  1. 1. 11 Successful Implementation & Improved OperationAdvances in FOUNDATIONfieldbus provide improvedusabilityJonas Berge
  2. 2. 22 Advances in FOUNDATION fieldbus provide improved usabilityReleased2007Introducing Three Revolutionary Products- iPhone (1st generation)Widescreen iPod with touchcontrolsRevolutionary mobile phoneBreakthrough InternetcommunicatorYouTube 4:47
  3. 3. 33 Advances in FOUNDATION fieldbus provide improved usabilityQuiz: Which was the first phone with webbrowser?Apple iPhoneNokia 9000 CommunicatorMotorola RazrReleased1996• Not easy to navigate• People not yetInternet savvy• No habit ofsearching web
  4. 4. 44 Advances in FOUNDATION fieldbus provide improved usabilityQuiz: Which was the first phone withmusic player?Apple iPhoneNokia 9000 CommunicatorSony Ericsson W800Released2005• Had to rip CDs andcopy files• Not easy tofind/search songs
  5. 5. 55 Advances in FOUNDATION fieldbus provide improved usabilityQuiz: Which was the first phone whereyou can install applications?Apple iPhoneHandspring (Palm) Treo 180Sony Ericsson W800Released2002• Apps not easy to buy• Not easy to use• “too small”
  6. 6. 66 Advances in FOUNDATION fieldbus provide improved usabilityiPhone Ease-of-Use- Human Centered DesigniTunes storeWider screenMulti-touch gesturesThreaded text messagingYouTube as applicationPower of Context:The time was right;people were readyfor computer,Internet, synching,and dependent onthe web
  7. 7. 77 Advances in FOUNDATION fieldbus provide improved usability“We’re Gonna Reinvent the Phone”
  8. 8. 88 Advances in FOUNDATION fieldbus provide improved usabilityPast Fieldbus Learning CurveDifferent from 4-20 mAHad to download DDfrom the Internet– Computer skills– Internet skillsHad to load DD on thesystem– System skillsCan’t see signal withmultimeterToo DifficultDownload errorsConfiguration errorsCryptic device errorcodesHad to change systemconfiguration at devicereplacementScattered parameterswith cryptic namesConservative designprocess andconstraintsThis was aproblem inbefore butisn’t today
  9. 9. 99 Successful Implementation & Improved OperationFieldbus Ease of UseBetter but not so different...
  10. 10. 1010 Advances in FOUNDATION fieldbus provide improved usabilityKey Feature Enhancements till DateSelection Configuration Commissioning Maintenance ReplacementError FreeDownloadFieldDiagnosticSpecificationHost Profile Test and RegistrationDeviceReplacementGuideline andSpecificationsDevice Level Methods and Views
  11. 11. 1111 Advances in FOUNDATION fieldbus provide improved usabilityCommissioning:- Faster, but...User Experience– Download offline configuration results in errors– Multiple downloads typically resolve errors, but thisincreases overall commissioning timeAnalysis– Devices apply checks to maintain consistency duringdownload– Device expects a specific order for parameterdownload– Some parameters should not be written during anautomated download
  12. 12. 1212 Advances in FOUNDATION fieldbus provide improved usabilityITK6 Profile Improves CommissioningNew “no_download” lists inform host whichparameters should not be part of an automateddownload– Described in EDD– e.g. calibration parameters– e.g. vendor specific behavioral parametersNew deferral of inter-parameter checks– Disables consistency checks during automateddownload– Once completed, device re-evaluates configuration– Reduces errors due to parameter order mismatchNew parameter BLOCK_ERR_DESC_n– Provides more detail to the configuration block error
  13. 13. 1313 Advances in FOUNDATION fieldbus provide improved usabilityMaintenance- Rationalized with diagnostics, but...User Experience– Diagnostic data is represented in different forms,making integration difficultAnalysis– A common structured approach across networks isnecessary to bring the right information to the rightperson in context
  14. 14. 1414 Advances in FOUNDATION fieldbus provide improved usabilityITK6 NAMUR NE107 Improves Self-Monitoring and Diagnosis of Field DevicesDiagnosis results must be reliableDiagnosis results must always be viewed inthe context of the application.Internal diagnosis must be categorized into 4standard “status signals”Configuration must be free, as reactions willdepend on the users requirementsDetailed information can be read out by thedevice specialist
  15. 15. 1515 Advances in FOUNDATION fieldbus provide improved usabilityRole-Based Diagnostics1Asset ManagementMaintenance StationProcess ControlEngineering StationHSE Control NetworkH1 Process NetworkPlantoperatorsPlant maintenanceengineering
  16. 16. 1616 Advances in FOUNDATION fieldbus provide improved usabilityDevice Replacement- Interoperability works, but...User Experience– Replacing devices requires access to system softwareAnalysis– Replacement devices are sometimes newer than thedevice used before– A new type or version of device requires the DD to beloaded and the tag to be updated
  17. 17. 1717 Advances in FOUNDATION fieldbus provide improved usabilityITK6 Improves Device ReplacementFieldbus Foundation published an applicationnote for suppliers to define rules for ‘Like’ devicereplacementNew parameter COMPATIBILITY_REV declarecompatibility rulesEnables systems to use an updated device thatwas commissioned with a prior version deviceversionSimplify the 2 a.m. device replacement scenario
  18. 18. 1818 Advances in FOUNDATION fieldbus provide improved usabilityDevice Setup and Diagnostics- Device management improved, but...User Experience– Users must browse through many blocks to get anoverview of health from all diagnostics– Users must go to many blocks to completely configurethe deviceAnalysis– Traditional DD accessed the blocks one by one
  19. 19. 1919 Advances in FOUNDATION fieldbus provide improved usabilityITK6/HPR Graphically Enhanced EDDLIntegrating Data from Multiple BlocksEasier overviewDrill down for details
  20. 20. 2020 Advances in FOUNDATION fieldbus provide improved usabilityEDDL Wizards Across Blocks
  21. 21. 2121 Advances in FOUNDATION fieldbus provide improved usabilityHost Profile Registration2008 2009 2010 2011 20121H 2H 1H 2H 1H 2H 1H 2H 1H 2HHostInteroperabilitySupport Test(HIST)Host 6Xb Profile Test/RegistrationHost 6Xa Profile Test/RegistrationValid through June 2010
  22. 22. 2222 Advances in FOUNDATION fieldbus provide improved usability“Project Gemstone”Next wave of usability improvements– Device templates– Device replacement– Etc.ITK7HPR compliance level ‘C’
  23. 23. 2323 Successful Implementation & Improved OperationSummary
  24. 24. 2424 Advances in FOUNDATION fieldbus provide improved usabilitySummaryNew features improve configuration,commissioning, maintenance and replacementReduce complexity while increasinginteroperability and productivityHPR assures features are consistent acrosssystems
  25. 25. 2525 Advances in FOUNDATION fieldbus provide improved usabilityExisting Fieldbus UsersUpgrade your fieldbus system to latest version totake advantage of these features
  26. 26. 2626 Advances in FOUNDATION fieldbus provide improved usabilityWe’re Reinventing FieldbusSmartITK4ITK5HISTITK6HPR61bsmartNot so smarteasytousehardtouseGemstone

×