Successfully reported this slideshow.
We use your LinkedIn profile and activity data to personalize ads and to show you more relevant ads. You can change your ad preferences anytime.

Motor Control TeSys D Contactors Briefing

130 views

Published on

Learn how to select a TeSys D Contactor (from 9 up to 65A)and see examples.
For more details:
http://www.schneider-electric.com/en/product-range/664-tesys-d/?parent-category-id=1500&parent-subcategory-id=1510

Published in: Technology
  • Be the first to comment

Motor Control TeSys D Contactors Briefing

  1. 1. Property of Schneider Electric TeSys D contactors briefing (from 9 up to 65 A) Simply reliable. Simply available. December 2017
  2. 2. Table of content Page 2Property of Schneider Electric | • Introduction: TeSys D contactor offer • TeSys D: How to select  Learning by examples • TeSys D: Auxiliary contactors  Learning by examples • TeSys D: Offer structure synthesis • Where to find further details • Quiz
  3. 3. TeSys D contactor offer structure Page 3Property of Schneider Electric | Contactor Reversers Auxiliaries AC std LC1D LC2D CAD DC std LC1D LC2D CAD DC low consumption LC1D LC2D CAD Connexion type: Screw clamp, spring, fast on, lugs, Everlink. Coil: AC, DC
  4. 4. How to select a TeSys D contactor Page 4Property of Schneider Electric | All TeSys D contactors have 2 embedded auxiliary contacts: 1 NO and 1NC TeSys D 3P contactor, 9 A AC3, 230 V AC coil with 1 NO and 1 NC auxiliary contacts LC1 Schneider ElectricTM 3P contactor 09 9 A AC3 P7 230 V AC D TeSysTM D range LC1 D 09 P7
  5. 5. Learning by examples Main coils in the TeSys ranges Page 5Property of Schneider Electric | 3P contactor, 12 A AC3, 230 V AC control circuit LC1D12 P7 3P contactor, 9 A AC3, 24 V ACLC1D09 B7 3P contactor, 9 A AC3, 220 V ACLC1D09 M7 3P contactor, 12 A AC3, 24 V DCLC1D12 BD 3P contactor, 18 A AC3, 48 V DCLC1D18 ED 3P contactor, 18 A AC3, 24 V DC low-consumption coil LC1D18 BL To remember 7 – AC standard coil D – DC standard coil L – DC low-consumption coil
  6. 6. Learning by examples Page 6Property of Schneider Electric | 4P contactor, 20 A AC1, 230 V AC control circuit Reversers: 2 contactors mounted to pilot a two-way motor 3P reversing contactor, 18 A AC3, 230 V AC control circuit 4-pole contactors: Contactors with 4 poles T as Tetra = 4 LC1D T 20P7 2 x 3P contactors LC 2 D18P7
  7. 7. Learning by examples Terminal type: By default screw clamp but other terminals are available Page 7Property of Schneider Electric | Screw clampLC1D09P7 Spring terminalLC1D093P7 LC1D096P7 LC1D099P7 EverLink screw connectorLC1D40AP LC1D40A3P7 LC1D40A6P7 Lugs-ring terminal Lugs-ring terminal Spring terminal Lugs-ring terminal
  8. 8. TeSys D and auxiliary contactor Auxiliary contactors Page 8Property of Schneider Electric | • Are used to pilot other contactor control circuits • Have 5 poles: 5 NO or 3 NO and 2 NC All TeSys D auxiliary contactors have a 10 A AC1 500 V circuit 3 3 NO TeSys D auxiliary contactor with 3 NO and 2 NC contacts, 230 V AC coil 2 2 NC 5 5 NO TeSys D auxiliary contactor with 5 NO and 0 NC contacts, 24 V DC coil 0 0 NC CAD 3 2 P7 CAD 5 0 BD
  9. 9. Learning by examples: TeSys D Page 9Property of Schneider Electric |
  10. 10. TeSys K offer structure synthesis Page 10Property of Schneider Electric | DOL Reversers Auxiliaries AC std LC1D LC2D CAD 3P: 9,12,18A, 25, 32, 38A, 40, 50, 65ª 3P: 5 NO CAD50x7 4P: 20, 25, 32, 40A, 60, 80ª LC1DT20x7 4P: 3 NO – 2 NC CAD32x7 DC std LC1D LC2D CAD 3P: 3P: 5 NO CAD50xD 4P: 4P: 3 NO – 2 NC CAD32xD DC low energy LC1D LC2D CAD 3P: 3P: 5 NO CAD50xL 4P: 4P: 3 NO – 2 NC: CAD32xL Connexion type: screw clamp, spring, fast on, lugs, Everlink Coil: AC, DC
  11. 11. • Click here to find info on SE.com • Click here to find TeSys D on SE.com • Click here to access our Digicat • Click here to access to CAD files • Click on the link below for FAQs (frequently asked question) Where to find details Page 11Property of Schneider Electric |
  12. 12. Property of Schneider Electric | Quiz Based on what you’ve learned so far, try to build a reference with the given technical characteristics. ? Page 12 Q1 3P contactor, 9 A, 230 V AC std coil, screw clamp Q2 3P reverser, 25 A, 24 V DC low cons coil, screw clamp Q3 4P contactor, 32 A, 24 V AC std coil, lugs-ring terminal Q4 3P contactor, 60 A, 230 V AC std coil, EverLink BTR screw connector Q5 4P contactor, 20 A, 24 V DC std coil, spring terminal
  13. 13. Property of Schneider Electric | Quiz answers Page 13 Answers LC1D09P7Q1 3P contactor, 9 A, 230 V AC std coil, screw clamp LC2D25BLQ2 3P reverser, 25 A, 24 V DC low cons coil, screw clamp LC1DT326BDQ3 4P contactor, 32 A, 24 V AC std coil, lugs-ring terminal LC1D65AP7Q4 3P contactor, 60 A, 230 V AC std coil, EverLink BTR screw connector LC1DT203BDQ5 4P contactor, 20 A, 24 V DC std coil, spring terminal
  14. 14. Page 14Property of Schneider Electric | Thank you

×