TI00437P/00/EN/17.12No. 71190904Technical InformationDeltapilot M FMB50/51/52/53Hydrostatic level measurementPressure sens...
Deltapilot M FMB50/51/52/532 Endress+HauserTable of contentsFunction and system design. . . . . . . . . . . . . . . . . . ...
3 Endress+HauserDeltapilot M FMB50/51/52/53North-American practice for installation of process seals . . . . . . . 52Order...
Deltapilot M FMB50/51/52/534 Endress+HauserFunction and system designDevice selectionDeltapilot M –Product familyFMB50P01-...
Deltapilot M FMB50/51/52/53Endress+Hauser 5FMB50/51/52 universal application• Modular probe program to ensure optimum proc...
Deltapilot M FMB50/51/52/536 Endress+HauserMeasuring principleP01-FMB5xxxx-15-xx-xx-xx-004Deltapilot M hydrostatic level m...
Deltapilot M FMB50/51/52/53Endress+Hauser 7Level measurement in closedtanks with pressure overlayYou can determine the dif...
Deltapilot M FMB50/51/52/538 Endress+HauserLevel measurement withautomatic density correction(with media changing in theta...
Deltapilot M FMB50/51/52/53Endress+Hauser 9Communication protocol • 4 to 20 mA with HART communication protocol• PROFIBUS ...
Deltapilot M FMB50/51/52/5310 Endress+HauserInputMeasured variable Hydrostatic pressureMeasuring rangeNominalvalueRange li...
Deltapilot M FMB50/51/52/53Endress+Hauser 11Explanation of terms Explanation of terms: turn down (TD),set span and span ba...
Deltapilot M FMB50/51/52/5312 Endress+HauserOutputOutput signal • 4 to 20 mA with superimposed digital communication proto...
Deltapilot M FMB50/51/52/53Endress+Hauser 13Dead time, time constantP01-xxxxxxxx-05-xx-xx-xx-036Presentation of the dead t...
Deltapilot M FMB50/51/52/5314 Endress+HauserDynamic behavior:PROFIBUS PAReading cycle• Cyclic: max. 30/s (dependent on the...
Deltapilot M FMB50/51/52/53Endress+Hauser 15Data of the FOUNDATIONFieldbus interfaceBasic dataVirtual communication refere...
Deltapilot M FMB50/51/52/5316 Endress+HauserFunction blocksBlock Content Numberof blocksExecution time FunctionalityResour...
Deltapilot M FMB50/51/52/53Endress+Hauser 17Power supplyElectrical connection Note!• When using the measuring device in ha...
Deltapilot M FMB50/51/52/5318 Endress+HauserPROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).FOUNDATION ...
Deltapilot M FMB50/51/52/53Endress+Hauser 19Devices with M12 plugPIN assignment for M12 connectorEndress+Hauser offers the...
Deltapilot M FMB50/51/52/5320 Endress+HauserSupply voltage Note!• When using the measuring device in hazardous areas, inst...
Deltapilot M FMB50/51/52/53Endress+Hauser 21Performance characteristicsReference operatingconditions• As per IEC 60770• Am...
Deltapilot M FMB50/51/52/5322 Endress+HauserTotal performance The "Total performance" specification comprises the non-line...
Deltapilot M FMB50/51/52/53Endress+Hauser 23Operating conditions (installation)General installationinstructions• The posit...
Deltapilot M FMB50/51/52/5324 Endress+HauserSupplementary installationinstructionsProcess isolating diaphragm• Do not clea...
Deltapilot M FMB50/51/52/53Endress+Hauser 25"Separate housing" version With the "separate housing" version, you are able t...
Deltapilot M FMB50/51/52/5326 Endress+HauserOxygen applications Oxygen and other gases can react explosively to oils, grea...
Deltapilot M FMB50/51/52/53Endress+Hauser 27Operating conditions (environment)Ambient temperature rangeStorage temperature...
Deltapilot M FMB50/51/52/5328 Endress+HauserOvervoltage protection(optional)The device can be fitted with overvoltage prot...
Deltapilot M FMB50/51/52/53Endress+Hauser 29Operating conditions (process)Process temperature rangeLateral load FMB51 (sta...
Deltapilot M FMB50/51/52/5330 Endress+HauserMechanical constructionF31 aluminum housingdimensionsP01-F31xxxx-06-00-xx-xx-0...
Deltapilot M FMB50/51/52/53Endress+Hauser 31Installation height H, devices with a threadProcess connections FMB50(compact ...
Deltapilot M FMB50/51/52/5332 Endress+HauserProcess connections FMB50(compact version) - continuedANSI flanges, connection...
Deltapilot M FMB50/51/52/53Endress+Hauser 33Process connections FMB50(compact version) - continuedJIS flanges, connection ...
Deltapilot M FMB50/51/52/5334 Endress+HauserProcess connections FMB50(compact version) - continuedUniversal adapterP01-FMB...
Deltapilot M FMB50/51/52/53Endress+Hauser 35Process connections FMB50(compact version) - continuedHygienic connectionsP01-...
Deltapilot M FMB50/51/52/5336 Endress+HauserProcess connections FMB51(rod version)Threaded connection ISO 228 and NPTP01-F...
Deltapilot M FMB50/51/52/53Endress+Hauser 37Process connections FMB52(cable version)Threaded connection ISO 228 and NPTP01...
Deltapilot M FMB50/51/52/5338 Endress+HauserDimensions of Deltapilot MFMB53 (suspension clamp andmounting bracket)P01-FMB5...
Deltapilot M FMB50/51/52/53Endress+Hauser 39Wall and pipe mounting with"Separate housing" versionP01-xMx5xxxx-06-xx-xx-xx-...
Deltapilot M FMB50/51/52/5340 Endress+HauserA minimum bending radius (r) of 120 mm (4,72 in) must be observed for the cabl...
Deltapilot M FMB50/51/52/53Endress+Hauser 41Separate housingNote!Total weight = weight of separate housing + weight cable ...
Deltapilot M FMB50/51/52/5342 Endress+Hauser• Total weight of device with flange connection = weight of housing (→ ä 40) +...
Deltapilot M FMB50/51/52/53Endress+Hauser 43Material (not wetted) HousingP01-xMxx3xxx-14-xx-xx-xx-002Front view, left-hand...
Deltapilot M FMB50/51/52/5344 Endress+HauserP01-xMxx3xxx-14-xx-xx-xx-002Front view, left-hand side view, top view123456789...
Deltapilot M FMB50/51/52/53Endress+Hauser 45Connecting partsP01-xMxx3xxx-14-xx-xx-xx-003Filling oil• Synthetic oil polyalp...
Deltapilot M FMB50/51/52/5346 Endress+HauserMaterial (wetted)P01-xMxx3xxx-14-xx-xx-xx-003Item number Component part Materi...
Deltapilot M FMB50/51/52/53Endress+Hauser 47Note!The wetted device components are listed in the "Mechanical construction" ...
Deltapilot M FMB50/51/52/5348 Endress+HauserHuman interfaceOperating elements Local display (optional)A 4-line liquid crys...
Deltapilot M FMB50/51/52/53Endress+Hauser 49Operating keys and elements located on the electronic insertOnsite operationP0...
Deltapilot M FMB50/51/52/5350 Endress+HauserRemote operation All software parameters are accessible depending on the posit...
Deltapilot M FMB50/51/52/53Endress+Hauser 51Hardware and software foronsite and remote operationCommubox FXA195For intrins...
Deltapilot M FMB50/51/52/5352 Endress+HauserCertificates and approvalsCE mark The device meets the legal requirements of t...
Deltapilot M FMB50/51/52/53Endress+Hauser 53Ordering informationFMB50 This overview does not mark options which are mutual...
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Hydrostatic level measurement-Deltapilot M FMB50/51/52/53
Upcoming SlideShare
Loading in …5
×

Hydrostatic level measurement-Deltapilot M FMB50/51/52/53

2,453 views

Published on

Pressure sensor with the CONTITETM measuring cell. Level, volume or mass measurements in liquids… Email: lam.nguyen@vietan-enviro.com HP: 0945 293292

Published in: Technology, Business
0 Comments
1 Like
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
2,453
On SlideShare
0
From Embeds
0
Number of Embeds
4
Actions
Shares
0
Downloads
52
Comments
0
Likes
1
Embeds 0
No embeds

No notes for slide

Hydrostatic level measurement-Deltapilot M FMB50/51/52/53

  1. 1. TI00437P/00/EN/17.12No. 71190904Technical InformationDeltapilot M FMB50/51/52/53Hydrostatic level measurementPressure sensor with the CONTITETMmeasuring cellCondensate-resistant offering long-term stability; communicationvia HART, PROFIBUS PA or FOUNDATION Fieldbus.ApplicationThe hydrostatic pressure sensor is used for the followingmeasuring tasks:• Hydrostatic pressure measurement in liquids andpaste-like media in all areas of process engineering,process measuring technology, pharmaceuticals andthe food industry• Level, volume or mass measurements in liquidsYour benefits• Very good reproducibility and long-term stability• Turn down 100:1• Hermetically sealed CONTITETM measuring cell:– Condensate-resistant and climatic-proofed– High reference accuracy: ±0.2 %,optionally ±0.1 %– Minimum temperature effects• End-to-end modularity for differential pressure,hydrostatics and pressure (Deltabar M –Deltapilot M – Cerabar M), e.g.– replaceable display– universal electronics• Easy commissioning without the need for an operatingtool• Easy and safe menu-guided operation– on-site via display module– via 4 to 20 mA with HART– via PROFIBUS PA– via FOUNDATION Fieldbus• Wide range of approvals (e.g. ATEX, FM, CSA, etc.) forinternational use• Usage in drinking water: KTW, NSF• Used for process pressure monitoring up to SIL2,certified to IEC 61508 Edition 2.0 and IEC 61511 byTÜV NORD
  2. 2. Deltapilot M FMB50/51/52/532 Endress+HauserTable of contentsFunction and system design. . . . . . . . . . . . . . . . . . . . . 4Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Level measurement in closed tanks with pressure overlay . . . . . . . 7Density measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Level measurement with automatic density correction (with mediachanging in the tank) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Electrical differential pressure measurement with gauge pressuresensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Signal range – 4 to 20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . 12Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Load - 4 to 20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Dead time, time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Dynamic behavior: current output . . . . . . . . . . . . . . . . . . . . . . . 13Dynamic behavior: HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Dynamic behavior: PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . 14Dynamic behavior: FOUNDATION Fieldbus . . . . . . . . . . . . . . . . 14Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Data of the FOUNDATION Fieldbus interface . . . . . . . . . . . . . . . 15Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Start-up current HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Performance characteristics. . . . . . . . . . . . . . . . . . . . 21Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 21Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Influence of orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Warm-up period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Calibration position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Total performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Total error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Thermal change in the zero output and the output span . . . . . . . 22Operating conditions (installation) . . . . . . . . . . . . . . 23General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . 23FMB50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23FMB51/FMB52/FMB53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Supplementary installation instructions . . . . . . . . . . . . . . . . . . . . 24Wall and pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24"Separate housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26PWIS cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Applications with hydrogen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Special measuring cells for acids, alkalis or sea water(not FMB50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Operating conditions (environment) . . . . . . . . . . . . . 27Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 27Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . 28Operating conditions (process) . . . . . . . . . . . . . . . . . 29Process temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Lateral load FMB51 (static) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 30F31 aluminum housing dimensions . . . . . . . . . . . . . . . . . . . . . . 30F15 stainless steel housing dimensions (hygienic) . . . . . . . . . . . . 30Process connections FMB50 (compact version) . . . . . . . . . . . . . . 30Process connections FMB50 (compact version) - continued . . . . 31Process connections FMB50 (compact version) - continued . . . . 32Process connections FMB50 (compact version) - continued . . . . 33Process connections FMB50 (compact version) - continued . . . . 33Process connections FMB50 (compact version) - continued . . . . 34Process connections FMB50 (compact version) - continued . . . . 34Process connections FMB50 (compact version) - continued . . . . 35Process connections FMB51 (rod version) . . . . . . . . . . . . . . . . . 36Process connections FMB52 (cable version) . . . . . . . . . . . . . . . . 37Dimensions of Deltapilot M FMB53 (suspension clamp andmounting bracket) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Wall and pipe mounting with "Separate housing" version . . . . . . 39Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Material (not wetted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Material (wetted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Onsite operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Hardware and software for onsite and remote operation . . . . . . . 51Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 52CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Suitability for hygienic processes . . . . . . . . . . . . . . . . . . . . . . . . . 52Pharma (CoC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Functional safety SIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Marine approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . 52Drinking water approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
  3. 3. 3 Endress+HauserDeltapilot M FMB50/51/52/53North-American practice for installation of process seals . . . . . . . 52Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 53FMB50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53FMB50 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54FMB50 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55FMB50 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56FMB51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57FMB51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58FMB51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59FMB52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60FMB52 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61FMB52 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62FMB53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63FMB53 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64FMB53 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Brief Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Functional safety manual (SIL) . . . . . . . . . . . . . . . . . . . . . . . . . . 66Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 67Overfill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Suspension clamp (FMB53 only) . . . . . . . . . . . . . . . . . . . . . . . . 68Extension cable shortening kit (FMB53 only) . . . . . . . . . . . . . . . 68M12 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Welding necks and Weld-in tool flanges . . . . . . . . . . . . . . . . . . . 68Adapter Uni . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Configuration data sheet . . . . . . . . . . . . . . . . . . . . . . 70Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
  4. 4. Deltapilot M FMB50/51/52/534 Endress+HauserFunction and system designDevice selectionDeltapilot M –Product familyFMB50P01-FMB5xxxx-14-xx-xx-xx-000Compact versionFMB51P01-FMB5xxxx-14-xx-xx-xx-001Rod versionFMB52P01-FMB5xxxx-14-xx-xx-xx-002Cable versionFMB53P01-FMB5xxxx-14-xx-xx-xx-003Cable version withmounting clampField of application – Level measurement– Pressure measurementIndustries Food, pharmaceuticals, chemicals Environment (freshwater andwastewater)Process connections – Thread– Flanges– Flush-mounted hygienicconnections– Thread– Flanges– Thread– FlangesSuspension clampMeasuring ranges From –0.1 to +0.1 (-1,5 to +1,5 psi) bar to –1 bar to +10 bar (-15 to 150 psi)OPL 1) Max. 40 bar (600 psi)Process temperature range –10 to +100°C (+14 to +212°F)(+135°C (275°F) for 30 minutesmaximum)–10 to +85°C(+14 to +185°F)With PE cable: –10 to +70°C (+14 to +158°F)With FEP cable: –10 to +80°C (+14 to +176°F)Ambient temperature range • Without LCD display: -40 to +85°C (-40 to +185°F)• With LCD display: -20 to +70°C (-4 to +158°F) (extended temperature application range -40 to 85°C (-40 to +158°F) withrestrictions in optical properties such as display speed and contrast)• Separate housing: –20 to +60°C (–4 to +140°F)Reference accuracy 0.2 % (option 0.1 %) depends on the measuring range → ä 21Supply voltage – 11.5 to 45 V DC (versions with plug-in connection 35 V DC)– For intrinsically safe device versions: 11.5 to 30 V DCOutput 4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION FieldbusOptions – Gold/rhodium-coated process isolating diaphragm– 3.1 inspection certificate– 3A approval and EHEDG approval for FMB50– Specific firmware versions– Initial device settings can be ordered– Separate housingSpecialties – Absolute resistance to condensate thanks to hermetically sealed CONTITETM cell– Maximum flexibility thanks to modular design– Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops1) OPL = over pressure limit; depends on the lowest-rated element, with regard to pressure, of the selected components
  5. 5. Deltapilot M FMB50/51/52/53Endress+Hauser 5FMB50/51/52 universal application• Modular probe program to ensure optimum process adaptation• FMB50 compact version: installation in the tank from below or from the side• FMB51/52 rod and cable extension: installation from above, i.e. easy to retrofit ground tanks, no additionalopening in the tank floorFMB50 optimized for the food-processing and pharmaceutical industry• All typical flush-mounted process connections can be supplied• Welding flanges• Stainless steel housing• All the sanitary process connections are gap-free and can be cleaned so that the unit is free of residue, e.g.CIP cleaning• USDA/H1-approved transfer liquid as per FDA Directive• 3A approval or EHEDG approvalsP01-DB5xxxxx-12-xx-xx-xx-004FMB53 for level measurement in water and wastewater• The housing with the electronic insert is mounted outside shafts and tanks in such a way that it is protectedfrom flooding. The extension cable is secured with a suspension clamp.• The measuring cell tube made of stainless steel (AISI 316L) and the Alloy process isolating diaphragm allowuse in aggressive media such as wastewater for example.• Extension cable up to 400 m (1312 ft) in length (up to 100 m (328 ft) in Ex-areas) without strain relief.• Special measuring cell with gold/rhodium coating for applications in which severe hydrogen formation canoccur (e.g. digested sludge); → ä 26.• Special measuring cell with gold/platinum coating for acids, alkalis or sea water; → ä 26.74 -74 -TYPE ELFebruary 2010
  6. 6. Deltapilot M FMB50/51/52/536 Endress+HauserMeasuring principleP01-FMB5xxxx-15-xx-xx-xx-004Deltapilot M hydrostatic level measurement and measuring principle1 Rear isolating membrane of the CONTITE™ measuring cell2 Measuring element3 Process isolating diaphragmg Gravitational accelerationh Level heightp ges Total pressure = hydrostatic pressure + atmospheric pressurep atm Atmospheric pressurep hydr. Hydrostatic pressurep mess Measured pressure in the measuring cell = hydrostatic pressureρ Density of the mediumDue to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the hydrostaticpressure depends solely on the height h of the liquid column.The CONTITE™ measuring cell, which works on the principle of the gauge pressure sensor, constitutes thecore of Deltapilot M. In contrast to conventional gauge pressure sensors, the precision measuring element (2)in the CONTITE™ measuring cell is absolutely protected, situated between the process isolating diaphragm(3) and the rear isolating membrane (1). Thanks to this hermetic sealing of the measuring element, theCONTITE™ measuring cell is absolutely insensitive to condensate/condensation and aggressive gases. Thepressure applied is transferred from the process isolating diaphragm to the measuring element by means of anoil without any loss in pressure.Two temperature sensors, which measure the distribution of temperature in the cell, are arranged between theprocess isolating diaphragm and measuring element. The electronics can compensate any measuring errorsresulting from fluctuations in temperature with these measured temperature values.A linearization function with max. 32 points, based on a table entered either manually or semi-automatically,can be activated locally or remotely. This function facilitatesmeasurement in engineering units, and provides a linear output signal for spherical and horizontal cylindricaltanks, and vessels with a conical outlet.hh =pr · gh ppatmhydr.ppatmpatmgesphydr.p+patm=gesp)hydr.p+(patmpatmpmess = –pgespatmpmess = –pgespatmpmess = –123
  7. 7. Deltapilot M FMB50/51/52/53Endress+Hauser 7Level measurement in closedtanks with pressure overlayYou can determine the differential pressure in tanks with pressure overlay using two Deltapilot M. The pressuremeasured values of the two probes are sent to a signal processing unit such as Endress+Hauser RMA or a PLC.The signal processing unit or PLC determines the difference in pressure and uses this to calculate the level andthe density where necessary.P01-FMB5xxxx-15-xx-xx-xx-005Level measurement in a closed tank with pressure overlay1 Probe 1 measures the total pressure (hydrostatic pressure and top pressure)2 Probe 2 measures the top pressure3 Signal processing unit determines the difference in pressure and uses this to calculate the levelNote!• When selecting the Deltapilot M probes, make sure you select measuring ranges that are sufficiently wide(→ see example).• The process isolating diaphragm of probe 2 must not be flooded. This generates additional hydrostaticpressure which distorts the measurement.• The ratio of hydrostatic pressure to top pressure should be no more than 1:6.Example:• Max. hydrostatic pressure = 0.6 bar (9 psi)• Max. top pressure (probe 2) = 0.3 bar (4.5 psi)• Max. total pressure, measured with probe 1 = 0.3 bar (4..5 psi) + 0.6 bar (9 psi) = 0.9 bar (13.5 psi) Measuring cell to be selected: 0 to 1.2 bar (0 to 18 psi)• Max. pressure, measured with probe 2: 0.3 bar (4.5 psi) Measuring cell to be selected: 0 to 0.4 bar (0 to 6 psi)Density measurement You can measure the density in tanks with pressure overlay using two Deltapilot M and a signal processing unitor a PLC. The signal processing unit or the PLC calculates the density from the known distance Δh betweenthe two probes and the two measured values p1 and p2.P01-FMB5xxxx-15-xx-xx-xx-006Level measurement in a closed tank with pressure overlay1 Deltapilot M determines pressure measured value p12 Deltapilot M determines pressure measured value p23 Signal processing unit determines the density from the two measured values p1 and p2 and the distance Δh➁➀➂p2p1Dh➁➀➂
  8. 8. Deltapilot M FMB50/51/52/538 Endress+HauserLevel measurement withautomatic density correction(with media changing in thetank)Level measurement with automatic density correction is possible in conjunction with a limit switch such asLiquiphant and a PLC. The limit switch always switches at the same level. In the switch point, the signalprocessing unit determines the corrected density from the pressure of the Deltapilot M currently measured andthe known distance between Deltapilot M and the limit switch. The signal processing unit then calculates thelevel from the new density and the measured pressure of the Deltapilot M.P01-FMB5xxxx-15-xx-xx-xx-007Level measurement with automatic density correction1 Deltapilot M2 Liquiphant3 PLCElectrical differential pressuremeasurement with gaugepressure sensorsP01-FMB5xxxx-14-xx-xx-xx-0041 Shut-off valves2 e.g. filterIn the example given, two Deltapilot M devices (each with a gauge pressure sensor) are interconnected. Thepressure difference can thus be measured using two independent Deltapilot M devices.Caution!If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically safe circuitsas stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.System integration The device can be fitted with a tag name and a preset bus address, see → ä 53 ff "Ordering information"feature 895 "Identification:" version "Z1" and "Z2".Dh➁➀➂FieldgateFXA520FXN520FXN520Multidrop-ConnectorFXN520Deltapilot M➀➁➀➁
  9. 9. Deltapilot M FMB50/51/52/53Endress+Hauser 9Communication protocol • 4 to 20 mA with HART communication protocol• PROFIBUS PA– The Endress+Hauser devices meet the requirements of the FISCO model.– Due to the low current consumption of 11 mA ± 1 mA, the following number of devices can be operatedon one bus segment if installing as per FISCO:– up to 8 Deltapilot M for Ex ia, CSA IS and FM IS applications– up to 31 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.• FOUNDATION Fieldbus– The Endress+Hauser devices meet the requirements of the FISCO model.– Due to the low current consumption of 16 mA ± 1 mA, the following number of devices can be operatedon one bus segment if installing as per FISCO:– up to 6 Deltapilot M for Ex ia, CSA IS and FM IS applications– up to 22 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.Further information on FOUNDATION Fieldbus, such as requirements for bus system components can befound in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
  10. 10. Deltapilot M FMB50/51/52/5310 Endress+HauserInputMeasured variable Hydrostatic pressureMeasuring rangeNominalvalueRange limit Smallest span(factory calibration)1)MWP 2)OPL 3)Vacuum resistance 4)Version in theorder code 5)lower (LRL) 6)upper (URL) Synthetic oil/Inert oil[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [barabs (psiabs)]0.1 (1.45) –0.1 (-1.5) +0.1 (+1.5) 0.01 (0.15) 2.7 (40.5) 4 (60) 0.01/0.04(0,15/0,6)1C0.4 (6) –0.4 (-6) +0.4 (+6) 0.02 (0.3) 5.3 (79.5) 8 (120) 1F1.2 (18) –1 (-15) +1.2 (+18) 0.06 (1) 16 (240) 24 (360) 1H4 (60) –1 (-15) +4 (+60) 0.2 (3) 16 (240) 24 (360) 1M10 (150) –1 (-15) +10 (+150) 0.5 (7.5) 27 (405) 40 (600) 1P1) Recommended Turn down: Max 100:1.Factory calibration Turn down: Max 20:1, higher on request.2) The MWP (maximum working pressure) for the measuring device depends on the lowest-rated element, with regard to pressure, of the selected components,i.e. the process connection (→ ä 30 ff) has to be taken into consideration in addition to the measuring cell (→ see Table above). Pay attention to the pressure-temperature dependence also. For the appropriate standards and other information, see → ä 29, Pressure specifications section.3) OPL: over pressure limit; depends on the lowest-rated element, with regard to pressure, of the selected components4) The vacuum resistance applies to the measuring cell at reference conditions.5) → ä 53 ff, "Ordering information" section, feature 70 "Sensor range"6) By default, the device is set to a lower range limit of 0 bar. Please specify in the order if the lower range limit is to be set to a different default value.
  11. 11. Deltapilot M FMB50/51/52/53Endress+Hauser 11Explanation of terms Explanation of terms: turn down (TD),set span and span based on zero pointCase 1:• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value(URV)⏐Example:• Lower range value (LRV) = 0 mbar• Upper range value (URV) = 40 mbar (0.6 psi)• Nominal value (URL) = 400 mbar (6 psi)Turn down:• TD = URL / ⏐URV⏐ = 10:1Set span:• URV – LRV = 40 mbar (0.6 psi)This span is based on the zero point. P01-DBxxxxxx-05-xx-xx-xx-001Example: 400 mbar (6 psi) measuring cellCase 2:• ⏐Lower range value (LRV)⏐ ≥ ⏐Upper range value(URV)⏐Example:• Lower range value (LRV) = –200 mbar (3 psi)• Upper range value (URV) = 0 bar• Nominal value (URL) = 400 mbar (6 psi)Turn down:• TD = URL /⏐(LRV)⏐ = 2:1Set span:• URV – LRV = 200 mbar (3 psi)This span is based on the zero point.P01-DBxxxxxx-05-xx-xx-xx-002Example: 400 mbar (6 psi) measuring cell1 Set span2 Span based on zero point3 Nominal value i upper range limit (URL)4 Nominal measuring range5 Sensor measuring rangeLRL Lower range limitURL Upper range limitLRV Lower range valueURV Upper range value–400 mbar 0 +400 mbar40LRL LRV URLURV➁➀=➂➃➄–400 mbar +400 mbarLRV URLURV➂0LRL–200 mbar➁➀=➃➄
  12. 12. Deltapilot M FMB50/51/52/5312 Endress+HauserOutputOutput signal • 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire• Digital communication signal PROFIBUS PA (Profile 3.02)• Digital communication signal FOUNDATION FieldbusSignal range –4 to 20 mA HART3.8 to 20.5 mASignal on alarm As per NAMUR NE 43• 4 to 20 mA HARTOptions:– Max. alarm: can be set from 21 to 23 mA (Factory setting: 22 mA)– Hold measured value: last measured value is held– Min. alarm: 3.6 mA• PROFIBUS PA: can be set in the Analog Input block,Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad• FOUNDATION Fieldbus: can be set in the Analog Input block,Options: Last Good Value, Fail-safe Value (factory setting), Wrong ValueLoad - 4 to 20 mA HARTP01-xxxxxxxx-05-xx-xx-xx-002Load diagram1 Power supply 11.5 to 30 V DC for intrinsically safe device versions2 Power supply 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and foruncertified device versionsRLmax Maximum load resistanceU Supply voltageNote!When operating via a handheld terminal or via a PC with an operating program, a minimum communicationresistance of 250 Ω must be taken into account.Resolution • Current output: 1 μA• Display HART: can be set (factory setting: presentation of the maximum accuracy of the transmitter)U – 11.5 VRLmax 0.023 A£302011.5 U[V]40 4512391456804369[ ]WRLmax➀➁
  13. 13. Deltapilot M FMB50/51/52/53Endress+Hauser 13Dead time, time constantP01-xxxxxxxx-05-xx-xx-xx-036Presentation of the dead time and the time constantDynamic behavior:current outputDynamic behavior: HARTReading cycle• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)• Cyclic (Burst): max. 3/s, typical 2/sThe Deltapilot M commands the BURST MODE function for cyclic value transmission via the HARTcommunication protocol.Cycle time (Update time)Cyclic (Burst): min. 300 msResponse time• Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles)• Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)I63 %100 %tt1 t290 %t3Type Dead time (t1) [ms] Time constant T63 (= t2) [ms] Time constant T90 (= t3) [ms]max. FMB50 60 90 210max. FMB51FMB52FMB53500 250 -Type Dead time (t1) [ms] Dead time (t1) [ms] +Time constant T63 (= t2) [ms]Dead time (t1) [ms] +Time constant T90 (= t3) [ms]min.FMB50220 310 370max. 1020 1110 1170min. FMB51FMB52FMB53660 910 -max. 1460 1710 -
  14. 14. Deltapilot M FMB50/51/52/5314 Endress+HauserDynamic behavior:PROFIBUS PAReading cycle• Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control loop)• Acyclic: typical 25/sCycle time (update time)min. 100 msThe cycle time in a bus segment in cyclic data communication depends on the number of devices, on thesegment coupler used and on the internal PLC cycle time.Response time• Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval)• Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval)Dynamic behavior:FOUNDATION FieldbusReading cycle• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control loop)• Acyclic: typical 5/sCycle time (update time)Cyclic: min. 100 msResponse time• Cyclic: max. 20 ms (for standard bus parameter settings)• Acyclic: typical 70 ms (for standard bus parameter settings)Damping A damping affects all outputs (output signal, display).• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s• Via DIP-switch on the electronic insert, switch position"on" (= set value) and "off" (= damping switched off)• Factory setting: 2 sType Dead time (t1) [ms] Dead time (t1) [ms] +Time constant T63 (= t2) [ms]Dead time (t1) [ms] +Time constant T90 (= t3) [ms]min.FMB5095 185 245max. 1195 1285 1345min. FMB51FMB52FMB53535 785 -max. 1635 1885 -Type Dead time (t1)[ms]Dead time (t1) [ms] +Time constant T63 (= t2) [ms]Dead time (t1) [ms] +Time constant T90 (= t3) [ms]min.FMB50105 195 255max. 1105 1195 1255min. FMB51FMB52FMB53545 795 -max. 1545 1795 -
  15. 15. Deltapilot M FMB50/51/52/53Endress+Hauser 15Data of the FOUNDATIONFieldbus interfaceBasic dataVirtual communication references (VCRs)Link settingsTransducer BlocksDevice Type 0x1023Device Revision 01 (hex)DD Revision 0x01021CFF Revision 0x000102ITK Version 5.2.0ITK Certification Driver No. IT067500Link-Master (LAS) capable YesLink Master / Basic DeviceselectableYes; Factory setting: Basic DeviceNumber of VCRs 44Number of Link Objects in VFD 50Number of FB-Schedule Objects 40Permanent Entries 44Client VCRs 0Server VCRs 5Source VCRs 8Sink VCRs 0Subscriber VCRs 12Publisher VCRs 19Slot time 4Min. inter PDU delay 12Max. response delay 40Block Content Output valuesTRD1 Block Contains all parameters related to the measurement • Pressure or level (channel 1)• Process temperature (channel 2)• Measured pressure value (channel 3)• Max. pressure (channel 4)• Level before linearization (channel 5)Diagnostic Block Contains diagnostic information Error code via DI channels(channel 10 to 15)Display Block Contains parameters to configure the onsite display No output values
  16. 16. Deltapilot M FMB50/51/52/5316 Endress+HauserFunction blocksBlock Content Numberof blocksExecution time FunctionalityResource Block The Resource Block contains all the data thatuniquely identify the device. It is an electronicversion of a nameplate of the device.1 enhancedAnalog InputBlock 1Analog InputBlock 2The AI Block receives the measuring data from theSensor Block, (selectable via a channel number) andmakes the data available to other function blocks atits output. Enhancement: digital outputs for processalarms, fail safe mode.2 25 ms enhancedDigital InputBlockThis block contains the discrete data of the DiagnoseBlock (selectable via a channel number 10 to 15) andprovides them for other blocks at the output.1 20 ms standardDigital OutputBlockThis block converts the discrete input and thusinitiates an action (selectable via a channel number)in the DP Flow Block or in the im TRD1 Block.Channel 20 resets the counter for max. pressuretransgressions value and Channel 21 resets theTotalizer.1 20 ms standardPID Block The PID Block serves as a proportional-integral-derivative controller and is used almost universallyfor closed-loop-control in the field including cascadeand feedforward. Input IN can be indicated on thedisplay. The selection is performed in the DisplayBlock (DISPLAY_MAIN_LINE_CONTENT).1 40 ms standardArithmeticBlockThis block is designed to permit simple use of popularmeasurement math functions. The user does not haveto know how to write equations. The math algorithmis selected by name, chosen by the user for thefunction to be performed.1 35 ms standardInput SelectorBlockThe Input Selector Block facilitates the selection of upto four inputs and generates an output based on theconfigured action. This block normally receives itsinputs from AI Blocks. The block performs maximum,minimum, average and ‘first good’ signal selection.Inputs IN1 to IN4 can be indicated on the display.The selection is performed in the Display Block(DISPLAY_MAIN_LINE_1_CONTENT).1 30 ms standardSignalCharacterizerBlockThe Signal Characterizer Block has two sections,each with an output that is a non-linear function ofthe respective input. The non-linear function isgenerated by a single look-up table with 21 arbitraryx-y pairs.1 40 ms standardIntegratorBlockThe Integrator Block integrates a variable as afunction of the time or accumulates the counts from aPulse Input Block. The block may be used as atotalizer that counts up until reset or as a batchtotalizer that has a setpoint, where the integrated oraccumulated value is compared to pre-trip and tripsettings, generating a binary signal when the setpointis reached.1 35 ms standardAdditional function block information:Instantiate Function Block YESNumber of instantiate blocks 20
  17. 17. Deltapilot M FMB50/51/52/53Endress+Hauser 17Power supplyElectrical connection Note!• When using the measuring device in hazardous areas, installation must comply with the correspondingnational standards and regulations and the Safety Instructions or Installation or Control Drawings. → ä 66ff, "Safety Instructions" and "Installation/Control Drawings" sections.• According to IEC/EN61010 a suitable disconnector has to be installed for the device• HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia IIC and IECEx ia can be ordered as an option (see "Ordering information" section).• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.• The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also providesthe power supply.P01-xMx5xxxx-04-xx-xx-xx-004Electrical connection1 External grounding terminal2 Internal grounding terminal3 Supply voltage → ä 204 4...20 mA for HART devices5 For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be configuredanywhere along the bus line via menu operation.6 Terminals7 For HART devices: test terminals, see section "Taking 4 to 20 mA test signal"4 to 20 mA HARTTaking 4 to 20 mA test signalA 4 to 20 mA test signal may be measured via the test terminals without interrupting the measurement.PROFIBUS PAFor further information on the network structure and grounding, and for further bus system components suchas bus cables, see the relevant documentation, e.g. Operating Instructions BA00034S "PROFIBUS DP/PA:Guidelines for planning and commissioning" and the PNO Guideline.Cable specifications:Use a twisted, shielded two-wire cable, preferably cable type ANote!For further information on the cable specifications, see Operating Instructions BA00034S"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092- +1234567
  18. 18. Deltapilot M FMB50/51/52/5318 Endress+HauserPROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).FOUNDATION FieldbusThe digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides thepower supply. For further information on the network structure and grounding and for further bus systemcomponents such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00013S"FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.Cable specifications:Use a twisted, shielded two-wire cable, preferably cable type ANote!For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATIONFieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).Devices with valve connectorP01-xMx5xxxx-04-xx-xx-xx-005Left: electrical connection for devices with a valve connectorRight: view of the connector at the deviceMaterial: PA 6.6Devices with Harting plug Han7DP01-xMD7xxxx-04-xx-xx-xx-000Left: electrical connection for devices with Harting plug Han7DRight: view of the plug connector at the deviceMaterial: CuZn–++ –+–Han7D–++ – –+15467823
  19. 19. Deltapilot M FMB50/51/52/53Endress+Hauser 19Devices with M12 plugPIN assignment for M12 connectorEndress+Hauser offers the following accessories for devices with an M12 plug:Plug-in jack M 12x1, straight• Material: body PA; coupling nut CuZn, nickel-plated• Degree of protection (fully locked): IP66/67• Order number: 52006263Plug-in jack M 12x1, elbowed• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated• Degree of protection (fully locked): IP66/67• Order number: 71114212Cable 4x0.34 mm² (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)• Material: body PUR; coupling nut CuSn/Ni; cable PVC• Degree of protection (fully locked): IP66/67• Order number: 52010285Devices with 7/8" plugPIN assignment for 7/8" connectorExternal thread: 7/8 - 16 UNC• Material: housing / body CuZn, nickel-plated• Protection: IP66/68Cable glandTerminalsFor wire cross-sections of 0.5 to 2.5 mm² (20 to 14 AWG)A0011175PIN Meaning1 Signal +2 Not assigned3 Signal –4 EarthA0011176PIN Meaning1 Signal –2 Signal +3 Shield4 Not assignedApproval Type Clamping areaStandard, CSA GPATEX II1/2G or II2G Ex ia,IEC Ex ia Ga/Gb or Ex ia Gb,FM/ CSA ISPlastic M20x1.5 5 to 10 mm (0,2 to 0,39 in)ATEX II1/2D Ex t, II1/2GD Ex ia,II3G Ex nA,IEC Ex t Da/DbMetal M20x1.5 (Ex e) 7 to 10.5 mm (0,28 to 0,41 in)2134+–nc2143
  20. 20. Deltapilot M FMB50/51/52/5320 Endress+HauserSupply voltage Note!• When using the measuring device in hazardous areas, installation must comply with the correspondingnational standards and regulations and the Safety Instructions or Installation or Control Drawings.• All explosion protection data are given in separate documentation which is available upon request. TheEx documentation is supplied as standard with all devices approved for use in explosion hazardous areas.→ ä 66 ff, "Safety Instructions" and "Installation/Control Drawings" sections.4 to 20 mA HARTPROFIBUS PA• Version for non-hazardous areas: 9 to 32 V DCFOUNDATION Fieldbus• Version for non-hazardous areas: 9 to 32 V DCStart-up current HART 12 mA or 22 mA (selectable)Current consumption • PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21Cable entry → ä 53 ff, feature 50 "Electrical connection".Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables.• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) depends on the used cable gland (→ ä 19)Residual ripple No influence on 4 to 20 mA signal up to ± 5 % residual ripple within the permitted voltage range [according toHART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]Influence of power supply ≤ 0.0006 % of URL/1 VType of protection Supply voltage• Intrinsically safe 11.5 ... 30 V DC• Other types of protection• Devices without certificate11.5 ... 45 V DC (Versions with plug-in connection 35 V DC)
  21. 21. Deltapilot M FMB50/51/52/53Endress+Hauser 21Performance characteristicsReference operatingconditions• As per IEC 60770• Ambient temperature TA = constant, in the range of: +21 to +33°C (+70 to 91 °F)• Humidity ϕ = constant, in the range of: 5 to 80 % RH• Ambient pressure pA = constant, in the range of: 860 to 1060 mbar (12.47 to 15.37 psi)• Position of the measuring cell: constant, in range:FMB50: horizontally ±1°FMB51/FMB52/FMB53: vertically ±1°• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value• Span based on zero point• Material of the process isolating diaphragm: Alloy C276 (2.4819) and Alloy C276 (2.4819) with coating(AuRh or AuPt)• Measuring cell material (meter body): Alloy C276 (2.4819), 316L (1.4435)• Filling oil: synthetic oil (FDA)/inert oil• Supply voltage: 24 V DC ± 3 V DC• Load with HART: 250 ΩLong-term stabilityInfluence of orientation • < 2.3 mbar (0.0345 psi) when using synthetic oil (FDA)• < 5 mbar (0.075 psi) when using inert oilNote!Position-dependent zero point shift can be corrected. → ä 23, "General installation instructions" section.Warm-up period • 4 to 20 mA HART:– FMB50 = ≤5 s– FMB51/FMB52/FMB53 = ≤8 s• PROFIBUS PA: ≤8 s• FOUNDATION Fieldbus: ≤20 s (after a TOTAL-reset ≤45 s)Calibration positionReference accuracy The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and non-reproducibility as per IEC 60770. The data refer to the calibrated span.Measuring cell Long-term stability [%]0.1 bar (1,5 psi)• < 0.18 of the upper range limit (URL) / year• < 0.45 of the upper range limit (URL) / 5 years0.4 bar (6 psi)1.2 bar (18 psi)• < 0.1 of the upper range limit (URL) / year• < 0.25 of the upper range limit (URL) / 5 years4 bar (60 psi)10 bar (150 psi)• < 0.05 of the upper range limit (URL) / year• < 0.125 of the upper range limit (URL) / 5 years➀ FMB50➁ FMB51, FMB52, FMB53To minimize the effect ofthe orientation (e.g. in thecase of vertical deviceinstallation), position offsetis preset at the factory.P01-FMB5xxxx-11-xx-xx-xx-001➀ ➁Reference accuracy in % of the calibrated spanMeasuring cell TD "Standard" option "Platinum" option0.1 bar (1.5 psi)• TD ≤ 2:1• TD > 2:1• < 0.2• < 0.1 x TD• < 0.15• < 0.075 x TD
  22. 22. Deltapilot M FMB50/51/52/5322 Endress+HauserTotal performance The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility aswell as the thermal change in the zero point.Total error The total error comprises the long-term stability and the total performance:Thermal change in the zerooutput and the output span0.4 bar (6 psi)• TD ≤ 4:1• TD > 4:1• < 0.2• < 0.05 x TD• < 0.15• < 0.0375 x TD1.2 bar (18 psi)• TD ≤ 2:1• TD > 2:1• < 0.2• < 0.1 x TD• < 0.1• < 0.05 x TD4 bar (60 psi)• TD ≤ 4:1• TD > 4:1• < 0.2• < 0.05 x TD• < 0.1• < 0.025 x TD10 bar (150 psi)• TD ≤ 2.5:1• TD > 2.5:1• < 0.2• < 0.08 x TD• < 0.1• < 0.04 x TDReference accuracy in % of the calibrated spanMeasuring cell TD "Standard" option "Platinum" optionTotal performance in % of the URLVersion Measuring cell -10 to +60°C(+14 to +140 °F)60 to 85°C(140 to 185 °F)85 to 100 C(185 to 212 °F)FMB50FMB51/52/53 snap-on0.1 bar (1.5 psi) < 0.35 < 0.45 < 0.6FMB51/52/53 welded 0.1 bar (1.5 psi) < 0.8 < 1 < 1.4FMB50/51/52/530.4 bar (6 psi) < 0.35 < 0.45 < 0.61.2 bar (18 psi), 4 bar (60 psi),10 bar (150 psi)< 0.15 < 0.2 < 0.25Measuring cell % of the URL/year (in the permitted temperature range)0.1 bar (1.5 psi)• Snap-on: ±0.63• Welded: ±1.00.4 bar (6 psi) ±0.611.2 bar (18 psi) ±0.274 bar (60 psi), 10 bar (150 psi) ±0.25Version Measuring cell -10 to +60°C(-94 to +752°F)60 to 85 °C(+140 to +185°F)Only FMB50:85 to 100 °C(+140 to +185°F)% of the calibrated spanFMB50FMB51/52/53 snap-on0.1 bar (1.5 psi) < (0.32 + 0.30 x TD) < (0.34 + 0.40 x TD) < (0.34 + 0.55 x TD)FMB51/52/53 welded 0.1 bar (1.5 psi) < (0.32 + 0.50 x TD) < (0.34 + 0.60 x TD) -FMB50/51/52/530.4 bar (6 psi) < (0.31 + 0.25 x TD) < (0.32 + 0.30 x TD) -1.2 bar (18 psi),4 bar (60 psi),10 bar (150 psi)< (0.31 + 0.10 x TD) < (0.32 + 0.15 x TD) < (0.33 + 0.20 x TD)
  23. 23. Deltapilot M FMB50/51/52/53Endress+Hauser 23Operating conditions (installation)General installationinstructions• The position-dependent zero point shift can be corrected:– directly at the device via an operating key– directly at the device via operating keys on the display– via digital communication if the cover is not openNote!In hazardous areas, comply strictly with the safety instructions when the housing cover is closed and open.• The local display can be rotated in 90° stages.FMB50 Level measurement• Always install the device below the lowest measuring point.• Do not install the device at the following positions:– in the filling curtain– in the tank outflow– or at a point in the tank that can be affected by pressure pulses from the agitator• The calibration and functional test can be carried out more easily if you mount the device downstream of ashutoff device.• Deltapilot M must be included in the insulation for media that can harden when cold.Pressure measurement in gases• Mount Deltapilot M with shutoff device above the tapping point so that any condensate can flow into theprocess.Pressure measurement in steams• Mount Deltapilot M with siphon above the tapping point.• Fill the siphon with liquid before commissioning.The siphon reduces the temperature to almost the ambient temperature.Pressure measurement in liquids• Mount Deltapilot M with the shutoff device below or at the same level as the tapping point.FMB51/FMB52/FMB53 • When mounting rod and cable versions, make sure that the probe head is located at a point as free as possiblefrom flow. To protect the probe from impact resulting from lateral movement, mount the probe in a guidetube (preferably made of plastic) or secure it with a clamping fixture.• In the case of devices for hazardous areas, comply strictly with the safety instructions when the housingcover is open.• The length of the extension cable or the probe rod is based on the planned level zero point. The height ofthe protective cap must be taken into consideration when designing the layout of the measuring point. Thelevel zero point (E) corresponds to the position of the process isolating diaphragm.Level zero point = E; top of the probe = L.• Suspension clamp (FMB53 only)Material: → ä 46 ffOrder number: 52010869 → ä 53 ff, feature 620 , "Accessory enclosed", version "PO".LE61238
  24. 24. Deltapilot M FMB50/51/52/5324 Endress+HauserSupplementary installationinstructionsProcess isolating diaphragm• Do not clean or touch process isolating diaphragms with hard or pointed objects.• The process isolating diaphragm in the rod and cable version is protected against mechanical damage by aplastic cap.Seal• Deltapilot M devices with a G 1 ½ thread:When screwing the device into the tank, the flat seal has to be positioned on the sealing surface of the processconnection. To avoid additional strain on the process isolating diaphragm, the thread should never be sealedwith hemp or similar materials.• Deltapilot M devices with NPT threads:– Wrap Teflon tape around the thread to seal it.– Tighten the device at the hexagonal bolt only. Do not turn the device at the housing.– Do not overtighten the thread when screwing in the screw. Max. torque: 20 to 30 Nm(14.75 to 22.13 lbf ft)Sealing the probe housingMoisture must not penetrate the housing when mounting the device, establishing the electrical connection andduring operation.• Always firmly tighten the housing cover and the cable entries.• Lubricant is provided on the O-ring seal in the housing cover and on the thread of the aluminum cover. Toensure that the cover seals tight, any lubricant which has been removed must be replaced. Use siliconegrease or graphite paste as the lubricant. Mineral oil-based grease can destroy the O-ring.PE cable length > 300 m (984 ft)• Two suspension clamps must be used for PE cables longer than 300 meters (984 ft).Cable length tollerances• FMB52– Cable length < 5 m (16 ft): up to -35 mm (-1.38 in)– Cable length 5...10 m (16...33 ft): up to -75 mm (-2.95 in)– Cable length 10...100 m (33...328 ft): up to -100 mm (-3.94 in)• FMB53– Cable length < 5 m (16 ft): up to ±17.5 mm (±0.69 in)– Cable length 5...10 m (16...33 ft): up to ±37.5 mm (±1.48 in)– Cable length 10...100 m (33...328 ft): up to ±50 mm (±1.97 in)Rod length tollerances• FMB51– Rod length < 4000 mm (157 in): up to -4 mm (-0,16 in)Wall and pipe mounting For installing the device on pipes or walls, Endress+Hauser provides a mounting bracket which is included inthe scope of supply or can be ordered as a separate accessory (part no. 71102216).For the dimensions, see → ä 39.
  25. 25. Deltapilot M FMB50/51/52/53Endress+Hauser 25"Separate housing" version With the "separate housing" version, you are able to mount the housing with the electronics insert at a distancefrom the measuring point. This allows for trouble-free measurement:• Under particularly difficult measuring conditions (at installation locations that are cramped or difficult toaccess)• If rapid cleaning of the measuring point is required• If the measuring point is exposed to vibrationsYou can choose between different cable versions:• PE (2 m (6.6 ft), 5 m (16 ft) and 10 m (33 ft))• FEP (5 m (16 ft)).→ ä 53 ff, feature 600, "Separate housing".For the dimensions, see → ä 39.P01-PMx5xxxx-11-xx-xx-en-002In the case of the "separate housing" version, the sensor is delivered with the process connection and cable readymounted. The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at bothends. These sockets are simply connected to the housing and the sensor.1 Process connection with sensor2 Cable, both ends are fitted with a socket3 Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)4 Housing with electronic insertDegree of protection for the process connection and sensor with the use of• FEP cable:– IP 69K– IP 66 NEMA 4/6P– IP 68 (1.83 mH2O for 24 h) NEMA 4/6P• PE cable:– IP 66 NEMA 4/6P– IP 68 (1.83 mH2O for 24 h) NEMA 4/6PTechnical data of the PE and FEP cable:• Minimum bending radius: 120 mm (4.72 in)• Cable extraction force: max. 450 N (101 lbf)• Resistance to UV lightUse in hazardous area:• Intrinsically safe installations (Ex ia/IS)• FM/CSA IS: for Div.1 installation only➀➁➂➃r ³ 120 mmIP xx(see chapter“Ordering information”)FEP cable:IP 69KIP 66/68 NEMA 4/6PPE cable:IP 66/68 NEMA 4/6P
  26. 26. Deltapilot M FMB50/51/52/5326 Endress+HauserOxygen applications Oxygen and other gases can react explosively to oils, grease and plastics. As a result, the following are some ofthe precautions that must be taken:– All components of the system, such as measuring devices, must be cleaned in accordance with the BAM(DIN 19247) requirements.– Depending on the materials used, a certain maximum temperature and maximum pressure must not beexceeded for oxygen applications. The maximum temperature Tmax for oxygen applications is 60°C (140°F).The devices suitable for gaseous oxygen applications are listed in the following table with the specification pmax.PWIS cleaning Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops → ä 53 fffeature 570 "Service", version "HC".The stability of the materials used must be checked before using them in the medium.The protective cap of the process isolating diaphragm must be removed if necessary (FMB51/FMB52/FMB53).Applications with hydrogen With regard to materials in which hydrogen formation takes place (e.g. digested sludge), hydrogen atoms candiffuse through the metal process isolating diaphragm. This can result in incorrect measurement results.Endress+Hauser offers process isolating diaphragms with a gold/rhodium coating for such instances.→ Order via feature 170 "Material of the process isolating diaphragm", version "L".Note!To reduce the formation of hydrogen, you should not use galvanized assemblies.Special measuring cells foracids, alkalis or sea water(not FMB50)For acids, alkalis or sea water, Endress+Hauser offers process isolating diaphragms with a gold/platinumcoating.Note!With temperature exposure (up to 85 °C (185 °F)) there is an additional zero point deviation of 1,1 mbar(0,0165 psi).→ Order via feature 170 "Material of the process isolating diaphragm", version "N".Order code for devices1)cleanedfor oxygen applications1) Only device, not accessory or enclosed accessorypmax for oxygen applicationsFMB50 2)2) Feature 570 "Service" version "HB"• Depends on the lowest-rated element, with regard to pressure, of the selectedcomponents: over pressure limit (OPL) of the sensor or process connection (1.5x PN) 3)• Depends on filling oil 4)3) → ä 10, "Measuring range" section and → ä 30 ff, "Mechanical construction" section4) Oxygen applications possible with FKM seal and inert oil.FMB51 2)• Depends on the lowest-rated element, with regard to pressure, of the selectedcomponents: over pressure limit (OPL) of the sensor or process connection (1.5x PN) 3)• Depends on filling oil 4)• Depends on seal material
  27. 27. Deltapilot M FMB50/51/52/53Endress+Hauser 27Operating conditions (environment)Ambient temperature rangeStorage temperature rangeDegree of protection • → ä 53 ff, feature 50 "Electrical connection".• Separate housing → ä 25Climate class Class 4K4H (air temperature: –20 to 55°C (–4 to +131°F), relative humidity: 4 to 100%) satisfied as perDIN EN 60721-3-4 (condensation possible)Vibration resistanceElectromagnetic compatibility • Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and NAMURRecommendation EMC (NE21). Details can be found in the Declaration of Conformity (in the Downloadarea of "www.de.endress.com", "search area - Approvals and Certificates", "Manufact. Declaration").• Max. deviation during EMC-tests < 0.5% of the span• All tests were performed with full measurement range (TD 1:1).Version FMB50 FMB51 FMB52 FMB53Without LCD display –40°C to +85°C(-40°F to +185°F)With PE cable: -40°C to +70°C (-40°F to +158°F)With FEP cable: –40°C to +80°C (-40°F to +176°F)With LCD display 1)1) Extended temperature application range (-40°C to +85°C (–40°F to +185°F)) with restrictions in optical propertiessuch as display speed and contrast–20°C to +70°C (-4°F to +158°F)With M12 plug , elbowed -25°C to +85°C(-13°F to +185°F)With PE cable: -25°C to +70°C (-13°F to +158°F)With FEP cable: -25°C to +80°C (-13°F to +176°F)With separate housing (PEand FEP cable)-20°C to +60 °C (-4°F to +140°F)Version FMB50 FMB51 FMB52 FMB53Without LCD display –40°C to +90°C(-40°F to +194 °F) With PE cable: -40°C to +70°C (-40°F to +158°F)With FEP cable: –40°C to +80°C (-40°F to +176°F)With LCD display –40°C to +85°C(-40°F to +185°F)With M12 plug , elbowed -25°C to +90°C(-13°F to +194°F)With PE cable: -25°C to +70°C (-13°F to +158°F)With FEP cable: -25°C to +80°C (-13°F to +176°F)With separate housing andFEP cable-20°C to +60°C (-4°F to +140°F)Device/accessory Test standard Vibration resistanceFMB50, FMB52, FMB53 GL VI-7-2• Part 7: Guidelines for the Performance of TypeApprovals• Chapter 2: Test Requirements for Electrical /Electronic Equipment and SystemsGuaranteed for:5 to 25 Hz: ±1.6 mm (0.06 in);25 to 100 Hz: 4 gin all 3 planesFMB50, FMB52, FMB53with mounting bracketIEC 61298-3 Guaranteed for:10 to 60 Hz: ±0.15 mm (0.01 in);60 to 500 Hz: 2 gin all 3 planesFMB51 IEC 60068-2-6 Guaranteed for:10 to Hz: ±0.075 mm (0.003 in)60...150 Hz 1g in all 3 planes
  28. 28. Deltapilot M FMB50/51/52/5328 Endress+HauserOvervoltage protection(optional)The device can be fitted with overvoltage protection, see → ä 53 ff "Ordering information" feature 610"Accessory mounted:" version "NA". The overvoltage protection is mounted at the factory on the housingthread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in length (take additional length intoaccount when installing). The device is connected as illustrated in the following graphic.For details refer to TI001013KEN, XA01003KA3 and BA00304KA2.P01-xMx5xxxx-04-xx-xx-en-006➀➁Unit to beprotectedConnectioncablesIncomingconnection cablesHAW569-DA2B+-+-RedBlack+-Shield groundingwithoutdirect➀➁
  29. 29. Deltapilot M FMB50/51/52/53Endress+Hauser 29Operating conditions (process)Process temperature rangeLateral load FMB51 (static) ≤30 NmPressure specifications • The maximum pressure for the measuring device depends on the lowest-rated element with regard topressure. See the following sections:– → ä 10 ff, "Measuring range" section– "Mechanical construction" section.The MWP (maximum working pressure) is specified on the nameplate. This value refers to a referencetemperature of +20°C (68°F) or 100°F (38°C) for ANSI flanges and may be applied to the device for anunlimited time. Pay attention to pressure-temperature dependencies.• The pressure values permitted at higher temperatures can be found in the following standards:– EN 1092-1: 2001 Tab. 18 1– ASME B 16.5a – 1998 Tab. 2-2.2 F316– ASME B 16.5a – 1998 Tab. 2.3.8 N10276– JIS B 2220.• The test pressure corresponds to the over pressure limit of the device (OPL = 1.5 x MWP) and may be appliedfor only a limited time period in order to avoid permanent damage.• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The abbreviation"PS" corresponds to the MWP (maximum working pressure) of the measuring device.• In the case of sensor range and process connection combinations where the OPL (over pressure limit) of theprocess connection is smaller than the nominal value of the sensor, the device is set at the factory, at thevery maximum, to the OPL value of the process connection. If you want to use the entire sensor range, selecta process connection with a higher OPL value (1.5 x PN; PN = MWP).• In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per → ä 26, "Oxygenapplications" may not be exceeded.FMB50 FMB51 FMB52 FMB53–10°C to +100°C (+14°F to 212°F)135°C (275°F) for 30 min. maximum–10°C to +85°C(+14°F to +185°F)With PE cable: -10°C to +70°C (-14°F to 158°F)With FEP cable: –10°C to +80°C (-14°F to 176°F)Min. process temperature when using the KALREZ seal : -3 °C (27 °F).1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EOin EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
  30. 30. Deltapilot M FMB50/51/52/5330 Endress+HauserMechanical constructionF31 aluminum housingdimensionsP01-F31xxxx-06-00-xx-xx-000Front view, left-hand side view, top view➀ The cover with viewing window is 15 mm (0,59 in) higher than the cover without viewing window.→ For installation height H for housing with viewing window, see the specific process connection. Housing weight→ ä 40F15 stainless steel housingdimensions (hygienic)P01-F15xxxx-06-00-xx-xx-000Front view, top view.➀ The cover with viewing window is 19 mm (0,75 in) higher than the cover without viewing window.→ For installation height H for housing with viewing window, see the specific process connection. Housing weight→ ä 40Process connections FMB50(compact version)Threaded connection ISO 228 and NPTP01-FMB5xxxx-06-xx-xx-xx-005→ For the installation height, see the following table. For weight, see → ä 40.1 Thread ISO 228 G 1 ½ A;Material version GGJ: AISI 316L (1.4435), version GGC: Alloy C276 (2.4819)2 Thread ANSI 1 ½ MNPT;Material version RGJ: AISI 316L (1.4435)11510394H➀1576100H➀19➂G 1 1/2H➁ 1 1/2 NPTSW 5050 AFHø55G 1 1/2ø5525ø55G 1 1/2ø55251 1/2 NPTø55ø5525SW 5050 AF➀ G 1 1/2HSW 5050 AFø55G 1 1/2ø5525ø55G 1 1/2ø5525ab
  31. 31. Deltapilot M FMB50/51/52/53Endress+Hauser 31Installation height H, devices with a threadProcess connections FMB50(compact version) - continuedEN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527P01-FMB70xxx-06-09-xx-xx-002Flange with raised faceH: device height = height of device without flange h + flange thickness bHeight H, see → ä 33.F31 housing F15 housing156 mm (6.14 in) 148 mm (5.83 in)Dkbg2gH2hFlange 1)BoltholesVersion Material 2) NominaldiameterNominalpressureShape 3) Diameter Thickness Diameterof raisedfaceHeightofraisedfaceQuantity Diameter HolecircleFlangeweight 4)D b g f g2 k[mm] [mm] [mm] [mm] [mm] [mm] [kg]CEJ AISI 316L DN 40 PN 10/16 B1 (C) 150 18 88 2 4 18 110 2.6CFJ AISI 316L DN 50 PN 10/16 B1 (C) 165 18 102 2 4 18 125 3.3CGJ AISI 316L DN 80 PN 10/16 B1 (C) 200 20 138 2 8 18 160 5.1CHJ AISI 316L DN 100 PN 10/16 B1 (C) 220 20 158 2 8 18 180 6.31) The roughness of the surface in contact with the medium, including the sealing surface of the flanges, is Ra 0.8 μm (31,5 μin). Lower surface roughnessavailable on request.2) Endress+Hauser supplies DIN/EN stainless steel flanges as per AISI 316L (DIN/ EN material number 1.4404 or 14435). With regard to their stability-temperature property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN 1092-1: 2001 Tab.18. The chemical composition of the twomaterials can be identical.3) Designation as per DIN 2526 in brackets4) Weight incl. pipe and measuring cell, housing weight, see → ä 40
  32. 32. Deltapilot M FMB50/51/52/5332 Endress+HauserProcess connections FMB50(compact version) - continuedANSI flanges, connection dimensions as per ANSI B 16.5, raised face RFP01-FMB70xxx-06-09-xx-xx-002Flange with raised faceH: device height = height of device without flange h + flange thickness bHeight H, see → ä 33.Dkbg2gH2hFlange 1)BoltholesVersion Material 2) NominaldiameterClass Diameter Thickness Diameter ofraised faceHeight ofraised faceQuantity Diameter HolecircleFlangeweight 3)D b g f g2 k[in] [lb./sq in] [in][mm][in][mm][in][mm][in][mm][in][mm][in][mm][kg]AEJNot FMB51/52AISI 316/316L1 ½ 150 51270.6917.52.8873.20.061.64 0.6215.73.8898.62.1AFJ AISI 316/316L2 150 6152.40.7519.13.6291.90.061.64 0.7519.14.75120.73.0AGJ AISI 316/316L3 150 7.5190.50.9423.951270.061.64 0.7519.16152.45.7AHJ AISI 316/316L4 150 9228.60.9423.96.19157.20.061.68 0.7519.17.5190.57.81) The roughness of the surface in contact with the medium, including the sealing surface of the flanges, is Ra 0.8 μm (31,5 μin). Lower surface roughnessavailable on request.2) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)3) Weight incl. pipe and measuring cell, housing weight, see → ä 40
  33. 33. Deltapilot M FMB50/51/52/53Endress+Hauser 33Process connections FMB50(compact version) - continuedJIS flanges, connection dimensions as per JIS B 2220 BL, raised face RFP01-FMB70xxx-06-09-xx-xx-002Flange with raised face, material: AISI 316L (1.4435)H: device height = height of device without flange + flange thickness bHeight H, see → ä 33.Process connections FMB50(compact version) - continuedInstallation height H, devices with flangeDkbg2gH2hFlange 1)BoltholesVersion NominaldiameterNominalpressureDiameter Thickness Diameter ofraised faceHeight ofraised faceQuantity Diameter HolecircleFlangeweight 2)D b g f g2 k[mm] [mm] [mm] [mm] [mm] [mm] [kg]KEJ 40 A 10 K 140 16 81 2 4 19 105 2.1KFJ 50 A 10 K 155 16 96 2 4 19 120 2.5KGJ 80 A 10 K 185 18 126 2 8 19 150 3.8KHJ 100 A 10 K 210 18 151 2 8 19 175 4.91) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), is Ra 0.8 μm (31,5 μin). Lower surfaceroughness available on request.2) Weight incl. pipe and measuring cell, housing weight, see → ä 40F31 housing F15 housing165 mm (6.5 in) 157 mm (6.18 in)
  34. 34. Deltapilot M FMB50/51/52/5334 Endress+HauserProcess connections FMB50(compact version) - continuedUniversal adapterP01-FMB70xxx-06-09-xx-xx-003material: b = top section AISI 316L (1.4404), a = bottom section AISI 316L (1.4435);Surface roughness of the surfaces in contact with the medium Ra ≤ 0.76 μm (30 μin) as standard. Lower surface roughnessavailable on request.1 Version UPJ 1): universal adapter incl. silicone molded seal, EHEDG, 3A Class I, FDA CFR 21§177.2600,USP Plastic Class VI-70C; Order no.: 52023572Version UNJ 1): universal adapter incl. EPDM molded seal, EHEDG, FDA CFR 21§177.2600;Order no.: 711007192 Version UQJ 1): universal adapter, 6 inch extension including silicone molded seal, EHEDG, 3A,FDA CFR 21§177.2600, USP Plastic Class VI-70CVersion UOJ 1): universal adapter, 6 inch extension including EPDM molded seal, EHEDG,FDA CFR 21§177.2600Installation height H, devices with universal adapterProcess connections FMB50(compact version) - continuedAnderson adapterP01-FMBX0xxx-06-09-xx-xx-000Material: b = top section AISI 316L (1.4404), a = bottom section AISI 316L (1.4435), slotted nut AISI 316L (1.4404);Surface roughness of the surfaces in contact with the medium Ra ≤ 0.76 μm (30 μin) as standard. Lower surface roughnessavailable on request.1 Version USJ: Anderson adapter short 2-3/16", incl. silicone molded seal, 3A, FDA CFR 21§177.26002 Version UTJ: Anderson adapter long 6-½", incl. silicone molded seal, 3A, FDA CFR 21§177.2600Installation height H, devices with Anderson adapterø43.5Hø43.5Habab➀ ➁1) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material number 1.4307).F31 housing F15 housingUniversal adapter 196 mm (7.72 in) 189 mm (7.44 in)Universal adapter with 6 inch extension 307 mm (12.1 in) 299 mm (11.8 in)Hø2" ø2"ø3"ø3"Habab➀ ➁F31 housing F15 housingAnderson short 204 mm (8.03 in) 196 mm (7.72 in)Anderson long 314 mm (12.4 in) 306 mm (12 in)
  35. 35. Deltapilot M FMB50/51/52/53Endress+Hauser 35Process connections FMB50(compact version) - continuedHygienic connectionsP01-FMB5xxxx-06-xx-xx-xx-001Hygienic connections, material AISI 316L (1.4435)Surface roughness of the surfaces in contact with the medium Ra ≤0.76 μm (30 μin) as standard. Lower surface roughnessavailable on request. For weight, see → ä 40.1 Version MZJ: DIN 11851 DN 40 PN 25, EHEDG, 3A2 Version MRJ: DIN 11851 DN 50 PN 25, EHEDG, 3A3 Version NDJ: DIN11864-1 A DN50 PN16 pipe DIN11866-A, slotted nut, 316L, EHEDG, 3A4 Version TDJ: Tri-Clamp ISO 2852 DN 40 – DN 51 (2"), DIN 32676 DN 50, EHEDG, 3A5 Version TIJ: DRD DN50 (65 mm) PN 25, 316L6 Version TRJ: Varivent Typ N for pipes 40 – 162, PN 40, EHEDG, 3A7 Version TXJ: SMS 2", PN25, EHEDG, 3A8 Version S4J: NEUMO, D50, PN16, 316L, 3AInstallation height H, devices with Tri-Clamp or hygienic connection➄ Varivent N DN 40 – DN 162Clamp ISO 2852 DN40 - DN 51 (2")/DIN 32676 DN 50DRD DN50 (65 mm)➃➀ DIN 11851 DN 40 ➁ DIN 11851 DN 504 x ø11.5ø105ø84ø65–1.223.5HHø64ø56.520.5HRd 70 x1/6ø65ø84ø56Rd 65 x 1/610.2Hø68.5Rd 78 x 1/611.2HSMS 2"➅ø68H20.5ø84➆ NEUMOø927ø49.9ø70ø90H➇ø68.5Rd 78 x 1/620,5HDIN 11864-1 A DN 50➂F31 housing F15 housing185 mm (7.28 in) 178 mm (7.01 in)
  36. 36. Deltapilot M FMB50/51/52/5336 Endress+HauserProcess connections FMB51(rod version)Threaded connection ISO 228 and NPTP01-FMB51xxx-06-xx-xx-en-000Rod version with thread G 1 ½ or 1 ½ NPTL Probe length = 0.4 to 4 m (1.3 ft to 13 ft)H For installation height H → ä 31→ For dimensions of process connections → ä 30 ff.EN/DIN, ANSI and JIS flangesP01-FMB51xxx-06-xx-xx-xx-001Rod version with flangeL Probe length = 0.4 to 4 m (1.3 ft to 13 ft)H For installation height H → ä 33→ For dimensions of process connections → ä 30 ff.25ø21.3208ø43.5HLø42.4AF50gø21.3g2H208fDkbLø43.5ø42.4
  37. 37. Deltapilot M FMB50/51/52/53Endress+Hauser 37Process connections FMB52(cable version)Threaded connection ISO 228 and NPTP01-FMB52xxx-06-xx-xx-en-000Cable version with thread G 1 ½ and 1 ½ NPTL Probe length = 0.5 to 400 m (1.6 to 1312 ft)H For installation height H → ä 31→ For dimensions of process connections → ä 30 ff.EN/DIN, ANSI and JIS flangesP01-FMB52xxx-06-xx-xx-xx-001Cable version with flangeL Probe length = 0.5 to 400 m (1.6 to 1312 ft)H For installation height H → ä 33→ For dimensions of process connections → ä 30 ff.ø10.423625LHø43.5ø42.4AF50fg2bHkDgø10.4236Lø43.5ø42.4
  38. 38. Deltapilot M FMB50/51/52/5338 Endress+HauserDimensions of Deltapilot MFMB53 (suspension clamp andmounting bracket)P01-FMB53xxx-06-xx-xx-xx-000FMB53 with suspension clamp and mounting bracket1 Mounting bracket for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)2 Suspension clamp3 Measuring cell tubeL Probe length = 0.5 to 400 m (1.6 to 1312 ft)Dimensions (in mm)ø42.4ø43.523661238ø10.4➁➂LGø94➀ ➀Aø94FEBC DR200mmPipe mounting Wall mountingA [mm (in)] C [mm (in)] B [mm (in)] D [mm (in)]CoverflatCoverhighCoverflatCoverhighCoverflatCoverhighCoverflatCoverhighF15 housing 154.7 (6.09) 173.7 (6.84) 197.1 (776) 210.6 (8.29) 167.7 (6.6) 186.7 (7.35) 210.1 (8.27) 223.6 (8.8)F31 housing 167 (6.57) 181.3 (7.14) 211.8 (8.34) 221.7 (8.73) 180 (7.09) 194.3 (7.65) 224.8 (8.85) 234.7 (9.24)E [mm (in)] F [mm (in)] G [mm (in)]F15 housing 146 (5.75) 127 (5) 159 (6.26)F31 housing 156.2 (6.15) 137.2 (5.4) 169.2 (6.66)
  39. 39. Deltapilot M FMB50/51/52/53Endress+Hauser 39Wall and pipe mounting with"Separate housing" versionP01-xMx5xxxx-06-xx-xx-xx-004L: PE-cable 2 m (6.6 ft), 5 m (16 ft) or 10 m (33 ft). FEP-cable 5m (16 ft).F31 housing dimensions. Housing weight → ä 40. ➀ Cover without viewing window. ➁ Cover with viewing window.F15 housing dimensions. Housing weight → ä 40. ➂ Cover without viewing window. ➃ Cover with viewing window.Reduction in installation heightIf the separate housing is used, the mounting height of the process connection is reduced compared to thedimensions of the standard version (see graphic).P01-xMx5xxxx-06-xx-xx-xx-0001 Process connection adapter.122ø6528670ø5269112127➀➁6395114➂➃140158 1758150Lø6,4(0.25)ø54.181F15r ³ 120 mmr ³ 120 mm r ³ 120 mmr ³ 120 mmr ³ 120 mmr ³ 120 mm➀➀➀F3129441736
  40. 40. Deltapilot M FMB50/51/52/5340 Endress+HauserA minimum bending radius (r) of 120 mm (4,72 in) must be observed for the cable.Example for a "Separate housing" versionP01-FMB5xxxx-06-xx-xx-xx-003Connecting cable with process connection adapter and mounting bracket, here shown with an FMB521 Mounting bracket for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)2 Process connection adapter3 Measuring cell tubeL1 PE cable = 2 m (6.6 ft), 5m (16 ft) or 10 m (33 ft)FEP cable = 5 m (16 ft)L Probe length = 0.5 to 400 m (1.6 to 1312 ft)Note!For FMB50, FMB51, FMB52, order the separate housing via feature 600 "Separate housing".Weight Housing➀ø6121.7L1LR120mm³➁➂ø54.1F31 housing F15 housingAluminum AISI 316LWith electronic insertand local display1.1 kg (2.43 lbs) 0.8 kg (1.76 lbs)
  41. 41. Deltapilot M FMB50/51/52/53Endress+Hauser 41Separate housingNote!Total weight = weight of separate housing + weight cable + weight mounting bracket +Pipe bend + weight process connection adapter + (see following chapters)Process connections FMB50 or Process connection and pioe FMB51 or Process connection and cable FMB52Process connections FMB50Note!Total weight of device = weight of housing (→ ä 40) + weight of process connection FMB50Process connection and pipe FMB51Note!• Total weight of device with threaded connection = weight of housing (→ ä 40) + weight of pipe incl. cablex length + weight of process connection FMB51Designation WeightSeparate housing for FMB50 Weight of housing (→ ä 40) + 0.5 kg (1.10 lbs).Separate housing for FMB51 and FMB52 Weight of housing (→ ä 40) + 0.65 kg (1.43 lbs).Process connection adapter 0.4 kg (0.88 lbs)Mounting bracket 0.2 kg (0.44 lbs)Pipe bend incl. cable entry 0.65 kg (1.43 lbs)PE cable 2 m (6,6 ft) 0.16 kg (0.35 lbs)PE cable 5 m (16 ft) 0.32 kg (0.71 lbs)PE cable 10 m (33 ft) 0.59 kg (1.30 lbs)FEP cable 5 m (16 ft) 0.62 kg (1.37 lbs)Process connection incl. sensor WeightDIN 11851 DN 40 0.7 kg (1.54 lbs)DIN 11851 DN 50 0.9 kg (1.98 lbs)Tri-Clamp ISO 2852 DN 40 – DN 51 (2")/DIN 32676 DN 50 0.7 kg (1.54 lbs)DRD DN50 (65 mm) 1.1 kg (2.43 lbs)Varivent Typ N for pipes DN 40 – DN 162 1.0 kg (2.21 lbs)SMS 2" 0.7 kg (1.54 lbs)NEUMO D50 1.1 kg (2.43 lbs)Universal adapter 0.8 kg (1.76 lbs)Universal adapter with 6 inch extended diaphragm seal 1.7 kg (3.75 lbs)Anderson Adapter short 1.5 kg (3.31 lbs)Anderson Adapter long 2.9 kg (6.39 lbs)Thread ISO228 G1 ½A, AISI316L / 1.4435 0.8 kg (1.76 lbs)Thread ISO228 G1 ½A, Alloy C276 / 2.4819 0.8 kg (1.76 lbs)Thread ANSI 1 ½ MNPT, AISI316L / 1.4435 0.8 kg (1.76 lbs)Flange connection, incl. sensor, without a flange 0.45 kg (0.99 lbs)Process connection incl. sensor WeightPipe incl. cable 0.77 kg/m (1.70 lbs/3.3 ft)Threaded connection incl. measuring cell tube and sensor 1.65 kg (3.64 lbs)Flange connection incl. measuring cell tube and sensor, without a flange 1.3 kg (2.87 lbs)
  42. 42. Deltapilot M FMB50/51/52/5342 Endress+Hauser• Total weight of device with flange connection = weight of housing (→ ä 40) + weight of pipe incl. cable xlength + weight of process connection FMB51Process connection and cable FMB52Note!• Total weight of device with threaded connection = weight of housing (→ ä 40) + weight of cable x length+ weight of process connection FMB52• Total weight of device with flange connection = weight of housing (→ ä 40) + weight of pipe incl. cable xlength + weight of process connection FMB52 + weight of flange (→ ä 31 ff)Process connection FMB53 – secured with suspension clamp and mounting bracketNote!Total weight of device = weight of housing (→ ä 40) + weight of cable x length + weight of mounting bracket+ weight of pipe bend + weight of suspension clamp + weight of measuring cell tube.Cable length > 120 m (394 ft) = Delivery on cable reel.Process connection incl. sensor WeightPE cable 0.13 kg/m (0.28 lbs/3.3 ft)FEP cable 0.18 kg/m (0.40 lbs/3.3 ft)Threaded connection incl. measuring cell tube and sensor 1.65 kg (3.64 lbs)Flange connection incl. measuring cell tube and sensor, without a flange 1.3 kg (2.87 lbs)Process connection incl. sensor WeightPE cable 0.13 kg/m (0.28 lbs/3.3 ft)FEP cable 0.18 kg/m (0.40 lbs/3.3 ft)Mounting bracket 0.2 kg (0.44 lbs)Pipe bend incl. cable entry 0.65 kg (1.43 lbs)Suspension clamp 0.4 kg (0.88 lbs)Measuring cell tube incl. sensor 1.0 kg (2.21 lbs)
  43. 43. Deltapilot M FMB50/51/52/53Endress+Hauser 43Material (not wetted) HousingP01-xMxx3xxx-14-xx-xx-xx-002Front view, left-hand side view, top view15123467891011121314516Item num-berComponent part Material1F31 housing, RAL 5012 (blue) Die-cast aluminum with protective powder-coating onpolyester base2Cover, RAL 7035 (gray) Die-cast aluminum with protective powder-coating onpolyester base3 Cover seal EPDM4 Sight glass Mineral glass5 Sight glass seal Silicone (VMQ)6 External ground terminal AISI 304 (1.4301)7 Nameplates Plastic film8 Attachement for tie-on label AISI 304 (1.4301)/ AISI 316 (1.4401)9 Pressure compensation filter PA6 GF1010 Pressure compensation filter, O-ring Silicone (VMQ)11 Sealing ring EPDM12 Snap ring PC Plastic13 Seal of cable gland and blind plug EPDM/NBR14 Cable gland Polyamide (PA) or CuZn nickel-plated15 Blind plug PBT-GF30 FRfor dust ignition-proof, Ex d, FM XP and CSA XP:AISI 316L (1.4435)16 Cover clamp Clamp AISI 316L (1.4435), screw A4
  44. 44. Deltapilot M FMB50/51/52/5344 Endress+HauserP01-xMxx3xxx-14-xx-xx-xx-002Front view, left-hand side view, top view1234567891011121314Item number Component part Material1 F15 housingAISI 316L (1.4404)2 Cover3 Cover seal Silicone with PTFE coating4 Sight glass for non-hazardous area, ATEX Ex ia,NEPSI Zone 0/1 Ex ia, IECEx Zone 0/1 Ex ia, FMNI, FM IS, CSA ISPolycarbonate (PC)4 Sight glass for ATEX 1/2 D, ATEX 1/3 D, ATEX 1GD, ATEX 1/2 GD, ATEX 3 G, FM DIP, CSA dustignition-proofMineral glass5 Sight glass seal Silicone (VMQ)6 External ground terminal AISI 304 (1.4301)7 Attachement for tie-on label AISI 304 (1.4301)/ AISI 316 (1.4401)8 Pressure compensation filter PA6 GF109 Pressure compensation filter, O-ring Silicone (VMQ)10 Nameplates lasered11 Cable gland Polyamide (PA), for dust ignition-proof: CuZn nickel-plated12 Seal of cable gland and blind plug NBR/Silicone/EPDM13 Sealing ring EPDM14 Screw A4-50
  45. 45. Deltapilot M FMB50/51/52/53Endress+Hauser 45Connecting partsP01-xMxx3xxx-14-xx-xx-xx-003Filling oil• Synthetic oil polyalphaolefin FDA 21 CFR 178.3570, NSF H1• Inert oilItem number Component part Material1 Connection between thehousing and process connectionAISI 316L (1.4404)2 Mounting bracket Bracket AISI 304 (1.4301), AISI 304L (1.4306)3 Screw and nuts A2-704 Half-shells: AISI 304L (1.4306)5 Seal for cable fromseparate housingFKM, EPDM6 Gland for cable from separatehousing:Screws:AISI 316L (1.4404)A27 PE cable for separate housing Abrasion-proof cable with strain-relief Dynema members; shielded usingaluminum-coated film; insulated with polyethylene (PE-LD), black;copper wires, twisted, UV-resistant8 FEP cable for separate housing Abrasion-proof cable; shielded using galvanized steel wire netting;insulated with fluorinated ethylene propylene (FEP), black;copper wires, twisted, UV-resistant9 Process connection adapter forseparate housingAISI 316L (1.4404)10 Housing adapter FMB50, FMB51, FMB52: AISI 316L (1.4404)FMB53: AISI 304 (1.4301)11 Cable gland:Sealing insert:O-ring:CuZn nickel-platedTPE-VNBR112 346678955410 11
  46. 46. Deltapilot M FMB50/51/52/5346 Endress+HauserMaterial (wetted)P01-xMxx3xxx-14-xx-xx-xx-003Item number Component part Material1 Process connection → ä 30 ff2 Socket AISI 316L (1.4404) or Alloy C4 (2.4610)3 Rod AISI 316L (1.4435) or Alloy C4 (2.4610)PE cable Abrasion-proof cable with strain-relief Dynema members; shielded usingaluminum-coated film; insulated with polyethylene (PE-LD), black/blue;copper wires, twisted, UV-resistantPE cable(with Drinking water approval)Abrasion-proof cable with strain-relief Dynema members; shielded usingaluminum-coated film; insulated with polyethylene (PE-LD), black;copper wires, twisted, UV-resistantFEP cable Abrasion-proof cable; shielded using galvanized steel wire netting;insulated with fluorinated ethylene propylene (FEP), black;copper wires, twisted, UV-resistant4 Socket AISI 316L (1.4404) or Alloy C4 (2.4610)5 Probe tube AISI 316L (1.4404) or Alloy C22 (2.4602)6 Process isolating diaphragm andmeter body→ ä 53 ff7 Seals → ä 53 ff8 Protection cap PPO9 Process connection Alloy C276 (2.4819)FMB51ISO228 Version “GGC“FMB52FMB53112233344 4678 889955 5ISO228 Version “GGC“15151010111112126 67 78 8131314141617
  47. 47. Deltapilot M FMB50/51/52/53Endress+Hauser 47Note!The wetted device components are listed in the "Mechanical construction" (→ ä 30 ff) and "Orderinginformation" (→ ä 53 ff) sections.DIN/EN flangesEndress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L as per material numbers 1.4435or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are groupedtogether under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.TSE Certificate of Suitability (Transmissible Spongiform Encephalopathy)The following applies to all process wetted device components:• They do not contain any materials derived from animals.• No auxiliaries or operating materials derived from animals are used in production or processing.10 Socket Alloy C4 (2.4610)11 Rod Alloy C4 (2.4610)12 Socket Alloy C4 (2.4610)13 Probe tube Alloy C22 (2.4602)14 Process isolating diaphragm andmeter body→ ä 53 ff15 Seals → ä 53 ff16 Suspension clamp AISI 316L (1.4404)17 Clamping jaw PA-GFItem number Component part Material
  48. 48. Deltapilot M FMB50/51/52/5348 Endress+HauserHuman interfaceOperating elements Local display (optional)A 4-line liquid crystal display (LCD) is used for display and operation. The local display shows measured values,dialog texts as well as fault and notice messages in plain text, thereby supporting the user at every stage ofoperation. The liquid crystal display of the device can be turned in 90° stages.Depending on the orientation of the device, this makes it easy to operate the device and read the measuredvalues.Functions:• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as currentdisplay; or for PROFIBUS PA as graphic display of the standardized value of the AI Block; for FOUNDATIONFieldbus as graphic display of the transducer output in relation to the set pressure range.• Three keys for operation• Simple and complete menu guidance as parameters are split into several levels and groups• Each parameter is given a 3-digit ID number for easy navigation• Possibility of configuring the display to suit individual requirements and preferences, such as language,alternating display, contrast setting, display of other measured values such as sensor temperature etc.• Comprehensive diagnostic functions (fault and warning message etc.)P01-Mxxxxxxx-07-xx-xx-xx-002E+–SymbolOperating keysValueDevice tagMeasured value displayUnitBargraphOperating menuParameter with selection listFreely editable parameterDirectAccessCodeValue thatcan beeditedSelectionoptionsHeader lineInformationlineMain line
  49. 49. Deltapilot M FMB50/51/52/53Endress+Hauser 49Operating keys and elements located on the electronic insertOnsite operationP01-Mxxxxxxx-19-xx-xx-xx-001HART electronic insert1 DIP switch for locking/unlocking parametersrelevant to the measured value2 DIP switch for switching damping on/off3 DIP switch for alarm current SW / Alarm Min(3.6 mA)4 DIP switch only for Deltabar M5 Slot for optional local display6 Green LED to indicate successful operation7 Operating keys for lower range value (zero)and upper range value (span)P01-Mxxxxxxx-19-xx-xx-xx-013PROFIBUS PA electronic insert1 DIP switch for locking/unlocking parametersrelevant to the measured value2 DIP switch for switching damping on/off3/4/5 Not used6 DIP-switch for hardware address7 DIP-switch for bus address SW / HW8 Slot for optional local display9 Operating key for position zero adjustment orreset (Zero)10 Green LED to indicate successful operationP01-Mxxxxxxx-19-xx-xx-xx-014FOUNDATION Fieldbus electronic insert1 DIP switch for locking/unlocking parametersrelevant to the measured value2 DIP switch for switching damping on/off3 DIP-switch for simulation mode4/5 Not used6 Slot for optional local display7 Green LED to indicate successful operation8 Operating key for position zero adjustment orreset (Zero)➂➁➅onoffSW/P2=HighSW/AlarmminSW/Ödamping1 2 3 4 5➃➄➀➆ onoffDisplayZeroSpanSW/P2=HighdeltaponlySW/AlarmminSW/Ödamping➂➁➅onoffSW/P2=Highdamping1 2 3 4 5➃➄➀➇on:P2=delta ponly High off:SW12345off:SWon:Öonoffdampnot usedAddressSWHWZeroonoffDisplay➆910SW/Ö➂➁➅onoffSW/P2=HighSimulationSW/Ödamping1 2 3 4 5➃➄➀➆➇ onoffDisplayZerosimulationTMFOUNDATIONSW/P2=HighSW/ÖdampingdeltaponlyFunction Operation with operating keys and operating elements on the electronic insertAnalog electronics HART PROFIBUS PA FOUNDATION FieldbusPosition adjustment (zero point correction) X X X XSetting lower range value and upper range value -reference pressure present at the deviceX X -- --Device reset X X X XLocking and unlocking parameters relevant to themeasured value-- X X XValue acceptance indicated by the green LED X X X XSwitching damping on and off X X X XFunction Operation via displayAnalog electronics HART PROFIBUS PA FOUNDATION FieldbusPosition adjustment (zero point correction) -- X X XSetting lower range value and upper range value -reference pressure present at the device-- X X XDevice reset -- X X XLocking and unlocking parameters relevant to themeasured value-- X X XValue acceptance indicated by the green LED -- -- -- --Switching damping on and off -- X X X
  50. 50. Deltapilot M FMB50/51/52/5350 Endress+HauserRemote operation All software parameters are accessible depending on the position of the write protection switch on the device.HARTRemote operation via:• FieldCare (see "Hardware and software for onsite and remote operation" section → ä 51 ff) withCommubox FXA195 (see "Hardware and software for onsite and remote operation" section → ä 51 ff)• Field Xpert SFX100. Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauserbased on Windows Mobile. It communicates via wireless with the optional VIATOR Bluetooth modemconnected to a HART device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520.Field Xpert also works as a stand-alone device for asset management applications. For details refer toBA00060S/00/EN.PROFIBUS PARemote operation via:• FieldCare (see "Hardware and software for onsite and remote operation" section → ä 51 ff)– Profiboard: For connecting a PC to PROFIBUS– Proficard: For connecting a laptop to PROFIBUSFOUNDATION FieldbusRemote operation via:• Use an FF-configuration program for example NI-FBUS Configurator, to– connect devices with "FOUNDATION Fieldbus signal" into an FF-network– set FF-specific parametersOperation with NI-FBUS Configurator:The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and aschedule based on the fieldbus concepts.You can use the NI-FBUS Configurator to configure a fieldbus network as follows:– Set block and device tags– Set device addresses– Create and edit function block control strategies (function block applications)– Configure vendor-defined function and transducer blocks– Create and edit schedules– Read and write to function block control strategies (function block applications)– Invoke Device Description (DD) methods– Display DD menus– Download a configuration– Verify a configuration and compare it to a saved configuration– Monitor a downloaded configuration– Replace a virtual device by a real device– Save and print a configuration• FieldCare (see "Hardware and software for onsite and remote operation" → ä 51 ff)– NI PCMCIA-FBUS series 2 to connect a laptop to FF.Note!For further information please contact your local Endress+Hauser Sales Center.
  51. 51. Deltapilot M FMB50/51/52/53Endress+Hauser 51Hardware and software foronsite and remote operationCommubox FXA195For intrinsically safe HART communication with FieldCare via the USB interface. For details refer toTI00404F/00/EN.Field Xpert SFX100Compact, flexible and robust industry handheld terminal for remote parametrization and measured valueinspection via the HART current output (4-20mA).For details refer to Operating Instructions BA00060S/04/EN.FieldCareFieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you canconfigure all Endress+Hauser devices as well as devices from other manufacturers that support the FDTstandard.FieldCare supports the following functions:• Configuration of transmitters in offline and online mode• Loading and saving device data (upload/download)• Documentation of the measuring pointConnection options:• HART via Commubox FXA195 and the USB port on a computer• PROFIBUS PA via segment coupler and PROFIBUS interface card• FOUNDATION Fieldbus via NI interface cardFor further information ➝ www.endress.com
  52. 52. Deltapilot M FMB50/51/52/5352 Endress+HauserCertificates and approvalsCE mark The device meets the legal requirements of the relevant EC directives.Endress+Hauser confirms that the device has been successfully tested by applying the CE mark.Ex approvals • ATEX• FM• CSA• Also combinations of different approvalsAll explosion protection data are given in separate documentation which is available upon request. The Exdocumentation is supplied as standard with all devices approved for use in explosion hazardous areas.→ ä 66 ff, "Safety Instructions" and "Installation/Control Drawings" sections.Suitability for hygienicprocessesPharma (CoC) Certificate of Compliance (CoC) (according to ASME BPE-2007)See "Ordering information", → ä 53 ff, feature 590 "Additional Option:", option"LW".Functional safety SIL The Deltapilot M with 4 to 20 mA output signal has been developed to assessed and certified by TÜV NORDCERT as per IEC 61508 Edition 2.0 and IEC 61511. These devices can be used to monitor the process leveland pressure up to SIL 2. For a detailed description of the safety functions with Deltapilot M, settings andfunctional safety data, see the "Functional safety manual - Deltapilot M" SD00347P. Ordering Information→ ä 53 ff, feature 590 "Additional Approval:" version LA "SIL".Marine approval • DNV (Det Norske Veritas)• GL (German Lloyd)Standards and guidelines DIN EN 60770 (IEC 60770):Transmitters for use in industrial process control systemsPart 1: Methods for inspection and routine testingDIN 16086:Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure measuringinstruments,concepts, specifications on data sheetsEN 61326 series:EMC product family standard for electrical equipment for measurement, control and laboratory use.Pressure Equipment Directive(PED)The Deltapilot M device corresponds to Article 3 (3) of the EC directive 97/23/EC (Pressure EquipmentDirective) and has been designed and manufactured according to good engineering practice.Drinking water approval • KTW certificate• NSF 61 approval• ACS approvalNorth-American practice forinstallation of process sealsEndress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or dual sealdevices with annunciation, allowing the user to waive the use and save the cost of installing external secondaryprocess seals in the conduit as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1(CEC). These instruments comply with the North-American installation practice and provide a very safe andcost-saving installation for pressurized applications with hazardous fluids.Further information can be found in the control drawings of the relevant devices.The Deltapilot M is suitable for use in hygienic processes.Overview of permitted process connections from → ä 30.Many versions meet the requirements of 3A-Sanitary Standard No. 74 andare certified by the EHEDG.Suitable fittings and seals must be used for hygienic design in accordancewith 3A and EHEDG specifications.Note!Gap-free connections can be cleanedwithout residue using the usual cleaning methods.TYPE ELFebruary 201074 -74 -
  53. 53. Deltapilot M FMB50/51/52/53Endress+Hauser 53Ordering informationFMB50 This overview does not mark options which are mutually exclusive.10 Approval:AA For non-hazardous areasBA ATEX II 1/2G Ex ia IIC T6BB ATEX II 1/2D Ex t IIICBD ATEX II 3G Ex nA IIC T6BE ATEX II 2G Ex ia IIC T6BG ATEX II 3G Ex ic IIC T6B1 ATEX II 1/2G Ex ia IIC T6 + ATEX II 1/2D, Ex iaDIA IEC Ex ia IIC T6 Ga/GbID IEC Ex t IIIC Da/DbIE IEC Ex ic IIC T6 GcI1 IEC Ex ia IIC T6 Ga/Gb+Ex ia IIIC Da/DbNA NEPSI Ex ia IIC T6TA TIIS Ex ia IIC T4CA CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, CSA C/US IS Cl.I Div.2 Gr.A-D, Ex ia, C: Zone 0,1,2/US: Zone 0,1,2,20,21,22CC CSA C/US Cl.II, III Div.1 Gr.E-G, US: Zone 21,22CD CSA General PurposeFA FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, FM NI Cl.I Div.2 Gr.A-D, FM IS: zone 0,1,2,20,21,22/FM NI: zone 2FC FM DIP Cl.II, III Div.1 Gr.E-G, zone 21,22FD FM NI Cl.I Div.2 Gr.A-D, Zone 28C ATEX II Ex ia + FM/CSA IS ATEX II 2G Ex ia IIC T6 + FM/CSA IS CL.I Div. 1 Gr.A-D, FM/CSA: Zone 1,299 Special version20 Output:2 4-20mA HART3 PROFIBUS PA4 FOUNDATION Fieldbus9 Special version30 Display, operation1 LCD, push buttons on display/electronics2 W/o LCD, push buttons on electronics9 Special version40 Housing:I F31 aluminumJ F31 aluminum, glass windowQ F15 stainless steel HygieneR F15 stainless steel Hygiene, glass, windowS F15 stainless steel Hygiene, plastic, windowY Special version50 Electrical connection:A Gland M20, IP66/68 NEMA4X/6PC Thread G½, IP66/68 NEMA4X/6PD Thread NPT½, IP66/68 NEMA4X/6PI Connector M12, IP66/67, NEMA4X/6PM Connector 7/8", IP66/68, NEMA4X/6PP Connector Han7D, 90deg, IP65S PE Cable 5m, IP66/68 NEMA4X/6P + pressure compensation via cableV Valve connector ISO4400 M16, IP64Y Special version70 Sensor range:1C 100mbar/10kPa/1.5psi relative, 1mH2O/3ftH2O/40inH2OOverload: 4bar/400kPa/60psi1F 400mbar/40kPa/6psi relative, 4mH2O/13ftH2O/160inH2OOverload: 8bar/800kPa/120psi1H 1.2bar/120kPa/18psi relative, 12mH2O/40ftH2O/480inH2OOverload: 24bar/2.4MPa/350psi1M 4bar/400kPa/60psi relative, 40mH2O/133ftH2O/1600inH2OOverload: 24bar/2.4MPa/350psi1P 10bar/1MPa/150psi relative, 100mH2O/333ftH2O/4000inH2OOverload: 40bar/4MPa/600psi99 Special version

×