Certificação de Cabeamento Estruturado

Richard Landim
Product Sales Specialist
Fluke Networks
AGENDA

•
•
•
•
•
•
•
•
•

Introdução da Fluke Networks
Tipos de Certificação
Metodologias de Certificação
Equipamentos de...
$18B Science & Technology Company
 Danaher named #1 by 2011
Test & Measurement World Magazine
 Market Size: $12B &
Growth: 5-7%
 Sales: $3.4B

Test &
Mea...
www.flukenetworks.com
FLUKE NETWORKS
Data Communications Installers

Private Network Owners… Network & IT Managers

Copper and fiber premise cab...
Por que Certificar?
Ter certeza de que o cabeamento instalado atende os
requesitos pelo qual está sendo pago.
 Conector C...
Razões simples para uma Certificação…
Tipos de Cerificações
Cobre
•TIA
•ISO
•Balance Measurements
•Aus-NZ
•China
•EN
•JIS
•Korea
•Russia
•Taiwan
•Application
•R...
CERTIFICÃÇÃO DE NÍVEL 1 (OLTS)
Horizontal Cables
TR

50/125 m cabling

X X

X

104 m backbone cable
3 m patch cord
102 m ...
CERTIFICÃÇÃO DE NÍVEL 2 (OTDR)
Horizontal Cables

TR

X X

MC

X

X
Backbone Cables

OTDR
characterizes link
details
CERTIFICÃÇÃO DE NÍVEL 2 (OTDR)
PARA FLUKE NETWORKS

EventMap

Event Table

13
VERSIV
A PLATAFORMA DE TESTE QUE FAZ TUDO

DSX-5000 CableAnalyzer
Twisted Pair Certification
& Troubleshooting

Certifiber...
VERSIV
A PLATAFORMA DE TESTE QUE FAZ TUDO

DSX-5000 CableAnalyzer
Twisted Pair Certification
& Troubleshooting
Certifiber ...
VERSIV
A PLATAFORMA DE TESTE QUE FAZ TUDO
TEMPOS DE TESTE
•
•
•
•

Cat 5e / Class D ≈ 9 segundos
Cat 6 / Class E ≈ 9 segundos
Cat 6A / Class EA ≈ 10 segundos
Class ...
CAT. 6A TEST: COMPARING DTX & DSX

DONE
LEVEL V ACCURACY
CLASS FA 1 GHZ - LEVEL V ACCURACY
IEC-61935-1 Ed.3 :

•

•

To those customer that want top performance, Class FA
manufact...
FEITO PARA ALIEN CROSSTALK

•

Sem módulos adicionais

- O DSX CableAnalyzer é o PRIMEIRO TESTADOR DE CAMPO a ter
o teste ...
PS ANEXT

• Power Sum Alien Near End Crosstalk
CAMERAS IP E ACCESS POINTS
•

The far end is terminated with an RJ45 plug

No warning of different adapters, unlike DTX Ca...
NEW CABLE TYPES
•

Adopting ISO/IEC (US) naming

U/UTP
- Individual pairs are unshielded
- No overall shield
F/UTP
- Indiv...
READY FOR TODAY’S AND TOMORROW’S
REQUIREMENTS

Shield integrity

Balance measurements:

• Now it’s just shield continuity ...
SHIELD INTEGRITY
•
•

ALL wire mappers would think the shield was connected
Grounding of two racks makes this happen

•
•
...
SHIELD INTEGRITY
•

Shield is open at one end due to incorrect termination
SHIELD INTEGRITY
•

Even when the two connectors are grounded together
SHIELD INTEGRITY
•

Other Wire Maps testers will show this connected
DESBALANCEAMENTO RESISTIVO
•

Difference in Resistance between the pair
1.87 Ω

1.85 Ω

Resistance = 3.7 Ω
Resistance Unba...
TESTES ADICIONAIS PARA POE
•

Works as long as the resistance unbalance is within xx Ω
Desbalancemaneto Resistivo - Use teste para
identificar CCA

• Aluminum has a higher resistance than Cu,
and is less expen...
NOVOS LIMITES DE TESTE
•

New folder Balance Measurements
Testes de Balanceamento – TCL e ELTCL
O Balanceamento Elimina a Interferência
TCL (TRANSVERSE CONVERSION LOSS)
•

Transverse Conversion Loss is the ratio (in dB) of a
common-mode voltage measured on a...
TESTANDO FIBRAS
INSPECIONE ANTES DE INICIAR OS TESTES
•

Optional fiber camera to inspect end
face of fiber connectors
A CLEAN CONNECTOR
CONNECTOR WITH A FINGER PRINT
THIS PART OF THE PRESENTATION IS ONLY FOR
THOSE >17 YEARS OLD
NOTICE THE RING WHERE THE CONTACT
OCCURRED IN THE CENTER
CLEANED AND INSPECTED
PROCEDIMENTO OFICIAL DA AT&T
•

A AT&T considera 6
procedimentos de limpeza
antes de poder condenar o
conector a troca.
100000

Velocidades Maiores
40000

Distâncias menores
100

10

52

266100

10000
1000

E-SR10

16

Fibre
Fibre
Channel
Cha...
Desempenho de fibras para DATACENTERS
Aplicação

Velocidade

Norma

Fibra Padrão

Distancia

Perda Máxima

Ethernet

10 Mb...
AJUSTANDO A REFERÊNCIA
•
•
•

Now the units have warmed up
sufficiently
Press SET REF
RUN WIZARD will walk you through
the...
RODANDO O TESTE
• Change back to
Main Meter (2)  (6) Remote Source
Main Source (3)  (7) Remote Meter

• We run 3 tests …...
REDUZINDO A INCERTEZA NO MULTIMODO
•

Encircled Flux (EF) is the final piece in the puzzle to reducing
measurement uncerta...
FORMA ERRADA DE FAZER A REFERÊNCIA

•

Wrong way!

? dB

•

Issues
- You have no idea what the loss is in the adapter
- Wh...
Inspecione e limpe os cordões de referência e as portas dos
módulos do DTX antes
DISCONECTE APENAS NA PORTA DE ENTRADA “INPUT”
CONECTE UM BOM CORDÃO CONHECIDO AS UNIDADES
PRINCIPAL E REMOTA
EXECUTE O AUTOTEST

•

Se a perda for menor que 0.10 dB, você saberá que seu cordão
é bom

•

Salve este teste para ser ap...
DISCONECTE
O cassete tem de ser melhor que 2 adaptadores de 0.75 dB cada
≤0.75 dB

≤0.75 dB

300 m
≤ 1.05 dB

10GBASE-SR requisito é ...
•

Isso não funcionará para um DataCenter
≤0.75 dB

≤0.75 dB

300 m
≤ 1.05 dB
≤0.75 dB

≤0.75 dB

10GBASE-SR requesito é 2...
TESTANDO FIBRAS ÚNICAS
•

•
•
•

Applications:
- Mostly Telecom
- FTTx
- CCTV
- Remote Sensors
SimpliFiber PRO was better ...
1.

2.
3.

Press on remote CertiFiber PRO the
button one and then hold until MM
led begins to blinkg Red/Green
Select Test...
SINGLE FIBER TESTING …
REMOTE SIMPLIFIBER PRO LIGHT SOURCE

1. Select Power Meter
/Light Source Mode
2. Select the remote
...
COMO OS TESTES DE OTDR SE
PARECEM?

61
OTDR
É o que eu estou
pensando?
OTDR EM AÇÃO

Perda

Distancia
O OTDR mede a energia refletida e
Não o nível de luz transmitida.

63
TYPICAL OTDR TEST RESULT

Reflection

Backscatter

64
REFLECTION EVENT

Connector

65
LOSS EVENT

Non-reflective event
Splice or severe bend

66
END EVENT

End of Fiber

67
MAPA DE FALHAS

• Facilidade no entendimento
• Ícones representativos.
•
•
•
•
•

Evento reflexivo bom
Evento reflexive ru...
Company Confidential

AJUDA CONTEXTUALIZADA
• Com um clique no ícone de ajuda obtenha informação
precisa sobre o problema ...
Company Confidential

PORQUE NÃO FAZER MELHOR!
Company Confidential

PORQUE NÃO FAZER MELHOR!
Something New
ProjX Project Management
Get to System Acceptance
(and Payment) faster!
A NEW PARADIGM FOR INFRASTRUCTURE CERTIFICATION
Multiple jobs, teams, testers, and requirements – a
single error can erode...
VERSIV WAS DESIGNED TO WORK DIFFERENTLY
THAN LEGACY TESTERS
Project
A

Installation
Floor 1

Testing
Floor 1

Installation...
PROJX MANAGEMENT SYSTEM
•
•
•
•

Easy to set up, minimize test limit errors/better manage multiple projects.
Create new pr...
PROJX
Planning

Setup

Test

Troubleshoot

Report

• Limitations of legacy cable testers
• ProjX to the rescue
• Examples
...
PROJX TO THE RESCUE

• Allows project setup to be stored, shared and
easily recalled
• Creates punch lists for failing lin...
PROJX TO THE RESCUE

• Powerful IN FIELD project & results
management
- Transfer
- Manage
- Move
IN FIELD PROJECT & RESULTS
MANAGEMENT
•

Transfer
- Copy and transfer projects & results
- Projects include project info a...
IN FIELD PROJECT & RESULTS
MANAGEMENT
•

Transfer
- Copy and transfer projects & results
- Projects include project info a...
SO YOU HAVE A FAILING LINK….

• Run Test
- Pass or Fail

Result

?
SO YOU HAVE A FAILING LINK….

• Run Test
- Pass or Fail
• Failing link options
- Repair and Test
Again
- Save and Fix Late...
SO YOU HAVE A FAILING LINK….

• Run Test
- Pass or Fail
• Failing link options
- Repair and Test
Again
- Save and Fix Late...
JOB COMPLETE PERCENTAGE
•

Percentage of job complete
- Includes all links: pass and fail

Hardrock
0✔ 0✖
0%
F1-001 ...
F1...
JOB COMPLETE PERCENTAGE
•

Percentage of job complete
- Includes all links: pass and fail

Hardrock
0✔ 0✖

Hardrock
47✔ 3✖...
JOB COMPLETE PERCENTAGE
•

•

Percentage of job complete
- Includes all links: pass and fail
Don’t lose cable ids when lin...
JOB COMPLETE PERCENTAGE
•

•
•

Percentage of job complete
- Includes all links: pass and fail
Don’t lose cable ids when l...
O QUE DEVO EXIGIR E COMO
DEVO ANALISAR?
CAT 5 BARATO OU CAT 3 CARO?
Use the least expensive cable that meets your needs
Cable, Connector or Installer?
HOW TO READ TEST RESULTS
HOW TO READ TEST RESULTS
CABOS CCA OU BIMETALICOS
CABOS CCA OU BIMETALICOS
TRADE-IN 2013
http://www.flukenetworks.com/tradeinbrasil
LINKRUNNER AT

TruePower™
PoE Loading

User configurable
AutoTest

IPv4 and IPv6
Support

Link at 10/100/Gig
on copper and...
TRUEPOWER™ POE

• Valida a performance PoE
solicitando carga até 25.5W
(802.3at)

• Carrega o circuito para stressar os
sw...
LINKRUNNER AT
Obrigado, Gracias, Thank you

richard.landim@flukenetworks.com
tel: (11) 4058-0198
A importância de se exigir a certificação de redes
A importância de se exigir a certificação de redes
A importância de se exigir a certificação de redes
Upcoming SlideShare
Loading in …5
×

A importância de se exigir a certificação de redes

730 views

Published on

Tipos de certificação em cobre e fibra, conforme normas técnicas aplicáveis;
Equipamentos de certificação de rede disponível no mercado;
Metodologias de certificação;
Como fazer uma certificação corretamente;
O que deve ser exigido do integrador contratado para instalar a rede de sua empresa;
O que analisar no relatório de certificação;
Qual a relação entre a garantia estendida do fabricante de cabeamento e certificação de rede;
Testando PoE - Power over Ethernet, com o equipamento LinkRunner AT.

PREPARE-SE PARA SE SUPERAR.
PREPARE-SE PARA O VERSIV.

Published in: Technology, Business
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total views
730
On SlideShare
0
From Embeds
0
Number of Embeds
2
Actions
Shares
0
Downloads
19
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

A importância de se exigir a certificação de redes

  1. 1. Certificação de Cabeamento Estruturado Richard Landim Product Sales Specialist Fluke Networks
  2. 2. AGENDA • • • • • • • • • Introdução da Fluke Networks Tipos de Certificação Metodologias de Certificação Equipamentos de Certificação Como fazer O que deve ser exigiido de uma instalação Como interpreter os relatórios Garantia estendida do fabricante Testanto PoE
  3. 3. $18B Science & Technology Company
  4. 4.  Danaher named #1 by 2011 Test & Measurement World Magazine  Market Size: $12B & Growth: 5-7%  Sales: $3.4B Test & Measurement Group  Focused on network test & analysis and service assurance & protection  Four segment leaders with great brands, innovative products and strong customers  Market: ~$5B @ ~8% Communication Test Platform Operating Company We know networks.  Leader in local area network analysis & media testing  Served Market Size: ~$1.5B & Market Growth: ~5%  Sales: ~$325M Strong Peers in the #1 T&M Company in the World
  5. 5. www.flukenetworks.com
  6. 6. FLUKE NETWORKS Data Communications Installers Private Network Owners… Network & IT Managers Copper and fiber premise cable certification and diagnostic instruments Network and application performance monitoring Private Network Owners… Network Techs & Engrs Communication Service Providers Portable network analysis and tools for all local network mediums Telco line technician tools and DSL line test instruments  Offering more ways to look at your networks than anyone else  Providing unique views into your networks you can’t get anywhere else  Delivering the right tools to every level of your network support organization Outfitting Network Pros & Heroes At Every
  7. 7. Por que Certificar? Ter certeza de que o cabeamento instalado atende os requesitos pelo qual está sendo pago.  Conector Cat 6a + Cabo Cat 6a + Instalador Cat 6a ≠ Cat 6a  Para ser pago pelo trabalho  O histórico nos mostra que redes Certificadas são mais rápidas  Erros de CRC/FCS causam re-transmissões  Componentes mais baratos podem ser considerados desde que atendam suas necessidades  Certificação é como um selo de qualidade para seu cabeamento 
  8. 8. Razões simples para uma Certificação…
  9. 9. Tipos de Cerificações Cobre •TIA •ISO •Balance Measurements •Aus-NZ •China •EN •JIS •Korea •Russia •Taiwan •Application •Rollover Fibra – Nível 1 Fibra – Nível 2 Fibra – Nível 1 •TIA •ISO •EN •China •JIS •Korea •Application Fibra – Nível 2 •TIA •ISO •EN •JIS •Application
  10. 10. CERTIFICÃÇÃO DE NÍVEL 1 (OLTS) Horizontal Cables TR 50/125 m cabling X X X 104 m backbone cable 3 m patch cord 102 m to the wall outlet MC X Backbone Cables 2.60 dB for 10GBase-SR per IEEE Power Meter 2.00 dB Light Source PMLS measures total link loss
  11. 11. CERTIFICÃÇÃO DE NÍVEL 2 (OTDR) Horizontal Cables TR X X MC X X Backbone Cables OTDR characterizes link details
  12. 12. CERTIFICÃÇÃO DE NÍVEL 2 (OTDR) PARA FLUKE NETWORKS EventMap Event Table 13
  13. 13. VERSIV A PLATAFORMA DE TESTE QUE FAZ TUDO DSX-5000 CableAnalyzer Twisted Pair Certification & Troubleshooting Certifiber Pro OLTS Fiber Loss Certification OptiFiber Pro OTDR Troubleshooting & Certification OneTouch AT Wi-Fi and Wired Network Analysis
  14. 14. VERSIV A PLATAFORMA DE TESTE QUE FAZ TUDO DSX-5000 CableAnalyzer Twisted Pair Certification & Troubleshooting Certifiber Pro OLTS Fiber Loss Certification OptiFiber Pro OTDR Troubleshooting & Certification OneTouch AT Wi-Fi and Wired Network Analysis
  15. 15. VERSIV A PLATAFORMA DE TESTE QUE FAZ TUDO
  16. 16. TEMPOS DE TESTE • • • • Cat 5e / Class D ≈ 9 segundos Cat 6 / Class E ≈ 9 segundos Cat 6A / Class EA ≈ 10 segundos Class FA ≈ 14 segundos • Teste de Malha adiciona 0,6 segundos ao teste selecionado • O primeiro teste após o equipamento ser inicializado adiciona 1,5 segundos pois envia dados sobre a calibração a unidade remota • WireMap AC adiciona 3 segundos
  17. 17. CAT. 6A TEST: COMPARING DTX & DSX DONE
  18. 18. LEVEL V ACCURACY
  19. 19. CLASS FA 1 GHZ - LEVEL V ACCURACY IEC-61935-1 Ed.3 : • • To those customer that want top performance, Class FA manufacturers want to demonstrate performance of their systems up to 1GHz. The DSX-5000 adequately meets the proposed for Level V tester requirements. Worst case uncertainty at 1GHz is proposed to be within 1dB comparable with Level-IV at 600MHz. Fluke Networks is the 1st Field Testing Company to have: - A FULL and COMPLETE accuracy specification introduced with IEC to support field testing to Class FA, 1 GHz Level V is the new accuracy designation … It’s much more than just frequency …
  20. 20. FEITO PARA ALIEN CROSSTALK • Sem módulos adicionais - O DSX CableAnalyzer é o PRIMEIRO TESTADOR DE CAMPO a ter o teste de Alien Crosstalk embutido - Pela norma ANSI/TIA-568-C.2 seção 6.1.13 o teste de PSANEXT é obrigatório para Canal e Link Permanente.
  21. 21. PS ANEXT • Power Sum Alien Near End Crosstalk
  22. 22. CAMERAS IP E ACCESS POINTS • The far end is terminated with an RJ45 plug No warning of different adapters, unlike DTX CableAnalyzer
  23. 23. NEW CABLE TYPES • Adopting ISO/IEC (US) naming U/UTP - Individual pairs are unshielded - No overall shield F/UTP - Individual pairs are unshielded - Overall shield S/FTP - Individual pairs are shielded - Overall shield
  24. 24. READY FOR TODAY’S AND TOMORROW’S REQUIREMENTS Shield integrity Balance measurements: • Now it’s just shield continuity is a DC • Important for successful 10GBASE-T. measurement. • Specified in ANSI/TIA-568-C.2 & TSBs. • The DSX-5000 reports distance to shield • Specified in ISO/IEC 11801:2010 integrity issues using a patented AC measurement technique. • Finds shield faults in the datacenter – even with common ground. Resistance Unbalance: • Important for successful PoE operation. • Specified in IEEE 802.3af and 802.3at. • Specified in ANSI/TIA-568-C.2. • Specified in ISO/IEC 11801:2010. All the measurements are currently not specified as a field measurement because it was thought it could never be done in the field. The DSX-5000 CableAnalyzer is the FIRST FIELD TESTER to measure them!
  25. 25. SHIELD INTEGRITY • • ALL wire mappers would think the shield was connected Grounding of two racks makes this happen • • DSX can not only tell you the shield is open It can also locate the distance to the shield issue
  26. 26. SHIELD INTEGRITY • Shield is open at one end due to incorrect termination
  27. 27. SHIELD INTEGRITY • Even when the two connectors are grounded together
  28. 28. SHIELD INTEGRITY • Other Wire Maps testers will show this connected
  29. 29. DESBALANCEAMENTO RESISTIVO • Difference in Resistance between the pair 1.87 Ω 1.85 Ω Resistance = 3.7 Ω Resistance Unbalance = 0.02 Ω
  30. 30. TESTES ADICIONAIS PARA POE • Works as long as the resistance unbalance is within xx Ω
  31. 31. Desbalancemaneto Resistivo - Use teste para identificar CCA • Aluminum has a higher resistance than Cu, and is less expensive • It can be used in CCA cables but these cables are do not meet TIA standards which require pure copper conductors • Customers don’t want this cable as it is a fire hazard and may not support PoE
  32. 32. NOVOS LIMITES DE TESTE • New folder Balance Measurements
  33. 33. Testes de Balanceamento – TCL e ELTCL
  34. 34. O Balanceamento Elimina a Interferência
  35. 35. TCL (TRANSVERSE CONVERSION LOSS) • Transverse Conversion Loss is the ratio (in dB) of a common-mode voltage measured on a wire pair relative to a differential-mode voltage applied to the same end of the pair. The TCL value shows you how well the impedances of the pair’s conductors are balanced. Differential Signal Applied Common Mode Voltage Measured
  36. 36. TESTANDO FIBRAS
  37. 37. INSPECIONE ANTES DE INICIAR OS TESTES • Optional fiber camera to inspect end face of fiber connectors
  38. 38. A CLEAN CONNECTOR
  39. 39. CONNECTOR WITH A FINGER PRINT
  40. 40. THIS PART OF THE PRESENTATION IS ONLY FOR THOSE >17 YEARS OLD
  41. 41. NOTICE THE RING WHERE THE CONTACT OCCURRED IN THE CENTER
  42. 42. CLEANED AND INSPECTED
  43. 43. PROCEDIMENTO OFICIAL DA AT&T • A AT&T considera 6 procedimentos de limpeza antes de poder condenar o conector a troca.
  44. 44. 100000 Velocidades Maiores 40000 Distâncias menores 100 10 52 266100 10000 1000 E-SR10 16 Fibre Fibre Channel Channel 100BASE100BASEFX FX 1000 1000 BASE-SX BASE-SX 10GBASE10GBASES S 40GBASE40GBASESR4 SR4 100GBAS 100GBAS E-SR10 10 ATM ATM 4 Token 3500 120000 3000 100000 2500 80000 2000 60000 1500 1000 40000 500 20000 00 Token Ring 4 Mb Ring 4 Mb 10BASE10BASEFOIL FOIL Token Token Ring 16 Ring 16 FDDI/TP FDDI/TP PMD PMD 10BASE10BASEFL FL Mbps Meters HISTÓRICO 1986 1987 1989 1992 1993 1993 1994 1995 1998 2002 2010 2010 1986 1987 1989 1992 1993 1993 1994 1995 1998 2002 2010 2010
  45. 45. Desempenho de fibras para DATACENTERS Aplicação Velocidade Norma Fibra Padrão Distancia Perda Máxima Ethernet 10 Mbps IEEE802.3 OM1 2 KM 12.5 dB Fast Ethernet 100 Mbps IEEE802.3 OM1 2 KM 11 dB 1G Ethernet 1 Gbps IEEE802.3z OM2 550m 3.56 dB 10G Ethernet 10 Gbps IEEE802.3ae OM3 300m 2.6 dB 40G Ethernet 40 Gbps IEEE802.3ba OM3 100m 1.9 dB 100G Ethernet 100 Gbps IEEE802.3ba OM4 150m 1.5 dB
  46. 46. AJUSTANDO A REFERÊNCIA • • • Now the units have warmed up sufficiently Press SET REF RUN WIZARD will walk you through the process 1. 2. 3. 4. 5. 6. Connect TRC with mandrel (VLM) Press SET REFERENCE Disconnect from Meter and insert second TRC in both paths VERSIV will check whether the TRC are good enough for the job If yes … you are ready to test Let’s connect to the artifact We connect to the good links Main Meter (2)  (6) Remote Source Main Source (3) --- (7) Remote Meter
  47. 47. RODANDO O TESTE • Change back to Main Meter (2)  (6) Remote Source Main Source (3)  (7) Remote Meter • We run 3 tests …. “Manual SAVE” !!!
  48. 48. REDUZINDO A INCERTEZA NO MULTIMODO • Encircled Flux (EF) is the final piece in the puzzle to reducing measurement uncertainty in the field
  49. 49. FORMA ERRADA DE FAZER A REFERÊNCIA • Wrong way! ? dB • Issues - You have no idea what the loss is in the adapter - Whatever it is, it’s subtracted from your measurement - The uncertainty is horrendous – negative loss
  50. 50. Inspecione e limpe os cordões de referência e as portas dos módulos do DTX antes
  51. 51. DISCONECTE APENAS NA PORTA DE ENTRADA “INPUT”
  52. 52. CONECTE UM BOM CORDÃO CONHECIDO AS UNIDADES PRINCIPAL E REMOTA
  53. 53. EXECUTE O AUTOTEST • Se a perda for menor que 0.10 dB, você saberá que seu cordão é bom • Salve este teste para ser apresentado ao cliente como prova.
  54. 54. DISCONECTE
  55. 55. O cassete tem de ser melhor que 2 adaptadores de 0.75 dB cada ≤0.75 dB ≤0.75 dB 300 m ≤ 1.05 dB 10GBASE-SR requisito é 2.6 dB @ 850 nm A perda aqui seria de 2.55 dB; BOM
  56. 56. • Isso não funcionará para um DataCenter ≤0.75 dB ≤0.75 dB 300 m ≤ 1.05 dB ≤0.75 dB ≤0.75 dB 10GBASE-SR requesito é 2.6 dB @ 850 nm A perda seria de 4.05 dB; RUIM
  57. 57. TESTANDO FIBRAS ÚNICAS • • • • Applications: - Mostly Telecom - FTTx - CCTV - Remote Sensors SimpliFiber PRO was better suited for the job then DTX or DSP CertiFiber works like/with SimpliFiber PRO Competition LT offers bi-directional testing on a single fiber - This is common for deticated Telecom tester but comes at price ! - …. The lack of a non-critical port on the meter side means no support of 1 JumperMethode. EVER !
  58. 58. 1. 2. 3. Press on remote CertiFiber PRO the button one and then hold until MM led begins to blinkg Red/Green Select Test Mode “Auto CertifFiber PRO” Perform REF procedure and test identical to procedure for SimpliFiber PRO PRESS BUTTON
  59. 59. SINGLE FIBER TESTING … REMOTE SIMPLIFIBER PRO LIGHT SOURCE 1. Select Power Meter /Light Source Mode 2. Select the remote source 3. Set Reference 4. Connect to Link 5. Wait for result 6. Save Result
  60. 60. COMO OS TESTES DE OTDR SE PARECEM? 61
  61. 61. OTDR É o que eu estou pensando?
  62. 62. OTDR EM AÇÃO Perda Distancia O OTDR mede a energia refletida e Não o nível de luz transmitida. 63
  63. 63. TYPICAL OTDR TEST RESULT Reflection Backscatter 64
  64. 64. REFLECTION EVENT Connector 65
  65. 65. LOSS EVENT Non-reflective event Splice or severe bend 66
  66. 66. END EVENT End of Fiber 67
  67. 67. MAPA DE FALHAS • Facilidade no entendimento • Ícones representativos. • • • • • Evento reflexivo bom Evento reflexive ruim Evento reflexive oculto Evento de perda bom Evento perda ruim Perda do evento oculto adicionado ao evento anterior
  68. 68. Company Confidential AJUDA CONTEXTUALIZADA • Com um clique no ícone de ajuda obtenha informação precisa sobre o problema apresentado. • Um pouco de teoria para quem precisar de embasamento teorico
  69. 69. Company Confidential PORQUE NÃO FAZER MELHOR!
  70. 70. Company Confidential PORQUE NÃO FAZER MELHOR!
  71. 71. Something New ProjX Project Management Get to System Acceptance (and Payment) faster!
  72. 72. A NEW PARADIGM FOR INFRASTRUCTURE CERTIFICATION Multiple jobs, teams, testers, and requirements – a single error can erode your project’s profitability Waiting for the project manager or “expert” to set things up and deliver the tester is all too common. Testing can always be faster: now it is Planning Setup Test Troubleshoot Multiple skill levels of technicians means that projects are delayed while troubleshooting. Working in an environment with multiple testers, standards, and test regimes makes generating reports time consuming ,delaying system acceptance. Customers struggle to understand multiple complex reports which delays systems acceptance. Report Systems Acceptance
  73. 73. VERSIV WAS DESIGNED TO WORK DIFFERENTLY THAN LEGACY TESTERS Project A Installation Floor 1 Testing Floor 1 Installation Floor 2 Project B Project C Installation Trouble Shoot Testing Installation Trouble Shoot Floor 1& 2 Testing Floor 2 Testing Floor 1 Trouble Shoot Roaming testers: contractors manage multiple projects, testers and tasks Concurrent testing: contractors need to simultaneously perform fiber & copper testing and troubleshooting with multiple testers on multiple jobs Project Configuration: contractors need to be able to eliminate wasted time and avoid costly errors due to redundant and time consuming loading of configurations, test limits and cable identifiers
  74. 74. PROJX MANAGEMENT SYSTEM • • • • Easy to set up, minimize test limit errors/better manage multiple projects. Create new project for different jobs, locations or customers. Easily define project requirements ahead of time. Store jobs in LinkWare for each transfer to other Versiv testers.
  75. 75. PROJX Planning Setup Test Troubleshoot Report • Limitations of legacy cable testers • ProjX to the rescue • Examples - So you have a failing link…. - Two testers, 1 job, no problem! - Help – need to go back to an old job….. Systems Acceptance
  76. 76. PROJX TO THE RESCUE • Allows project setup to be stored, shared and easily recalled • Creates punch lists for failing links - No longer lose failing link information • Keeps track of multiple cable ids - Allows users to jump around in cable id list - Doesn’t lose order when a link fails - Easily move to different projects with unique cable ids • No LinkWare dependence - Able to move files or project setup in the field
  77. 77. PROJX TO THE RESCUE • Powerful IN FIELD project & results management - Transfer - Manage - Move
  78. 78. IN FIELD PROJECT & RESULTS MANAGEMENT • Transfer - Copy and transfer projects & results - Projects include project info and test setup
  79. 79. IN FIELD PROJECT & RESULTS MANAGEMENT • Transfer - Copy and transfer projects & results - Projects include project info and test setup
  80. 80. SO YOU HAVE A FAILING LINK…. • Run Test - Pass or Fail Result ?
  81. 81. SO YOU HAVE A FAILING LINK…. • Run Test - Pass or Fail • Failing link options - Repair and Test Again - Save and Fix Later Result ?
  82. 82. SO YOU HAVE A FAILING LINK…. • Run Test - Pass or Fail • Failing link options - Repair and Test Again - Save and Fix Later • Punch list - Created by Fix Later Result ? “Punch Lists”
  83. 83. JOB COMPLETE PERCENTAGE • Percentage of job complete - Includes all links: pass and fail Hardrock 0✔ 0✖ 0% F1-001 ... F1-100 .
  84. 84. JOB COMPLETE PERCENTAGE • Percentage of job complete - Includes all links: pass and fail Hardrock 0✔ 0✖ Hardrock 47✔ 3✖ 0% F1-001 ... F1-100 . 50 % F1-001 ... F1-100 .
  85. 85. JOB COMPLETE PERCENTAGE • • Percentage of job complete - Includes all links: pass and fail Don’t lose cable ids when link fails Hardrock 0✔ 0✖ Hardrock 47✔ 3✖ Hardrock 95✔ 5✖ 0% F1-001 ... F1-100 . 50 % F1-001 ... F1-100 . 100 % F1-001 ... F1-100 .
  86. 86. JOB COMPLETE PERCENTAGE • • • Percentage of job complete - Includes all links: pass and fail Don’t lose cable ids when link fails Allows you to move punch list to different tester or team! Hardrock 0✔ 0✖ Hardrock 47✔ 3✖ Hardrock 95✔ 5✖ Hardrock 100✔ 0✖ 0% F1-001 ... F1-100 . 50 % F1-001 ... F1-100 . 100 % F1-001 ... F1-100 . 100 % F1-001 ... F1-100 .
  87. 87. O QUE DEVO EXIGIR E COMO DEVO ANALISAR?
  88. 88. CAT 5 BARATO OU CAT 3 CARO?
  89. 89. Use the least expensive cable that meets your needs
  90. 90. Cable, Connector or Installer?
  91. 91. HOW TO READ TEST RESULTS
  92. 92. HOW TO READ TEST RESULTS
  93. 93. CABOS CCA OU BIMETALICOS
  94. 94. CABOS CCA OU BIMETALICOS
  95. 95. TRADE-IN 2013 http://www.flukenetworks.com/tradeinbrasil
  96. 96. LINKRUNNER AT TruePower™ PoE Loading User configurable AutoTest IPv4 and IPv6 Support Link at 10/100/Gig on copper and fiber Ping and TCP connectivity Full Color 2.8 in ¼ VGA LCD Size: 8.9cm x 19.8cm x 4.8cm Weight: 0.5kg Critical Switch Port Details USB Access for Upgrades and Reports Lithium Ion Battery 6+ hours life One Click to the Answers You Need Graphical, color wiremap and cable details Powers on in Under 3 Seconds Multi-language UI Comprehensive, one button AutoTest
  97. 97. TRUEPOWER™ POE • Valida a performance PoE solicitando carga até 25.5W (802.3at) • Carrega o circuito para stressar os switches, cabeamentos e os patch-panels • Garante uma implantação segura dos dispositivos PoE
  98. 98. LINKRUNNER AT
  99. 99. Obrigado, Gracias, Thank you richard.landim@flukenetworks.com tel: (11) 4058-0198

×