A case study on how IKEA Richmond, British Columbia, reduced their power costs by 5% after installing Legend Power's Automated Voltage Regulator technology.

Legend's system is essentially a "smart transformer" that manages voltage levels coming into a facility from the grid and reduces excess energy consumption from peak voltage periods.

Published in: Technology, Business
  • Be the first to comment

  • Be the first to like this

Case Study: IKEA Richmond Reduces Power Costs by 5%

  1. 1. IKEA Richmond Reduces Power Costs by 5.4% Using Harmonizer Automatic Voltage Regulator Background IKEA’s Richmond, British Columbia facility is a large retail and warehouse shopping facility. Standard operating hours are between 10:00AM and 9:00PM Monday to Friday, and 9:00AM to 8:00PM on weekends with an average of 77 hours of operation per week. Prior to installing an electrical Harmonizer-AVR, IKEA consumed 3,000,000 kWh annually with a peak demand of 725 kW. For the purpose of this case study, these numbers will be used as a benchmark for energy consumption. In 2002, Legend Power completed a beta installation of a 1000 amp Electrical Harmonizer-AVR to help reduce IKEA’s electrical energy consumption. After completing the installation, initial measurement and verification found that IKEA had successfully saved electrical energy. In 2009, Legend Power completed a technical review of this project to verify that the Electrical Harmonizer-AVR installed in 2002 is still effectively saving electrical energy. The results of this review are as follows. Methodology – Auditing & Verification The instantaneous effect of changing the voltage applied to a facility can be easily measured by making measurements for a few seconds before and after the voltage change. For many loads the change in power will happen immediately but in others the load will need time to settle into its new steady state condition. Two sequential measurements within 0.5% of each other are adequate to ensure that transients have passed. If individual loads or circuits cannot be isolated, there is the likelihood that random changes in the total load will make it difficult to isolate the effect of voltage changes. To avoid this, several steps of voltage up and down were analysed to obtain at least two samples where the steps in power are consistent. This allows the relationship between the voltage and power to be obtained at that particular time. The control software was set up so that on power up a series of voltage steps was executed every 30 minutes over a period of four days. These steps were from the actual tap setting to bypass and back. That is to say that the output voltage was never taken too low. If the control was already selected bypass nothing would change. Each of the series of steps were analysed to determine the change in real power produced by the AVR at that time and day. This resulted in 48 samples per day for four days. For the purposes of verification the actual average power over 30 minutes centred on each sample will be divided by the percentage AVR change determined for that
  2. 2. sample to determine the average real and reactive power which would have been drawn without the AVR. Finally the kWh for the complete week was determined by summing the 30 minute samples above, which will yield the actual kWh used and the kWh which would have been used without the AVR. Comparing the two totals allows the weekly percentage effect of the AVR to be calculated. For the purpose of calculating the percent savings, the original energy data from 2002 will be used as a benchmark. Load Profile IKEA’s Richmond location has the following electrical load profile: • 58% Lighting • 29% Motor & HVAC • 6% Office Equipment • 7% Kitchen & Refrigeration Incandescent 5% 2% 12% 6% Fluorescent Metal Halide (50-150 Watts) Metal Halide (175-400 Watts) High Pressure Sodium (70-150 Watts) HVAC and Air moving 29% 33% Office Equipment a Refrigeration Kitchen 4% 5% 4%
  3. 3. Four Day Power Profile The following chart displays IKEA’s power usage with the Harmonizer-AVR on, displayed in blue and the power usage with the Harmonizer-AVR in bypass, displayed in red. The power savings can clearly be seen in the power profile diagram. POWER WITH AVR (kW) POWER AT BYPASS (kW) 600.00 400.00 200.00 0.00 Thursday Friday Saturday Sunday 40 40 40 40 40 40 40 40 40 40 40 10 10 10 10 10 10 10 10 10 10 10 0. 1 1. 2 2. 3 3. 4 4. 5 5. 5 5 5 5 5 5 Four Day Voltage Profile The chart below displays the voltage with the Harmonizer-AVR on, in blue, and with the Harmonizer-AVR in bypass, in red. Significant voltage fluctuations throughout the four day period ranging from 625V to 590V can be clearly seen. Most electrical equipment is designed operate between 630V and 570V, operating equipment on the higher side of 600V, which IKEA was doing prior to installing an Electrical Harmonizer-AVR, will cause equipment to consume more electrical energy than required to operate effectively. VOLTAGE with AVR (V) Voltage at Bypass (V) 630.00 620.00 610.00 600.00 590.00 580.00 570.00 560.00 Thursday Friday Saturday Sunday 40 40 40 40 40 40 40 40 40 40 40 10 10 10 10 10 10 10 10 10 10 10 0. 1 1. 2 2. 3 3. 4 4. 5 5. 5 5 5 5 5 5 Results Nearing seven years after installing an Electrical Harmonizer-AVR, IKEA Richmond continues to save energy through Legend Power’s technology. The load profile in this facility is largely lighting and motor loads with some small electronic loads. Most electronic loads use front end regulated power supplies and do not save energy through
  4. 4. voltage optimization, because of this only lighting and motor & HVAC loads will be considered in this case study. The following provides an explanation on how the savings respective to both motor loads and lighting loads was achieved. Resistive & Lighting Loads These include most heaters and traditional incandescent lighting loads. The instantaneous electrical power consumption is proportional to the square of the instantaneous voltage and the temperature of the resistor typically changes much slower than variations in the voltage. This means that the average power can easily controlled via the voltage, irrespective of the waveform. It should be noted that some loads are temperature dependent. An incandescent lamp typically draws several times its normal current for the brief interval until the filament warms up. The useful light output and lamp life are also not straightforward functions of voltage. At low voltages a lamp will last a long time but not be very bright. At high voltages a lamp will be better at converting electricity into visible light but burn out quickly. Many heating loads are thermostatically controlled. This means that although controlling the voltage will control the instantaneous power the average power and energy consumed will be unchanged since the heater at lower voltage will simply rum for longer at a lower heat output. The initial facility audit performed in 2007 prior to installing an Electrical Harmonizer- AVR included an isolated voltage reduction of 6% on the buildings lighting loads which revealed an 8.9% instantaneous power savings. Although a voltage optimization simulation was not performed as part of this case study, Legend Power does not see a reason why voltage optimization would not reduce power by 8.9% on the buildings lighting loads. Motor Loads Traditional induction motor loads directly connected to the AC line draw real power which goes into supplying the mechanical output and also the iron and copper losses in the motor. There is also a reactive power drawn to maintain the magnetic flux in the machine, which reduces the power factor. The magnetic characteristics of the motor also mean that harmonic currents are drawn from the supply. The effect of voltage regulation on this complex load is not straightforward. In general the rated conditions given on the nameplate do not represent the most efficient point for motor operation and many mechanical loads are variable and/or partial. The higher the voltage the higher the reactive power demand and the higher the harmonic current
  5. 5. flow. The losses in the iron will also increase. The conversion of electrical power into mechanical power is generally lower at lower voltages but only increases negligibly if the voltage is above the rated value and is offset by other losses. In summary, the overall motor efficiency and power factor are usually increased by reducing the motor voltage to its rated value or below. Based on the data gather for this case study, the savings found in the facility’s motor loads and HVAC system is negligible at less than 1% savings. However, by optimizing the voltage it is expected that the motors will have a much longer life expectancy. This life expectancy extension will result in a significant dollar savings by minimizing equipment maintenance and replacement costs. Total Savings As a result of installing an Electrical Harmonizer-AVR, IKEA Richmond has achieved the following results: Annual kWh Savings: 187,000 kWh Average kW Reduction: 21.4 kW Peak kW Reduction: 40 kW Percent Savings: 5.44% Dollar Savings: $10,285 The savings achieved through voltage optimization is expected to persist over the life of the Electrical Harmonizer-AVR. After 10 years, IKEA Richmond will have saved an estimated 1,870,000 kWh of electrical energy and $102,850. ABOUT LEGEND POWER Legend Power Systems Inc. is an electrical energy conservation company that uses a patented device to achieve significant energy conservation through voltage optimization. Installation results have yielded measurable reductions in electric bills, maintenance costs and greenhouse gases. Legend Power helps facilities reduce their environmental footprint while increasing their competitiveness through cost effective and sustainable investments in energy efficiency. Find out if the Legend Power Electrical Harmonizer-AVR is right for your facility. Contact: David Orton sales@legendpower.com 604.420.1500

×