5.2.c gen basics

1,761 views

Published on

Published in: Education
0 Comments
1 Like
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
1,761
On SlideShare
0
From Embeds
0
Number of Embeds
2
Actions
Shares
0
Downloads
138
Comments
0
Likes
1
Embeds 0
No embeds

No notes for slide

5.2.c gen basics

  1. 1. Generator & Exciter BasicsWhitby Hydro Energy Services Corporation: Engineering & Construction ServicesThe relationship between magnetism and electrical the rate at which the conductor crosses the magneticcurrent was discovered and documented by Oerstad in field. The induced voltage has a polarity that will1819. He found that if an electric current was caused to oppose the change causing the induction – Lenz’s law.flow through a conductor that a magnetic field was This natural phenomenon is known as Generatorproduced around that conductor. Action and is described today by Faraday’s Law ofIn 1831, Michael Faraday discovered that if a conductor Electro Magnetic Induction: (Vind = ∆Ø/∆t), whereis moved through a magnetic field, an electrical voltage Vind = induced voltage, ∆Ø = change in flux density,is induced in the conductor. ∆t = change in timeThe magnitude of this generated voltage is directly All rotary generators built today use the basic principlesproportional to the strength of the magnetic field and of Generator Action.GENERATOR ACTIONSTHE PHYSICS OF GENERATOR ACTION THE ELEMENTARY AC GENERATOR The elementary ac generator consists of a conductor (or loop of wire) in a magnetic field (usually produced by an electromagnet). The two ends of the loop are connected to slip rings and they are in contact with two brushes. When the loop rotates it cuts magnetic lines of force, first in one direction and then the other. In the first half turn of rotation, a positive current is produced and in the second half of rotation produces aTHE BASIC GENERATOR negative current. This completes one cycle of ac generation.
  2. 2. ASP MODEL COMPONENTSDEVELOPMENT OF THE SINE WAVE THREE PHASE VOLTAGEAt the instant the loop is in the vertical position, the Three phase voltage is developed using the sameloop sides are moving parallel to the field and do not cut principles as the development of single phase voltage.magnetic lines of force. Three (3) coils are required positioned 120 electrical In this instant, there is degrees apart. no voltage induced in A rotating magnetic the loop. As the loop field induces voltage rotates, sides will cut in the coils which the magnetic lines of when aggregated force inducing voltage produce the familiar three in the loop. phase voltage pattern. When the loop is in the horizontal position, maximum voltage is induced. The rotation of the coil through 360 degrees results in an ac sine wave outputTYPES OF GENERATORSEssentially, there are two basic types of generators:• DC generators• AC generators - Asynchronous (Induction) generators - Synchronous generatorsINDUCTION GENERATORSThe induction generator is nothing more than an The induction generator requires one additional iteminduction motor driven above its synchronous speed by before it can produce power – it requires a source ofan amount not exceeding the full load slip the unit leading VAR’s for excitation. The VAR’s may be suppliedwould have as a motor. by capacitors (this requires complex control) or from the utility grid.Assuming a full load slip of 3%, a motor with asynchronous speed of 1200 rpm would have a full load Induction generators are inexpensive and simplespeed of 1164 rpm. This unit could also be driven by an machines, however, they offer little control over theirexternal prime mover at 1236 rpm for use as an output. The induction generator requires no separateinduction generator. DC excitation, regulator controls, frequency control or governor.
  3. 3. ASP MODEL COMPONENTSSYNCHRONOUS GENERATORSSynchronous generators are used because they offer The magnitude of the AC voltage generated is controlledprecise control of voltage, frequency, VARs and WATTs. by the amount of DC exciting current supplied to the field.This control is achieved through the use of voltage If “FIXED” excitation were applied, the voltageregulators and governors. magnitude would be controlled by the speed of theA synchronous machine consists of a stationary rotor (E=4.44fnBA), however, this would necessitate aarmature winding (stator) with many wires connected in changing frequency!series or parallel to obtain the desired terminal voltage. Since the frequency component of the power system isThe armature winding is placed into a slotted laminated to be held constant, solid state voltage regulators orsteel core. A synchronous machine also consists of a static exciters are commonly used to control the fieldrevolving DC field - the rotor. current and thereby accurately control generatorA mutual flux developed across the air gap between the terminal voltage.rotor and stator causes the interaction necessary to The frequency of the voltage developed by theproduce an EMF. As the magnetic flux developed by the DC generator depends on the speed of the rotor and thefield poles crosses the air gap of the stator windings, a number of field poles. For a 60 Hz system, Frequency =sinusoidal voltage is developed at the generator output speed(rpm)*pole pairs/60.terminals. This process is called electromagnetic induction.GENERATOR PARTS & FUNCTIONGenerator Frame: Provides the structural strength and Stator Coil End Turns: Formed when coils leave one slot rigidity for the generator and serves as a housing to in a stator core and are returned to a different slot guide cooling air flow Terminal Leads: Serve to conduct the three phaseInner End Shield: Is a baffle used to form a path for voltage and current flow from the generator stator to cooled air the external systemGenerator Fan: Provides continuous circulation of cooling air STATOR DESIGNRotating Field: A magnetic field which induces AC The stator frame is fabricated from mild steel plate, voltage in the stator windings forming a rigid structure. The core is built up fromCollector Rings: Provide a connection and path for DC segmental laminations of grain oriented silicon steel for power into the rotating field windings low loss and high permeability. Radial ventilating ductsMain Coupling: Is the connection to the drive shaft are formed at intervals along the core by steel spacers.Generator Coolers: Remove heat from the generator The core is hydraulically pressed during the assembly cooling air operation to ensure uniform compaction. When finished, it is clamped between heavy steel end plates. The statorStator Core: Houses the stationary windings and forms winding is usually a two layer conventional lap-wound a magnetic path necessary for induced voltages design. The insulation is class F (155C)Air Gap: Is the radial clearance between the rotating field and the stator core
  4. 4. SALIENT VS CYLINDRICAL ROTORThere are two (2) basic rotor structures used, depending Salient pole rotors are too weak mechanically andon speed. develop too much wind resistance and noise to be used in large, high speed machines.For low speed machines, such as hydraulic turbines, arelatively large number of poles are required to produce Cylindrical rotor machines have a relatively uniform airrated frequency, hence a rotor with salient poles is well gap, therefore, it can be assumed that a cylindrical rotorsuited to this application. Such rotors often have field will produce a uniform air-gap flux regardless ofdamper windings (amortisseurs) in the form of copper angular direction.or brass rods embedded in the pole face, they are This cannot be said of a salient -pole machine as the air-intended to dampen out speed oscillations. gap is much larger between the poles (i.e. along theFor high speed machines, such as steam and gas quadrature axis) than it is at the centres of the polesturbines, a relatively small number of poles ( 2 to 4 ) are (i.e. on the direct axis).required to produce rated frequency, hence a cylindricalrotor is well suited to this application.GENERATOR COOLINGDepending upon rating and design, the generator stator AIR COOLED GENERATORScore and windings may be cooled by air, oil, hydrogen orwater. For direct cooled generators, the coolant is in Air cooled generators are produced in two (2) basicdirect contact with the heat producing members such as configurations: open ventilated (OV) & totally enclosedthe stator winding. For indirect cooled generators, the water -to-air-cooled (TEWAC)coolant cools the generator by relying on heat transfer In the OV design, air is drawn from outside the unitthrough the insulation. through filters, passes through the generator and isFor any generator, a failure of the cooling system can discharged outside the generator.result in rapid deterioration of the stator core In the TEWAC design, air is circulated within thelamination insulation and/or stator winding conductors generator passing through frame mounted air-to-waterand insulation. heat exchangers.REASONS WHY GENERATORS FAILFOREIGN OBJECT DAMAGE STATOR WINDING VIBRATIONProblem: Objects can come from external sources or Problem: Primarily a design related problem that failure of internal components, they can pick up energy affects large (>300Mw) generators which have from the spinning rotor and do extensive damage insufficient end winding bracing to limit the movement of end turns.Prevention: Inspect on a regular basis all internal parts that are prone to failure or can be dislodged. Prevention: Proper bracing of the end winding is Inspection tests can be a combination of visual required to limit motion caused by steady state and inspection along with ultrasonic or magnetic particle transient electromagnetic forces. tests on rotating components
  5. 5. ROTOR WINDING DISTORTION CONTAMINATIONProblem: Rotor winding distortion caused by poor end Problem: For air cooled machines, dirt and dust cause turn blocking support design or by foreshortening of tracking which can lead to electrical ground faults. the rotor coils. Foreshortening is caused by thermal Prevention: Inspect air filterson a regular basis , the forces which compress rotor coils. filters must be checked and cleaned regularly.Prevention: Proper design of rotor coils and bracing to Polarization index (PI) tests give a good indication of support the coils under axial load is essential. overall cleanliness of the rotor winding. Rotors should be tested for turn to turn shorts at operating speed. ROTOR VIBRATIONSTATOR WINDING VIBRATION Problem: There are many causes, turn-to-turn shorts, rotor coil foreshortening, electrical grounds,Problem: Primarily a design related problem that mechanical imbalances, overheating, etc. affects large (>300Mw) generators which have Prevention: Comprehensive vibration measuring is effective insufficient end winding bracing to limit the combined with a regular maintenance program. movement of end turns.Prevention: Proper bracing of the end winding is STATOR WEDGE LOOSENESS required to limit motion caused by steady state and transient electromagnetic forces. Problem: When stator wedges become loose, coils can vibrate causing insulation wear leading to groundOVERHEATING faults or turn-to-turn shorts. Prevention: Inspect on a regular basis tightness ofProblem: Overheating of the rotor or stator can lead to wedge blocks. insulation failure, shorting of turns and ground faults. Overheating can result from blocked ventilation passages caused by shifting insulation STATOR CORE DAMAGE components or slot wedges. Problem: Stator core looseness can occur over time asPrevention: Inspect on a regular basis to ensure all rotor pre-tensioned through bolts relax. A loose core wedges are "locked" in place preventing migration results in insulation wear to coils and laminations and thus blocking of cooling passages. resulting in hot spots and core-to-coil failures. Prevention: Inspect bolt tightness on a regular basis.GENERATOR MAINTENANCEThe following tests which should be carried out annually B) INSPECTION ON STATIC EXCITERin addition to vendor recommended maintenance. • Remove exciter end cover • Examine condition of diode carrierA) INITIAL GENERATOR TEST • Examine exciter armature/stator for contamination • Examine exciter armature/stator for winding wear• “Megger” rotor winding • Check pmg magnets for contamination• “Megger” exciter armature winding• “Megger” exciter field winding• Complete polarization index (pi) on main stator• Check bearing insulation
  6. 6. C) ELECTRICAL CONTROL/PROTECTION PANEL E) ROTOR EARTH FAULT PROTECTOR• Visually inspect external surfaces of panel • Carry out static checks to confirm operation of• Complete insulation resistance checks of panel wiring detector• Check function of all relays • Carry out functional check to confirm operation of• Check all fuses detector• Check all lamps• Check operation of all switches F) SLIP-RINGS AND BRUSH-GEAR (IF FITTED)• Check operation of panel heaters • Check all brushes for grade and length• Run generator; recalibrate avr • Check condition of brush holders/mountings• Secondary inject all protective relays • Check that spring tensions are correct • Check conditions of slip-ringsD) LINESIDE CUBICLE/NEUTRAL CUBICLE • Check mechanical run-out of slip-rings• Check condition of main generator terminal bushings • Check cooler and leakage alarms• Check all busbar/cable connections• Check ct/vt connections• Check condition of neutral earthing transformer• Check condition of neutral earthing resistor• Check operation of cubicle heaters• Clean all post insulators and examine for damage• Carry out insulation checkEXCITOR BASICSThe exciter is the "backbone" of the generator control The amount ofsystem. It is the power source that supplies the dc excitation requiredmagnetizing current to the field windings of a by a generator forsynchronous generator thereby ultimately inducing ac a particular loadvoltage and current in the generator armature is defined by the "generatorTwo basic kinds of excitors saturation curve".• Rotating (Brush and brushless)• Static exciters (Shunt and series)The amount of excitation required to maintain theoutput voltage constant is a function of the generator The amount ofload. As the generator load increases, the amount of power that aexcitation increases. generator can deliver is defined• Reactive lagging pf loads require more excitation than by the "generator unity pf loads capability curve".• Leading pf loads require less excitation than unity pf loads
  7. 7. ROTATING EXCITERS BRUSHLESS EXCITERSBrushless: do not require slip-rings, commutators, brushes and are practically maintenance free.Brush Type: require slip-rings, commutators and brushes and require periodic maintenanceSTATIC EXCITERSStatic excitation means no moving parts. It providesfaster transient response than rotary excitersShunt Type: operating field power from generator output voltageSeries Type: operating field power from generator output voltage & currentEXCITERS PRINCIPALS OF AUTOMATIC VOLTAGE CONTROL Voltage transformers provide signals proportional to line voltage to the avr where it is compared to a stable reference voltage. The difference (error) signal is used to control the output of the exciter field. For example, if load on the generator increases, the reduction in output voltage produces an error signal which increases the exciter field current resulting in a corresponding increase in rotor current and thus generator output voltage. Due to the high inductance of the generator field windings, it is difficult to make rapid changes in field current. This introduces a considerable "lag" in the control system which makes it necessary to include a stabilizing control to prevent instability and optimize the generator voltage response to load changes. Without stabilizing control, the regulator would keep increasing and reducing excitation and the line voltage would continually fluctuate above and below the required value. Modern voltage regulators are designed to maintain the generator line voltage within better than +/- 1% of nominal for wide variations of machine load.
  8. 8. GENERATOR OPERATION PARALLEL GENERATORS (INFINITE BUS)When a generator is used to supply power, it can be When a machine operates in parallel with a poweroperated in the following modes: system, the voltage and frequency will be fixed by• isolated (sometimes referred to as island) mode or the system.• parallel with a system or other machines. The voltage regulator no longer controls the generatorIn both cases, the power (WATTs) supplied at the output voltage.generator terminals is a function of the fuel supplied to The fuel supply to the prime mover which is controlledthe prime mover, which is controlled by the governor. by the governor determines the power which is supplied by the generator .ISLAND OPERATION The generator excitation determines the internal emf of the machine and therefore affects the power factor.The machine speed is determined by the load and When excitation is increased above the level to achievefuel supply. nominal no load voltage, rather than the voltageThe generator voltage is determined by the excitation. increasing, the reactive current (vars) flowing from theFor example, an increase in load will have two effects: generator to the load increases resulting in a lagging pf condition on the generator.• Speed will initially fall because the energy being supplied by the fuel is less than that required by the When the excitation is reduced below the level to load. The speed reduction is detected by the governor achieve nominal no load voltage, rather than the voltage which opens the fuel valve by the required amount to decreasing, the reactive current (vars) flowing to the maintain the required speed. generator from the load increases resulting in a leading pf condition on the generator.• Voltage will initially fall, the reduction is detected by the AVR which increases the excitation by the amount required to maintain output voltage. For more information contact: Kevin Whitehead, Director - Engineering & Construction Services (905) 668-5878 or kwhitehead@whitbyhydro.on.ca

×