APTRANSCO       Wadapally 132/33 kvSS100% Reliability Against Contamination Induced Flashovers       with Dow Corning Sylg...
Wadapally 132 kvSS equipments before application of    Rationale for application of Sylgard HVIC+                         ...
Wadapally 132 kvSS and India Cements Plant in the                             BackgroundIndia Cements plant in the backgro...
Isolator Switches being coated with Sylgard HVIC +                       at Wadapally 132 kvSS132 kv Isolator Coating in p...
Hydrophobic Behavior on surface of Sylgard HVIC+      coated insulators at Wadapally 132 kvSS after a rainThe hydrophobic ...
Raasi Feeder during and after the coating of all equipments                   with Sylgard HVIC+While most of the Sylgard ...
Trafo Bushings in-situ and bus strings (new discs) at          Wadapally 132 kvSS Coated with Sylgard HVIC +Over 300 discs...
Sylgard HVIC+ Coated Equipments at Wadapally 132 kvSS                   at evening time                                   ...
Upcoming SlideShare
Loading in …5
×

100% Reliability Against Contamination Induced Flashovers at APTRANSCO 132 kvSS Wadapally Andhra Pradesh India

312 views

Published on

Published in: Technology, Business
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total views
312
On SlideShare
0
From Embeds
0
Number of Embeds
1
Actions
Shares
0
Downloads
9
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

100% Reliability Against Contamination Induced Flashovers at APTRANSCO 132 kvSS Wadapally Andhra Pradesh India

  1. 1. APTRANSCO Wadapally 132/33 kvSS100% Reliability Against Contamination Induced Flashovers with Dow Corning Sylgard HVIC + Coating By Project Sales Corp, Visakhapatnam Some Application Pictures
  2. 2. Wadapally 132 kvSS equipments before application of Rationale for application of Sylgard HVIC+ Wadapally 132 kvSS, located in the India Cement premises at Wadapally, Damacherla Mandal, Nalgonda District. The pictures shows the various levels of contamination and depositions on the surface of the insulators at site. Cement, gypsum and other dusts bonds onto high energy porcelain surfaces making their cleaning difficult. The contaminated surfaces leads to surface leakage currents during rains or early morning dew, develops into dry bands and arcing and leads to eventual flashovers resulting in the loss of revenue to APTRANSCO as well as customer dis-satisfaction. Wadapally is among the high revenue sub-stations in AP due to many large cement plants located in the district which draw power from this industrial feeder sub-station. Please note the build-up also seen on conductor wires. Cleaning of these regularly is neither a feasible nor a cost-effective solution. In the coming slides, you will see pictures of Sylgard HVIC+ application onto these equipments. Sylgard HVIC+ is a proven cost-effective long-term maintenance free solution to prevent contamination build-up and wetting of the insulator surface. Its low molecular weight silicones also ensure contamination particles seating on the insulator surface do not wet and form a conductive solution thus interrupting the flashover process at an early stage.
  3. 3. Wadapally 132 kvSS and India Cements Plant in the BackgroundIndia Cements plant in the background. The APTRANSCO Wadapally 132 kvSS located in thepremises exposes the sub-station to the cement and other raw material dusts, which settles on theinsulator surface, and during light rains or early morning dew these contamination gets wetted andforms a conductive solution resulting in leakage currents, dry bands and eventual flashovers.
  4. 4. Isolator Switches being coated with Sylgard HVIC + at Wadapally 132 kvSS132 kv Isolator Coating in progress in pictures 1-3. Picture 4 and 5 shows the coated isolatorsarranged and kept in the verandah. Interestingly picture 6 shows the composite strings procured byAPTRANSCO kept at Wadapally SS waiting erection. Note the similarity in the look on the surface ofthe composite rubber and Sylgard HVIC+ coated equipment.
  5. 5. Hydrophobic Behavior on surface of Sylgard HVIC+ coated insulators at Wadapally 132 kvSS after a rainThe hydrophobic behavior of Sylgard HVIC+ could be witnessed after a rain during the applicationperiod at Wadapally 132 kvSS. Some pictures here show the water forming into droplets. This doesnot allow the wetting of the insulator surface or formation of continuous conductive film on thesurface.
  6. 6. Raasi Feeder during and after the coating of all equipments with Sylgard HVIC+While most of the Sylgard HVIC+ application were done on new equipments which were subsequentlyerected, some of the equipment at Raasi feeder was coated while the Sylgard HVIC+ coatedequipments were getting erected ensuring no downtime for the application.
  7. 7. Trafo Bushings in-situ and bus strings (new discs) at Wadapally 132 kvSS Coated with Sylgard HVIC +Over 300 discs were coated with Sylgard HVIC+ to be installed in the 132 kv and 33 kv side atWadapally 132/33 kvSS. These coated discs were subsequently strung on the towers by the erectioncontractors. The trafo bushings were cleaned with IPA, primed and coated with Sylgard HVIC + in-situwhile the 33 kv equipment erection was in progress.
  8. 8. Sylgard HVIC+ Coated Equipments at Wadapally 132 kvSS at evening time Sylgard HVIC+ on equipments at Raasi and Chanakya feeders. The Sylgard HVIC+ coated equipments offer a breathtaking site during the evenings with the floodlights in the substation. Isolators, CTs, Lighting Arresters, PTs, and bus- strings were all coated ensuring 100% reliability against contamination induced flashovers for these critical feeder bays.

×