Control Dampers

4,344 views

Published on

Control Dampers - March 211 Illinois Chapter of ASHRAE Meeting.

Published in: Technology
0 Comments
3 Likes
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
4,344
On SlideShare
0
From Embeds
0
Number of Embeds
35
Actions
Shares
0
Downloads
217
Comments
0
Likes
3
Embeds 0
No embeds

No notes for slide

Control Dampers

  1. 1. Air Control Considerations For Energy Conservation & BMS IntegrationPresenter: James Livingston,Ruskin Company
  2. 2. We Will Discuss Control Damper Basics Control Damper Leakage Control Damper Design For Energy Conservation Fire/Smoke Damper Acutators For Energy Conservation
  3. 3. What is a Control Damper?One or more movable bladesMounts in ducts or openingsRegulates the flow of air
  4. 4. Control Damper Applications Air Handling Units (AHU) Mixing Boxes Fresh Air (FA) Return Air (RA) Backdraft Dampers (BD) Zone Mixing Dampers (ZMD)
  5. 5. Parts of a Control Damper Frame Linkage Blade Jamb Seals Blade Seals
  6. 6. Damper Construction Galvanized Aluminum FramesV-Groove Blades Airfoil Blades
  7. 7. V-Groove Blade Dampers• Velocities less than 1500 FPM• 3”- 4” Static Pressure• Noise not a factor
  8. 8. Airfoil Blade Dampers• Velocities above 2000 FPM• Above 3”- 4” Static Pressure• Noise is a concern• Lowest Pressure Drop Required
  9. 9. How Are Fire, Fire/Smoke andSmoke Dampers Different? Maintains fire or smoke walls Fire dampers - steel construction Often have sleeves Usually not controlling air That is changing!
  10. 10. Damper Leakage – What is it?Per AMCA Publication 502, DamperApplication Manual for Heating,Ventilating and Air Conditioning:“The Air Leakage, or SealingPerformance, of a closed damper isthe airflow leakage rate through thedamper for a given pressuredifferential across the damper.”
  11. 11. Leakage
  12. 12. Why Are We Concerned? Code requirements Energy losses due to escaping conditioned air through closed damper Maintaining pressure in system with closed damper
  13. 13. Control Damper Leakage Classes
  14. 14. Smoke & Fire/Smoke DamperLeakage Classes
  15. 15. Damper Leakage Notes Leakage is a function of Pressure, not Airflow Generally expressed or plotted as: Cfm/ft² of damper face area at a certain pressure and with a certain seating torque Metric: m³/second per m² Example for a 24” x 24” opposed blade damper: 32 cfm/ft² @ 4” w.g. pressure with 5 inch- pounds/ft² torque applied holding damper closed
  16. 16. Calculating Leakage Most dampers have published leakage at 1” w.g. Multiply the cfm leakage at 1” times the square root of the desired pressure Example 10 cfm @ 1” w.g. = 20 cfm @ 4” w.g. Be sure the damper is rated for the higher pressure!
  17. 17. International CodesInternational codes have been adopted inAll 50 states, D.C. & Puerto Rico One or more International Codes currently enforced statewide www.iccsafe.org 17
  18. 18. International CodesInternational codes mandate… Occupancy-based ventilation (IMC 403.3) VAV systems shall have controls to monitor and maintain O.A. flow based on 403 requirements, through the entire range of the system (IMC403.3.3) All dampers penetrating the building envelope shall be class 1 leakage rated, not to exceed 4cfm/sf @ 1” w.c. (IMC301.2, IBC1301 & IECC) Motorized dampers required on building envelope penetrations (IECC 502.4.4 & 503.2.4.4) D.O.E. mandates ASHRAE 90.1 as a minimum for all Federal buildings. (IECC 4 CFM Supersedes)
  19. 19. International Codes “The occupant load utilized for design of the ventilation system shall not be less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3”
  20. 20. International Mechanical Code
  21. 21. International Mechanical Code ergy g En rdin tion ega rvaRC onse
  22. 22. International Building Code rgy Ene ding ion R egar rvat Co nse
  23. 23. International Energy Conservation Code
  24. 24. International Energy Conservation Code • Required in all states that have adopted the IBC or IMC. • Addresses OA & EA Damper leakage 4 cfm/ft2 @ 1” w.g. • Economizers Required (503.3.1 & 503.4.1) • Refers to 90.1 for climate zones and as a standard for applications not covered in the code.
  25. 25. ASHRAE 90.1 6.4.3.3.3 Motorized dampers required on OA & EA applications 6.5.1.1 Economizers required
  26. 26. Specifying Low LeakageDampers AMCA 511 Certification Independent testing Verified catalogs Periodic Check Tests
  27. 27. AMCA InternationalCertified Ratings Program… How do you know the product you specified is licensed by AMCA International?There are basically four ways to determine if a product is participating in AMCA International’s Certified Ratings Program. They are: WWW.AMCA.org Manufacture Model # Manufacture’s Catalog (most are online) Certified Ratings Seal on the product (could be too late) Contact AMCA International Phone 847-394-0150 Fax 847-253-0088 Email crp@amca.org 27
  28. 28. AMCA 511 Damper Air Leakage At least two sizes tested 12” x 48” Max width x 36” Up to two more sizes can be tested, 36” max tall AMCA configs 5.4, 5.5 or 5.6 Round dampers Min & Max sizes tested
  29. 29. AMCA 511 Damper Air Leakage AMCA 500 Test StandardFigure 5.5 Leakage & Pressure
  30. 30. Damper Leakage Chart
  31. 31. Damper Leakage Performance
  32. 32. Air Leakage Certification Not the same!Be sure it’s rated for Air Leakage, not just Air Performance!
  33. 33. Energy Saving DamperConstruction Blades Jamb Seals Blade Seals
  34. 34. Blades Galvanized AluminumV-Groove Blades Generally not Class 1 Airfoil BladesClass 1 and 1A available
  35. 35. Airfoil Blades Advantages Best Torsion Performance No Twist Best Closure Seal For All Blade Lengths Class 1 & 1A available
  36. 36. Airfoil vs. “V” Groove Maximums Blade Shape Matters Airfoil 60” Span @ 3.5 w.g. 3000 FPM 3-VEE 48’ Span @ 2.5 w.g. 1500 FPM
  37. 37. Airfoil vs. “V” Groove Pressure DropAirfoil 24” x 24” .07 w.g. @ 2000 FPM3-VEE .19 w.g. @ 2000 FPMAlmost 3 times the Pressure Drop!
  38. 38. Jamb Seals Between ends of blades and jamb frames Metallic or synthetic material Compresses when blades close
  39. 39. Blade Seals Blade Seals Mechanically Locked Inflatable Maintenance Wiper Type No Adhesive or Clip On Style
  40. 40. Insulated Dampers Reduces thermal energy loss Different methods Double airfoil damper - expensive Single airfoil foam injected blades – less expensive Thermal break frames available Class 1 leakage Applications down to -100°F
  41. 41. Combination Louvers Drainable fixed louver & airfoil control damper in same frame Class 1 leakage Meets IECC building envelope leakage requirement! Available w/ most electric actuatorsLouver & Damper Less product cost than separatein One! louver, damper & sleeve Less installation cost 41
  42. 42. Damper Electric Actuators
  43. 43. Electric Actuator Types Actuators are available in three types: 1) Two Position Spring Return 2) Modulating 3) Power Open-Power Closed Can be controlled by BMS Most Damper applications call for Two Position Spring Return or Modulating
  44. 44. Two PositionLimit to limit operation – does notfloatOpen/close applicationsSpring reverses direction whenpower failsTypically 120V or 24V voltagePower draw for common 175 in/lbmodel 120V – 60 VA driving, 13 VA holding 24V – 40 VA driving, 8 VA holding
  45. 45. ModulatingActuator moves too any point withinits rotation limits to control airflowRequires a control signal 2-10 Vdc or 4-20 mASignal can come from BMS based on: Temperature Pressure Air pollutants and/or occupancyPower draw for common 175 in/lbmodel 24V – 16 VA driving, 5 VA holding
  46. 46. Actuator Installation Options
  47. 47. Modulating Considerations Airflow not linear to blade position
  48. 48. Modulating Considerations Linear flow damper characteristics From AMCA Pub 502 Damper Application Manual
  49. 49. Modulating Fire/Smoke and SmokeDamper Actuators BMS signal controls blade position in normal condition Damper closes fully during fire Damper opens fully to relieve smoke
  50. 50. Modulating Smoke & F/S Dampers
  51. 51. Modulating Smoke & F/S DampersEliminates balancingdampers Less pressure drop Less costUse smoke dampers forreturn air on Air HandlersMaintain floor pressure inmulti floor systems
  52. 52. Modulating Smoke & F/S DampersAdvantage overmanual balancingdampers Modulating actuator goes full-open for smoke purge Smoke system does not have to fight semi- closed manual dampers
  53. 53. 3-Position Smoke & F/S Dampers No Control Signal Required Built in potentiometer to 20% to 100% balance position Allows the damper to be SET at any position for BALANCING AIRFLOW under normal operations, open or closed for SMOKE CONTROL and closed as required in the fire area
  54. 54. Summary Current building codes require low leakage dampers Damper construction greatly affects leakage characteristics Modulating actuators can be controlled by BMS to adjust airflow for temperature and IAQ requirements Smoke and Fire/Smoke dampers are available w/ modulating & 3-position actuators
  55. 55. Questions?
  56. 56. Thank You!

×