DeltaV Electronic Marshalling

4,497 views

Published on

0 Comments
2 Likes
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
4,497
On SlideShare
0
From Embeds
0
Number of Embeds
25
Actions
Shares
0
Downloads
131
Comments
0
Likes
2
Embeds 0
No embeds

No notes for slide

DeltaV Electronic Marshalling

  1. 1. DeltaV Product Data SheetNovember 2009 – Page 1 S-series Electronic MarshallingS-series Electronic Marshalling The DeltaV CHARM I/O Card (CIOC) I/O Anywhere you need it Introduction DeltaV’s S-series Electronic Marshalling delivers a new Single Channel granularity level of control system I/O performance with unprecedented flexibility and ease of use. The CHARM Reduces installed cost of system I/O card (CIOC) supports up to 96 individually configurable channels and is designed specifically for multi-core home Fully redundant architecture run cables in centrally located marshalling cabinets. It can also be installed in field junction boxes to further reduce Field mounted capable hardware system design and installation costs. All communications are completely redundant from the channel (CHARM) to Plug and Play I/O the DeltaV S-series controller.www.EmersonProcess.com/DeltaV
  2. 2. DeltaV Product Data SheetNovember 2009 – Page 2 S-series Electronic MarshallingBenefits to create the I/O definition automatically in your DeltaV configuration database. CHARMs use a self keyingI/O Anywhere you need it. DeltaV CHARM I/O system to automatically set a channel for a specificCard (CIOC) provides an unprecedented flexibility in CHARM type. Users cannot mistakenly insert a CHARMcontrol system I/O topology. Using standard Ethernet into the wrong terminal block. Assign all, one or anyinfrastructure hardware you can add I/O anywhere you number of channels to a controller with a simple click andneed it. From a local I/O cabinet to remote enclosures drag.miles away, simply install the hardware and connect it tothe DeltaV control network. Each I/O card can serve I/Osignals to any four controllers in the system with 50 msupdates for fast, reliable control.Single Channel granularity. The CHARM I/Oarchitecture allows each individual channel to becharacterized for the requirements of the field device. Anyinstrument signal can be wired to any terminal block. Thechannel is then electronically marshalled by installing theappropriate CHARM and assigning the channel to one offour controllers. Home run multi-core instrument cablescan be landed in order on a series of CHARM terminalblocks without concern for signal types.Reduces installed cost of system. DeltaV’sElectronic Marshalling helps reduce overall system cost byeliminating internal cabinet cross wiring, reducing overallfootprint, simplifying I/O channel assignments, andreducing FAT activities. Electronic Marshalling providesseparation between I&E hardware installation schedulesand Control Strategy development. Wiring can beginearlier knowing any late changes can be done without CHARM and Terminal Block installation.lifting a wire. Separation of the controller and I/O allowsmore efficient cabinet designs knowing late scopechanges can add I/O anywhere. Adding addition control Field power is provided through a redundant 24VDC buscapacity does not require re-wiring I/O. Simply assign the to each CHARM, with up to 100 mA per CHARM. Highercontrol modules and their I/O signals to the new controller, current Discrete Channels can be powered throughwithout lifting a wire. integrated power injection bus local to each CHARMFully redundant communications. The CIOC Baseplate.architecture is fully redundant. This starts with the two I/Ocards on a carrier. The carrier has redundantcommunication modules for primary and secondarynetwork connections. There are two 24 VDC input powerconnections. The carrier connects to the CHARMSBaseplates and provides redundant power andcommunication buses to the CHARMs. Everything isredundant down to the individual channel.Field mounted capable hardware. Allcomponents of the CIOC are rated for installation in Class1/Div 2 or Zone 2 hazardous locations. The extendedoperating temperature ranges and G3 environment ratingallows them to be installed in field mounted junctionboxes. This further reduces the foot print of the centralequipment rooms as well as reducing the overall wiringinfrastructure of traditional multi-core instrumentationcable.Plug and Play I/O. The DeltaV CIOC has beendesigned for ease of use, both in physical installation andits software tools. Components snap together with secureDIN-rail latches and interlocking carrier connectors.Attach a series of 96 I/O channels to a DIN-rail in a matterof minutes. Insert the CHARMS and auto sense the node
  3. 3. DeltaV Product Data SheetNovember 2009 – Page 3 S-series Electronic MarshallingProduct Description The CHARM I/O card carrier is mounted to the top of a vertical DIN rail and up to eight CHARM Baseplates areElectronic Marshalling hardware includes: mounted below it, snapping easily to the DIN rail as they are connected to each other. The bus termination  CHARM I/O Carrier (DIN rail mounted and assembly is attached at the bottom. A standard DIN-rail supports redundant pair of CHARM I/O Cards) lock to keep the entire assembly in place.  CHARM I/O Card (provides communication Each Baseplate is ordered pre-loaded with 12 terminal between CHARMS and the Ethernet I/O network blocks that are ready to receive field wires from 2, 3 and 4- to S-series controllers) wire devices. Electronic Marshalling eliminates the need to scramble the field wiring or to partition the I/O in order  CHARM Base plate (DIN rail mounted with to match signals to channel types of specific cards. interleaving power and bus connectors. Supports Simply connect field signal multi-cores in an orderly 12 CHARMS and their terminal blocks, as well as fashion as desired. Insert the appropriate CHARM into connection for injected field power) each terminal block to complete the field circuit and the signal is ready to be used by any one of 4 S-series  CHARM Terminal Block (removable terminal controllers. No Cross-Wiring. block providing terminal connections to field wiring and physical latch for CHARM) Each CHARM acts as circuit protection device and field wiring disconnects. Signals are current limited or fused to  CHARMs (Characterizing Module for each field protect against wiring faults to ground. Each CHARM signal. Provides basic analog to digital provides surge protection to meet industry standards in conversion and signal isolation to the redundant the area of EMC, and is designed to fail during overvoltage conditions due to incorrect field wiring. Signal communication bus) faults are isolated to the single charm.  Bulk AC to 24 VDC power supply for CIOC and field devices. (connected to the CIOC carrier with optional redundant power connections) CHARMS can be partially ejected to a locked  Cable Extenders that provide flexibility in carrier position that disconnects mounting. the field wiring from the system to perform field  I/O bus termination (provides bus maintenance actions or to terminations for redundant I/O bus) remove power to a field device. Activating the CHARM latch ejects the CHARM to the detent position. Closing the latch locks the CHARM in place and isolates the field wiring for field work.. CHARM Latch mechanism The CIOC communicates over Ethernet with up to 4 controllers, allowing great flexibility and ease of system expansion. Additional controllers can be added to accommodate increased control scope and I/O can be reassigned without changing the physical wiring. CHARMs can be added to any existing base plate position and autosensed online. Additional CIOC’s can be added on line. CHARM I/O Card.
  4. 4. DeltaV Product Data SheetNovember 2009 – Page 4 S-series Electronic MarshallingCHARM Types The Injected Power Terminal block is designed to be used with the Isolated CHARM types, allowing the CHARM toA variety of analog and discrete CHARMs are available to provide up to 1 amp of system power to the field device.meet your specific requirements. The following CHARMS Supplemental field power is connected to the baseplate’sare available in v11: injected power input terminals, located on the Address Plug terminal block, and distributed to the 12 CHARMs  AI 0/4-20 mA HART through the local power bus of the baseplate. Injected  AO-0/4-20 mA HART power Terminal Blocks connect to this power bus and  DI NAMUR provide system power to the circuit. The injected power  DI 24 VDC Low Side Detection can be 24 VDC, 120 VAC or 230 VAC and can provide a  DO 24 VDC High Side total of 10 Amps of field power for the 12 channels of the  Thermocouple/mV baseplate.  RTD  Voltage 0-10V Typically, all the CHARMs installed on a base plate will have compatible voltage levels as these signals mostIn addition, the following CHARMs will be available as likely share the same multi-core cable. It is also commonisolated channels supporting higher current and voltage practice to separate low voltage and high voltage signalsratings. for safety. Standard Terminal blocks and Injected Power terminal blocks can be used on the same carrier, typically  DI 24 VDC Isolated to allow the use of DO 24 VDC isolated CHARMs on  DO 24 VDC Isolated higher wattage devices along side of standard 24 VDC  DI 120 VAC Isolated instrumentation signals.  DI 230 VAC Isolated  DO 120 VAC Isolated CHARM Keying Posts  DO 230 VAC Isolated The terminal blocks contain keying posts that areAll CHARMs have a bi-color Power/Integrity LED that automatically set and locked to the unique position of theindicates the health of the CHARM. The indications follow first CHARM installed. The keys prevent the insertion ofNE44 guidelines and provide clear, actionable instruction an incorrect CHARM during maintenance activities. Ifto the maintenance personnel. needed, the Keys can be manually reset to allow a - Green Solid: Normal Operation channel to be re-tasked for a different signal type. - Green Blink: Normal awaiting configuration - Red Blink: Fault detected on wiring - Red Solid: Internal Fault detectedDiscrete CHARMs have a Yellow LED to indicate the stateof the field signal.All CHARMs meet ISA G3 corrosion specifications by thecareful selection of superior electronic components andthe use of conformal coating.Discrete input CHARMS support Pulse Counters with amaximum frequency of 10 KHz.I/O Terminal Block OptionsThere are 2 different I/O terminal blocks available to meetthe wiring needs of field signals. CHARM standard Terminal block  Standard Terminal Block  Injected Power Terminal Block The keying mechanism consists of two keying posts thatThe Standard Terminal block can be used with all rotate and lock into the terminal block base. EachCHARMS types. For traditional wiring of field CHARM is assigned a unique key.instrumentation, the CHARMs provide loop power throughthe internally distributed 24 VDC field power. Refer tospecific CHARM specifications for wiring information.
  5. 5. DeltaV Product Data SheetNovember 2009 – Page 5 S-series Electronic MarshallingHardware Specifications Common Environmental Specifications (all components) Operating temperature -40 to 70 C (-40 to 158 F) Storage temperature -40 to 85 C (-40 to 185 F) Relative humidity 5 to 95% , non-condensing Protection rating IP 20, NEMA 12 Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating Shock 10 g ½-sine wave for 11 ms Vibration 1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz CHARM I/O card and carrier
  6. 6. DeltaV Product Data SheetNovember 2009 – Page 6 S-series Electronic Marshalling CHARM I/O Baseplate with CHARMS CHARM
  7. 7. DeltaV Product Data SheetNovember 2009 – Page 7 S-series Electronic Marshalling CHARM Standard Terminal Block CHARM Injected Power Terminal Block
  8. 8. DeltaV Product Data SheetNovember 2009 – Page 8 S-series Electronic Marshalling Address Plus Address Plug Terminal Block
  9. 9. DeltaV Product Data SheetNovember 2009 – Page 9 S-series Electronic MarshallingCHARM I/O Card hardware Specifications for CHARM I//O Carrier Number of I/O Cards per carrier 2 (redundant pair) Input power (redundant) 24 VDC ±10% at 15 A maximum Redundant Ethernet connections Fiber-optic: 100BASE-FX with MTRJ connectors; - Full duplex operation; - 2 km nominal distance. • Copper twisted pair: 10/100BASE-TX with RJ45 connectors; - Full duplex operation - 100 m distance Mounting DIN rail Latch to T-type rail Specifications for CHARM IO Card Number of I/O Channels 96 Channels, Individually defined signal types Number of I/O Clients 4 (Controllers) Number or CIOC’s per Controller 16 Number or CIOC’s per system 300 I/O update rates 50ms User memory N/A CIOC input power (24 VDC) 0.28 Amps per Redundant CIOC node (CHARM power requirements are in addition) CIOC Heat Dissipation 6.68 Watts per Redundant CIOC node - 2 Watts per CIOC - 1.34 Watts per Communication module CIOC output to CHARMS 6.3 VDC redundant power, 24 Watts maximum Fuse Protection (internal) Non-replaceable Fuse Mounting 2-wide CHARM I/O Carrier Communication Redundant Ethernet connections via CHARM I/O Carrier Network Addressing Auto Assigned during commissioning LED Indicators: Green – Power Indicates DC power is applied. Red – Error Indicates an error condition. Green – Active/Standby Indicates operating mode of each CIOC Yellow flashing – Pri./Sec. CN Indicates valid control network communication.
  10. 10. DeltaV Product Data SheetNovember 2009 – Page 10 S-series Electronic Marshalling CHARM Baseplate Number of channels per baseplate 12 Number of base plates per CIOC 8 Addressing One Address Plug (1 through 8) Terminal blocks - Standard Terminal Block - Injected Power Terminal Block Shield connections 1 per channel, plus 1 for cable shield 2 2.1 -0.32 mm / 14 – 22 AWG Gold plated connectors for shield continuity Shield drain connection in Bus Terminator Mounting DIN rail Latch to T-type rail Specifications for Bus Termination Number of connections 2 (Shield Drain wire) 2 Cross Section 2.1 -0.32 mm / 14 – 22 AWG Connection type Screw Cage Strip length 9 - 11 mm / 0.36 – 0.43 in.
  11. 11. DeltaV Product Data SheetNovember 2009 – Page 11 S-series Electronic Marshalling Specifications for Standard Terminal Block Number of connections 4 2 Cross Section 2.1 -0.32 mm / 14 – 22 AWG Connection type Screw Cage * Maximum Current 1 Amp continuous Color Black Strip length 9 - 11 mm / 0.36 – 0.43 in. Specifications for Injected Power Terminal Block Number of connections 2 2 Cross Section -025 -0.32 mm / 14 – 22 AWG Connection type Screw Cage * Maximum Current 1 Amp continuous Color Black Strip length 9 - 11 mm / 0.36 – 0.43 in. Specifications for Address Plug Terminal Block Number of connections 2 sets of 2 connections 2 Cross Section -025 -0.32 mm / 14 – 22 AWG Connection type Screw Cage * Maximum Current 10 Amp continuous Color Black Strip length 9 - 11 mm / 0.36 – 0.43 in. * Maximum Current is limited by CHARM and Baseplate limits
  12. 12. DeltaV Product Data SheetNovember 2009 – Page 12 S-series Electronic MarshallingAnalog Input CHARMS Specifications for AI CHARM, 0/4 to 20 mA, HART Sensor Types 4-20 mA with or without HART 0-20 mA Supports 2-wire and 4-wire device types Nominal signal range (span) 4-20 mA, (0-20 mA optional) Full signal range 0 to 24 mA Field Power (2-wire) 17.4 V at 20 mA @ 24 VDC input Accuracy over temperature range 0.1% of span (0-60º C) 0.25% of span (over -40 -70º C) Repeatability 0.05% of span Resolution 16 bit A/D converter Calibration None required DC/50/60 Hz Common mode N/A rejection Rolloff Frequency (Anti Aliasing) -3dB at 2.7 Hz, -20.5dB at 20 Hz Field Circuit Protection Current Limiting circuit and field wiring disconnect CHARM power req. 30 mA max @ 24 VDC CHARM Heat Dissipation 0.35 W HART support HART v7 pass-through for AMS HART v7 variable and device status available to control HART data update rates 500 ms Simplified circuit and connection diagrams for HART AI-Charm 0/ 4 to 20 mA two wire and four wire transmitters
  13. 13. DeltaV Product Data SheetNovember 2009 – Page 13 S-series Electronic MarshallingRTD CHARMS Specifications for RTD Input CHARM Sensor types RTD input (Types listed in Table) Sensor Configuration 2 wire, 3 wire, or 4 wire Full Scale signal range See Table next page Accuracy See Table next page Repeatability 0.05% of span Resolution 24 Bit A/D converter Calibration None required Sensor excitation current 500 µA in 2-wire and 4 wire configurations 250 µA in 3-wire DC/50/60 Hz Common mode 90dB rejection Rolloff Frequency (Anti Aliasing) -3dB at 2.7 Hz, -20.5dB at 20 Hz Isolation Each sensor galvanically isolated and factory tested to 1000 VDC Open sensor detection Yes Field Circuit Protection Current Limiting circuit and field wiring disconnect CHARM power req. 10 mA max @ 24 VDC CHARM Heat Dissipation 0.25 W
  14. 14. DeltaV Product Data SheetNovember 2009 – Page 14 S-series Electronic Marshalling RTD, ohms Sensor Type Specifications Sensor Type Operating 25° Reference Temperature Resolution Range Accuracy Drift Pt100 -200 to 850°C ± 0.25° C ± 0.02° C/°C ~0.02° C Pt200 -200 to 850°C ± 0.25° C ± 0.02° C/°C ~0.02° C Pt500 -200 to 850°C ± 0.25° C ± 0.02° C/°C ~0.02° C Pt1000 -200 to 260°C ± 0.25° C ± 0.02° C/°C ~0.01° C Ni120 -80 to 260°C ± 0.15° C ± 0.01° C/°C ~0.01° C Ni100 -80 to 260°C ± 0.20° C ± 0.01° C/°C ~0.01° C Ni200 -80 to 260°C ± 0.20° C ± 0.01° C/°C ~0.01° C Ni500 -80 to 260°C ± 0.20° C ± 0.01° C/°C ~0.01° C Ni1000 -80 to 150°C ± 0.20° C ± 0.01° C/°C ~0.01° C Cu10 -200 to 260°C ± 0.25° C ± 0.02° C/°C ~0.01° C Resistance/user defined 0 to 2,000 Ω ± 0.25 Ω ± 0.03 Ω/°C ~0.031 Ω Simplified circuit diagram for RTD CHARM
  15. 15. DeltaV Product Data SheetNovember 2009 – Page 15 S-series Electronic MarshallingThermocouple/mV CHARMS Specifications for Thermocouple/mV Input CHARM, Sensor types  Thermocouple B, E, J, K, N, R, S, T, uncharacterized  mV Low level voltage source Full Scale signal range See Table next page Accuracy See Table next page Repeatability 0.05% of span Resolution 24 Bit A/D converter Calibration None required Cold junction compensation(CJC) Accuracy ± 1.0º C Range -40 to 85º C Location Local/Remote DC/50/60 Hz Common mode 90dB rejection Rolloff Frequency (Anti Aliasing) -3dB at 2.7 Hz, -20.5dB at 20 Hz Isolation Each sensor galvanically isolated and factory tested to 1000 VDC Open sensor detection Yes Field Circuit Protection Field wiring disconnect CHARM power req. 10 mA max @ 24 VDC CHARM Heat Dissipation 0.25 W
  16. 16. DeltaV Product Data Sheet November 2009 – Page 16 S-series Electronic Marshalling Sensor Type Specifications Sensor Type 25° Reference Temperature Drift Nominal Full Scale Operating Range 1 Accuracy Resolution B ± 0.8° C ± 0.03 ° C/ °C ~ 0.024° C 250 to 1810° C 500 to 1810° C E ± 0.4° C ± 0.03° C/ °C ~ 0.018° C -200 to 1000° C -200 to 1000° C J ± 0.6° C ± 0.04° C/ °C ~ 0.022° C -210 to 1200° C -190 to 1200° C K ± 0.4° C ± 0.03° C/ °C ~ 0.025° C -270 to 1372° C -200 to 1372° C N ± 0.6° C ± 0.04° C/ °C ~ 0.024° C -270 to 1300° C -190 to 1300° C R ± 0.8° C ± 0.05° C/ °C ~ 0.028° C -50 to 1768° C -50 to 1768° C S ± 0.8° C ± 0.05° C/ °C ~ 0.028° C -50 to 1768° C -40 to 1768° C T ± 0.5° C ± 0.02° C/ °C ~ 0.01° C -270 to 400° C -200 to 400° C ± 100 mV 0.025 mV ± 0.002 mV/ °C ~ 0.0031mV -100 to 100 mV -100 to 100 mV ± 50 mV 0.020 mV ± 0.001 mV/ °C ~ 0.0015mV -50 to 50 mV -50 to 50 mV ± 20 mV 0.010 mV ± 0.0005 mV/ °C ~ 0.0006mV -20 to 20 mV -20 to 20 mV1 Total error is made up of the 25 C reference accuracy value, plus the CJC accuracy value, plus the sensor accuracy value Simplified circuit diagram of Thermocouple/mV CHARM
  17. 17. DeltaV Product Data SheetNovember 2009 – Page 17 S-series Electronic MarshallingAnalog Output CHARMS Specifications for HART AO CHARM, 0/4 to 20 mA Sensor Types 4 to 20 mA with or without HART 0 to 20 mA Nominal signal range (span) 4 to 20 mA, (0 to 20 mA option) Full signal range 0 to 24 mA Accuracy over temperature range 0.25% of span (0 to 60 ºC) 0.5% of span (-40 to 70 ºC) Resolution 16 bit D/A converter Calibration Non required Available field power 20 mA at 15 VDC supply into 750  load Open-Loop Detection < 0.70 mA (on 4 to 20 mA signal) Field Circuit Protection Current Limiting Circuit and field wiring disconnect CHARM power req. 30 mA max @ 24 VDC CHARM Heat Dissipation 0.42 W HART support HART v7 pass-through for AMS HART v7 variable and device status available to control HART data update rates 500 ms Simplified circuit and connection diagram for HART AO CHARM
  18. 18. DeltaV Product Data SheetNovember 2009 – Page 18 S-series Electronic MarshallingDiscrete Input CHARMS Specifications for DI CHARM, 24 VDC, NAMUR Sensor Types NAMUR Sensors, Dry Contacts Detection level for On  2.1 mA Detection level for Off  1.2 mA Channel Impedance 1.5 K (approximate) Wetting Voltage 12 Volts (± 5%) Fault Detection capable NAMUR Sensors or field resistor pack Configurable channel types:  Discrete input Dry contact or discrete state sensor changing <2 Hz  Pulse Count Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width Field Circuit Protection Current Limiting circuit with field disconnect CHARM power req. 26 mA max @ 24 VDC CHARM Heat Dissipation 0.58 W Simplified circuit and connection diagram for DI NAMUR CHARM
  19. 19. DeltaV Product Data SheetNovember 2009 – Page 19 S-series Electronic Marshalling Specifications for DI CHARM 24 VDC, Low Side Detect Sensor Types 24 VDC Dry Contacts Detection level for On  2.25 mA Detection level for Off  1.75 mA Channel Impedance 4.8 K (approximate) Wetting Voltage 22.5Volts (± 5%), current limited to 12.5 mA nominal Fault Detection capable field resistor pack (optional) Configurable channel types:  Discrete input Dry contact or discrete state sensor changing <2 Hz  Pulse Count Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width Field Circuit Protection Current Limiting circuit with field disconnect CHARM power req. 15 mA max @ 24 VDC CHARM Heat Dissipation 0.30 W Simplified circuit and connection diagram for DI 24 VDC, CHARM
  20. 20. DeltaV Product Data SheetNovember 2009 – Page 20 S-series Electronic Marshalling Specifications for DI CHARM, 24 VDC, Isolated Detection level for On  1.4 mA Detection level for Off  0.56 mA Wetting Current 2 mA @ 24 VDC Output Impedance 60 K (approximately) Field circuit power per card 15 mA max @ 24 VDC Isolation Each channel is optically isolated from the system at 250 VAC Internally fused 2.0 A CHARM power req. 15 mA max @ 24 VDC CHARM Heat Dissipation 0.30 W TBD Simplified circuit and connection diagram for DI CHARM, 24 VDC, isolated
  21. 21. DeltaV Product Data SheetNovember 2009 – Page 21 S-series Electronic Marshalling Specifications for DI CHARM, 120 VAC, Isolated Detection level for On  1.4 mA Detection level for Off  0.56 mA Wetting Current 2 mA at 120 VAC Output Impedance 60 K (approximately) Field circuit power per card 15 mA max at 120 VAC Isolation Each channel is optically isolated from the system at 250 VAC Internally fused 2.0 A CHARM power req. 15 mA max @ 24 VDC CHARM Heat Dissipation 0.30 W TBD Simplified circuit and connection diagram for DI CHARM, 120 VAC, isolated
  22. 22. DeltaV Product Data SheetNovember 2009 – Page 22 S-series Electronic Marshalling Specifications for DI CHARM, 230VAC, Isolated Detection level for On 84 to 130 VAC Detection level for Off 0 to 34 VAC Wetting Current 2 mA at 120 VAC Input Impedance 60 K (approximately) Field circuit power per card None Isolation Each channel is optically isolated from the system at 250 VAC and from other channels at 250 VAC. Internally fused 2.0 A CHARM power req. CHARM Heat Dissipation TBD Simplified circuit and connection diagram for DI CHARM 230 VAC, Isolated
  23. 23. DeltaV Product Data SheetNovember 2009 – Page 23 S-series Electronic MarshallingDiscrete Output CHARMS Specifications for DO CHARM 24 VDC, High Side Device Type 24 VDC Solenoid coils On State Output rating 100 mA continuous @ 24 VDC Off-state leakage 1 mA maximum Line Fault Detection Short Circuit < 50 Ohms load Open Circuit > 20 K Ohms load Configurable output behavior Latching Output Momentary Output Continuous Pulse Output Field Protection Current Limiting circuitry and field disconnect (Short Circuit protected to 200 mA) CHARM power req. 110 mA max @ 24 VDC CHARM Heat Dissipation 0.30 W Simplified circuit and connection diagram for DO 24 VDC CHARM
  24. 24. DeltaV Product Data SheetNovember 2009 – Page 24 S-series Electronic Marshalling Specifications for DO CHARM 24 VDC, Isolated Device Type 24 VDC Inductive Load Output range 4 VDC to 32 VDC Output rating 1.0 A continuous ( 2 A inrush for < 100 msec) Off state leakage 1 mA maximum Configurable channel types: Output signal profile  Discrete output Output stays in last state submitted by the control logic.  Momentary output Output remains active for a pre-configured time period.  Continuous pulse output Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms Isolation The output channel is galvanically isolated and factory tested to 1000 VDC. Field Protection Current Limiting circuitry and field disconnect CHARM power req. 10 mA max @ 24 VDC CHARM Heat Dissipation 0.24 W Simplified circuit and connection diagrams for DO 24 VDC, Isolated CHARM
  25. 25. DeltaV Product Data SheetNovember 2009 – Page 25 S-series Electronic Marshalling Specifications for DO CHARM 120/230 VAC, Isolated Sensor types 120 VAC Inductive load Off state leakage 2 mA maximum at 120 VAC Output range 20 to 250 VAC 1.0A maximum continuous per channel; Output rating (inrush 5A for < 100 ms: 20A for < 20 ms) Configurable channel types:  Discrete output Output signal profile  Momentary output Output stays in last state submitted  Continuous pulse output Output remains active for a pre-configured time period. Output is active as a percentage of a pre-configured base time period (100 ms to 100 s). Resolution = 5 ms Each channel is optically isolated from system at Isolation 1500 VDC and from other channels at 1500 VDC Field Protection Current Limiting circuitry and field disconnect CHARM power req. TBD CHARM Heat Dissipation TBD TBD Simplified circuit and connection diagram for DO CHARM, 120 VAC, Isolated
  26. 26. DeltaV Product Data SheetNovember 2009 – Page 26 S-series Electronic MarshallingVoltage Charms Specifications for Input CHARM 0-10 Volts Isolated Sensor types Voltage device Full Scale signal range See Table next page Accuracy See Table next page Input Impedance 10 MΩ Repeatability 0.05% of span Resolution 24 bit A/D converter Calibration None required Common mode rejection 90dB at 50/60 Hz Isolation Each sensor galvanically isolated and factory tested to 1500 VDC Open sensor detection Yes Field Circuit Protection Field wiring disconnect CHARM power req. 10 mA max @ 24 VDC CHARM Heat Dissipation 0.25 W
  27. 27. DeltaV Product Data Sheet November 2009 – Page 27 S-series Electronic Marshalling Isolated Input mV/V Sensor Type Specifications Sensor Type 25° Reference Temperature Drift Nominal Full Scale Operating Range 1 Accuracy Resolution ± 20 mV 0.010 mV ± 0.0005 mV/ °C ~ 0.0006mV -20 to 20 mV -20 to 20 mV ± 50 mV 0.020 mV ± 0.001 mV/ °C ~ 0.0015mV -50 to 50 mV -50 to 50 mV ± 100 mV 0.025 mV ± 0.002 mV/ °C ~ 0.0031mV -100 to 100 mV -100 to 100 mV 0-5V 0.025 mV ± 0.002 mV/ °C 0.00009 V 0 to 5 V 0 to 5 V 0 - 10 V 0.005 V 0.0002 V/° C 0.00016 V 0 to 10 V 0 to 10 V 1-5V ± 0.010 V 0.0004 V/° C 0.00009 V 1 to 5 V 1 to 5 V 1V 0.0005 V 0.0002 V/° C 0.00015 V 1V 1V 5V 0.0025 V 0.0002 V/° C 0.00017 V 5V 5V 10 V 0.005 V 0.0002 V/° C 0.0003 V 10 V 10 V1 Total error is made up of the 25 C reference accuracy value, plus the sensor accuracy value TBD Simplified circuit diagram of Isolated Voltage CHARM
  28. 28. DeltaV Product Data SheetNovember 2009 – Page 28 S-series Electronic MarshallingSystem Compatibility Marine Certifications:CHARM I/O hardware requires: IACS E10:2006 Rev.5 Control, protection & Safety SX or SD Plus controllers - ABS Certificate of Design Assessment - Bureau Veritas CertificateS-series Controllers with CHARMS I/O and M-series - DNV Marine Certificatecontrollers can be installed on the same DeltaV Area - Lloyds RegisterControl Network in v11 and beyond. Control modules canbe assigned to either series of controller and inter- GOST Hazardous Area certification Zone 2controller references are fully supported between (Russian)controller series.Certifications Other country specific certifications may also be available. Verify with your local Emerson sales office to confirm anyThe following certifications are pending for CHARM I/O certification requirements not listed here.products. Please verify with the appropriate certifyingagency for a specific list of approved components.CE:- EMC- EN 61326-1:2006- LVD- EN 61010-1:2001CSA:- CLASS 2252 05 - PROCESS CONTROL EQUIPMENT: CAN/CSA-C22.2 No. O-M91 General Requirements- Canadian Electrical Code, Part II CAN/CSA-C22.2 No. 61010-1-04 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General RequirementsCENELEC Zone 2 ATEX EN 60079-15:2005 Certifying agency: Nemko Certificate Number: TBD Refer to document TBD "DeltaV ™ Scalable Process System Zone 2 Installation Instructions"FM Approval Class 1 Division 2 Hazardous Locations Certifying agency: FM Approvals Certificate Number: TBD Refer to document TBD "DeltaV ™ Scalable Process System Class 1 Division 2 installation Instructions”
  29. 29. DeltaV Product Data SheetNovember 2009 – Page 29 S-series Electronic MarshallingOrdering Information CHARM I/O CARD Description Model NumberRedundant CIOC, includes 2 CHARMS I/O Cards, CHARMS I/O Carrier with screw SE6501T01terminals, two dual port Communications modules for twisted copper, and DIN-Rail Stop withIntegrated Bus TerminatorsRedundant CIOC with fiber optics, includes 2 CHARMS I/O Cards, CHARMS I/O Carrier SE6501T02with screw terminals, two single port Communications modules for multi mode fiber opticcable, and DIN-Rail Stop with Integrated Bus TerminatorsCHARMS Baseplate Assembly, includes CHARMS Baseplate, CHARM Address Terminal SE4601T01Block with screw terminals, and 12 Standard CHARM Terminal blocksCHARMS Baseplate Assembly with Injected Field Power, includes CHARMS Baseplate, SE4601T02CHARM Address Terminal Block with screw terminals, and 12 Injected Power CHARMTerminal blocksCHARMS Addressing Plugs, includes Address Plugs 1 through 8 SE4602CHARMS Baseplate DIN-Rail Stop with Integrated Bus Terminators SE4603T01CHARMS Baseplate DIN-Rail Stop with Cable Connections SE4603T02CHARMS Baseplate DIN-Rail Cap with Integrated Bus Terminators SE4604T01CHARMS Baseplate Cable Extender SE4605T01 Low Voltage Instrumentation CHARMSDI NAMUR SE4301T01DI 24 VDC Low Side Detection SE4301T02DO 24 VDC High Side SE4302T01DO 24 VDC Isolated SE4302T02AI 0/4-20 mA HART SE4303T01Thermocouple/mV SE4303T02RTD SE4303T03AO-0/4-20 mA HART SE4304T01DI 24 VDC Isolated RTQ High Voltage Instrumentation CHARMSDI 120 VAC Isolated RTQDI 230 VAC Isolated RTQDO 120 VAC Isolated RTQDO 230 VAC Isolated RTQ Specialty Instrumentation CHARMSAI 0-10 Volt Isolated RTQ
  30. 30. DeltaV Product Data SheetNovember 2009 – Page 30 S-series Electronic MarshallingPrerequisitesS-Series Electronic Marshalling hardware requires DeltaV v11.3 or later software.To locate a sales office near you, visit our website at: For large power, water, and wastewater applicationswww.EmersonProcess.com/DeltaV contact Power and Water Solutions at:Or call us at: www.EmersonProcess-powerwater.comAsia Pacific: 65.777.8211 Or call us at:Europe, Middle East: 41.41.768.6111 Asia Pacific: 65.777.8211North America, Latin America: +1 800.833.8314 or Europe, Middle East, Africa: 48.22.630.2443 +1 512.832.3774 North America, Latin America: +1 412.963.4000© Emerson Process Management 2009. All rights reserved. For Emerson Process Management trademarks and service marks, go to:http://www.emersonprocess.com/home/news/resources/marks.pdf.The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to beconstrued as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governedby our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any timewithout notice.www.EmersonProcess.com/DeltaV

×