IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________________
Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 300
FAILURE ANALYSIS OF A POWER TRANSFORMER USING
DISSOLVED GAS ANALYSIS – A CASE STUDY
Ankush Chander1
Nishant2
1
M. Tech Scholar, EEE Department Arni University Indora Himachal Pradesh, India
2
Assistant Professor, EEE Department, Arni University Indora Himachal Pradesh, India
Abstract
Reliable and continued performance of power Transformer is the key to profitable generation and transmission of electric power.
Failure of a large power transformer not only results in the loss of very expensive equipment, but it can cause significant guarantied
damage as well. Replacement of that transformer can take up to a year if the failure is not disastrous and can result in tremendous
revenue losses and fines. A Power Transformer in operation is subjected to various stresses like thermal stress and electrical stress,
resulting in liberation of gases from the hydrocarbon mineral oil which is used as insulant and coolant. Dissolved Gas Analysis is a
technique used to assess incipient faults of the transformer by analyzing specific dissolved gas concentrations arising from the
deterioration of the transformer. DGA is used not only as a diagnostic tool but also to track apparatus failure. In this case study the
fault and defects that occurred in 400kV/220kV/132kV/66kV Sub Station can be found by DGA.
Keywords: Power Transformer, Dissolved Gas Analysis,
----------------------------------------------------------------------***----------------------------------------------------------------------
1. INTRODUCTION
A power transformer is one of the most important and costly
devices in electrical systems. Its importance is attributed
directly to the continuity of power supply, since its loss
through failure or defect means a supply stoppage. This is a
large piece of equipment whose substitution is expensive and
involves a lengthy process [11]. Power transformers, which
are often the most valuable asset in a substation or plant, are
indispensable components of high-voltage equipment for
power generation plants, transmission systems and large
industrial plants [15]. Unexpected failures cause major
disturbances to operating systems, resulting in unscheduled
outages and power delivery problems. Such failures can be the
result of poor maintenance, poor operation, poor protection,
undetected faults, or even severe lightning or short circuits.
Power transformer failure could result in huge economic loss
and unplanned outage of the power system, which may
affect a large number of industries and commercial
customers also Transformer failure will result in great loss in
electrical system. Hence, a well establish maintenance should
be conducted [10]
2. FAILURES ANALYSIS
A typical power transformer has a life expectancy of more
than 30 years. During this time it is obvious that such a device
has several failures, thus needing maintenance to ensure that
the expectancy is fulfilled. Because transformer failures are
responsible for a very high amount of costs, some of the most
important causes of failures in power transformers are shown
in table
Table 2.1 Failure Mode of Transformer
Description Failures Duration
No % TTF ATF
Periodical Test 48 12 80:39:00 1:40:4
9
Services 56 14 88:16:00 1:34:3
4
Protective
Operation
206 50 264:22:0
0
1:17:0
0
Insulation
Problems
16 04 107:40:0
0
6:43:4
5
Others 86 21 113:23:0
0
1:19:0
6
Total 412 100 654:20:0
0
-
Results of Table 2.1 show that protective operation is the
highest failure mode, but average times of the fault is the
lowest, due to their causes are temporary and are removed
after a little time. Further, in Fig.1.1, the percentage of any
type of failures is shown.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________________
Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 301
Fig 2.1 The persentage of Failures
In other hand insulation problems are not too much but they
have the highest average time of faults. The 5th group is
consists of development interruption, bushing faults, tap
changer faults, operator failures, lightning, unknown operation
errors and etc. The most number of faults of this group are
related to Tap Changer failures The main causes of the
Tap changers failures start from sparking and erosion of
the Tap Changer contacts. Moving parts malfunctioning can
also lead to a failure. Eroded contacts produce sparking and
sticking. In off -load Tap Changers long period without
operation, leads to a corrosion and sludge build up which
causes jamming of the moving parts and consequently, a
failure of the Tap Changer. Therefore maintenance and
periodical test and services can be reduced this type of
failures.
3. DISSOLVED GAS ANALYSIS
Gases are formed in oil in the transformer due to natural aging
and at much greater rate as a result of faults and incipient
faults [1] [12]. The type and severity of a fault may often be
inferred from the composition of the gases and the rate at
which they are formed. In the case of an incipient fault, the
gases formed remain partly dissolved in the oil and only in
special cases will free gases be formed. Periodical sampling of
oil from transformer and analysis of the dissolved gases assist
in the detection of faults at an early stage of development and
may enable serious future damage to transformer to be
prevented [2] [9].
The gases involved are hydrogen, some hydrocarbons, carbon
oxides and atmospheric gases. Some of each of these gases
will be formed during normal operation and these amounts are
classified as norm [3]. Fault conditions produce gases in
higher quantity and in different proportions which vary from
the norm, the type and energy of the fault altering the carbon
to hydrogen ratio of oil molecules in specifically related ways
and producing variation in the carbon oxide ratios when solid
insulation is involved [8].
DGA was the first most effective diagnostic test, which was
applied to transformers in service for condition monitoring
[10]. Gases dissolved in oil are analyzed by gas
Chromatography. The technique helps in detecting incipient
faults developing in transformers. DGA is supplemented by
other tests to confirm diagnosis [4]. Partial lists of fault gases
that can be found within a unit are shown in the following
three groups:
Fig 3.1: Gases Presented in Transformer Oil
The major (minor) fault gases can be categorized as follows in
Table 3.1 and Interpretation of rise in gas concentration in
Table 3.2 by the type of material that is involved and the type
of fault present [5]: In this table characterization of various
fault gases has been done and the major/minor faults occurring
due to presence of gases have been shown [18]. If hydrogen
traces found in oil then it resembles corona [14]
Table 3.1 Major/minor fault gases characterization
Corona
Oil H2
Cellulose H2 ,CO, CO2
Pyrolysis
Oil
Low temperature CH4, C2H6
High temperature C2H4, H2 (CH4,C2H6)
Cellulose
Low temperature CO2(CO)
High temperature CO (CO2
Arcing H2, C2 H2, (CH4,
C2H6, C2H4
Table 3.2 Interpretation of rise in gas concentration:
Rise in Gas
Concentration
Interpretation
Nil or not
appreciable
Normal Aging
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________________
Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 302
H2 Corona, Partial Discharge
CH4 & C2H6 Thermal fault of low
temperature upto 300® C
C2H4 With or
Without CH4, C2H6,
H2
Thermal fault of 300® C to
700® C or above
C2H2 with or
Without H2 C2H4
and CH4
Arc or Flashover
The main drawbacks [6] of this conventional method are
unable to predict the fault of a particular transformer owing to
the lack of expert knowledge in them.
4. CASE STUDY DISSOLVED GAS ANALYSIS:
400KV/220KV/132KV/66KV S/S
The case study include on the measurement of gas content in
transformer oil using Dissolved Gas Analysis. The case study
carried out 400 KV Power Transformer, the rating of power
transformer is given bellow:
The details of the transformer are as under: -
a. Rating: 12.5/16 MVA, 66/11 kV
b. Sr.no. 2800061017
c. Make: NGEF
d. Date of Commissioning: 17-07-2003
e. Date of last dehydration of Oil: 2003
The DGA testing results for the above mentioned Power
Transformer are shown in table5.1 given bellow
Table 4.1 DGA Testing Result
Methane trends shows events of sparking and Ethane, carbon
dioxide content is showing local & severe overheating
respectively. However, other gases found within permissible
limits. Periodic testing and regular DGA is recommended for
the Power Transformer, so that proper monitoring can be done
to enhance the life of the Power Transformer. Further, for the
4 years the DGA Trend for the transformer is plotted in the
graph shown in Fig 4.1
Fig 4.1 Yearly Graph Plot for DGA Result
Oil condition of the transformer is analyzed on the basis of
DGA results. It is also seen that by dehydration of oil its BDV
increases as well as the traces of various key gases also.
5. CONCLUSIONS
Dissolved Gas Analysis gives a good basis for a monitoring
system as it can give a general picture of transformer health.
Other parameters can be correlated with DGA to provide the
user with detailed information about the condition of a
transformer. From this work, the critical components can be
carefully maintained. The known causes of failure can help to
improve the equipment reliability. In this paper test results of
DGA has been discussed and investigated and an attempt is
made to find out the cause of fault and its preventive action. It
has been found that proper and scheduled monitoring leads to
enhanced life of Power Transformer and techniques like
dehydration plays an important role in boosting up the
condition of Transformer Oil as well the transformer life.
However, still some advanced condition monitoring
techniques like Partial discharge measurement,
Spectrophotometer and SFRA etc. are not yet adaptive by the
utilities and thus awareness and training on these issues is
required for the betterment of the system
S.
N
Gas Quantity
detected in
ppm
Dated:10-10-
2007
Dated:
10-10-
2009
Dated:
08-10-
2011
Date
d:
30-
07-
2013
1 Methan
e
65 12 14 14
2 Ethane 17 10 11 11
3 Ethylen
e
50 20 18 18
4 Acetyle
ne
ND ND ND ND
5 Carbon
dioxide
350 765 770 770
6 Hydrog
en
25 ND ND ND
7 TGC,
per 100
ml
of oil.
12.15 ml 11.85
ml
11.90
ml
11.90
ml
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________________
Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 303
REFERENCES
[1]. M. Wang, A.J. Vandermaar, and K.D. Srivastava,
“Review of condition assessment of power transformers in
service,” Electrical Insulation Magazine, IEEE vol.18, pp. 12
– 25, Nov.-Dec. 2002
[2]. IEEE guide for the interpretation of gases generated in oil-
immersed transformers, IEEE Standard C57.104-1991, July
1992.
[3]. S.D. Myers, J.J. Kelly, and R.H. Parrish, A Guide To
Transformer Maintenance. United Stated of America: S.D.
Myers Inc, 1981, p. 323
[4]. M. Arshad, S.M. Islam, and A. Khalig, “Power
transformer critical diagnostics for reliability and life
extension,” Electrical and Computer Engineering, IEEE vol. 2,
pp.625-628, May 2004.
[5]. R.A. Jongen, P.H.F. Morshuis, J.J. Smit, A.L.J. Janssen,
and E.Gulski, “Failure data of power transformers as input for
statistical failure analysis,” presented at the 15th Int. Conf.
High Voltage Engineering, Slovenia, 2007.
[6]. Statistical and Neural Network Analysis of Dissolved
gases in power Transformers. K F Thang, R K aggarwal, D G
ESP,A J McGrail, Dielectric Materials, Measurement and
Applications ,Conference Publication No.473,IEE2000
[7]. CIGRE. Life management techniques for power
transformers. Technical Brochure 227. Paris June 2003
[8]. Indian standard method of Evaluating of gases in oil filled
Electrical Equipments. IS: 10593 - 1983.
[9]. IEEE Guide for the Interpretation of Gases Generated in
Oil Immersed Transformers, ANSI/IEEE Standard C57. 1 04-
1991.
[10]. Sanchez and Lav, Artificial Neural Network Newyork,
USA: IEEE press, 1992.
[11]. L.Haykin, Neural Networks: A comprehensive
Foundation. Montreal, Canada: Macmillan College Publishing
Company Inc., 1994
[12]. Wang, M., Vandermaar, A.J., Srivastava, K.D. Review
of condition assessment of power transformers in service.
Electrical Insulation Magazine, IEEE Nov.-Dec. 2002 18(6):
p. 12 -25
[13]. A. De Pablo, A.M., New guidelines for furans analysis as
well as dissolved gas analysis in oil-filled transformers, in the
International Council on Large Electric Systems (CIGRÉ), .
1996: Paris, France
[14]. E. Gockenbach, H.B., Diagnostic methods for
transformers on-site, in Proc. Int. Symp. Elec. Insul. Matls.,
1998: Toyohashi, Japan. p. 2~36.
[15]. Kachler, A.J., Diagnostic and monitoring technology for
large power transformers, in CIGRé SC 12, Sydney
Colloquium, . 1997: Sydney, Australia
[16]. R.J. Schwabe, et.al., On-line diagnostics of oil paper
insulated instrument transformers, in theInternational Council
on Large Electric Systems (CIGRé), . 2000: Paris, France
[17]. KIRTLEY, J.L., Jr., HAGMAN, Wayne H., et.al,
Monitoring the health of power transformers. Computer
Applications in Power, IEEE Jan. 1996 9(1): p. 18-23.
[18]. A. Mollmann, B.P., New guidelines for interpretation of
dissolved gas analysis in oil filled transformers. Electra,
1999(186): p. 30~51.

More Related Content

What's hot

Fault interpretation for power transformer using dissolved gas
Fault interpretation for power transformer using dissolved gasFault interpretation for power transformer using dissolved gas
Fault interpretation for power transformer using dissolved gasMohammad Sohaib
 
Practicing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGAPracticing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGATRANSEQUIPOS S.A.
 
Maitenance of transformer
Maitenance of transformerMaitenance of transformer
Maitenance of transformerRohit Dave
 
Transformer oil analysis
Transformer oil analysisTransformer oil analysis
Transformer oil analysisMolla Morshad
 
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...TRANSEQUIPOS S.A.
 
Biodiesel from Waste Cooking Oil
Biodiesel from Waste Cooking OilBiodiesel from Waste Cooking Oil
Biodiesel from Waste Cooking OilTuhin Samanta
 
Transformer Maintenance
Transformer Maintenance Transformer Maintenance
Transformer Maintenance Molla Morshad
 
Cng as alternate to gasoline
Cng as alternate to gasolineCng as alternate to gasoline
Cng as alternate to gasolineShailendra Gohil
 
Renewable Energy for Sustainable Development of Nepal
Renewable Energy for Sustainable Development of NepalRenewable Energy for Sustainable Development of Nepal
Renewable Energy for Sustainable Development of NepalKushal Gurung
 
Ethanol Blended Petrol and Diesel
Ethanol Blended Petrol and Diesel Ethanol Blended Petrol and Diesel
Ethanol Blended Petrol and Diesel ahmdfurkan
 
Transformer oil-specifications new
Transformer oil-specifications newTransformer oil-specifications new
Transformer oil-specifications newMolla Morshad
 
Summer Training Report at IOCL (chemical engineering)
Summer Training Report at IOCL (chemical engineering)Summer Training Report at IOCL (chemical engineering)
Summer Training Report at IOCL (chemical engineering)Gaurav Singh
 
summer training report of Iocl,haldia
summer training report of Iocl,haldiasummer training report of Iocl,haldia
summer training report of Iocl,haldiasumanscience
 
Industrial training at Indian Oil Corporation Limited (IOCL) Noonmati
Industrial training at Indian Oil Corporation Limited (IOCL) NoonmatiIndustrial training at Indian Oil Corporation Limited (IOCL) Noonmati
Industrial training at Indian Oil Corporation Limited (IOCL) NoonmatiPriyam Jyoti Borah
 
Furan Testing of Transformers Oil
Furan Testing of Transformers OilFuran Testing of Transformers Oil
Furan Testing of Transformers OilNitish Kumar
 
Transformer oil analysis
Transformer oil analysisTransformer oil analysis
Transformer oil analysiscomayl
 
Combined Cycle Power Plant
Combined Cycle Power PlantCombined Cycle Power Plant
Combined Cycle Power PlantMd. Rimon Mia
 

What's hot (20)

Fault interpretation for power transformer using dissolved gas
Fault interpretation for power transformer using dissolved gasFault interpretation for power transformer using dissolved gas
Fault interpretation for power transformer using dissolved gas
 
Practicing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGAPracticing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGA
 
Maitenance of transformer
Maitenance of transformerMaitenance of transformer
Maitenance of transformer
 
Transformer oil analysis
Transformer oil analysisTransformer oil analysis
Transformer oil analysis
 
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...
Diagnóstico por cromatografía de gases basado en triángulos y pentágonos de D...
 
Hydrogen fuel cell
Hydrogen fuel cellHydrogen fuel cell
Hydrogen fuel cell
 
Biodiesel from Waste Cooking Oil
Biodiesel from Waste Cooking OilBiodiesel from Waste Cooking Oil
Biodiesel from Waste Cooking Oil
 
Transformer Maintenance
Transformer Maintenance Transformer Maintenance
Transformer Maintenance
 
Cng as alternate to gasoline
Cng as alternate to gasolineCng as alternate to gasoline
Cng as alternate to gasoline
 
Renewable Energy for Sustainable Development of Nepal
Renewable Energy for Sustainable Development of NepalRenewable Energy for Sustainable Development of Nepal
Renewable Energy for Sustainable Development of Nepal
 
Cng
CngCng
Cng
 
Ethanol Blended Petrol and Diesel
Ethanol Blended Petrol and Diesel Ethanol Blended Petrol and Diesel
Ethanol Blended Petrol and Diesel
 
Transformer oil-specifications new
Transformer oil-specifications newTransformer oil-specifications new
Transformer oil-specifications new
 
Summer Training Report at IOCL (chemical engineering)
Summer Training Report at IOCL (chemical engineering)Summer Training Report at IOCL (chemical engineering)
Summer Training Report at IOCL (chemical engineering)
 
summer training report of Iocl,haldia
summer training report of Iocl,haldiasummer training report of Iocl,haldia
summer training report of Iocl,haldia
 
Industrial training at Indian Oil Corporation Limited (IOCL) Noonmati
Industrial training at Indian Oil Corporation Limited (IOCL) NoonmatiIndustrial training at Indian Oil Corporation Limited (IOCL) Noonmati
Industrial training at Indian Oil Corporation Limited (IOCL) Noonmati
 
Furan Testing of Transformers Oil
Furan Testing of Transformers OilFuran Testing of Transformers Oil
Furan Testing of Transformers Oil
 
Transformer oil analysis
Transformer oil analysisTransformer oil analysis
Transformer oil analysis
 
Combined Cycle Power Plant
Combined Cycle Power PlantCombined Cycle Power Plant
Combined Cycle Power Plant
 
Amines
AminesAmines
Amines
 

Similar to Failure analysis of a power transformer using dissolved gas analysis – a case study

IRJET- Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...
IRJET-  	  Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...IRJET-  	  Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...
IRJET- Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...IRJET Journal
 
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...eSAT Publishing House
 
Energy saving opportunities in oxygen plant–a case study
Energy saving opportunities in oxygen plant–a case studyEnergy saving opportunities in oxygen plant–a case study
Energy saving opportunities in oxygen plant–a case studyeSAT Publishing House
 
Energy saving opportunities in oxygen plant a case study
Energy saving opportunities in oxygen plant   a case studyEnergy saving opportunities in oxygen plant   a case study
Energy saving opportunities in oxygen plant a case studyeSAT Journals
 
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...ijics
 
Analysis of interference methods on transformers based on the results of dis...
Analysis of interference methods on transformers based on the  results of dis...Analysis of interference methods on transformers based on the  results of dis...
Analysis of interference methods on transformers based on the results of dis...IJECEIAES
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...Alexander Decker
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Alexander Decker
 
01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.pptvikram desai
 
Analysis of various sensors to measure the physical parameters of the oil sto...
Analysis of various sensors to measure the physical parameters of the oil sto...Analysis of various sensors to measure the physical parameters of the oil sto...
Analysis of various sensors to measure the physical parameters of the oil sto...IRJET Journal
 
Experimental Inspection by using the Effect of Magnetic Field on the Performa...
Experimental Inspection by using the Effect of Magnetic Field on the Performa...Experimental Inspection by using the Effect of Magnetic Field on the Performa...
Experimental Inspection by using the Effect of Magnetic Field on the Performa...IRJET Journal
 
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...eSAT Publishing House
 
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...eSAT Journals
 
Energy Auditing of Thermal Power plant
Energy Auditing of Thermal Power plantEnergy Auditing of Thermal Power plant
Energy Auditing of Thermal Power plantIRJET Journal
 
Performance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizerPerformance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizereSAT Journals
 
Performance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizerPerformance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizerLaukik Raut
 
Experimental investigation of performance and
Experimental investigation of performance andExperimental investigation of performance and
Experimental investigation of performance andeSAT Publishing House
 
IRJET- Static Structural and Modal Analysis of Secondary Air Flow System
IRJET- Static Structural and Modal Analysis of Secondary Air Flow SystemIRJET- Static Structural and Modal Analysis of Secondary Air Flow System
IRJET- Static Structural and Modal Analysis of Secondary Air Flow SystemIRJET Journal
 

Similar to Failure analysis of a power transformer using dissolved gas analysis – a case study (20)

H010514852
H010514852H010514852
H010514852
 
Agc wp-sustelecpwr
Agc wp-sustelecpwrAgc wp-sustelecpwr
Agc wp-sustelecpwr
 
IRJET- Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...
IRJET-  	  Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...IRJET-  	  Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...
IRJET- Combined Dissolved Gas Analysis: A Prescient Methodology for Recog...
 
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...
Effect of nanofluids and mass flow rate of air on heat transfer rate in autom...
 
Energy saving opportunities in oxygen plant–a case study
Energy saving opportunities in oxygen plant–a case studyEnergy saving opportunities in oxygen plant–a case study
Energy saving opportunities in oxygen plant–a case study
 
Energy saving opportunities in oxygen plant a case study
Energy saving opportunities in oxygen plant   a case studyEnergy saving opportunities in oxygen plant   a case study
Energy saving opportunities in oxygen plant a case study
 
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...
MULTIPLE LINEAR REGRESSION ANALYSIS FOR PREDICTION OF BOILER LOSSES AND BOILE...
 
Analysis of interference methods on transformers based on the results of dis...
Analysis of interference methods on transformers based on the  results of dis...Analysis of interference methods on transformers based on the  results of dis...
Analysis of interference methods on transformers based on the results of dis...
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...
 
01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt
 
Analysis of various sensors to measure the physical parameters of the oil sto...
Analysis of various sensors to measure the physical parameters of the oil sto...Analysis of various sensors to measure the physical parameters of the oil sto...
Analysis of various sensors to measure the physical parameters of the oil sto...
 
Experimental Inspection by using the Effect of Magnetic Field on the Performa...
Experimental Inspection by using the Effect of Magnetic Field on the Performa...Experimental Inspection by using the Effect of Magnetic Field on the Performa...
Experimental Inspection by using the Effect of Magnetic Field on the Performa...
 
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
 
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
Analysis of fuel consumption and oxides of nitrogen using oxygen enriched air...
 
Energy Auditing of Thermal Power plant
Energy Auditing of Thermal Power plantEnergy Auditing of Thermal Power plant
Energy Auditing of Thermal Power plant
 
Performance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizerPerformance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizer
 
Performance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizerPerformance analysis of ic engine using air energizer
Performance analysis of ic engine using air energizer
 
Experimental investigation of performance and
Experimental investigation of performance andExperimental investigation of performance and
Experimental investigation of performance and
 
IRJET- Static Structural and Modal Analysis of Secondary Air Flow System
IRJET- Static Structural and Modal Analysis of Secondary Air Flow SystemIRJET- Static Structural and Modal Analysis of Secondary Air Flow System
IRJET- Static Structural and Modal Analysis of Secondary Air Flow System
 

More from eSAT Publishing House

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnameSAT Publishing House
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...eSAT Publishing House
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnameSAT Publishing House
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...eSAT Publishing House
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaeSAT Publishing House
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingeSAT Publishing House
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...eSAT Publishing House
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...eSAT Publishing House
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...eSAT Publishing House
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a revieweSAT Publishing House
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...eSAT Publishing House
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard managementeSAT Publishing House
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallseSAT Publishing House
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...eSAT Publishing House
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...eSAT Publishing House
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaeSAT Publishing House
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structureseSAT Publishing House
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingseSAT Publishing House
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...eSAT Publishing House
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...eSAT Publishing House
 

More from eSAT Publishing House (20)

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
 

Recently uploaded

Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsSachinPawar510423
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitterShivangiSharma879191
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catcherssdickerson1
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the weldingMuhammadUzairLiaqat
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptJasonTagapanGulla
 

Recently uploaded (20)

Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documents
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the welding
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.ppt
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

Failure analysis of a power transformer using dissolved gas analysis – a case study

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________________ Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 300 FAILURE ANALYSIS OF A POWER TRANSFORMER USING DISSOLVED GAS ANALYSIS – A CASE STUDY Ankush Chander1 Nishant2 1 M. Tech Scholar, EEE Department Arni University Indora Himachal Pradesh, India 2 Assistant Professor, EEE Department, Arni University Indora Himachal Pradesh, India Abstract Reliable and continued performance of power Transformer is the key to profitable generation and transmission of electric power. Failure of a large power transformer not only results in the loss of very expensive equipment, but it can cause significant guarantied damage as well. Replacement of that transformer can take up to a year if the failure is not disastrous and can result in tremendous revenue losses and fines. A Power Transformer in operation is subjected to various stresses like thermal stress and electrical stress, resulting in liberation of gases from the hydrocarbon mineral oil which is used as insulant and coolant. Dissolved Gas Analysis is a technique used to assess incipient faults of the transformer by analyzing specific dissolved gas concentrations arising from the deterioration of the transformer. DGA is used not only as a diagnostic tool but also to track apparatus failure. In this case study the fault and defects that occurred in 400kV/220kV/132kV/66kV Sub Station can be found by DGA. Keywords: Power Transformer, Dissolved Gas Analysis, ----------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION A power transformer is one of the most important and costly devices in electrical systems. Its importance is attributed directly to the continuity of power supply, since its loss through failure or defect means a supply stoppage. This is a large piece of equipment whose substitution is expensive and involves a lengthy process [11]. Power transformers, which are often the most valuable asset in a substation or plant, are indispensable components of high-voltage equipment for power generation plants, transmission systems and large industrial plants [15]. Unexpected failures cause major disturbances to operating systems, resulting in unscheduled outages and power delivery problems. Such failures can be the result of poor maintenance, poor operation, poor protection, undetected faults, or even severe lightning or short circuits. Power transformer failure could result in huge economic loss and unplanned outage of the power system, which may affect a large number of industries and commercial customers also Transformer failure will result in great loss in electrical system. Hence, a well establish maintenance should be conducted [10] 2. FAILURES ANALYSIS A typical power transformer has a life expectancy of more than 30 years. During this time it is obvious that such a device has several failures, thus needing maintenance to ensure that the expectancy is fulfilled. Because transformer failures are responsible for a very high amount of costs, some of the most important causes of failures in power transformers are shown in table Table 2.1 Failure Mode of Transformer Description Failures Duration No % TTF ATF Periodical Test 48 12 80:39:00 1:40:4 9 Services 56 14 88:16:00 1:34:3 4 Protective Operation 206 50 264:22:0 0 1:17:0 0 Insulation Problems 16 04 107:40:0 0 6:43:4 5 Others 86 21 113:23:0 0 1:19:0 6 Total 412 100 654:20:0 0 - Results of Table 2.1 show that protective operation is the highest failure mode, but average times of the fault is the lowest, due to their causes are temporary and are removed after a little time. Further, in Fig.1.1, the percentage of any type of failures is shown.
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________________ Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 301 Fig 2.1 The persentage of Failures In other hand insulation problems are not too much but they have the highest average time of faults. The 5th group is consists of development interruption, bushing faults, tap changer faults, operator failures, lightning, unknown operation errors and etc. The most number of faults of this group are related to Tap Changer failures The main causes of the Tap changers failures start from sparking and erosion of the Tap Changer contacts. Moving parts malfunctioning can also lead to a failure. Eroded contacts produce sparking and sticking. In off -load Tap Changers long period without operation, leads to a corrosion and sludge build up which causes jamming of the moving parts and consequently, a failure of the Tap Changer. Therefore maintenance and periodical test and services can be reduced this type of failures. 3. DISSOLVED GAS ANALYSIS Gases are formed in oil in the transformer due to natural aging and at much greater rate as a result of faults and incipient faults [1] [12]. The type and severity of a fault may often be inferred from the composition of the gases and the rate at which they are formed. In the case of an incipient fault, the gases formed remain partly dissolved in the oil and only in special cases will free gases be formed. Periodical sampling of oil from transformer and analysis of the dissolved gases assist in the detection of faults at an early stage of development and may enable serious future damage to transformer to be prevented [2] [9]. The gases involved are hydrogen, some hydrocarbons, carbon oxides and atmospheric gases. Some of each of these gases will be formed during normal operation and these amounts are classified as norm [3]. Fault conditions produce gases in higher quantity and in different proportions which vary from the norm, the type and energy of the fault altering the carbon to hydrogen ratio of oil molecules in specifically related ways and producing variation in the carbon oxide ratios when solid insulation is involved [8]. DGA was the first most effective diagnostic test, which was applied to transformers in service for condition monitoring [10]. Gases dissolved in oil are analyzed by gas Chromatography. The technique helps in detecting incipient faults developing in transformers. DGA is supplemented by other tests to confirm diagnosis [4]. Partial lists of fault gases that can be found within a unit are shown in the following three groups: Fig 3.1: Gases Presented in Transformer Oil The major (minor) fault gases can be categorized as follows in Table 3.1 and Interpretation of rise in gas concentration in Table 3.2 by the type of material that is involved and the type of fault present [5]: In this table characterization of various fault gases has been done and the major/minor faults occurring due to presence of gases have been shown [18]. If hydrogen traces found in oil then it resembles corona [14] Table 3.1 Major/minor fault gases characterization Corona Oil H2 Cellulose H2 ,CO, CO2 Pyrolysis Oil Low temperature CH4, C2H6 High temperature C2H4, H2 (CH4,C2H6) Cellulose Low temperature CO2(CO) High temperature CO (CO2 Arcing H2, C2 H2, (CH4, C2H6, C2H4 Table 3.2 Interpretation of rise in gas concentration: Rise in Gas Concentration Interpretation Nil or not appreciable Normal Aging
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________________ Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 302 H2 Corona, Partial Discharge CH4 & C2H6 Thermal fault of low temperature upto 300® C C2H4 With or Without CH4, C2H6, H2 Thermal fault of 300® C to 700® C or above C2H2 with or Without H2 C2H4 and CH4 Arc or Flashover The main drawbacks [6] of this conventional method are unable to predict the fault of a particular transformer owing to the lack of expert knowledge in them. 4. CASE STUDY DISSOLVED GAS ANALYSIS: 400KV/220KV/132KV/66KV S/S The case study include on the measurement of gas content in transformer oil using Dissolved Gas Analysis. The case study carried out 400 KV Power Transformer, the rating of power transformer is given bellow: The details of the transformer are as under: - a. Rating: 12.5/16 MVA, 66/11 kV b. Sr.no. 2800061017 c. Make: NGEF d. Date of Commissioning: 17-07-2003 e. Date of last dehydration of Oil: 2003 The DGA testing results for the above mentioned Power Transformer are shown in table5.1 given bellow Table 4.1 DGA Testing Result Methane trends shows events of sparking and Ethane, carbon dioxide content is showing local & severe overheating respectively. However, other gases found within permissible limits. Periodic testing and regular DGA is recommended for the Power Transformer, so that proper monitoring can be done to enhance the life of the Power Transformer. Further, for the 4 years the DGA Trend for the transformer is plotted in the graph shown in Fig 4.1 Fig 4.1 Yearly Graph Plot for DGA Result Oil condition of the transformer is analyzed on the basis of DGA results. It is also seen that by dehydration of oil its BDV increases as well as the traces of various key gases also. 5. CONCLUSIONS Dissolved Gas Analysis gives a good basis for a monitoring system as it can give a general picture of transformer health. Other parameters can be correlated with DGA to provide the user with detailed information about the condition of a transformer. From this work, the critical components can be carefully maintained. The known causes of failure can help to improve the equipment reliability. In this paper test results of DGA has been discussed and investigated and an attempt is made to find out the cause of fault and its preventive action. It has been found that proper and scheduled monitoring leads to enhanced life of Power Transformer and techniques like dehydration plays an important role in boosting up the condition of Transformer Oil as well the transformer life. However, still some advanced condition monitoring techniques like Partial discharge measurement, Spectrophotometer and SFRA etc. are not yet adaptive by the utilities and thus awareness and training on these issues is required for the betterment of the system S. N Gas Quantity detected in ppm Dated:10-10- 2007 Dated: 10-10- 2009 Dated: 08-10- 2011 Date d: 30- 07- 2013 1 Methan e 65 12 14 14 2 Ethane 17 10 11 11 3 Ethylen e 50 20 18 18 4 Acetyle ne ND ND ND ND 5 Carbon dioxide 350 765 770 770 6 Hydrog en 25 ND ND ND 7 TGC, per 100 ml of oil. 12.15 ml 11.85 ml 11.90 ml 11.90 ml
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________________ Volume: 03 Issue: 05 | May-2014, Available @ http://www.ijret.org 303 REFERENCES [1]. M. Wang, A.J. Vandermaar, and K.D. Srivastava, “Review of condition assessment of power transformers in service,” Electrical Insulation Magazine, IEEE vol.18, pp. 12 – 25, Nov.-Dec. 2002 [2]. IEEE guide for the interpretation of gases generated in oil- immersed transformers, IEEE Standard C57.104-1991, July 1992. [3]. S.D. Myers, J.J. Kelly, and R.H. Parrish, A Guide To Transformer Maintenance. United Stated of America: S.D. Myers Inc, 1981, p. 323 [4]. M. Arshad, S.M. Islam, and A. Khalig, “Power transformer critical diagnostics for reliability and life extension,” Electrical and Computer Engineering, IEEE vol. 2, pp.625-628, May 2004. [5]. R.A. Jongen, P.H.F. Morshuis, J.J. Smit, A.L.J. Janssen, and E.Gulski, “Failure data of power transformers as input for statistical failure analysis,” presented at the 15th Int. Conf. High Voltage Engineering, Slovenia, 2007. [6]. Statistical and Neural Network Analysis of Dissolved gases in power Transformers. K F Thang, R K aggarwal, D G ESP,A J McGrail, Dielectric Materials, Measurement and Applications ,Conference Publication No.473,IEE2000 [7]. CIGRE. Life management techniques for power transformers. Technical Brochure 227. Paris June 2003 [8]. Indian standard method of Evaluating of gases in oil filled Electrical Equipments. IS: 10593 - 1983. [9]. IEEE Guide for the Interpretation of Gases Generated in Oil Immersed Transformers, ANSI/IEEE Standard C57. 1 04- 1991. [10]. Sanchez and Lav, Artificial Neural Network Newyork, USA: IEEE press, 1992. [11]. L.Haykin, Neural Networks: A comprehensive Foundation. Montreal, Canada: Macmillan College Publishing Company Inc., 1994 [12]. Wang, M., Vandermaar, A.J., Srivastava, K.D. Review of condition assessment of power transformers in service. Electrical Insulation Magazine, IEEE Nov.-Dec. 2002 18(6): p. 12 -25 [13]. A. De Pablo, A.M., New guidelines for furans analysis as well as dissolved gas analysis in oil-filled transformers, in the International Council on Large Electric Systems (CIGRÉ), . 1996: Paris, France [14]. E. Gockenbach, H.B., Diagnostic methods for transformers on-site, in Proc. Int. Symp. Elec. Insul. Matls., 1998: Toyohashi, Japan. p. 2~36. [15]. Kachler, A.J., Diagnostic and monitoring technology for large power transformers, in CIGRé SC 12, Sydney Colloquium, . 1997: Sydney, Australia [16]. R.J. Schwabe, et.al., On-line diagnostics of oil paper insulated instrument transformers, in theInternational Council on Large Electric Systems (CIGRé), . 2000: Paris, France [17]. KIRTLEY, J.L., Jr., HAGMAN, Wayne H., et.al, Monitoring the health of power transformers. Computer Applications in Power, IEEE Jan. 1996 9(1): p. 18-23. [18]. A. Mollmann, B.P., New guidelines for interpretation of dissolved gas analysis in oil filled transformers. Electra, 1999(186): p. 30~51.