Coupling between
   transmission
underground cables
   and pipelines



   Alain Xémard EDF R&D
Object of this type of studies

                      Safety
                         • In normal operating condition, ind...
Examples of pipeline damages due
        to corrosion




3   12/05/2009   THEMIS
Phenomena involved in case of
        underground transmission systems

                 No capacitive coupling because of...
Evaluation of the inductive coupling


            Application of the line theory at 50 / 60 Hz ;



             Use of E...
Evaluation of the inductive coupling
             Processing of the calculation

                  1 – Determination of th...
Determination of segments for
        which the line theory can be applied


                                             ...
Example of Application


                                     Underground
                                     line       ...
Description of the configuration


                 the 225 kV underground system is constituted of 3 single core
        ...
Modelling used to represent the
         system


          Pi-exact model to represent the cable in parallel with the pip...
Example of results

                            Induced voltage versus the type of coating

                  coating     ...
Perspectives


         A toolbox based on EMTP-RV, CRINOLINE, has been developed
         by a group of partners to facil...
Upcoming SlideShare
Loading in …5
×

Edf R&D Xemard Coupling Between Transmission Underground Cables And Pipelines

1,449 views

Published on

Published in: Technology, Business
  • Be the first to comment

Edf R&D Xemard Coupling Between Transmission Underground Cables And Pipelines

  1. 1. Coupling between transmission underground cables and pipelines Alain Xémard EDF R&D
  2. 2. Object of this type of studies Safety • In normal operating condition, induced voltage limited by national standards to 50 / 60 V. • Higher induced voltage accepted in case of fault on the transmission system. Corrosion of pipelines • Low level voltage induced by transmission systems disturbs cathodic protection of pipelines and might lead to corrosion. 2 12/05/2009 THEMIS
  3. 3. Examples of pipeline damages due to corrosion 3 12/05/2009 THEMIS
  4. 4. Phenomena involved in case of underground transmission systems No capacitive coupling because of the screening effect of the earth against electrical field. Inductive coupling ; voltage induced by the magnetic field generated by the transmission system. It appear both during normal operating condition and during faults. Conductive coupling ; fault current flowing in the ground during a fault create a potential rise of the electrode and of the neighbouring soil. Coating of tower is subject of the potential difference between local earth voltage and pipe potential. 4 12/05/2009 THEMIS
  5. 5. Evaluation of the inductive coupling Application of the line theory at 50 / 60 Hz ; Use of EMTP-RV ; Difficulty : how to use the line theory when the underground cable and the pipeline are not strictly parallel. 5 12/05/2009 THEMIS
  6. 6. Evaluation of the inductive coupling Processing of the calculation 1 – Determination of the segments for which the line theory can be applied. 2 – Evaluation of the parameters of the line model for each segment (PI-Exact). 3 – Construction of the EMTP-RV design and simulation in the frequency domain. 6 12/05/2009 THEMIS
  7. 7. Determination of segments for which the line theory can be applied Inducing system Influence area p q r s t v u Q R S T U V P Induced system 7 12/05/2009 THEMIS
  8. 8. Example of Application Underground line Charge Thevenin equivalent of the source pipeline 8 12/05/2009 THEMIS
  9. 9. Description of the configuration the 225 kV underground system is constituted of 3 single core cables single point grounded at the end of the cable. The pipeline is located 10 m from the underground cable, The length of parallelism is 600 m. The pipeline has a depth of 1 meter and a diameter of 300 mm ; permeability of 300. 9 12/05/2009 THEMIS
  10. 10. Modelling used to represent the system Pi-exact model to represent the cable in parallel with the pipeline Use of find steady state solution at 50 Hz 10 12/05/2009 THEMIS
  11. 11. Example of results Induced voltage versus the type of coating coating  (.m) Tan () Induced voltage (V / kA / kV) Bitumen coated 0.2 106 0.36 103 1.1 pipeline Polyethylene coated 1 108 0.71 2.1 pipeline Values not to be exceeded for the voltage according to CIGRE 290 : 10 Vrms if soil resistivity is higher than 25 Ohm.m ; 4 Vrms if soil resistivity is lower than 25 Ohm.m. 11 12/05/2009 THEMIS
  12. 12. Perspectives A toolbox based on EMTP-RV, CRINOLINE, has been developed by a group of partners to facilitate the calculation of voltage induced on pipelines and telecommunication cables. This group of partners is constituted of : Hydro-Québec, CEATI (representing US and Canadian utilities), RTE, ELIA, GRT Gaz, France Telecom and EDF. The goal of CRINOLINE is to calculate directly the induced voltage using the characteristics of both inducing and inducing systems With a software internationally recognized. 12 12/05/2009 THEMIS

×