝑅𝑒 = 𝜌 𝑉 𝐷 / 𝜇
For laminar flow, the chapter gives:
𝑓 = 64 / 𝑅𝑒
The key idea is the chain:
𝑅𝑒𝑦𝑛𝑜𝑙𝑑𝑠 𝑛𝑢𝑚𝑏𝑒𝑟 → 𝑓𝑙𝑜𝑤 𝑟𝑒𝑔𝑖𝑚𝑒 → 𝑓𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟 → 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝑙𝑜𝑠𝑠
15. Moody Chart and Friction Charts
The Moody chart relates Reynolds number, relative roughness, and friction factor. It is a graphical tool for
determining the friction factor required in the Darcy-Weisbach equation.
For HVAC design, friction charts are also convenient because they can combine airflow, duct dimensions,
velocity, and friction loss into a practical design tool. The supplied chapter shows an ASHRAE friction chart for
standard air.
Engineering note: Do not treat a friction chart as a black box. Understand first what it represents: it is a
graphical expression of the relationship between flow, duct geometry, roughness, velocity, and pressure
loss.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 10 of 14
Figure 9 — Moody Diagram: Reynolds Number, Relative Roughness, and Friction Factor
16. System Constant and System Curve
For a fixed system, the pressure drop is approximately proportional to the square of airflow. The chapter
presents the relationship as:
𝛥𝑝 = 𝐾 𝑄²
where K is the system constant and Q is volume flow rate in consistent units.
𝑄 = 𝐶ₛ √𝛥𝑝
The practical consequence is extremely important: if airflow is doubled, the system pressure drop is
approximately four times larger.
𝑄₂ = 2𝑄₁ → 𝛥𝑝₂ ≈ 4 𝛥𝑝₁
16.1 Why these matters for fans
A fan must operate against the resistance of the connected system. Because system resistance rises strongly
with airflow, a fan does not simply provide a fixed amount of air regardless of pressure. The actual operating
point later comes from the interaction between the fan curve and the system curve.
17. Density and Altitude Effects
Standard psychrometric charts and equipment performance data generally assume standard air and sea-level
operation. At higher elevations, air density is lower, and equipment performance can change.
The supplied chapter therefore provides altitude correction factors for several types of equipment and
recommends using appropriate references or manufacturer data when operating at significant altitude.
Engineering note: The engineering rule is simple: if the project is at a meaningful elevation, check whether
the manufacturer’s performance data and the design calculations require an altitude correction.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 11 of 14
18. Integrated Engineering View
The most useful way to remember this chapter is to connect the equations into one physical chain:
𝐹𝑙𝑜𝑤 𝑟𝑎𝑡𝑒 𝑄 → 𝑑𝑢𝑐𝑡 𝑎𝑟𝑒𝑎 𝐴 → 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑉
𝑉𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑉 → 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝑝ᵥ
𝑆𝑡𝑎𝑡𝑖𝑐 + 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒 → 𝑡𝑜𝑡𝑎𝑙 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒
𝑉𝑒𝑙𝑜𝑐𝑖𝑡𝑦 + 𝑔𝑒𝑜𝑚𝑒𝑡𝑟𝑦 + 𝑟𝑜𝑢𝑔ℎ𝑛𝑒𝑠𝑠 → 𝑓𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑙𝑜𝑠𝑠
𝐹𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑙𝑜𝑠𝑠 𝑜𝑓 𝑎𝑙𝑙 𝑐𝑜𝑚𝑝𝑜𝑛𝑒𝑛𝑡𝑠 → 𝑠𝑦𝑠𝑡𝑒𝑚 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒
𝑆𝑦𝑠𝑡𝑒𝑚 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 + 𝑑𝑒𝑠𝑖𝑔𝑛 𝑎𝑖𝑟𝑓𝑙𝑜𝑤 → 𝑓𝑎𝑛 𝑟𝑒𝑞𝑢𝑖𝑟𝑒𝑚𝑒𝑛𝑡
Once this chain becomes intuitive, later topics such as duct sizing, external static pressure, fan selection, and air-
terminal selection become much easier to follow.
19. Practical Example
Assume a supply duct carries 2.0 m³/s of air and has a cross-sectional area of 0.50 m².
𝑉 = 𝑄/𝐴 = 2.0 / 0.50 = 4.0 𝑚/𝑠
Using the standard-air velocity-pressure relation:
𝑝ᵥ = 0.602(4.0)² ≈ 9.63 𝑃𝑎
Now reduce the duct area to 0.25 m² while keeping the same airflow:
𝑉₂ = 𝑄/𝐴₂ = 2.0 / 0.25 = 8.0 𝑚/𝑠
𝑝ᵥ₂ = 0.602(8.0)² ≈ 38.5 𝑃𝑎
The velocity doubled, while the velocity pressure became about four times larger. This illustrates why duct
reductions can create large pressure consequences.
20. Common Errors New HVAC Engineers Make
• Confusing kg/s with m³/s or L/s.
• Using Celsius directly in absolute-temperature ratios.
• Calling static pressure “total pressure.”
• Forgetting that velocity changes when duct area changes.
• Ignoring air-density changes when conditions differ significantly from standard air.
• Assuming pressure loss rises linearly with airflow in a fixed system.
• Selecting a fan without accounting for the pressure resistance of the complete air system.
21. Key Equations
Quantity Equation
Density 𝜌 = 𝑚/𝑉
Specific volume 𝑣 = 1/𝜌
Hydrostatic pressure 𝛥𝑝 = 𝛾 𝛥ℎ
Continuity 𝜌₁𝐴₁𝑉₁ = 𝜌₂𝐴₂𝑉₂
Constant-density continuity 𝐴₁𝑉₁ = 𝐴₂𝑉₂
Air-density ratio at constant pressure 𝜌₁/𝜌₂ = 𝑇₂/𝑇₁
Mixed-air temperature 𝑇ₘ = [𝐿₁𝑇₁ + 𝐿₂𝑇₂]/[𝐿₁ + 𝐿₂]
Velocity pressure 𝑝ᵥ = 𝜌𝑉²/2
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 12 of 14
Standard-air velocity pressure 𝑝ᵥ = 0.602𝑉² 𝑃𝑎
Total pressure 𝑝ₜ = 𝑝ₛ + 𝑝ᵥ
Darcy-Weisbach friction loss 𝛥𝑝_𝑓 = 𝑓(𝐿/𝐷ₕ)(𝜌𝑉²/2)
Reynolds number 𝑅𝑒 = 𝜌𝑉𝐷/𝜇
Laminar friction factor 𝑓 = 64/𝑅𝑒
Fixed-system relation 𝛥𝑝 = 𝐾𝑄²
22. Summary
This chapter establishes the fluid-mechanics foundation needed for HVAC air-system design. The essential ideas
are conservation of mass, conservation of energy, the relationship between static and velocity pressure, and the
fact that real ducts create resistance.
For a fixed system, the pressure drop rises approximately with the square of airflow. Air density changes with
temperature and altitude, and duct pressure loss depends on velocity, geometry, length, roughness, and flow
regime.
Engineering note: Do not memorize the formulas in isolation. Be able to explain what happens physically
when a duct gets smaller, airflow increases, air is heated, or system resistance changes. That is the level of
understanding expected before moving into detailed duct design and fan selection.
23. References
• ASHRAE. 2009. ASHRAE Handbook—Fundamentals. Atlanta: American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
• Carrier. 1967. Altitude Effects. Syracuse, NY: Carrier Corp.
• Moody, L. 1944. Friction factors for pipe flow. ASME Transactions. New York: American Society of
Mechanical Engineers.
• Wright, D. 1945. A new friction chart for round ductwork. ASHVE Transactions. Atlanta: American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc.
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 13 of 14
24. Skill Development Exercises for Chapter I
Complete these questions by writing your answers on the worksheets at the back of this book.
I-1 In Figure 1-6, area A₁ = 2 m², area A₂ = 1.25 m² and velocity V₁ = 10 m/s. Calculate V₂ (m/s).
a) 16 m/s b) 25.6 m/s c) 7.5 m/s d) 12.6 m/s
I-2 The total pressure at a certain point in a system is determined to be 1.25 kPa, and the static pressure at that
point is determined to be 500 Pa. What is the velocity pressure (Pa) at that point?
a) 1.75 b) 1 c) 750 d) 250
I-3 Which of the following is the most correct definition of static pressure regain?
a) as the velocity of an airstream decreases, the static pressure increases.
b) as the velocity of an enclosed airstream decreases due to friction, the static pressure increases.
c) friction reduces static pressure, while velocity pressure increases with reduction in duct size.
I-4 An air-handling system is determined to have a 1500 Pa pressure drop through the system at a flow of 4000
L/s. What is the system constant?
a) 2.7 b) 6000 c) 77.4 d) 103
I-5 The product of fluid pressure and specific volume is __________?
a) internal energy b) Reynolds number (Re)
c) kinetic energy d) flow work
e) viscosity
I-6 A water manometer measures __________.
a) velocity b) pressure c) temperature d) all of the above
I-7 Fan pressures are typically indicated in what units?
a) Pa b) kg/m² c) N/m d) none of the above
I-8 If the cross-sectional area of a duct decreases in size, the velocity of an airstream passing through the duct
increases.
a) True b) False
I-9 Air passes through a length of inaccessible duct with a constant cross-sectional area. You suspect that there
is a serious leak in the duct. The velocity pressure drops from 200 to 160 Pa along the suspect section of duct.
Approximately what percentage of air is being lost through the leak?
a) 5% b) 10% c) 20% d) 41%
HVAC System Design — Advanced Engineering ASHRAE-ALIGNED
Eng. Ali Uday Harobey Page 14 of 14
I-10 2000 L/s of outdoor air at 2°C is drawn in over a heater and delivered into the building at 24°C. What
volume of air is delivered?
a) 1851 L/s b) 2000 L/s c) 2079 L/s d) 2160 L/s
I-11 In an air-conditioning system, 15 m³/s of return air at 25°C is mixing with 2.3 m³/s of outdoor air at 35°C.
What is the approximate resulting volume and temperature?
a) 17.3 m³/s, 22.7°C b) 17.3 m³/s, 29.9°C
c) 17.3 m³/s, 26.3°C d) 17.3 m³/s, 33.7°C