Successfully reported this slideshow.
Your SlideShare is downloading. ×

Upgrading Generator Protection Using Multiple Relay Ups.pptx

Ad
Ad
Ad
Ad
Ad
Ad
Ad
Ad
Ad
Ad
Ad
Loading in …3
×

Check these out next

1 of 9 Ad

More Related Content

Similar to Upgrading Generator Protection Using Multiple Relay Ups.pptx (20)

Advertisement

Upgrading Generator Protection Using Multiple Relay Ups.pptx

  1. 1. Upgrading Generator Protection Using Multiple Relay Ups
  2. 2. INTRODUCTION Contrary to popular belief, generators do experience short circuits and abnormal electrical conditions. In many cases, equipment damage due to these events can be reduced or prevented by proper generator protection. Generators, unlike some other power system components, need to be protected not only from short circuits, but from abnormal operating conditions. Examples of such abnormal conditions are: overexcitation, overvoltage, loss-of-field, unbalanced currents, reverse power, and abnormal frequency. When subjected to these conditions, damage or complete failure can occur within seconds, thus requiring automatic detection and tripping.
  3. 3. In a properly protected generator, automatic protection against harmful abnormal conditions is required. The bulk of this paper deals with the need to provide such protection. Objections to the addition of such protection is not that it will fail to operate when it should, but that it might operate improperly to remove a generator from service unnecessarily. This concern about upgrading protection can be greatly reduced by understanding the need for such upgrades, and how to apply them to a given generator. An unnecessary generator tripping is undesirable, but the consequences of not tripping and damaging the machine are far worse. The cost to the utility for such an occurrence includes not only the cost of repair or replacement of the damaged machine, but the substantial cost of replacement power during the periods when the unit is out of service.
  4. 4. An alert and skillful operator, at manned locations, can sometimes avoid removing a generator from service by correcting an abnormal operating condition. In the vast majority of cases, however, the event will occur too rapidly for the operator to react and automatic detection is required. Operators have also been known to make mistakes, creating abnormal conditions where generator tripping is required to avoid damage. Inadvertent energizing and over excitation are examples of such events. For these reasons, operating procedures are not a substitute for proper automatic protection.
  5. 5. IMPROVED SENSITIVITY PROTECTION AREAS Negative Sequence (unbalanced current) Protection There are a number of system conditions that can cause unbalanced three-phase currents in a generator. These system conditions produce negative sequence components of current which induce a double-frequency current in the surface of the rotor. The skin effect of the double-frequency rotor current causes it to be forced into the surface elements of the rotor. These rotor currents can cause excessive temperatures in a very short time.
  6. 6. Currents in the Rotor Surface
  7. 7. Sequential Tripping This method of shutting down a generator is used on steam generators to prevent over speed when delayed tripping has no detrimental effect on the generating unit. This method of generator tripping was recommended by generator manufacturers of steam turbines some years ago as a result of over speed generator failures and is an upgrade item. It is used to trip the generator for prime mover problems only where high speed tripping is not a requirement. The first device tripped is the turbine valves. A reverse power relay in series with the valves close position switches provides security against possible over speed of the turbine by ensuring that steam flows have been reduced, below the amount necessary to produce an over speeding condition, before the generator breaker(s) are tripped. For boiler/reactor or turbine mechanical problems, this is the preferred tripping mode since it prevents the over speed of the machine. Figure 12 shows the block diagram for sequential tripping.
  8. 8. CONCLUSION There are a number of functional protection areas on 20+ year old generators which have significant shortcom- ings. This paper identifies those protection areas and the risks of not addressing them. In addition, a cost- effective strategy to upgrade protection to current industry standards is outlined using multifunction digital relaying. Generation is the single most expensive capital investment of a utility. Protecting this investment to prevent failure should be a priority item with utilties as well as non-utility generator owners.
  9. 9. Thank You

×