SEISMIC PROTECTION OF THE RION-ANTIRION BRIDGE
Samuele Infanti1
, P. Papanikolas2
, M.G. Castellano3
1
FIP Industriale, Via Scapacchiò 41, 35030 Selvazzano Dentro (PD), Italy, infanti.fip@fip-group.it
2
Kinopraxia Gefyra, Antirio Aetolocarnania PC 300 20, Greece , ppapanikolas@gefyra.com
3
FIP Industriale, Via Scapacchiò 41, 35030 Selvazzano Dentro (PD), Italy, castellano.fip@fip-group.it
ABSTRACT
The Rion-Antirion Bridge, which crosses the homonymous strait in Greece, is located in a
region prone to high intensity earthquakes and large tectonic movements generated by local
active seismic faults. The deck of the multi-span cable stay bridge is continuous and fully
suspended (for its total length of 2,252 meters) from four pylons (with spans 286m + 560m +
560m + 560m + 286m). The approach viaducts to the main bridge comprises for 228m of
precast concrete girder decks on the Antirion side and for 990m of steel composite decks on
the Rion side. The structures are designed to withstand seismic events with peak ground
acceleration of 0.48g (2000 years return period) and tectonic movements between two piers
of 2 meters in any direction. This was possible through the use of innovative energy
dissipation systems that connect the deck to the top of each pier and limits the movement of
the decks during the specified earthquake, while dissipating the seismic energy.
The seismic protection system of the Main Bridge comprises fuse restraints and viscous
dampers acting in parallel, connecting the deck to the pylons. The restrainers are designed as
a rigid link intended to withstand the high wind loads up to a pre-determined force
corresponding to a value slightly higher than the wind load ultimate limit state. Under the
specified earthquake, the fuse restrainers are designed to fail, leaving the viscous dampers
free to dissipate the energy induced by the earthquake into the structure.
The behavior and the requirements of the dissipation systems were optimized with the help
of a non-linear time history numerical analysis on a 3D model. It resulted on seismic devices
(viscous dampers and fuse links) characterized by extreme design parameters in terms of
force, velocity and stroke, with dimensions and weight never attempted before. The design
assumptions and the actual behavior of the seismic protection system had to be confirmed
with extensive testing of full-scale prototypes.
The Approach Viaducts are isolated from the ground motion through a system composed of
elastomeric isolators designed to provide for the bearing function as well as the required
period shift effect and by viscous dampers providing for the energy dissipation. Even in this
case, numerical analysis provided the units optimized characteristics and full-scale tests have
been performed to verify the design assumptions.
The aim of the present paper is to describe the mentioned seismic protection systems as well
as the results of the full-scale prototype testing. The Viscous Damper Prototype tests were
performed at the laboratory of the University of San Diego California (USA), while the Fuse
Restraints tests and all the production tests were carried out at the FIP Industriale Testing
Laboratory in Italy.
1 INTRODUCTION
The Rion-Antirion Bridge (see figure 1), located in the Gulf of Corinth - an area prone to
strong seismic events and windstorms -, consists of a cable stayed main bridge 2,252 m long
on four large foundations with a span distribution equal to 286m + 560m + 560m + 560m +
560m + 286m and of two approach viaducts (987 m long on the Rion side and 239 m long on
the Antirion side).
The cable-stayed deck is a composite steel structure made of two longitudinal plate girders
2.2m high on each side of the deck with transverse plate girders spaced at 4m and a concrete
slab, the total width being 27m.
Each pylon is composed of four legs 4x4m, made of high strength concrete, joined at the top
to provide the rigidity necessary to support unsymmetrical service loads and seismic forces.
The pylons are rigidly embedded in the pier head to form a monolithic structure, up to 230 m
high, from the sea bottom to pylon top (see figure 2).
The deck of the main bridge is continuous and fully suspended by means of stay cables for
its total length of 2,252m. In the longitudinal direction, the deck is free to accommodate all
thermal and tectonic movements.
Figure 1. The Rion-Antirion Bridge
The bridge is equipped with a damping system that, for its characteristics and for the strict
design requirements, entitles to put this structure in the next generation of seismic protected
structures.
The seismic protection system of the main bridge comprises viscous dampers connecting in
the transverse direction the fully suspended deck to the pylon base.
These viscous dampers are of ever built dimensions and design capacity and shall be
installed at the pier to deck interfaces in order to reduce the transverse swing of the deck
during a dynamic event.
They are designed to dissipate the energy introduced into the structure by the earthquake.
Requirements for a proper and safe seismic behavior are sometimes not in agreement with
the everyday service life of the structure. Thus, large structural displacements induced by
moderate earthquakes or windstorms are avoided by an additional restraint system, that at the
occurrence of a major design event fails allowing the structure free to oscillate with its
damping system.
This system is composed by Fuse Restraints installed in parallel to the dampers, so that the
deck, when subjected to lateral loads not exceeding their design capacity, is linked rigidly to
the substructure, while after failure it leaves the deck free to swing coupled to the dampers.
The design failure force of the fuse restraints is set slightly higher than the maximum
expected wind load.
Four viscous dampers (Fmax 3500 kN, Stroke ±1750 mm) and one fuse restrainer (Fmax
10500 kN) shall be installed at each pylons, while at the transition piers two viscous dampers
(Fmax 3500 kN, Stroke ±2600 mm) and one Fuse Restrainer (Fmax 3400 kN) shall be
considered.
Figure 2. The main bridge under advanced construction (September 2003)
Figure 3 gives the general arrangement of the four viscous dampers and the restraint device
at one pylon.
Figure 4 shows the conceptual arrangement of the two viscous dampers installed at the
Transition Pier. This pier is composed by a rotating frame pivoting at the base. The
mentioned dampers are installed at the deck to substructure interface aligned along the deck
transverse center line and rotating with the pier itself. The Fuse Restrainer is installed on one
of the two dampers as a component of the damper itself.
The Approach Viaducts are seismically isolated through a system composed of elastomeric
isolators designed to provide for the bearing function as well as the required period shift
effect and by viscous dampers providing for the energy dissipation.
Even in this case, numerical analysis provided the units optimized characteristics and full-
scale tests have been performed to verify the design assumptions.
This paper describes the different seismic devices to be applied to the Rion-Antirion Bridge,
focusing on the full-scale tests carried out for qualification and acceptance purposes. General
information about non-linear viscous dampers are also given below.
Figure 3. Rion Antirion Main Bridge: arrangement of viscous
dampers on the main piers
Fuse RestrainerViscous Damper
2 NON-LINEAR VISCOUS DAMPERS
FIP fluid viscous dampers are piston/cylinder devices that utilize fluid flow through orifices
to absorb energy. Orifices are situated in the piston head, which allow the fluid to move back
and forth between the two chambers. The force generated by these devices is the result of a
pressure differential across the piston head. These devices are equipped with two spherical
hinges at both ends that keep the transmitted load aligned along their main axis. This detail is
of major importance to provide a reliable performance: it prevents the piston rod from
bending and thus the sealing system from failing. High strength steel components are used
for the vessel and the plated piston rod so as to withstand the actions imposed by a dynamic
load. The anchoring details depend only on the structure to which they are anchored: for
example, the tang plate/clevis system illustrated in Figure 5.
In the last few years, FIP dampers have undergone major testing programs at FIP laboratory
as well as at independent facilities (Earthquake Engineering Research Center, Berkeley CA –
USA, Boeing Testing Facility, Canoga Park CA – USA and Caltrans SRMD Testing
Laboratory at the University of California – San Diego - USA), which has entitled the
company to be a pre-qualified damper manufacturer for the Golden Gate Bridge Retrofit
project as well as to enter the CALTRANS (California Department of Transportation) list of
pre-qualified damper manufacturers. It should be noted that remarkable reaction stability has
been achieved by dynamically cycling within a very wide temperature range (-40°C ÷
+50°C) that guarantees proper behavior under any type of environmental conditions.
Figure 4. Transition pier configuration
A very important issue related to the utilization of the technology entails the correct
numerical modeling of the devices as integrated into the structural model and the
performance verification of the finished product.
The latter topic will be amply discussed in the following paragraphs.
.The most appropriate mathematical model to represent the behavior of an FIP viscous
damper is to use a Maxwell constitutive law characterized by a linear spring in series to a
non-linear dash-pot element (see Figure 6). The first element represents the elasticity of the
system that is mainly due to the compressibility of the silicon fluid, while the second depicts
its damping properties. The exponent that characterizes the non-linearity of the response as a
function of the velocity, is particularly important. Positive effects are undoubtedly related to
low exponent dampers: e.g. in bridge applications, reduced pier deformation, lower
expansion joint costs and cost effective bearings or in buildings, maximum reduction of
relative displacement at the isolation interface or in the braces.
FIP viscous dampers are designed to guarantee a 0.15 exponent so that, within a wide
velocity range, reaction is expected to be almost constant. This performance characteristic
permits the devices to initiate their damping reaction at low velocities, providing the
maximum reduction of the superstructure displacement.
Total system elasticity, mathematically represented by the stiffness K, depends on the
compressibility of the fluid and it is particularly evident at the point of motion reversal, or at
any rate, at the point of transitory phases: commonly, it is a secondary effect and often it is
not even computed.
Figure 5. Typical damper anchoring configuration (photo taken during the installation)
Test 1 - Performance Benchmark (TA #3)
-800
-600
-400
-200
0
200
400
600
800
-250 -200 -150 -100 -50 0 50 100 150 200 250 300
Displacement (mm)
Force(kN)
Maxwell Model
15.0
)(0
K
F
xCF
tsinxx
K C,
x(t)
Figure 6. Damper constitutive law equation and hysteresis loop
To evaluate the response of such a system, the differential non-linear equation representing
its constitutive law needs to be integrated.
Looking at the plot in Figure 6, it can be noted that this typical hysteresis loop looks almost
rectangular even if the displacement time–history is sinusoidal (thus velocity dependent).
This is due to the damper characteristic exponent (0.15). In fact, the behavior is almost
independent from velocity. Thus total damper behavior can be similar to that of a spring in
series to a ”perfectly plastic” element characterized by a constant threshold force.
3 MAIN BRIDGE SEISMIC ISOLATION SYSTEM
As above anticipated, the seismic isolation system of the main bridge comprises fluid viscous
dampers and fuse restraints.
The behavior and the requirements of the viscous dampers were optimized by means of non-
linear time-history analyses on a 3-D model of the entire bridge. Strict specifications were
imposed with regards to the behavior of the seismic protection system in order to ensure a
stable performance of all the devices: dampers reaction shall be within 15% of its
theoretical constitutive law and Fuse restrainers failure shall be within 10% of the design
value.
Full-scale tests aimed at verifying the design characteristics are described below.
3.1 Viscous Dampers Full-Scale Testing
The following paragraphs present the main result of the testing activities performed at both
FIP Industriale Testing Laboratory and at the Seismic Response Modification Device
(SRMD) Testing Laboratory of Caltrans at the University of California at San Diego on a
full-scale prototype of the viscous dampers to be utilized on the above mentioned bridge.
The prototype, characterized by a 3220 kN reaction at the maximum design velocity of 1.6
m/s (damping constant C=3000kN·(s/m)0.15
) and by a ±900mm stroke, was submitted by FIP
Industriale on February 2002 for evaluation.
This viscous damper is deemed to be the largest ever-built device of its type (6.4 m pin to
pin) and was tested up to its maximum design conditions. The prototype is equal in every
detail to the dampers designed for final installation with the exception of the length (and
consequently of the stroke), which is shorter so as to fit into the existing test rig of the
SRMD.
Table 1. Dampers Characteristics
Characteristics Pylons Transition Piers Prototype
Damper Series OTP350/3500 OTP350/5200 OTP350/1800
Stroke (mm) -1650/+1850 ± 2600 ± 900
Pin-to-Pin Length (mm) 10520 11320 6140
Total Length (mm) 11310 12025 6930
Maximum Diameter (mm) 500 550 500
Damper Weight (kg) 6500 8500 3300
Total Weight (kg) 9000 11000 5500
3.1.1 Prototype Full-scale testing at FIP Industriale Laboratory – Italy
The above mentioned prototype underwent to two series of tests. The first one was
performed at FIP Industriale Testing Laboratory, where the unit was tested for final tuning of
its damping characteristics before shipment to the UCSD laboratory for official testing in
presence of the client (Kinopraxia Gefyra - Greece) and of the bridge design checker
(Buckland & Taylor - Canada).
Figure 7. Production damper under test at FIP laboratory
FIP Industriale Testing Laboratory is equipped with a power system providing for 630 kW at
1200l/min thus resulting to be the most powerful in Europe for full-scale dynamic testing of
seismic devices.
Being the above unit of exceptional characteristics, the prototype was tested up to the
maximum velocity provided by the available system, which resulted to be 0.2 m/s.
In Figure 8, the prototype is shown during dynamic testing at FIP testing Laboratory.
Figure 9. Experimental measurements vs. damper constitutive law
Figure 8. Viscous Damper Prototype during testing at FIP Laboratory
Actuator
Test Rig
Frame
Servo-valve
Damper
For testing purposes, the unit was pinned at one end to the test rig (yellow colored) while its
piston rod was connected directly to the actuator through a 3000kN capacity load cell. The
damper reaction was measured through the mentioned load cell as well as indirectly from the
pressure detected on the actuator through a pressure gauge. The displacement was measured
through a magneto-strictive displacement transducer. In figure 9, the test results are
reassumed and it is evident how the damper behavior follows the theoretical constitutive law
with a minimal deviation.
3.1.2 Full-scale testing at SRMD Testing facility – California, USA
The damper OTP 350/1800 was tested at the Seismic Response Modification Device
(SRMD) testing facility of the University of California San Diego. The test matrix is reported
in Table 2 (tests are listed in the same order they were carried out).
It is worth noting that the tests were performed up to the maximum design velocity equal to
1.6m/s. It was the first time that a damper of a so high load capacity was tested at such a
high velocity.
The specimen was horizontally installed in the testing rig, connected at one end to a reaction
wall and at the other end to the movable platen. The six degrees of freedom table is capable
of unique level of displacement, forces and velocities. For this specific application the platen
was moved in the longitudinal direction, with a displacement control loop able to maintain
the components of motion in the other directions at negligible level. Figure 10 shows the
damper installed on the testing frame.
Figure 10. Prototype testing at SRMD Facility (UCSD)
Peak forces measured at different velocity levels are reported in Figure 11.
Table 2 Test Protocol Prototype FIP OTP 350/1800
Test
#
Test
Name
Input Number of
cycles
Stroke Testing conditions
(V = Peak Velocity)
1 Thermal Linear 1 895 mm V<0.05 mm/s for 5 minutes
Increase velocity to 1mm/s up to
completion of the displacement.
2 Velocity
Variation
Sinusoidal 5
5
5
3
2
300 mm
V=0.13 m/s
V=0.40 m/s
V=0.80 m/s
V=1.20 m/s
V=1.60 m/s
3 Full stroke
&
Velocity
Sinusoidal or
step loading
1 850 mm Vmax=1.6 m/s
4 Wear Linear 20000 5 mm V=15 mm/s
Every hour change position of the
piston of about 100 mm
5 Velocity
variation
Sinusoidal 2 300 mm Vmax=1.6 m/s
Maximum forces appear to be very symmetric in the all range of velocity. A difference of
7% was recorded at maximum speed (1.6 m/s) only for the first cycle. The second cycle of
the same test shows instead a deviation of 1.6%. The comparison among peak forces of
different cycles shows a reduction of the peak force of 3.8% between fifth cycle and first
cycle for test Velocity A (0.13 m/s). For the high speed tests the maximum force reduction is
equal to 10.4%.
Figure 11. Experimental vs.theoretical – damper constitutive law
The calculated energy dissipated per cycle (EDC) for the Full Stroke and Velocity Test was
11035 MNm (+6% of the theoretical EDC). In order to perform this test a 3.3 MW power
input was required.
Wear tests were completed with 10 sets of 2250 cycles, at constant velocity of 0.015 m/s and
10 mm total stroke.
Figure 12. Experimental damper hysteresis loop
The force vs. displacement response of the damper is reported in Figure 12 for the test at 1.2
m/s peak velocity.
Thermocouples were installed both internally and externally the damper body in order to
monitor temperature rise during and after the motions. Air and nitrogen gas was used, in a
cooling box, to restore the ambient temperature on the damper before a new test.
Temperature rise was recorded for each test. The maximum increase took place at the end of
the test Velocity Variation B, with 40 degrees Celsius recorded from the sensor installed
internally to the damper.
All the test results were deemed to be in agreement with the design specifications.
It is worth to stress how the test results obtained at the SRMD facility agreed very well with
the measurements performed at FIP testing laboratory and how the damper behavior resulted
to provide for stable reaction in a very wide velocity range (0.002 – 1.6 m/s).
The extrapolation of the damper reaction in the range of velocity 0.13-1.6 m/s from the test
performed at FIP laboratory up to 0.2 m/s differed from the measured reaction at the SRMD
facility by only few percent point. This result demonstrates how much predictable is the
damper behavior within the full test range.
The test aimed at verifying the damper reaction at low velocity (0.1 mm/s) measured a
reaction of 200kN.
3.1.3 Quality Control (production) tests at FIP Industriale Laboratory
The aim of the production tests was to verify the compliance of the production units with the
contract specification or, in other words, that their reaction and damping characteristics fall
within the design tolerance range.
The test is performed on 100% of the produced units and at the current time, two production
lots have been already full-scale tested at FIP Industriale Laboratory in Italy (see figure 7 for
the testing configuration of a production unit).
The contractual test program requires for the following tests:
Proof Pressure test: the test is aimed to verify that the damper vessel withstand with no
damage or leakage 125% of the design internal pressure.
Low velocity test: the test is aimed to verify that the damper reaction at low velocity
(less than 0.1mm/s) is less than 200kN in order to allow for easy of length adjustment
and to avoid fatigue loads on the bridge.
Dynamic test: the test is aimed to verify that the units provide for a reaction that
follows the theoretical constitutive law with a maximum deviation of 15%.
All the above mentioned tests have yielded a positive outcome.
In figure 13, a graph shows for all the units of the first two production lots (serial numbers
from 414946 to 414953) the measured reaction, normalized with reference to the theoretical
reaction, obtained imposing three sinusoidal cycles of 250mm stroke amplitude and reaching
a peak velocity of 100mm/s (see figure 14).
It is worth to note that the maximum measured deviation was -4.8% with respect to the
theoretical reaction at 100mm/s (2124kN). The measurements confirmed the results obtained
during the prototype testing at the SRMD Facility of the University of California at San
Diego.
Figure 13. Normalized reaction of the production units
Production Test
Damper Force Measured at 100mm/s
0,60
0,65
0,70
0,75
0,80
0,85
0,90
0,95
1,00
1,05
1,10
1,15
1,20
45 46 47 48 49 50 51 52 53 54
Serial Number
NormalizedForce
Lower Bound
(-15%)
Upper Bound
(+15%)
Theoretical Force
Measured Force
First Lot Second Lot
4 FUSE RESTRAINTS
Fuse restraints shall provide for a stiff link between the deck and the substructure for the
lateral service load as well as for low occurrence high-intensity windstorms. As anticipated,
only at the occurrence of high intensity events they are designed to fail allowing the damping
system to work properly.
They are located at the main piers as well as at the transition piers. The main pier units are
designed as single units equipped at their ends with spherical hinges. This configuration
allows for the design rotations as well as for a correct alignment of the load along the device
axis for any deck position. The element failing at the reaching of the desired design load –
the so-called Fuse Element - is installed in the middle of the unit, for a general configuration
of the unit see Figure 15.
The units to be installed on the main piers are characterized by a failure load of 10500kN.
Similarly the units installed at the transition piers, that are installed as components of the
dampers, are characterized by a failure load of 3400kN. The design tolerance on the failure
load of the units requires a precision of ±10%: a very strict design performance for such a
high capacity units.
Furthermore, a main design complication came from the need of minimizing the internal
forces of the laterally restraint deck induced by tectonic movements originated from seismic
fault located under the bridge. Thus, the units located on the main piers are equipped with a
system designed to allow for length adjustment. This operation is performed when a certain
load level is constantly applied to the link, so a load cell monitoring the load on the unit is
required. As part of the monitoring system of the bridge, this will allow to identify the
moment at which re-adjustment of the deck is required.
Another design requirement was that the units shall not disassemble after failure of the main
component, so the units were designed to allow for the same stroke provided by the dampers.
Being the restraints first function to withstand the every day actions (service loads), a test has
been required to evaluate the fatigue life as well as any influence on the failure strength.
-300 -200 -100 0 100 200 300
Stroke [mm]
-2500
-2000
-1500
-1000
-500
0
500
1000
1500
2000
2500Lo
ad
[k
N]
0 10 20 30 40 50 60
Time [s]
-300
-200
-100
0
100
200
300Str
ok
e
[m
m]
0 10 20 30 40 50 60
Time [s]
-100
-50
0
50
100
Ve
lo
cit
y
[m
m/
s]
Rion Antirion Main Bridge
OTP 350/3500 S. N° 414946
Data ref. :
Graph. ref. :
Date :
Force Vs Displacement Hysteresis Loop at 100 mm/s
Din100mms
Operator :
19/05/03
Ruggero D.
rioant01
Load Vs. Stroke Stroke Vs. Time
Velocity Vs. Time
3 Cycles Ampl. +/-250 mm Freq. 0.064 Hz
Figure 14. Dynamic test results
Figure 15. Fuse restraint general configuration
4.1 Testing program
The testing program was carried out on two full-scale prototypes of fuse element for each
typology.
It consisted on a first test performed on one unit increasing monotonically the load up to
failure, while a second test was performed on the other prototype imposing two millions of
cycles at a load level equal to 10% of the design failure load and then increasing
monotonically the load up to failure.
Failure test and fatigue test were carried out on different test rigs, the first one is a 8000 kN
capacity test rig commonly used for bearing test while the second one is a 3000kN dynamic
test rig: the same used for damper testing.
Testing results have shown that both prototypes failed within the design tolerance. The
difference between the measured failure loads before and after fatigue test can just confirm
that the design fatigue load cannot be considered as effecting the ultimate capacity of the
fuse restraints. In the following table, all the testing results are presented. Figure 16 shows
typical graphs obtained for both the 3400kN and 10500kN units.
Table 3. Test Results
Device Type Failure Load
Capacity
(kN)
Tolerance Range
(kN)
Measured Load
(kN)
Deviation
(%)
SR340 3400 3060-3740 3545 +4.3
SR340 3400 (Fatigue) 3591 +5.6
SR1050 10500 9450-11550 10382 -1.1
SR1050 10500 (Fatigue) 11765 +12.0
SR340 - Failure Test SR1050 - Failure Test
Figure 16. Failure Test
Figure 17 shows the SR1050 fuse element testing configuration during the fatigue test.
Figure 17. SR1050 Fuse element during fatigue test
5 THE RION-ANTIRION BRIDGE APPROACH VIADUCTS
5.1 Introduction
The approach viaducts, being of critical importance for the functionality of the main bridge
after a seismic attack, have been designed to withstand the same earthquake intensity level of
the main bridge (PGA=0.48g).
They present different design and construction technology but the same type of seismic
isolation system.
The Antirion approach viaduct, located on the mainland Greece side, has a total length of
227.96 m (6 spans: 2 spans of 37.460 m and 4 spans of 38.460 m) and it has been already
built as shown by figure 18.
The viaduct is made of pre-cast pre-stressed concrete girders with reinforced concrete deck
slab.
Longitudinally, the viaduct consists of simply supported spans linked by continuity deck
slabs at the location of supports.
The typical cross section consists of 8 pre-stressed concrete girders with transverse
diaphragm cross beams on support.
The piers of the viaduct are reinforced concrete frames in the transverse direction made of
four columns connected at their lower part by a pile-cap and at their upper part by a cross
head beam.
The abutment consists of bored cast-in-place piles and/or appropriate spread footing on
treated soil.
Figure 18. The Antirion Approach Viaduct
The Rion viaduct is located on the Peloponnesus side and has a total length of 986m. It is
currently under construction.
The viaduct consists of two independent composite bridges. Each composite structure is
made of two girders connected by cross beams.
The bearings of the bridge are elastomeric isolators or sliders and are located under the main
steel girders.
The typical cross section consists of a concrete slab connected to the steel beams by
connectors.
The piers of the viaduct are reinforced concrete frames in the transverse direction made of
two columns connected at their lower part by a pile-cap and at their upper part by a cross
head beam.
The piers are founded on piles.
The seismic isolation system used for the protection of all the approaches consists of a
combination of elastomeric isolators and viscous dampers.
The isolators provide for the bearing function as well as for the lateral flexibility required to
shift the period of the structure and so to reduce the acceleration of the deck.
These bearings are made of alternate layers of natural rubber and steel plates vulcanized
together and mechanically anchored to the deck and the substructure.
Figure 19. Approaches isolation system
Viscous dampers, dissipating the energy introduced by the earthquake and so
providing for the required damping, are set up in longitudinal and transverse
directions between the deck and the pier heads to limit relative displacement.
Isolators and dampers installed on the Antirion Approach Viaduct went through an extensive
test program performed at the testing departments of ALGA and FIP Industriale in Italy. The
main results are shown in the following paragraphs.
5.2 Seismic hardware tests
5.2.1 Elastomeric Isolators
Tests have been performed to check the quality and the mechanical characteristics of the
elastomeric isolators in order to evaluate stability, capacity, resistance to service loads and,
of course, the lateral stiffness.
Two typologies have been produced characterized respectively by 500x600x239mm and
500x600x253mm main dimensions and by natural rubber providing for a 1N/mm2
shear
modulus.
In figures 20 and 21, full-scale isolators under testing at ALGA Laboratory in Italy as well as
the graph depicting the measured Force vs. Displacement loop are respectively shown.
Figure 20. Isolators under tests
Figure 21. Isolators stiffness characteristics
5.2.2 Viscous Dampers
Tests aimed to verify the effective damping capacity under dynamic loads, the displacement
capacity and the accordance with the expected performance law (Force vs. velocity
relationship) were performed on full-scale units.
The Antirion Viaduct requires for 44 dampers to be installed both longitudinally and
transversally (see figure 22).
Figure 22. Dampers typical arrangement
Transverse Dampers
Longitudinal DampersElastomeric Isolator
The longitudinal dampers (24 units) are characterized by a 1200kN load capacity and by
strokes ranging from ±200 to ±250mm, whilst the transverse dampers (20 units) are
characterized by an 800kN load capacity and by strokes equal to those used longitudinally.
Being the proposed technology the same used on the main bridge, the dampers are
characterized by a 0.15 damping exponent, thus ensuring an effective damping action even
for low velocities.
In figure 23, a 1200 kN capacity damper under testing at FIP Industriale Laboratory is
shown.
In figure 24, the hysteresis loop obtained testing at constant velocity is presented.
The Rion Viaduct requires for the installation of 134 units characterized by 300, 600, 1200
and 2400kN load capacity and strokes ranging from ±250 to ±405mm that are currently
under production.
Figure 23. Production Tests at FIP Laboratory
6 CONCLUSIONS
Testing of full-scale viscous dampers and fuse elements were performed in order to confirm
the characteristics and the main design assumptions of the seismic dissipation system used
for the Rion-Antirion Cable Stayed Bridge and for the approach viaducts.
Tests performed on Fuse elements verified positively the design assumption showing that it
is possible to achieve a very tight tolerance ( 10%) on the predicted ultimate capacity even
when the units are designed for a very high failure load (10500kN).
The Viscous Damper prototype demonstrated very stable behavior even when tested under
dynamic conditions, requiring power dissipation higher than design parameters.
The measured energy dissipation and viscous reaction were always well within the design
tolerance of ±15% of the theoretical design parameters.
Testing aimed to represent the effect of structural vibrations induced by traffic and/or of
movement induced by structure thermal expansion did not produce any appreciable change
in the damper behavior.
The production tests confirmed that the dampers to be installed on the bridge provide for the
same characteristics of the prototype with a deviation from the theoretical constitutive law
lower than 5%.
Full-scale testing of large size dissipating devices proved to be a real challenge compared to
previous testing experiences as it pushed the limits of equipment available worldwide.
Experimental results on full-scale units give a high degree of confidence on seismic devices
as a means to protect large and important structures such as the Rion-Antirion Cable Stayed
Bridge and its approaches.
-120 -90 -60 -30 0 30 60 90 120
Displacement [mm]
-1000
-750
-500
-250
0
250
500
750
1000
Force[kN]
0 1 2 3 4 5 6 7 8 9 10
Time [s]
-120
-90
-60
-30
0
30
60
90
120
Displacement[mm]
0 1 2 3 4 5 6 7 8 9 10
Time [s]
-150
-120
-90
-60
-30
0
30
60
90
120
150
Velocity[mm/s]
Sep-Gefyra Kiropraxia
Test on Damper 120/400
Reaction = 878 kN
Data ref. :
Graph. ref. :
Date :
Force Vs Displacement Hysteresis Loop at 125 mm/s
Rionotp120a125mms
Operator :
09/07/02
Ruggero D.
Otp120gefyra
Force Vs. Displacement Displacement Vs. Time
Velocity Vs. Time
VP21/02Enclosure3Graph1
Figure 24. Hysteresis Loop
ACKNOWLEDGEMENT
The authors wish to express their sincere gratitude for the active and fruitful cooperation
rendered by Mr. Gianmario Benzoni of the UCSD Laboratory, as well as the indefatigable
support furnished by Mr. Renato Chiarotto of FIP Technical Department, Mr. Pierluigi
Galeazzo Testing Laboratory Manager of FIP Industriale and his staff.
A remarkable thank is addressed to Mr. Agostino Marioni (ALGA) and to Mr. Philippe
Salmon (Freyssinet) for their cooperation within the JV operations.
REFERENCES
Benzoni G., Seible F, “Rion-Antirion Bridge - Prototype Tests of Damper FIP OTP
350/1800” Caltrans SRMD Test Facility Report N. 2002/01, San Diego CA - USA,
2002.
Infanti S., Colato G.P., Castellano M.G., “Structural Devices for Bridge Engineering: the
Challenge Goes On”, Bridge Engineering Conference, Sharm El-Sheikh – Egypt,
2000.
Infanti S., “Seismic Protection of Seohae Bridge Approaches trough Viscous Dampers”,
Cable-Supported Bridges – Challenging Technical Limits, IABSE Conference,
Seoul - Korea, 2001.
Infanti S., Castellano M.G., “ Viscous Dampers: a Testing Investigation according to the
HITEC Protocol”, Fifth World Congress on Joints, Bearings and Seismic Systems
for Concrete Structures, Rome – Italy, 2001.
Infanti S., Castellano M.G., Benzoni G. “Non-Linear Viscous Dampers: Testing and Recent
Applications”, ATC 17-2A Seminar on response modification technologies for
performance -based seismic design, Los Angeles CA - USA, 2002.
Infanti S., Papanikolas P.., Theodossopoulos G. “Rion-Antirion Bridge: Full-Scale Testing of
Seismic Devices”, fib Symposium Concrete Structures in Seismic Regions, Athens
– Greece, 2003.
Technical Report “Evaluation Findings for FIP – Energy Absorption Systems, LLC Slider
Bearings ”, Highway Innovative Technology Evaluation Center, 1998.
Technical Report “Guidelines for Testing of Seismic Isolation and Energy Dissipating
Devices ”, Highway Innovative Technology Evaluation Center, 1998.
Technical Report “Evaluation Findings of FIP Industriale Viscous Dampers according to the
HITEC testing protocol”, Rocketdyne Division of Boeing, Canoga Park – CA USA,
2000.
Teyssandier J.P, Combault J, Morand P., “The Rion-Antirion Bridge Design and
Construction” 12th World Conference of Earthquake Engineering, Auckland – New
Zealand, 2000.
Teyssandier J.P, de Maublanc G., Morand P., Papanikolas P., “The Rion-Antirion Bridge”
fib Symposium Concrete Structures in Seismic Regions, Athens – Greece, 2003.
Soong T.T., Dargush G.F., ”Passive Energy Dissipation Systems in Structural Engineering”,
Wiley, Chichester – England, 1997, 356 pp
Skinner R.I., Robinson W.H., McVerry G.H., ”An Introduction to Seismic Isolation”, Wiley,
Chichester – England, 1993, 354 pp.
Virtuoso F., Guerrero L., Azevedo J., “Modelling the Seismic Behavior of Bridges With
Viscous Dampers”, 12th World Conference of Earthquake Engineering, Auckland –
New Zealand, 2000.

More Related Content

What's hot

Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...
Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...
Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...Constantin Ciobanu
 
IRJET- Seismic Effect of Rigid Floor Diaphragm
IRJET- Seismic Effect of Rigid Floor DiaphragmIRJET- Seismic Effect of Rigid Floor Diaphragm
IRJET- Seismic Effect of Rigid Floor DiaphragmIRJET Journal
 
HV tower design 3
HV tower design 3HV tower design 3
HV tower design 3Thy Khy
 
62617938 launching-girder
62617938 launching-girder62617938 launching-girder
62617938 launching-girderlotuseye
 
Vibration control system
Vibration control systemVibration control system
Vibration control systemKok Kei Liew
 
Effect of masonry walls in the progressive collapse of a ten storied rc building
Effect of masonry walls in the progressive collapse of a ten storied rc buildingEffect of masonry walls in the progressive collapse of a ten storied rc building
Effect of masonry walls in the progressive collapse of a ten storied rc buildingkunalsahu9883
 
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...Ursachi Răzvan
 
Somnath soni (iit ism) dhanbad presentation vphep
Somnath soni (iit ism) dhanbad presentation vphepSomnath soni (iit ism) dhanbad presentation vphep
Somnath soni (iit ism) dhanbad presentation vphepSomnath Soni
 
Seismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersSeismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersAyaz Malik
 
Barge Transportation Analysis & Load out activities in Modular Construction
Barge Transportation Analysis & Load out activities in Modular ConstructionBarge Transportation Analysis & Load out activities in Modular Construction
Barge Transportation Analysis & Load out activities in Modular ConstructionMrudul Thakar
 
Uses of special kind of technologies for implementation of special kind of st...
Uses of special kind of technologies for implementation of special kind of st...Uses of special kind of technologies for implementation of special kind of st...
Uses of special kind of technologies for implementation of special kind of st...Rajesh Prasad
 
PPT ON DESIGN OF COLUMN BRACES
PPT ON DESIGN OF COLUMN BRACESPPT ON DESIGN OF COLUMN BRACES
PPT ON DESIGN OF COLUMN BRACESsrinivas cnu
 
Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...eSAT Journals
 
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...IRJET Journal
 
Study on the effect of viscous dampers for RCC frame Structure
Study on the effect of viscous dampers for RCC frame StructureStudy on the effect of viscous dampers for RCC frame Structure
Study on the effect of viscous dampers for RCC frame StructurePuneet Sajjan
 
Design and Analysis of Transmission Tower at Allahabad
Design and Analysis of Transmission Tower at AllahabadDesign and Analysis of Transmission Tower at Allahabad
Design and Analysis of Transmission Tower at AllahabadAbhijit Kumar
 
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...IAEME Publication
 

What's hot (20)

Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...
Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...
Behaviour of the track in hot weather. Rail thermal forces for jointed and CW...
 
IRJET- Seismic Effect of Rigid Floor Diaphragm
IRJET- Seismic Effect of Rigid Floor DiaphragmIRJET- Seismic Effect of Rigid Floor Diaphragm
IRJET- Seismic Effect of Rigid Floor Diaphragm
 
HV tower design 3
HV tower design 3HV tower design 3
HV tower design 3
 
62617938 launching-girder
62617938 launching-girder62617938 launching-girder
62617938 launching-girder
 
Vibration control system
Vibration control systemVibration control system
Vibration control system
 
Effect of masonry walls in the progressive collapse of a ten storied rc building
Effect of masonry walls in the progressive collapse of a ten storied rc buildingEffect of masonry walls in the progressive collapse of a ten storied rc building
Effect of masonry walls in the progressive collapse of a ten storied rc building
 
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...
Lecture 2 s.s. iii continuare Design of Steel Structures - Faculty of Civil E...
 
Somnath soni (iit ism) dhanbad presentation vphep
Somnath soni (iit ism) dhanbad presentation vphepSomnath soni (iit ism) dhanbad presentation vphep
Somnath soni (iit ism) dhanbad presentation vphep
 
Seismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersSeismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampers
 
Barge Transportation Analysis & Load out activities in Modular Construction
Barge Transportation Analysis & Load out activities in Modular ConstructionBarge Transportation Analysis & Load out activities in Modular Construction
Barge Transportation Analysis & Load out activities in Modular Construction
 
Uses of special kind of technologies for implementation of special kind of st...
Uses of special kind of technologies for implementation of special kind of st...Uses of special kind of technologies for implementation of special kind of st...
Uses of special kind of technologies for implementation of special kind of st...
 
PPT ON DESIGN OF COLUMN BRACES
PPT ON DESIGN OF COLUMN BRACESPPT ON DESIGN OF COLUMN BRACES
PPT ON DESIGN OF COLUMN BRACES
 
Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...
 
Combined footing
Combined footingCombined footing
Combined footing
 
Building Vibration
Building VibrationBuilding Vibration
Building Vibration
 
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...
IRJET- Comparative Study of Usage of Outrigger and B-ELT Truss System for Hig...
 
Study on the effect of viscous dampers for RCC frame Structure
Study on the effect of viscous dampers for RCC frame StructureStudy on the effect of viscous dampers for RCC frame Structure
Study on the effect of viscous dampers for RCC frame Structure
 
Metro presentation
Metro presentationMetro presentation
Metro presentation
 
Design and Analysis of Transmission Tower at Allahabad
Design and Analysis of Transmission Tower at AllahabadDesign and Analysis of Transmission Tower at Allahabad
Design and Analysis of Transmission Tower at Allahabad
 
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...
STATIC AND DYNAMIC ANALYSIS OF CABLE-STAYED SUSPENSION HYBRID BRIDGE & VALIDA...
 

Similar to Seismic protection of the Rion-Antirion Bridge

Study About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewStudy About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewIRJET Journal
 
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes Theories
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes TheoriesDynamic Response of Offshore Articulated Tower-Under Airy and Stokes Theories
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes TheoriesIRJET Journal
 
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed Bridge
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed BridgeOptimum Location of Seismic Isolation for Manavgat Cable-Stayed Bridge
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed BridgeIJAEMSJORNAL
 
Seismic protection of cable stayed bridge using supplemental devices
Seismic protection of cable stayed bridge using supplemental devicesSeismic protection of cable stayed bridge using supplemental devices
Seismic protection of cable stayed bridge using supplemental devicesManish Mall
 
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating DevicesStrengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating Devicespaperpublications3
 
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...IRJET Journal
 
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGSEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGIRJET Journal
 
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...ijtsrd
 
Conceptual design and analysis of long span structures
Conceptual design and analysis of long span structuresConceptual design and analysis of long span structures
Conceptual design and analysis of long span structuresAnupama Krishnan
 
On Diagnosis of Longwall Systems
On Diagnosis of Longwall SystemsOn Diagnosis of Longwall Systems
On Diagnosis of Longwall Systemscsandit
 
On diagnosis of longwall systems
On diagnosis of longwall systemsOn diagnosis of longwall systems
On diagnosis of longwall systemscsandit
 
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...IRJET Journal
 
IRJET- Design and Analysis of Floating Residence
IRJET- Design and Analysis of Floating ResidenceIRJET- Design and Analysis of Floating Residence
IRJET- Design and Analysis of Floating ResidenceIRJET Journal
 
Review on Base Isolated Structures
Review on Base Isolated StructuresReview on Base Isolated Structures
Review on Base Isolated StructuresIRJET Journal
 
IRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET Journal
 
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperAnalysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperIRJET Journal
 
Parametric Study of Elevated Water Tank with Metallic and Friction Damper
Parametric Study of Elevated Water Tank with Metallic and Friction DamperParametric Study of Elevated Water Tank with Metallic and Friction Damper
Parametric Study of Elevated Water Tank with Metallic and Friction DamperIRJET Journal
 
IRJET- A Study on Seismic Performance of Reinforced Concrete Frame with L...
IRJET-  	  A Study on Seismic Performance of Reinforced Concrete Frame with L...IRJET-  	  A Study on Seismic Performance of Reinforced Concrete Frame with L...
IRJET- A Study on Seismic Performance of Reinforced Concrete Frame with L...IRJET Journal
 

Similar to Seismic protection of the Rion-Antirion Bridge (20)

Study About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewStudy About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A review
 
Ppt
PptPpt
Ppt
 
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes Theories
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes TheoriesDynamic Response of Offshore Articulated Tower-Under Airy and Stokes Theories
Dynamic Response of Offshore Articulated Tower-Under Airy and Stokes Theories
 
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed Bridge
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed BridgeOptimum Location of Seismic Isolation for Manavgat Cable-Stayed Bridge
Optimum Location of Seismic Isolation for Manavgat Cable-Stayed Bridge
 
Seismic protection of cable stayed bridge using supplemental devices
Seismic protection of cable stayed bridge using supplemental devicesSeismic protection of cable stayed bridge using supplemental devices
Seismic protection of cable stayed bridge using supplemental devices
 
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating DevicesStrengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
 
S7
S7S7
S7
 
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
 
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGSEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
 
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...
Structural Behaviors of Reinforced Concrete Dome with Shell System under Vari...
 
Conceptual design and analysis of long span structures
Conceptual design and analysis of long span structuresConceptual design and analysis of long span structures
Conceptual design and analysis of long span structures
 
On Diagnosis of Longwall Systems
On Diagnosis of Longwall SystemsOn Diagnosis of Longwall Systems
On Diagnosis of Longwall Systems
 
On diagnosis of longwall systems
On diagnosis of longwall systemsOn diagnosis of longwall systems
On diagnosis of longwall systems
 
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...
Seismic Analysis of Four Legged Telecommunication Towers using Fluid Viscous ...
 
IRJET- Design and Analysis of Floating Residence
IRJET- Design and Analysis of Floating ResidenceIRJET- Design and Analysis of Floating Residence
IRJET- Design and Analysis of Floating Residence
 
Review on Base Isolated Structures
Review on Base Isolated StructuresReview on Base Isolated Structures
Review on Base Isolated Structures
 
IRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise Building
 
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperAnalysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
 
Parametric Study of Elevated Water Tank with Metallic and Friction Damper
Parametric Study of Elevated Water Tank with Metallic and Friction DamperParametric Study of Elevated Water Tank with Metallic and Friction Damper
Parametric Study of Elevated Water Tank with Metallic and Friction Damper
 
IRJET- A Study on Seismic Performance of Reinforced Concrete Frame with L...
IRJET-  	  A Study on Seismic Performance of Reinforced Concrete Frame with L...IRJET-  	  A Study on Seismic Performance of Reinforced Concrete Frame with L...
IRJET- A Study on Seismic Performance of Reinforced Concrete Frame with L...
 

More from gefyra-rion

ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012
ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012
ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012gefyra-rion
 
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχων
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχωνΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχων
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχωνgefyra-rion
 
Universite de tous les savoirs
Universite de tous les savoirsUniversite de tous les savoirs
Universite de tous les savoirsgefyra-rion
 
The stay cable system papanikolas liolios
The stay cable system papanikolas lioliosThe stay cable system papanikolas liolios
The stay cable system papanikolas lioliosgefyra-rion
 
Patras 4th congress on steel structures
Patras 4th congress on steel structuresPatras 4th congress on steel structures
Patras 4th congress on steel structuresgefyra-rion
 
Montrιal o.flamand
Montrιal o.flamandMontrιal o.flamand
Montrιal o.flamandgefyra-rion
 
Mokpo symposium pecker 2006
Mokpo symposium pecker 2006Mokpo symposium pecker 2006
Mokpo symposium pecker 2006gefyra-rion
 
Iscd2009 flamand ppa_final
Iscd2009 flamand ppa_finalIscd2009 flamand ppa_final
Iscd2009 flamand ppa_finalgefyra-rion
 
Seismic Design for the Foundation of the Rion Antirion Bridge
Seismic Design for the Foundation of the Rion Antirion BridgeSeismic Design for the Foundation of the Rion Antirion Bridge
Seismic Design for the Foundation of the Rion Antirion Bridgegefyra-rion
 
Hsgf bolts papanikolas
Hsgf bolts papanikolasHsgf bolts papanikolas
Hsgf bolts papanikolasgefyra-rion
 
Geo trans2004 pecker
Geo trans2004 peckerGeo trans2004 pecker
Geo trans2004 peckergefyra-rion
 
Fib2010 article269 june 2008 eq case study_rev_a
Fib2010 article269 june 2008 eq case study_rev_aFib2010 article269 june 2008 eq case study_rev_a
Fib2010 article269 june 2008 eq case study_rev_agefyra-rion
 

More from gefyra-rion (20)

ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012
ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012
ΓΕΦΥΡΑ Α.Ε. – Ισολογισμός 31.12.2012
 
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχων
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχωνΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχων
ΓΕΦΥΡΑ Α.Ε. – Πρόσκληση σε τακτική γενική συνέλευση των μετόχων
 
Universite de tous les savoirs
Universite de tous les savoirsUniversite de tous les savoirs
Universite de tous les savoirs
 
Travaux no 809
Travaux no 809Travaux no 809
Travaux no 809
 
The stay cable system papanikolas liolios
The stay cable system papanikolas lioliosThe stay cable system papanikolas liolios
The stay cable system papanikolas liolios
 
Pecker aci2003
Pecker aci2003Pecker aci2003
Pecker aci2003
 
Pecker salencon
Pecker salenconPecker salencon
Pecker salencon
 
Patras 4th congress on steel structures
Patras 4th congress on steel structuresPatras 4th congress on steel structures
Patras 4th congress on steel structures
 
Montrιal o.flamand
Montrιal o.flamandMontrιal o.flamand
Montrιal o.flamand
 
Mokpo symposium pecker 2006
Mokpo symposium pecker 2006Mokpo symposium pecker 2006
Mokpo symposium pecker 2006
 
Londe ap
Londe apLonde ap
Londe ap
 
Lisbonne
LisbonneLisbonne
Lisbonne
 
La recherche
La rechercheLa recherche
La recherche
 
Ix 29
Ix 29Ix 29
Ix 29
 
Iscd2009 flamand ppa_final
Iscd2009 flamand ppa_finalIscd2009 flamand ppa_final
Iscd2009 flamand ppa_final
 
Seismic Design for the Foundation of the Rion Antirion Bridge
Seismic Design for the Foundation of the Rion Antirion BridgeSeismic Design for the Foundation of the Rion Antirion Bridge
Seismic Design for the Foundation of the Rion Antirion Bridge
 
Hsgf bolts papanikolas
Hsgf bolts papanikolasHsgf bolts papanikolas
Hsgf bolts papanikolas
 
Habib
HabibHabib
Habib
 
Geo trans2004 pecker
Geo trans2004 peckerGeo trans2004 pecker
Geo trans2004 pecker
 
Fib2010 article269 june 2008 eq case study_rev_a
Fib2010 article269 june 2008 eq case study_rev_aFib2010 article269 june 2008 eq case study_rev_a
Fib2010 article269 june 2008 eq case study_rev_a
 

Recently uploaded

Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxLoriGlavin3
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxLoriGlavin3
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity PlanDatabarracks
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 3652toLead Limited
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embeddingZilliz
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Manik S Magar
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxLoriGlavin3
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsNathaniel Shimoni
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersNicole Novielli
 

Recently uploaded (20)

Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptxA Deep Dive on Passkeys: FIDO Paris Seminar.pptx
A Deep Dive on Passkeys: FIDO Paris Seminar.pptx
 
How to write a Business Continuity Plan
How to write a Business Continuity PlanHow to write a Business Continuity Plan
How to write a Business Continuity Plan
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embedding
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!
 
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptxMerck Moving Beyond Passwords: FIDO Paris Seminar.pptx
Merck Moving Beyond Passwords: FIDO Paris Seminar.pptx
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directions
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software Developers
 

Seismic protection of the Rion-Antirion Bridge

  • 1. 8th World Seminar on Seismic Isolation, Energy Dissipation and Active Vibration Control of Structures Yerevan, Armenia, October 6-10, 2003 SEISMIC PROTECTION OF THE RION-ANTIRION BRIDGE Samuele Infanti1 , P. Papanikolas2 , M.G. Castellano3 1 FIP Industriale, Via Scapacchiò 41, 35030 Selvazzano Dentro (PD), Italy, infanti.fip@fip-group.it 2 Kinopraxia Gefyra, Antirio Aetolocarnania PC 300 20, Greece , ppapanikolas@gefyra.com 3 FIP Industriale, Via Scapacchiò 41, 35030 Selvazzano Dentro (PD), Italy, castellano.fip@fip-group.it ABSTRACT The Rion-Antirion Bridge, which crosses the homonymous strait in Greece, is located in a region prone to high intensity earthquakes and large tectonic movements generated by local active seismic faults. The deck of the multi-span cable stay bridge is continuous and fully suspended (for its total length of 2,252 meters) from four pylons (with spans 286m + 560m + 560m + 560m + 286m). The approach viaducts to the main bridge comprises for 228m of precast concrete girder decks on the Antirion side and for 990m of steel composite decks on the Rion side. The structures are designed to withstand seismic events with peak ground acceleration of 0.48g (2000 years return period) and tectonic movements between two piers of 2 meters in any direction. This was possible through the use of innovative energy dissipation systems that connect the deck to the top of each pier and limits the movement of the decks during the specified earthquake, while dissipating the seismic energy. The seismic protection system of the Main Bridge comprises fuse restraints and viscous dampers acting in parallel, connecting the deck to the pylons. The restrainers are designed as a rigid link intended to withstand the high wind loads up to a pre-determined force corresponding to a value slightly higher than the wind load ultimate limit state. Under the specified earthquake, the fuse restrainers are designed to fail, leaving the viscous dampers free to dissipate the energy induced by the earthquake into the structure. The behavior and the requirements of the dissipation systems were optimized with the help of a non-linear time history numerical analysis on a 3D model. It resulted on seismic devices (viscous dampers and fuse links) characterized by extreme design parameters in terms of force, velocity and stroke, with dimensions and weight never attempted before. The design assumptions and the actual behavior of the seismic protection system had to be confirmed with extensive testing of full-scale prototypes. The Approach Viaducts are isolated from the ground motion through a system composed of elastomeric isolators designed to provide for the bearing function as well as the required period shift effect and by viscous dampers providing for the energy dissipation. Even in this case, numerical analysis provided the units optimized characteristics and full-scale tests have been performed to verify the design assumptions. The aim of the present paper is to describe the mentioned seismic protection systems as well as the results of the full-scale prototype testing. The Viscous Damper Prototype tests were
  • 2. performed at the laboratory of the University of San Diego California (USA), while the Fuse Restraints tests and all the production tests were carried out at the FIP Industriale Testing Laboratory in Italy. 1 INTRODUCTION The Rion-Antirion Bridge (see figure 1), located in the Gulf of Corinth - an area prone to strong seismic events and windstorms -, consists of a cable stayed main bridge 2,252 m long on four large foundations with a span distribution equal to 286m + 560m + 560m + 560m + 560m + 286m and of two approach viaducts (987 m long on the Rion side and 239 m long on the Antirion side). The cable-stayed deck is a composite steel structure made of two longitudinal plate girders 2.2m high on each side of the deck with transverse plate girders spaced at 4m and a concrete slab, the total width being 27m. Each pylon is composed of four legs 4x4m, made of high strength concrete, joined at the top to provide the rigidity necessary to support unsymmetrical service loads and seismic forces. The pylons are rigidly embedded in the pier head to form a monolithic structure, up to 230 m high, from the sea bottom to pylon top (see figure 2). The deck of the main bridge is continuous and fully suspended by means of stay cables for its total length of 2,252m. In the longitudinal direction, the deck is free to accommodate all thermal and tectonic movements. Figure 1. The Rion-Antirion Bridge
  • 3. The bridge is equipped with a damping system that, for its characteristics and for the strict design requirements, entitles to put this structure in the next generation of seismic protected structures. The seismic protection system of the main bridge comprises viscous dampers connecting in the transverse direction the fully suspended deck to the pylon base. These viscous dampers are of ever built dimensions and design capacity and shall be installed at the pier to deck interfaces in order to reduce the transverse swing of the deck during a dynamic event. They are designed to dissipate the energy introduced into the structure by the earthquake. Requirements for a proper and safe seismic behavior are sometimes not in agreement with the everyday service life of the structure. Thus, large structural displacements induced by moderate earthquakes or windstorms are avoided by an additional restraint system, that at the occurrence of a major design event fails allowing the structure free to oscillate with its damping system. This system is composed by Fuse Restraints installed in parallel to the dampers, so that the deck, when subjected to lateral loads not exceeding their design capacity, is linked rigidly to the substructure, while after failure it leaves the deck free to swing coupled to the dampers. The design failure force of the fuse restraints is set slightly higher than the maximum expected wind load. Four viscous dampers (Fmax 3500 kN, Stroke ±1750 mm) and one fuse restrainer (Fmax 10500 kN) shall be installed at each pylons, while at the transition piers two viscous dampers (Fmax 3500 kN, Stroke ±2600 mm) and one Fuse Restrainer (Fmax 3400 kN) shall be considered. Figure 2. The main bridge under advanced construction (September 2003)
  • 4. Figure 3 gives the general arrangement of the four viscous dampers and the restraint device at one pylon. Figure 4 shows the conceptual arrangement of the two viscous dampers installed at the Transition Pier. This pier is composed by a rotating frame pivoting at the base. The mentioned dampers are installed at the deck to substructure interface aligned along the deck transverse center line and rotating with the pier itself. The Fuse Restrainer is installed on one of the two dampers as a component of the damper itself. The Approach Viaducts are seismically isolated through a system composed of elastomeric isolators designed to provide for the bearing function as well as the required period shift effect and by viscous dampers providing for the energy dissipation. Even in this case, numerical analysis provided the units optimized characteristics and full- scale tests have been performed to verify the design assumptions. This paper describes the different seismic devices to be applied to the Rion-Antirion Bridge, focusing on the full-scale tests carried out for qualification and acceptance purposes. General information about non-linear viscous dampers are also given below. Figure 3. Rion Antirion Main Bridge: arrangement of viscous dampers on the main piers Fuse RestrainerViscous Damper
  • 5. 2 NON-LINEAR VISCOUS DAMPERS FIP fluid viscous dampers are piston/cylinder devices that utilize fluid flow through orifices to absorb energy. Orifices are situated in the piston head, which allow the fluid to move back and forth between the two chambers. The force generated by these devices is the result of a pressure differential across the piston head. These devices are equipped with two spherical hinges at both ends that keep the transmitted load aligned along their main axis. This detail is of major importance to provide a reliable performance: it prevents the piston rod from bending and thus the sealing system from failing. High strength steel components are used for the vessel and the plated piston rod so as to withstand the actions imposed by a dynamic load. The anchoring details depend only on the structure to which they are anchored: for example, the tang plate/clevis system illustrated in Figure 5. In the last few years, FIP dampers have undergone major testing programs at FIP laboratory as well as at independent facilities (Earthquake Engineering Research Center, Berkeley CA – USA, Boeing Testing Facility, Canoga Park CA – USA and Caltrans SRMD Testing Laboratory at the University of California – San Diego - USA), which has entitled the company to be a pre-qualified damper manufacturer for the Golden Gate Bridge Retrofit project as well as to enter the CALTRANS (California Department of Transportation) list of pre-qualified damper manufacturers. It should be noted that remarkable reaction stability has been achieved by dynamically cycling within a very wide temperature range (-40°C ÷ +50°C) that guarantees proper behavior under any type of environmental conditions. Figure 4. Transition pier configuration
  • 6. A very important issue related to the utilization of the technology entails the correct numerical modeling of the devices as integrated into the structural model and the performance verification of the finished product. The latter topic will be amply discussed in the following paragraphs. .The most appropriate mathematical model to represent the behavior of an FIP viscous damper is to use a Maxwell constitutive law characterized by a linear spring in series to a non-linear dash-pot element (see Figure 6). The first element represents the elasticity of the system that is mainly due to the compressibility of the silicon fluid, while the second depicts its damping properties. The exponent that characterizes the non-linearity of the response as a function of the velocity, is particularly important. Positive effects are undoubtedly related to low exponent dampers: e.g. in bridge applications, reduced pier deformation, lower expansion joint costs and cost effective bearings or in buildings, maximum reduction of relative displacement at the isolation interface or in the braces. FIP viscous dampers are designed to guarantee a 0.15 exponent so that, within a wide velocity range, reaction is expected to be almost constant. This performance characteristic permits the devices to initiate their damping reaction at low velocities, providing the maximum reduction of the superstructure displacement. Total system elasticity, mathematically represented by the stiffness K, depends on the compressibility of the fluid and it is particularly evident at the point of motion reversal, or at any rate, at the point of transitory phases: commonly, it is a secondary effect and often it is not even computed. Figure 5. Typical damper anchoring configuration (photo taken during the installation)
  • 7. Test 1 - Performance Benchmark (TA #3) -800 -600 -400 -200 0 200 400 600 800 -250 -200 -150 -100 -50 0 50 100 150 200 250 300 Displacement (mm) Force(kN) Maxwell Model 15.0 )(0 K F xCF tsinxx K C, x(t) Figure 6. Damper constitutive law equation and hysteresis loop To evaluate the response of such a system, the differential non-linear equation representing its constitutive law needs to be integrated. Looking at the plot in Figure 6, it can be noted that this typical hysteresis loop looks almost rectangular even if the displacement time–history is sinusoidal (thus velocity dependent). This is due to the damper characteristic exponent (0.15). In fact, the behavior is almost independent from velocity. Thus total damper behavior can be similar to that of a spring in series to a ”perfectly plastic” element characterized by a constant threshold force. 3 MAIN BRIDGE SEISMIC ISOLATION SYSTEM As above anticipated, the seismic isolation system of the main bridge comprises fluid viscous dampers and fuse restraints. The behavior and the requirements of the viscous dampers were optimized by means of non- linear time-history analyses on a 3-D model of the entire bridge. Strict specifications were imposed with regards to the behavior of the seismic protection system in order to ensure a stable performance of all the devices: dampers reaction shall be within 15% of its theoretical constitutive law and Fuse restrainers failure shall be within 10% of the design value. Full-scale tests aimed at verifying the design characteristics are described below. 3.1 Viscous Dampers Full-Scale Testing The following paragraphs present the main result of the testing activities performed at both FIP Industriale Testing Laboratory and at the Seismic Response Modification Device (SRMD) Testing Laboratory of Caltrans at the University of California at San Diego on a full-scale prototype of the viscous dampers to be utilized on the above mentioned bridge.
  • 8. The prototype, characterized by a 3220 kN reaction at the maximum design velocity of 1.6 m/s (damping constant C=3000kN·(s/m)0.15 ) and by a ±900mm stroke, was submitted by FIP Industriale on February 2002 for evaluation. This viscous damper is deemed to be the largest ever-built device of its type (6.4 m pin to pin) and was tested up to its maximum design conditions. The prototype is equal in every detail to the dampers designed for final installation with the exception of the length (and consequently of the stroke), which is shorter so as to fit into the existing test rig of the SRMD. Table 1. Dampers Characteristics Characteristics Pylons Transition Piers Prototype Damper Series OTP350/3500 OTP350/5200 OTP350/1800 Stroke (mm) -1650/+1850 ± 2600 ± 900 Pin-to-Pin Length (mm) 10520 11320 6140 Total Length (mm) 11310 12025 6930 Maximum Diameter (mm) 500 550 500 Damper Weight (kg) 6500 8500 3300 Total Weight (kg) 9000 11000 5500 3.1.1 Prototype Full-scale testing at FIP Industriale Laboratory – Italy The above mentioned prototype underwent to two series of tests. The first one was performed at FIP Industriale Testing Laboratory, where the unit was tested for final tuning of its damping characteristics before shipment to the UCSD laboratory for official testing in presence of the client (Kinopraxia Gefyra - Greece) and of the bridge design checker (Buckland & Taylor - Canada). Figure 7. Production damper under test at FIP laboratory
  • 9. FIP Industriale Testing Laboratory is equipped with a power system providing for 630 kW at 1200l/min thus resulting to be the most powerful in Europe for full-scale dynamic testing of seismic devices. Being the above unit of exceptional characteristics, the prototype was tested up to the maximum velocity provided by the available system, which resulted to be 0.2 m/s. In Figure 8, the prototype is shown during dynamic testing at FIP testing Laboratory. Figure 9. Experimental measurements vs. damper constitutive law Figure 8. Viscous Damper Prototype during testing at FIP Laboratory Actuator Test Rig Frame Servo-valve Damper
  • 10. For testing purposes, the unit was pinned at one end to the test rig (yellow colored) while its piston rod was connected directly to the actuator through a 3000kN capacity load cell. The damper reaction was measured through the mentioned load cell as well as indirectly from the pressure detected on the actuator through a pressure gauge. The displacement was measured through a magneto-strictive displacement transducer. In figure 9, the test results are reassumed and it is evident how the damper behavior follows the theoretical constitutive law with a minimal deviation. 3.1.2 Full-scale testing at SRMD Testing facility – California, USA The damper OTP 350/1800 was tested at the Seismic Response Modification Device (SRMD) testing facility of the University of California San Diego. The test matrix is reported in Table 2 (tests are listed in the same order they were carried out). It is worth noting that the tests were performed up to the maximum design velocity equal to 1.6m/s. It was the first time that a damper of a so high load capacity was tested at such a high velocity. The specimen was horizontally installed in the testing rig, connected at one end to a reaction wall and at the other end to the movable platen. The six degrees of freedom table is capable of unique level of displacement, forces and velocities. For this specific application the platen was moved in the longitudinal direction, with a displacement control loop able to maintain the components of motion in the other directions at negligible level. Figure 10 shows the damper installed on the testing frame. Figure 10. Prototype testing at SRMD Facility (UCSD) Peak forces measured at different velocity levels are reported in Figure 11.
  • 11. Table 2 Test Protocol Prototype FIP OTP 350/1800 Test # Test Name Input Number of cycles Stroke Testing conditions (V = Peak Velocity) 1 Thermal Linear 1 895 mm V<0.05 mm/s for 5 minutes Increase velocity to 1mm/s up to completion of the displacement. 2 Velocity Variation Sinusoidal 5 5 5 3 2 300 mm V=0.13 m/s V=0.40 m/s V=0.80 m/s V=1.20 m/s V=1.60 m/s 3 Full stroke & Velocity Sinusoidal or step loading 1 850 mm Vmax=1.6 m/s 4 Wear Linear 20000 5 mm V=15 mm/s Every hour change position of the piston of about 100 mm 5 Velocity variation Sinusoidal 2 300 mm Vmax=1.6 m/s Maximum forces appear to be very symmetric in the all range of velocity. A difference of 7% was recorded at maximum speed (1.6 m/s) only for the first cycle. The second cycle of the same test shows instead a deviation of 1.6%. The comparison among peak forces of different cycles shows a reduction of the peak force of 3.8% between fifth cycle and first cycle for test Velocity A (0.13 m/s). For the high speed tests the maximum force reduction is equal to 10.4%. Figure 11. Experimental vs.theoretical – damper constitutive law
  • 12. The calculated energy dissipated per cycle (EDC) for the Full Stroke and Velocity Test was 11035 MNm (+6% of the theoretical EDC). In order to perform this test a 3.3 MW power input was required. Wear tests were completed with 10 sets of 2250 cycles, at constant velocity of 0.015 m/s and 10 mm total stroke. Figure 12. Experimental damper hysteresis loop The force vs. displacement response of the damper is reported in Figure 12 for the test at 1.2 m/s peak velocity. Thermocouples were installed both internally and externally the damper body in order to monitor temperature rise during and after the motions. Air and nitrogen gas was used, in a cooling box, to restore the ambient temperature on the damper before a new test. Temperature rise was recorded for each test. The maximum increase took place at the end of the test Velocity Variation B, with 40 degrees Celsius recorded from the sensor installed internally to the damper. All the test results were deemed to be in agreement with the design specifications. It is worth to stress how the test results obtained at the SRMD facility agreed very well with the measurements performed at FIP testing laboratory and how the damper behavior resulted to provide for stable reaction in a very wide velocity range (0.002 – 1.6 m/s). The extrapolation of the damper reaction in the range of velocity 0.13-1.6 m/s from the test performed at FIP laboratory up to 0.2 m/s differed from the measured reaction at the SRMD facility by only few percent point. This result demonstrates how much predictable is the damper behavior within the full test range. The test aimed at verifying the damper reaction at low velocity (0.1 mm/s) measured a reaction of 200kN. 3.1.3 Quality Control (production) tests at FIP Industriale Laboratory The aim of the production tests was to verify the compliance of the production units with the contract specification or, in other words, that their reaction and damping characteristics fall within the design tolerance range. The test is performed on 100% of the produced units and at the current time, two production lots have been already full-scale tested at FIP Industriale Laboratory in Italy (see figure 7 for the testing configuration of a production unit).
  • 13. The contractual test program requires for the following tests: Proof Pressure test: the test is aimed to verify that the damper vessel withstand with no damage or leakage 125% of the design internal pressure. Low velocity test: the test is aimed to verify that the damper reaction at low velocity (less than 0.1mm/s) is less than 200kN in order to allow for easy of length adjustment and to avoid fatigue loads on the bridge. Dynamic test: the test is aimed to verify that the units provide for a reaction that follows the theoretical constitutive law with a maximum deviation of 15%. All the above mentioned tests have yielded a positive outcome. In figure 13, a graph shows for all the units of the first two production lots (serial numbers from 414946 to 414953) the measured reaction, normalized with reference to the theoretical reaction, obtained imposing three sinusoidal cycles of 250mm stroke amplitude and reaching a peak velocity of 100mm/s (see figure 14). It is worth to note that the maximum measured deviation was -4.8% with respect to the theoretical reaction at 100mm/s (2124kN). The measurements confirmed the results obtained during the prototype testing at the SRMD Facility of the University of California at San Diego. Figure 13. Normalized reaction of the production units Production Test Damper Force Measured at 100mm/s 0,60 0,65 0,70 0,75 0,80 0,85 0,90 0,95 1,00 1,05 1,10 1,15 1,20 45 46 47 48 49 50 51 52 53 54 Serial Number NormalizedForce Lower Bound (-15%) Upper Bound (+15%) Theoretical Force Measured Force First Lot Second Lot
  • 14. 4 FUSE RESTRAINTS Fuse restraints shall provide for a stiff link between the deck and the substructure for the lateral service load as well as for low occurrence high-intensity windstorms. As anticipated, only at the occurrence of high intensity events they are designed to fail allowing the damping system to work properly. They are located at the main piers as well as at the transition piers. The main pier units are designed as single units equipped at their ends with spherical hinges. This configuration allows for the design rotations as well as for a correct alignment of the load along the device axis for any deck position. The element failing at the reaching of the desired design load – the so-called Fuse Element - is installed in the middle of the unit, for a general configuration of the unit see Figure 15. The units to be installed on the main piers are characterized by a failure load of 10500kN. Similarly the units installed at the transition piers, that are installed as components of the dampers, are characterized by a failure load of 3400kN. The design tolerance on the failure load of the units requires a precision of ±10%: a very strict design performance for such a high capacity units. Furthermore, a main design complication came from the need of minimizing the internal forces of the laterally restraint deck induced by tectonic movements originated from seismic fault located under the bridge. Thus, the units located on the main piers are equipped with a system designed to allow for length adjustment. This operation is performed when a certain load level is constantly applied to the link, so a load cell monitoring the load on the unit is required. As part of the monitoring system of the bridge, this will allow to identify the moment at which re-adjustment of the deck is required. Another design requirement was that the units shall not disassemble after failure of the main component, so the units were designed to allow for the same stroke provided by the dampers. Being the restraints first function to withstand the every day actions (service loads), a test has been required to evaluate the fatigue life as well as any influence on the failure strength. -300 -200 -100 0 100 200 300 Stroke [mm] -2500 -2000 -1500 -1000 -500 0 500 1000 1500 2000 2500Lo ad [k N] 0 10 20 30 40 50 60 Time [s] -300 -200 -100 0 100 200 300Str ok e [m m] 0 10 20 30 40 50 60 Time [s] -100 -50 0 50 100 Ve lo cit y [m m/ s] Rion Antirion Main Bridge OTP 350/3500 S. N° 414946 Data ref. : Graph. ref. : Date : Force Vs Displacement Hysteresis Loop at 100 mm/s Din100mms Operator : 19/05/03 Ruggero D. rioant01 Load Vs. Stroke Stroke Vs. Time Velocity Vs. Time 3 Cycles Ampl. +/-250 mm Freq. 0.064 Hz Figure 14. Dynamic test results
  • 15. Figure 15. Fuse restraint general configuration 4.1 Testing program The testing program was carried out on two full-scale prototypes of fuse element for each typology. It consisted on a first test performed on one unit increasing monotonically the load up to failure, while a second test was performed on the other prototype imposing two millions of cycles at a load level equal to 10% of the design failure load and then increasing monotonically the load up to failure. Failure test and fatigue test were carried out on different test rigs, the first one is a 8000 kN capacity test rig commonly used for bearing test while the second one is a 3000kN dynamic test rig: the same used for damper testing. Testing results have shown that both prototypes failed within the design tolerance. The difference between the measured failure loads before and after fatigue test can just confirm that the design fatigue load cannot be considered as effecting the ultimate capacity of the fuse restraints. In the following table, all the testing results are presented. Figure 16 shows typical graphs obtained for both the 3400kN and 10500kN units. Table 3. Test Results Device Type Failure Load Capacity (kN) Tolerance Range (kN) Measured Load (kN) Deviation (%) SR340 3400 3060-3740 3545 +4.3 SR340 3400 (Fatigue) 3591 +5.6 SR1050 10500 9450-11550 10382 -1.1 SR1050 10500 (Fatigue) 11765 +12.0
  • 16. SR340 - Failure Test SR1050 - Failure Test Figure 16. Failure Test Figure 17 shows the SR1050 fuse element testing configuration during the fatigue test. Figure 17. SR1050 Fuse element during fatigue test
  • 17. 5 THE RION-ANTIRION BRIDGE APPROACH VIADUCTS 5.1 Introduction The approach viaducts, being of critical importance for the functionality of the main bridge after a seismic attack, have been designed to withstand the same earthquake intensity level of the main bridge (PGA=0.48g). They present different design and construction technology but the same type of seismic isolation system. The Antirion approach viaduct, located on the mainland Greece side, has a total length of 227.96 m (6 spans: 2 spans of 37.460 m and 4 spans of 38.460 m) and it has been already built as shown by figure 18. The viaduct is made of pre-cast pre-stressed concrete girders with reinforced concrete deck slab. Longitudinally, the viaduct consists of simply supported spans linked by continuity deck slabs at the location of supports. The typical cross section consists of 8 pre-stressed concrete girders with transverse diaphragm cross beams on support. The piers of the viaduct are reinforced concrete frames in the transverse direction made of four columns connected at their lower part by a pile-cap and at their upper part by a cross head beam. The abutment consists of bored cast-in-place piles and/or appropriate spread footing on treated soil. Figure 18. The Antirion Approach Viaduct
  • 18. The Rion viaduct is located on the Peloponnesus side and has a total length of 986m. It is currently under construction. The viaduct consists of two independent composite bridges. Each composite structure is made of two girders connected by cross beams. The bearings of the bridge are elastomeric isolators or sliders and are located under the main steel girders. The typical cross section consists of a concrete slab connected to the steel beams by connectors. The piers of the viaduct are reinforced concrete frames in the transverse direction made of two columns connected at their lower part by a pile-cap and at their upper part by a cross head beam. The piers are founded on piles. The seismic isolation system used for the protection of all the approaches consists of a combination of elastomeric isolators and viscous dampers. The isolators provide for the bearing function as well as for the lateral flexibility required to shift the period of the structure and so to reduce the acceleration of the deck. These bearings are made of alternate layers of natural rubber and steel plates vulcanized together and mechanically anchored to the deck and the substructure. Figure 19. Approaches isolation system
  • 19. Viscous dampers, dissipating the energy introduced by the earthquake and so providing for the required damping, are set up in longitudinal and transverse directions between the deck and the pier heads to limit relative displacement. Isolators and dampers installed on the Antirion Approach Viaduct went through an extensive test program performed at the testing departments of ALGA and FIP Industriale in Italy. The main results are shown in the following paragraphs. 5.2 Seismic hardware tests 5.2.1 Elastomeric Isolators Tests have been performed to check the quality and the mechanical characteristics of the elastomeric isolators in order to evaluate stability, capacity, resistance to service loads and, of course, the lateral stiffness. Two typologies have been produced characterized respectively by 500x600x239mm and 500x600x253mm main dimensions and by natural rubber providing for a 1N/mm2 shear modulus. In figures 20 and 21, full-scale isolators under testing at ALGA Laboratory in Italy as well as the graph depicting the measured Force vs. Displacement loop are respectively shown. Figure 20. Isolators under tests
  • 20. Figure 21. Isolators stiffness characteristics 5.2.2 Viscous Dampers Tests aimed to verify the effective damping capacity under dynamic loads, the displacement capacity and the accordance with the expected performance law (Force vs. velocity relationship) were performed on full-scale units. The Antirion Viaduct requires for 44 dampers to be installed both longitudinally and transversally (see figure 22). Figure 22. Dampers typical arrangement Transverse Dampers Longitudinal DampersElastomeric Isolator
  • 21. The longitudinal dampers (24 units) are characterized by a 1200kN load capacity and by strokes ranging from ±200 to ±250mm, whilst the transverse dampers (20 units) are characterized by an 800kN load capacity and by strokes equal to those used longitudinally. Being the proposed technology the same used on the main bridge, the dampers are characterized by a 0.15 damping exponent, thus ensuring an effective damping action even for low velocities. In figure 23, a 1200 kN capacity damper under testing at FIP Industriale Laboratory is shown. In figure 24, the hysteresis loop obtained testing at constant velocity is presented. The Rion Viaduct requires for the installation of 134 units characterized by 300, 600, 1200 and 2400kN load capacity and strokes ranging from ±250 to ±405mm that are currently under production. Figure 23. Production Tests at FIP Laboratory
  • 22. 6 CONCLUSIONS Testing of full-scale viscous dampers and fuse elements were performed in order to confirm the characteristics and the main design assumptions of the seismic dissipation system used for the Rion-Antirion Cable Stayed Bridge and for the approach viaducts. Tests performed on Fuse elements verified positively the design assumption showing that it is possible to achieve a very tight tolerance ( 10%) on the predicted ultimate capacity even when the units are designed for a very high failure load (10500kN). The Viscous Damper prototype demonstrated very stable behavior even when tested under dynamic conditions, requiring power dissipation higher than design parameters. The measured energy dissipation and viscous reaction were always well within the design tolerance of ±15% of the theoretical design parameters. Testing aimed to represent the effect of structural vibrations induced by traffic and/or of movement induced by structure thermal expansion did not produce any appreciable change in the damper behavior. The production tests confirmed that the dampers to be installed on the bridge provide for the same characteristics of the prototype with a deviation from the theoretical constitutive law lower than 5%. Full-scale testing of large size dissipating devices proved to be a real challenge compared to previous testing experiences as it pushed the limits of equipment available worldwide. Experimental results on full-scale units give a high degree of confidence on seismic devices as a means to protect large and important structures such as the Rion-Antirion Cable Stayed Bridge and its approaches. -120 -90 -60 -30 0 30 60 90 120 Displacement [mm] -1000 -750 -500 -250 0 250 500 750 1000 Force[kN] 0 1 2 3 4 5 6 7 8 9 10 Time [s] -120 -90 -60 -30 0 30 60 90 120 Displacement[mm] 0 1 2 3 4 5 6 7 8 9 10 Time [s] -150 -120 -90 -60 -30 0 30 60 90 120 150 Velocity[mm/s] Sep-Gefyra Kiropraxia Test on Damper 120/400 Reaction = 878 kN Data ref. : Graph. ref. : Date : Force Vs Displacement Hysteresis Loop at 125 mm/s Rionotp120a125mms Operator : 09/07/02 Ruggero D. Otp120gefyra Force Vs. Displacement Displacement Vs. Time Velocity Vs. Time VP21/02Enclosure3Graph1 Figure 24. Hysteresis Loop
  • 23. ACKNOWLEDGEMENT The authors wish to express their sincere gratitude for the active and fruitful cooperation rendered by Mr. Gianmario Benzoni of the UCSD Laboratory, as well as the indefatigable support furnished by Mr. Renato Chiarotto of FIP Technical Department, Mr. Pierluigi Galeazzo Testing Laboratory Manager of FIP Industriale and his staff. A remarkable thank is addressed to Mr. Agostino Marioni (ALGA) and to Mr. Philippe Salmon (Freyssinet) for their cooperation within the JV operations. REFERENCES Benzoni G., Seible F, “Rion-Antirion Bridge - Prototype Tests of Damper FIP OTP 350/1800” Caltrans SRMD Test Facility Report N. 2002/01, San Diego CA - USA, 2002. Infanti S., Colato G.P., Castellano M.G., “Structural Devices for Bridge Engineering: the Challenge Goes On”, Bridge Engineering Conference, Sharm El-Sheikh – Egypt, 2000. Infanti S., “Seismic Protection of Seohae Bridge Approaches trough Viscous Dampers”, Cable-Supported Bridges – Challenging Technical Limits, IABSE Conference, Seoul - Korea, 2001. Infanti S., Castellano M.G., “ Viscous Dampers: a Testing Investigation according to the HITEC Protocol”, Fifth World Congress on Joints, Bearings and Seismic Systems for Concrete Structures, Rome – Italy, 2001. Infanti S., Castellano M.G., Benzoni G. “Non-Linear Viscous Dampers: Testing and Recent Applications”, ATC 17-2A Seminar on response modification technologies for performance -based seismic design, Los Angeles CA - USA, 2002. Infanti S., Papanikolas P.., Theodossopoulos G. “Rion-Antirion Bridge: Full-Scale Testing of Seismic Devices”, fib Symposium Concrete Structures in Seismic Regions, Athens – Greece, 2003. Technical Report “Evaluation Findings for FIP – Energy Absorption Systems, LLC Slider Bearings ”, Highway Innovative Technology Evaluation Center, 1998. Technical Report “Guidelines for Testing of Seismic Isolation and Energy Dissipating Devices ”, Highway Innovative Technology Evaluation Center, 1998. Technical Report “Evaluation Findings of FIP Industriale Viscous Dampers according to the HITEC testing protocol”, Rocketdyne Division of Boeing, Canoga Park – CA USA, 2000. Teyssandier J.P, Combault J, Morand P., “The Rion-Antirion Bridge Design and Construction” 12th World Conference of Earthquake Engineering, Auckland – New Zealand, 2000.
  • 24. Teyssandier J.P, de Maublanc G., Morand P., Papanikolas P., “The Rion-Antirion Bridge” fib Symposium Concrete Structures in Seismic Regions, Athens – Greece, 2003. Soong T.T., Dargush G.F., ”Passive Energy Dissipation Systems in Structural Engineering”, Wiley, Chichester – England, 1997, 356 pp Skinner R.I., Robinson W.H., McVerry G.H., ”An Introduction to Seismic Isolation”, Wiley, Chichester – England, 1993, 354 pp. Virtuoso F., Guerrero L., Azevedo J., “Modelling the Seismic Behavior of Bridges With Viscous Dampers”, 12th World Conference of Earthquake Engineering, Auckland – New Zealand, 2000.