ACTUATOR FOR DAMPERSTy p e 2 3 2Actuator with rotation drive15 NmFor the application withRoom ventilation techniquesVAVVal...
2                   GENERAL OVERVIEW: ACTUATORS WITH ROTATION DRIVE                                              without s...
SUMMARY TYPE 232, 15 Nm                                                                                                   ...
4                   232-024-15, 232-024-15-P5, 232-024-15-S2                                                              ...
232-024-15, 232-024-15-P5, 232-024-15-S2                                                                                  ...
6                   232E3-230-15, 232E3-230-15-P5, 232E3-230-15-S2                                                        ...
232E3-230-15, 232E3-230-15-P5, 232E3-230-15-S2                                                                            ...
8                   232C-024-15                                                                                           ...
232C-024-15                                                                                                               ...
10                   MOUNTING EXAMPLES                                                                               Figur...
SPECIFIC CHARACTERISTICS OF CONTINUOUS CONTROL 11                               Wiring configuration and recommended cable...
12                   SPECIFIC CHARACTERISTICS OF CONTINUOUS CONTROL                                              Wiring co...
EXPLODED DRAWINGS                                                                   13                                    ...
14                   EXPLODED DRAWINGS                                                             232E3-230-15 / -S2 / -P...
NOTES                                                                              15GRUNER AG                            ...
YOUR WAY TO GRUNER                                                                 Stuttgart                A8            ...
Upcoming SlideShare
Loading in …5
×

Damper Servomotorları Gruner d 232_en

737 views

Published on

Damper Servomotorları Gruner d 232_en

Published in: Business
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total views
737
On SlideShare
0
From Embeds
0
Number of Embeds
7
Actions
Shares
0
Downloads
3
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

Damper Servomotorları Gruner d 232_en

  1. 1. ACTUATOR FOR DAMPERSTy p e 2 3 2Actuator with rotation drive15 NmFor the application withRoom ventilation techniquesVAVValves Page: Content: 2 General overview 3 Summary 232, 15 Nm 4 - 9 Technical characteristics, Type 232, 15 Nm 10 Mounting examples 11 - 12 Specific characteristics of continuous control 13 - 14 Exploded drawings 15 Notes 16 Your way to Gruner rnative alte GR UNER – he frie n dly tGRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  2. 2. 2 GENERAL OVERVIEW: ACTUATORS WITH ROTATION DRIVE without spring return with spring return ● = Standard ❍ = Optional Type 227 232 231 228 238 Torque 5 Nm (appr.1 m ) 15 Nm (appr.3 m ) 20 Nm (appr.4 m ) 5 Nm (appr.1 m ) 15 Nm (appr.3 m2) 2 2 2 2 8 Nm (appr.1.6 m2) 30 Nm (appr.6 m2) Control Tri-state ● ● ● ● ● On / Off ● ● ● ● ● Continuous (0) 2...10 VDC or ● ● ● ● ● Ω (0) 4...20 mA with 500Ω Power supply 24 VAC/DC ● ● ● ● ● 230 VAC ● ● ● ● ● Options Potentiometer ❍ ❍ ❍ Auxiliary switch(es) ❍ ❍ ❍ ❍ ❍ LON Interface ❍ VAV Interface ❍ ❍ ❍ ❍ ❍ Binding clamp ● ● ● ● ● Form locking ❍ ❍ ❍ Applications Motorised control of dampers, ball and butterfly valves. Application in mixed air and shut-offer damper control. For primary HVAC air-handling and zone units. Smoke and air isolation shut-off damper control for ventilation systems Ball valve control for domestic and drinking water, condensation water, air (i.e. zone units). The actuator 231L has digital communication capabilities and can be networked with a LON-Bus system. All actuators correspond to the UL, CSA & DIN-VDE standards, CE guidelines. GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  3. 3. SUMMARY TYPE 232, 15 Nm 3 5 2● = Standard -P -S 5 2 15 15 15 -P -S 5❍ = Optional -1 0- 0- 0- 15 15 15 24 23 23 23 4- 4- 4- -0 3- 3- 3- 02 02 02 2C 2E 2E 2E 2- 2- 2-Type 23 23 23 23 23 23 23Torque 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm 15 NmControl Tri-state ● ● ● ● ● ● On / Off ● ● ●Continuous control(0) 2...10 VDC or ●(0) 4...20 mAPower supply24 VAC/DC ● ● ● ●230 VAC ● ● ●OptionsPotentiometer ● ●Feedback signal ●Auxiliary switch(es) ● ●Page 4 4 4 6 6 6 8All actuators dispose of manual override button, a mechanical limitation of the angle of rotation and setting button for the rotation direction (cw/ccw).Actuators according to US-standards available upon demand.GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  4. 4. 4 232-024-15, 232-024-15-P5, 232-024-15-S2 Applications To regulate dampers, valves or other regulatory functions: • sturdy drive • direction of rotation changeable from outside • maintenance-free • auxiliary switch adjustable from inside • torque 15 Nm • electromagnetic compatibility controlled • position indication Technical characteristics Control On / Off + Tri-state Connecting voltage 24 VAC (50/60 Hz) / DC ±20% Power consumption 4.5 W / 8.0 VA Angle of rotation 0...95° Direction of rotation changeable from outside Running time 40...80 s @ 90° Torque 15 Nm Auxiliary switches 2, adjustable from inside Switching power auxiliary switch 24 VAC / 5 (2.5) A, change-over switch Potentiometer 5 kΩ Connection cable 900 mm / 0.75 mm2 Safety class III Protection IP54 (cable downwards) Dimensions 140 x 75 x 58 mm Ambient temperature -30...+50°C Maintenance maintenance-free CE 73/23/EWG, 89/336/EWG Weight 700 g 232-024-15 232-024-15-P5 232-024-15-S2 Connection scheme Connection scheme Connection scheme BU BNBK BU BNBK BU BNBK BU BNBK On / Off 2 1 3 BU BNBK BU BNBK S1 S2 Tri-state Potentiometer 1 2 3 4 5 6 Auxiliary switches GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  5. 5. 232-024-15, 232-024-15-P5, 232-024-15-S2 5 1 Indication of the angle of rotation (fig. 1) The damper position is indicated on the scale 0°...90°. )m m) Fixing of the shaft (fig. 1) m( (m 40 0 10 20 30 90 0° 75 ° 60 45 30 15 by the locking clamp to the damper shaft: ❑ 8...12 mm ∅ 8...16 mm 2 Adjustment of the auxiliary switches (fig. 2) The switching cams are not factory-adjusted. The auxiliary switches can be adjusted by the customer as requested within the range from 0°...10° or 80°...90°. They can also be adjusted upon customer request. 3 Adjustment of the direction of rotation (fig. 3) The actuator is adjusted to clockwise direction by the factory => “R“. For changing the direction of rota- tion, turn the adjusting knob to “L”. L R S1 S2 1 2 3 4 5 6 BU BN BK 24 VAC 5 (2,5) A Technical drawing 232-024-15GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  6. 6. 6 232E3-230-15, 232E3-230-15-P5, 232E3-230-15-S2 Applications To regulate dampers, valves or other regulatory functions: • sturdy drive • auxiliary switch adjustable from inside • maintenance-free • electromagnetic compatibility controlled • torque 15 Nm • position indication Technical characteristics Control Tri-state Connecting voltage 230 VAC (50/60 Hz) ±15% Power consumption 3.5 W / 3.5 VA Angle of rotation max. 95° Direction of rotation can be selected by type of connection Running time 120 s @ 90° Torque 15 Nm Auxiliary switches 2, adjustable from inside Switching power auxiliary switch 250 VAC / 5 (2.5) A, normally-open contact Potentiometer 5 kΩ Connection cable 900 mm / 0.75 mm2 Safety class II Protection IP54 (cable downwards) Dimensions 140 x 75 x 58 mm Ambient temperature -20...+50°C Maintenance maintenance-free CE 73/23/EWG, 89/336/EWG Weight 700 g 232E3-230-15 232E3-230-15-P5 232E3-230-15-S2 Connection scheme Connection scheme Connection scheme (Tri-state) (Tri-state) (Tri-state) S1 S2 1 2 3 4 Auxiliary switches BU BNBK BU BNBK 2 1 3 BU BNBK Potentiometer N N N L L L GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  7. 7. 232E3-230-15, 232E3-230-15-P5, 232E3-230-15-S2 7 1 Indication of the angle of rotation (fig. 1) The damper position is indicated on the scale 0°...90°. )m m) Fixing of the shaft (fig. 1) m( (m 40 0 10 20 30 90 0° 75 ° 60 45 30 15 by the locking clamp to the damper shaft: ❑ 8...12 mm ∅ 8...16 mm 2 Adjustment of the auxiliary switches (fig. 2) The switching cams are not factory-adjusted. The auxiliary switches can be adjusted by the customer as requested within the range from 0°...10° or 80°...90°. They can also be adjusted upon customer request. Technical drawing 232E3-230-15GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  8. 8. 8 232C-024-15 Applications To regulate dampers, valves or other regulatory functions: • sturdy drive • direction of rotation changeable from outside • maintenance-free • electromagnetic compatibility controlled • torque 15 Nm • position indication Technical characteristics Control Continuous control Control signal Y 0...10 VDC or 2...10 VDC (standard) or 0...20 mA or 4...20 mA Feedback signal U 0...10 VDC or 2...10 VDC (standard) or 10 VDC or 15 VDC Connecting voltage 24 VAC (50/60 Hz) / DC ±20% Power consumption 5.5 W / 7.0 VA Angle of rotation max. 95° Direction of rotation changeable from outside Running time 40...80 s @ 90° Torque 15 Nm Connection cable 900 mm / 0.75 mm2 Safety class III Protection IP54 (cable downwards) Dimensions 140 x 75 x 58 mm Ambient temperature -30...+50°C 232C-024-15 Maintenance maintenance-free CE 73/23/EWG, 89/336/EWG Connection scheme Weight 700 g (Continuous control) BUBN BK GY Y U GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  9. 9. 232C-024-15 9 1 Indication of the angle of rotation (fig. 1) The damper position is indicated on the scale 0°...90°. Fixing of the shaft (fig. 1) )m m) m( (m 40 0 10 20 30 by the locking clamp to the damper shaft: ❑ 8...12 mm 90 0° 75 ° 60 45 30 15 ∅ 8...16 mm 2 Adjustment of the functional switches (fig. 2) OFF ON Control signal Y 2...10 VDC (Standard) 1, 2 - 0...10 VDC 2 1 4...20 mA 1 2 0...20 mA - 1, 2 Feedback signal U 2...10 VDC (Standard) 4, (1) 3 ON 0...10 VDC 4 3, (1) OFF 1 2 3 4 5 6 15 VDC / 5 mA 3, 5 4 10 VDC / 5 mA 3 4, 5 Switches actually unused must be at position OFF. The constant voltage 15 VDC can be used i.e. for the power supply of the positioner FGEB. Technical drawing 232C-024-15GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  10. 10. 10 MOUNTING EXAMPLES Figure 1 Direct mounting to the damper shaft by locking clamp to the ...and fixing by the enclosed anti-torsion bow. damper shaft... Figure 2 Figure 3 Direct mounting by two hexagon screws M4 x 30, SW 7, Mounting if the damper is too short. if the actuator is not mounted directly on the damper. GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  11. 11. SPECIFIC CHARACTERISTICS OF CONTINUOUS CONTROL 11 Wiring configuration and recommended cable length - + Y U 232C - + Y U 232C BU BN BK GY BU BN BK GY L2 L1 (I +I ) R > A G L 24VAC max. cable length max. cable length transformer I R < G L L2 L1 24VAC transformer - + - + - + - + Y U Y U DC 0(2)...10V DC 0(2)...10V DC 0(2)...10V DC 0(2)...10V by the controller by the actuator by the controller by the actuator current of set valve selector actuator current cable cross section max. cable length cable resistance 0,75 mm2 23 m 1 mm2 31 m cable length 1,5 mm2 46 m 2,5 mm2 76 m cable cross section For several actuators switched in parallel the max. cable length must be divided by the number of actuators. Teach-in of range of angle > 30° 1. Actuator stand by 2. Adjusting mechanical endstops 3. 15 VDC at Y 4. Power on actuator 5. Actuator starts teach-in process of range of angle (60...120 s) BUBN BK GY 6. Remove 15 VDC at Y 15 VDCGRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  12. 12. 12 SPECIFIC CHARACTERISTICS OF CONTINUOUS CONTROL Wiring configuration of positioner FGEB Actuator with integrated power supply Actuator Positioner U Y Jumper S1 for - + Y U + Input - Output + - setting control signal Y BU BN BK GY 1 2 3 4 0-10 VDC 2-10 VDC 15 VDC L1 L2 (0) 2...10 VDC 24 VAC Transformer Wiring configuration of positioner FGEB Actuator without integrated power supply Actuator Positioner U Y - + Y U Input Output + - + - BU BN BK GY 1 2 3 4 15 VDC Feedback signal U L1 L2 (0) 2...10 VDC 24 VAC Transformer - + 15 VDC GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  13. 13. EXPLODED DRAWINGS 13 232-024-15-S2 232-024-15-P5GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  14. 14. 14 EXPLODED DRAWINGS 232E3-230-15 / -S2 / -P5 232C-024-15 GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.de PF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de 08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  15. 15. NOTES 15GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved
  16. 16. YOUR WAY TO GRUNER Stuttgart A8 München Balingen Karlsruhe Schömberg Wehingen A81 Freudenstadt B27 Gosheim Denkingen Tuttlingen Frittlingen Strasbourg Rottweil Spaichingen B14 Aldingen Schramberg Offenburg 34 B27 A5 B33 Freiburg Donaueschingen B31 Singen Zürich Basel N1 N3GRUNER AG Tel. (++49) 74 26 / 948 - 0 http://www.gruner.dePF 1149, D-78560 Wehingen Fax (++49) 74 26 / 948 - 200 E-Mail: info@gruner.de08/05 · CH89E · Copyright by Gruner AG · Technical changes are reserved

×