TREATMENT OF WATER SUPPLIES
Available raw water must be treated and purified
before they are supplied to the public for their
uses.
The extend of treatment depends upon the quality
and characteristics of raw water and also upon the
quality requirement for the intended use.
The available water must be made safe, good in
appearance and attractive to human taste and
tongue.
Methods of Purification of Water
Various methods adopted for purifying the public
water supplies are:
1. Screening
2. Plain sedimentation
3. Sedimentation aided with coagulation
4. Filtration
5. Disinfection
6. Aeration
7. Softening
8. Miscellaneous treatment such as fluoridation,
recarbonation liming, desalination, etc.
Screening: Removes big and visible objects such
as trees, branches, sticks, vegetation, fish, animal
life, etc.
Aeration: Removes unpleasant taste and odour
Plain Sedimentation: Removes coarser
suspended materials
Sedimentation aided with coagulation:
Effectiveness of sedimentation is increased by
adding some chemicals
Filtration: Removes finer particles in suspension
which remains even after sedimentation
Disinfection: Removes pathogenic bacteria
Softening: Removes Hardness of water
DeFluoridation: Removal of fluoride
Liming: Addition of lime for controlling acidity
and reduce corrosive action
Recarbonation: Addition of carbon dioxide to
prevent deposition of calcium carbonate scale
Desalination: Removal of excess salt
SCREENING
Screens are provided in front of intake structures to
exclude large sized particles
Coarse screen: Placed in front of fine screen.
It consists of parallel iron rods/ bars placed vertically or
inclined at 45o – 60o
It removes bigger floating bodies
Fine screen: Consist of woven wire mesh.
It removes fine materials.
Fine screens get clogged easily and are to be cleaned
frequently.
AERATION
OBJECTIVES
Aeration removes odour and tastes due to volatile gases
like hydrogen sulphide and due to algae and related
organisms.
Aeration also oxidise iron and manganese,
Increases dissolved oxygen content in water,
Removes CO2 and reduces corrosion and
Removes methane and other flammable gases.
Bacteria may be killed to some extend
Also used for mixing chemicals with water
Types of Aerators
Gravity aerators
Fountain aerators
Diffused aerators
Mechanical aerators.
Gravity Aerators (Cascades): In gravity aerators, water is
allowed to fall by gravity such that a large area of water is
exposed to atmosphere, sometimes aided by turbulence.
Fountain Aerators: These are also known as spray aerators
with special nozzles to produce a fine spray
Diffused Aerators: It consists of a tank with perforated
pipes, tubes or diffuser plates, fixed at the bottom to
release fine air bubbles from compressor unit.
Mechanical Aerators: Mixing paddles as in flocculation
are used. Paddles may be either submerged or at the
surface.
SEDIMENTATION
It is the removal of suspended particles by gravitational
settling
Sedimentation tanks are designed to reduce the velocity of
flow of water so as to permit suspended solids to settle out
of water by garvity
PLAIN SEDIMENTATION
When the impurities are separated from water by action of
natural forces alone ie, by gravitation & natural aggregation
of the particles is called plain sedimentation
SEDIMENTATION WITH COAGULATION/ CLARIFICATION
When chemicals or other substances are added to induce
seggregation & settling of colloidal suspended particles, the
operation is called clarification
Chemical Precipitation
When chemicals are added to separate dissolved
impurities the operation is called chemical
precipitation
Discrete Particles
A particle that doesnot alter its shape, size & weight
while settling or rising in water is known as discrete
particle
Types of Settling
Particles settle out of suspension in the following 4 ways,
Type I sedimentation (Discrete settling)
Type II (Flocculent settling)
Type III ( Hindered /Zone settling)
Type IV ( Compression settling)
Type I: Discrete particle settling –
Sedimentation of discrete particles
Particles settle individually without interaction with
neighbouring particles.
Also know as free settling
Type II: Flocculent settling–
This refers to dilute suspension
Particles flocculate during sedimentation process
Flocculation causes the particles to increase in mass
and settle at a faster rate.
Type III: Zone settling –
This refers to intermediate concentration
Inter particle forces hold the particles together & hence
the mass of the particles subside as a whole
The mass of particles tends to settle as a unit with
individual particles remaining in fixed positions with
respect to each other.
Type IV: Compression –
This refers to high concentration
Particles come in contact with each other resulting in the
formation of a structure
Further settling occur only by compression of the
structure due to weight of particles which are added to
the structure
PLAIN SEDIMENTATION (Type I
Settling)
Theory of sedimentation
Suspended impurities with specific gravity greater
than that of water settle under gravity if their flow is
retarded.
The following factors affect sedimentation process:
1. Velocity of flow
2. Viscosity of water
3. Size, shape and specific gravity of particles
1. Velocity of flow:
Horizontal velocity carries the particles horizontally
Greater the flow area, the lesser is the velocity & hence
more easily the particle will settle down
2. Viscosity of water:
The viscosity varies inversely with temperature
Warm water is less viscous therefore offer less
resistance to settlement
3. Size, shape and specific gravity of particles:
Large sized particles settle more than fine particles
The settling velocity of particles is given by Stock’s law
Where vs – settling velocity in cm/s
g- acceleration due to gravity in cm2/s (981 cm2/s)
μ- viscosity of water = 0.01 poise
G – Specific gravity of particle
d- diameter of particle in cm
Sedimentation Tank
Types of sedimentation tank-Depending upon the
methods of operation,
1. The Quiescent or Fill & Draw type
2. The continous flow type
1. The Quiescent or Fill & Draw type
The tank is filled with incoming water & is allowed to
rest for a certain time
During this period the suspended particles settle down
at the bottom
Detention time- 24 hrs
Clear water is drawn out through outlet
The tank is then cleaned & filled again
Cleaning process take 6 – 12 hrs
Cycle of operation- 30 – 36 hrs
2. The continuous flow type
In this type water continuously keeps on moving in the
tank, with a very small velocity during which the
particles settle at the bottom before they reach the
outlet
Two types- a) Horizontal flow tank
b) Vertical flow tank
In horizontal flow type, tank is generally rectangular
in plan having length equal to atleast twice the width
Water flows in horizontal direction, with max
permissible velocity of 0.3 m/s
Vertical flow type are generally deep, circular or
rectangular basins with hopper bottom
Horizontal flow tank
Direction of flow is horizontal
Aim is to achieve equal velocity at all points in the settling
zone
Design is based on the following assumptions,
1. Particles settle exactly in the same manner as in the
quiescent tank of equal depth
2. Flow is horizontal & steady & the velocity is uniform
3. The concentration of suspended particles of each size is
same at all points at the inlet end
4. A particle is removed when it reaches the bottom of the
settling zone
The basin can be divided into 4 zones,
1. The inlet zone
2. The settling zone
3. The bottom/ sludge zone
4. The outlet zone
Inlet zone: Region in which the flow is uniformly distributed
over the cross section such that the flow through settling zone
follows horizontal path
Settling zone: Settling occurs under quiescent conditions
Outlet zone: Clarified effluent is collected and discharge
through outlet weir.
Sludge zone: For collection of sludge below settling zone.
Let L & H be the length & depth of the settling zone
Let B be the width
Q be the discharge rate
Vd is the horizontal discharge velocity
Time of horizontal flow/ detention period for a
particle
Equation 3 defines the surface over flow rate (SOR) or
overflow rate, which is equal to flow divided by the
plan area of the basin
The equation states that for discrete particles &
unhindered settling, basin efficiency is a function of
settling velocity of particles & the surface area of the
basin
L/B = 3:1 to 5:1
D= 2.5 to 5 m (prefered value- 3m)
Horizontal flow velocity- 0.2 to 0.4 m/mt (prefered -
0.3 m/mt)
Bottom slopes range from 1% in rectangular tanks to
about 8% in circular tanks.
Slope of sludge hoppers range from 1.2 : 1 to 2: 1
( vert: Horz)
Circular tank with radial flow with
central feed
Water enters at the center
Water flows radially outward from the center
It has low velocity and hence particles get settled
Clear water is taken out at the periphery
Mechanical scrapper is provided for sludge removal
Circular tank with peripheral feed with radial flow
Raw water is fed from the periphery and the pure
water is taken out at the center
Problems
Qt. 1. A settling tank is designed for an overflow rate of
4000 l/m2/hr. What percentage of particles of
diameter a) 0.05mm & b) 0.02 mm will be removed in
the tank at 10 degree celsius.
Qt. 3. The maximum daily demand at a water purification plant
has been estimated as 12 million liters per day. Design the
dimension of a suitable sedimentation tank (fitted with
mechanical sludge removal) for the raw supplies, assuming a
detention period of 6 hours and velocity flow as 20 cm/minutes
Solution:
Quantity of water to be treated in 24 hours = 12 x 106 liters
Quantity of water to be treated during the detention period
of 6 hours =