Successfully reported this slideshow.
We use your LinkedIn profile and activity data to personalize ads and to show you more relevant ads. You can change your ad preferences anytime.

Central Heating Part 3

406 views

Published on

Central Heating Part 1 plumbing revision to be done with exams at www.prcaticeplumbingexams.com

Published in: Education
  • Be the first to comment

  • Be the first to like this

Central Heating Part 3

  1. 1. Central-heating system components PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  2. 2. By the end of this Part you should be able to, Identify the Following components of heating systems: • Cisterns • Air separators • Circulating pumps. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  3. 3. • The feed and expansion (F&E) cistern is to be used on open-vented central heating systems. • The main porous is to allow the system to be open to atmospheric pressure, allow for expansion and feed the central heating system. • The water should be set low to allow 4 % expansion + 25 mm so that the open vent is not submersed in the water. • • The cold feed from the F&E cistern to system is 15 mm minimum, and this pipe should not include any valves. • . • A servicing valve should be located on the cold water inlet pipework to the F&E cistern. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  4. 4.  The F&E cistern is located at the highest point in the system, it must not be affected by the position of the circulating pump or allow for over pumping  To avoid any problems with gravity primaries, a minimum height can be obtained by the following equation  The maximum head given by the pump ÷ 3  In a fully pumped system the level of water in the F&E cistern should be a minimum of 1 metre above the pumped primary to the hot-water storage cylinder.  No valves are to be on the feed or open vent This could have disastrous consequences if both are closed PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  5. 5. • The cistern and float valve must withstand temperatures of 100°C. The float valve must comply with (BS1212) • The system volume expands by around 4 % when heated. • How much would a system with 100 L of water expand by when heated ? ----------4L • This is why expansion + 25 mm must be allowed in the F&E cistern PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  6. 6. • This should rise to a minimum height of 450 mm above the water level in the F&E cistern to allow for any pressure surge created by the circulator pump. • The purpose of the primary open safety vent is to: • Allow for expansion in the event of over heating and allow the system to be open to atmospheric pressure. • There should be no valve on the open vent and should be a minimum of 22mm in diameter. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  7. 7. • Air separators are used when the connection of the open vent pipe and the cold feed need to be close together to comply with the design of the system. • The air separator allows for air in the system to escape through the open vent making the system quieter. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  8. 8. • Isolation valves must be fitted to both side of the pump to allow for servicing and maintenance. • Pumps contain a impeller which is turned by a motor circulating the water that's why pumps are relater to as impeller pumps or circulator pumps a • It is the pump’s job to circulate water around the central-heating system • Most pumps have three settings, the pump manufacturers provide performance data for each, which shows flow rate in litres per second and pressure in k Pa and m head. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  9. 9. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  10. 10.  Most pumps deliver 5 to 6 m head around 0.5 to 0.6 bar.  The flow rate on small bore systems should not be above 1 litter per second.  The flow rate on micro bore systems ( pipe work smaller than 15mm) should not deliver more than 1.5 letters per minute.  When positioning the pump you must make sure the pump provides a positive pressure to the system and does not allow for over pumping of the water through the open vent. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM
  11. 11. PRACTICE PLUMBING EXAMS © WWW.PRACTICEPLUMBINGEXAMS.COM

×