SlideShare a Scribd company logo
1 of 90
Download to read offline
Presented by Armstrong Okai Ababio
1
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Goal of the Presentation-1
To Appreciate the use of Ohmic and MVA Methods
for Symmetrical Short Circuit Calculation.
A symmetrical or balanced fault affects each of the
three-phases equally (Three phase fault)
2
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Goal of the Presentation-2
To appreciate the use of Symmetrical Components for
Asymmetrical Short Circuit Calculation.
An asymmetric or unbalanced fault does not affect each
of the three phases equally.
Common types of asymmetric faults:
line-to-line
line-to-ground
double line-to-ground
The analysis of this type of fault is often simplified by
using methods such as symmetrical components.
3
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Introduction
The operation of a power system departs from normal after the
occurrence of a fault. The most common faults in any electrical
installation are short circuits, i.e. a breakdown of insullation
between conductive parts which normally are at different
potential.
Fault give rise to abnormal operating conditions such as excessive
current and voltages at certain points in the network.
The magnitude of fault current depends on the generated power in
the system, the distance to these sources, fault resistance and for
ground fault it depends also on the neutral point treatment of the
system.
4
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Effect of Faults in a 3 phase Network
 A fault will cause voltage and current disturbances, including a complete
voltage collapse near the fault location.
 The voltage gradient in the ground and across the earthing resistance
create dangerous step and touch voltages near the fault.
 The dynamic forces of the fault current, the electric arc at the fault
location and the thermal effects of the current on the network elements in
the current path all cause damage to the plant equipment and personnel.
 The voltage and current disturbances interrupt the transmission of power
and thus also affect customers.
5
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Effect of Faults-2
 A large amount of power is dissipated at the fault point, which means lost of revenue for
the utility.
 Failure to remove a fault will usually result in rapid expansion of damage to the system.
 Various protection equipment are used in guarding against such faults condition. An
idea of the magnitudes of such fault currents gives the Engineer the current
settings of the various protection devices and ratings of circuit breakers in the
network.
6
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Effect of Faults-3
 In the light of the above discussed effects of faults, FAULT or SHORT CIRCUIT
ANALYSIS is highly needed.
 Performing short-circuit calculations requires an understanding of various
system components and their interaction.
 Components of Power System:
Generators, Transformers, Transmission lines, Protection Systems(control
and monitoring system), Switch gear, Load.
7
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Types of Fault/ Short Circuits in a 3
phase network Three-phase fault with or without earth (5%)
 Phase-to- phase clear of ground (10 – 15%)
 Two-phase-to-earth fault (10 – 20%)
 Phase-to-earth fault (65 – 70%)
 Fault Incident:
85% of faults are overhead line.
50% of these are due to lightning strikes.

L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
8
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
3 PHASE FAULTS-1
 A 3-ph fault affects the three-phase network equally (symmetrical fault). They rarely
occur. All three conductors are equally involved and carry the same rms short- circuit
current. There is the need to use only one conductor for the calculation.
 It is valid because system is maintained in a balanced state during fault.
 Voltages are equal and 120° apart.
 Currents are equal and 120° apart.
 Power system plant symmetrical:-
 Phase impedance equal
 Mutual impedance equal
 Shunt admittances equal
 Causes:
 System energization with maintenance earthing clamps still connected.
 1ø faults developing into 3ø faults. Etc.
9
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
3 PHASE FAULTS-2
 A 3-ph fault affects the three-phase network symmetrically. They rarely occur.
All three conductors are equally involved and carry the same rms short-
circuit current. There is the need to use only one phase (conductor ) for
the calculation.
The Per unit system or MVA method is used for the
analysis of Three phase fault.
10
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
3 PHASE FAULTS
11
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
3 PHASE FAULTS
12
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Over View of Per Unit System
 Per- Unit Notations. It is used to simplify calculations on system with more than two
voltages. ( The √ are eliminated)
It can be seen by inspection of any power system diagram that:
a. several voltage levels exist in a system
b. it is common practice to refer to plant MVA in terms of per unit or percentage values
c. transmission line and cable constants are given in ohms/km
 Before any system calculations can take place, the system parameters must be referred
to 'base quantities' and represented as a unified system of impedances in either,
percentage, or per unit values.
 Per-unit analysis is based on "normalized" representations of the electrical quantities
(i.e., voltage, current, impedance, etc.). The per-unit equivalent of any electrical
quantity is dimensionless. It is defined as the ratio of the actual quantity in units (i.e.,
volts, amperes, ohms, etc.) to an appropriate base value of the electrical quantity.
 Per Unit (p.u.) value = Actual value / Base value
13
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Referring Impedances
14
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana
Can be derived from V1/V2 = I2/I1
Which translates into V1/V2=(V2/R2)/ (V1/R1)
9/9/2016
Formulae used in Per-Unit Calculations
 The base quantities are:
three-phase power in MVA (MVA rating of largest item or 100MVA) It is constant at all
voltages .
The line voltage in kV. Fixed at one part and it is transferred through transformers to
obtain base voltages of the other part of the system.
The following Equations are used in Per- Unit Calculation:
- Ip.u = Iactual/ Ibase
- Sp.u = Sactual / S base
-Vp.u = Vactual / Vbase
- Base Current (kA), Ib = MVAb (3ø)/ {1.732 x kVb (L-L)}
- Base Impedance (Ohm) Zb= (kV)2
(L-L)/ MVAb 3ø
- Zp.u
(new)
= Z p.u
(old)
x[MVAb
(N)
/ MVAb
(old)
] x[kVb
(old)
/ kVb
(new)
]2
15
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Per Unit Impedance
16
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Per Unit Impedance
17
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Percentage Impedance
18
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Percentage Impedance
19
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Percentage Impedance
20
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Percentage Impedance
21
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Transformer Base Voltage Selection
22
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Example
23
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Example
24
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
MVA METHOD FOR 3 PHASE SHORT CIRCUIT
CALCULATION
 The MVA Method is recognized and widely acceptable by industry in
calculating power system short circuits where the reactance of all circuit
components far exceeds resistance producing a consistently high X/R
ratio throughout the system.
 Combined MVA of components connected in series and parallel are
calculated using the following formulas:
 series: MVA1, 2 = MVA1 X MVA2 / (MVA1 + MVA2)
 parallel: MVA1, 2 = MVA1 + MVA2
 As can be seen from the formulas above, series MVA’s are being
calculated same as resistances in parallel. Parallel MVA combinations are
done same as resistances in series.
 MVA diagram undergoes same reduction process as impedance diagram,
only that MVA values are used instead of per unit impedances or
reactances.
25
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
MVA METHOD FOR 3 PHASE SHORT CIRCUIT
CALCULATION
 The MVA method is a modification of the Ohmic method where the impedance of a circuit equals the sum of
the impedances of components constituting the circuit.
 In practice, the MVA method is used by separating the circuit into components and calculating each
component with its own infinite bus as shown in figures 1 and 2 below:
M
15 MVA
Xd = 0.2
20MVA
33 / 11kV
X = 10%
T2161 / 33 kV
X = 10%
161 kV T1
50MVA
Line 33kV
X = 4.0Ω
Sk
’’
= 700MVA
Figure 1-One Line Diagram
700 500 272.25
200
75
3ø F.
700 / 1 50 / 0.1 (33)2
/ 4
15 / 0.2
20 / 0.1
3ø F.
Figure 2- MVA Diagram
1 2 3
4
5
11kV
G
103.8 MVA
26
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
MVA METHOD FOR 3 PHASE SHORT CIRCUIT
CALCULATION
 In our example:
MVA’s 1& 2 are in series
- MVA (1&2) = (700 x 500) / (700 + 500) = 291.67
MVA’s (1&2) & 3 are in series
- MVA = (291.67 x 272.25) / (291.67 + 272.25) = 140.81
MVA’s (1,2&3) // MVA 4
- MVA at the point = 140.81 + 75 = 215.81
MVA’s (1,2,3&4) in series with MVA 5
MVA at the Fault point = (251.81 x 200) /(251.81 + 200) = 103.802
Considering Voltage Factor of 1.1, MVA = 103.802 x 1.1 = 114.18
- 3Ø ISC =MVA /(1.732 x Un) =114.18 /(1.732 x 11) = 5.99 kA
Per Unit System is more accurate than the MVA method in the analysis of
three (3) phase faults.
27
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
D.C. Transient and Offsets
28
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
END OF PART 1
WAGE OPENER FOR PART 2
RIDDLE!!!
29
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Goal of the Presentation-2
To appreciate the use of Symmetrical Components for
Asymmetrical Short Circuit Calculation.
An asymmetric or unbalanced fault does not affect each
of the three phases equally.
Common types of asymmetric faults:
line-to-line
line-to-ground
double line-to-ground
The analysis of this type of fault is often simplified by
using methods such as symmetrical components.
30
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
ASYMMETRICAL OR
UNBALANCED FAULTS
CALCULATIONS
Developed by Charles LeGeyt Fortescue (1876–1936) in
1918. Fortescue was an Electrical Engineer and he worked
for Westinghouse Corporation at East Pittsburgh,
Pennsylvania. He developed the method of Symmetrical
Components to resolve unbalance fault conditions.
31
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
UNBALANCED FAULTS-1
Unbalanced Faults may be classified into SHUNT
FAULTS and SERIES FAULTS
SHUNT FAULTS
Line to Ground
Line to Line
Line to Line to Ground
The above faults are described as single shunt faults
because they occur at one location and involve a
connection between one phase and another or to
earth. 32
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
UNBALANCED FAULTS-2
Unbalanced Faults may be classified into SHUNT
FAULTS and SERIES FAULTS
OPEN CIRCUIT/ SERIES FAULTS
Single phase open circuit
Double phase open circuit
33
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
CAUSES OF UNBALANCE FAULTS
CAUSES OF SHUNT FAULTS
Insulation Breakdown
Lightning Discharges
Mechanical Damage
CAUSES OF OPEN CIRCUIT FAULTS
Broken Conductor
Operation of Fuses
Mal-operation of single phase CB
During Unbalanced Faults, symmetry of system is
lost. Hence single phase representation is no longer
valid for the fault analysis.
34
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Analysis of Unbalanced Faults
Unbalanced faults are analysed using :-
Symmetrical Components
Equivalent Sequence Networks of the Power System
Connection of Sequence Networks appropriate to the
Type of Fault
35
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Sequence Components
The Symmetrical Components consist of three
subsystems for an unbalanced three-phase system.
They are;
Positive Sequence Subsystem-consisting of three
phasers of equal magnitude and 120° phase
displacement, and having the same phase sequence as
the original balanced system of phasers.
36
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Sequence Components
The second subsystem is termed the 'negative
sequence' system, consisting of three phasers of
equal magnitude and 120° phase displacement, and
having a phase sequence which is the reverse of the
original balanced system of phasers.
The final subsystem is termed the 'zero sequence'
system, consisting of three phasers of equal
magnitude and zero phase displacement.
37
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
ILLustration of Symmetrical
Components
Orientation of the symmetrical components are as follows:
V A1
V B1V C1
V C2
V A2 VAo
V B2
VBo
120° 240°
V Co
Zero Sequence Phasors
Negative Sequence PhasorsPositive Sequence Phasors
38
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Sequence Components-Three Phase
Fault
39
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Sequence Components
PHASE TO PHASE FAULT
ONLY +VE AND –VE SEQUENCE COMPNENTS EXISTS
E
Z1 Z2
I a11 I a22
Zo
I a00 = 0= 0
Sequence Network Interconnection for phase to phase fault
40
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Sequence Components-Single Phase-Earth Fault.
All sequence components are present
41
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
By definition, the magnitude and phase angle of
any phasor in an unbalanced three-phase system
is equal to the vector addition of the symmetrical
components from the respective sequence
subsystems.
Symmetrical Components
42
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Symmetrical Components
43
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Symmetrical Components
To provide a mathematical perspective on the
preceding discussion of phasor magnitudes and phase
displacements, it is necessary to define a phase
displacement operator 'a'.
a = 1<120° = -0.5 + j0.866
Successive applications of operator 'a' to a given
vector will result in rotation of that vector through
120°, 240° and 360°, degrees, as shown below.
44
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Symmetrical Components
a = 1<120° = 1ej2π/3
= -0.5 +j0.866
 a2
= 1<240° = 1ej4π/3
= -0.5 -j0.866
 a3
= 1<360° = 1e]2π
= 1
Therefore we have;
45
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Converting from phase value toConverting from phase value to
sequence componentssequence components
46
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Converting from phase value to
sequence components
47
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Symmetrical Components-Similarly Equations for
sequence Currents can be derived
48
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana
It can be deduced that
In= Ia + Ib + Ic = 3I0
9/9/2016
Phase Sequence Equivalent Circuits
E
a2
E
aE
I
a2
I
a I
P Q
P1 Q1
Z1 = E/I
Positive Sequence Impedance
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 49
Phase Sequence Equivalent Circuits
E
aE
a2
E
I
a2
I
a I
P Q
P2 Q2
Z2 = E/I
Negative Sequence Impedance
For static non-rotating plant :- Z2= Z1
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 50
Phase Sequence Equivalent Circuits
E
I
I
I
P Q
P0 Q0
Z0 = E/I
3I
Zero Sequence Impedance
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 51
Sequence Networks
+ve, -ve and zero sequence networks are drawn for a
‘reference’ phase. This is usually taken as the ‘A’ phase.
Faults are selected to be ‘balanced’ relative to the
reference ‘A’ phase.
e.g. For Ø/E faults, we consider an A-E fault
For Ø/Ø faults, we consider a B-C fault
 Sequence network interconnection is the simplest for the
reference phase.
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 52
1. Start with neutral point N1
-All generator and load neutrals are connected to N1
 2. Include all source voltages:- Phase-neutral voltage
 3. Impedance network:- Positive sequence impedance per
phase
 4. Diagram finishes at fault point F1
Positive Sequence Diagram
N1
E1
Z1
F1
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 53
Positive Sequence Diagram
G
T Line F
R
N
E
N1
E1 Z G1 Z T1 Z L1 I1
F1
N1
V1
V1=Positive sequence PH-N voltage at fault point
I1=Positive sequence phase current flowing into F1
V1=E1 –I1 (ZG1+ ZT1 + ZL1)
System Single Line Diagram
Positive Sequence Diagram
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 54
Negative Sequence Diagram
 Start with neutral point N2
-All generator and load neutrals are connected to N2
 No voltages included
-No negative sequence voltage is generated!
 Impedance network
-Negative sequence impedance per phase
 Diagram finishes at fault point F2
N2
Z2
F2
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 55
Negative Sequence Diagram
G
T Line F
R
N
E
N2
Z G2 Z T2 Z L2 I2
F2
N2
V2
V2=Negative sequence PH-N voltage at fault point
I2=Negative sequence phase current flowing into F2
V2= –I2 (ZG2+ ZT2 + ZL2)
System Single Line Diagram
Negative Sequence Diagram
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 56
Zero Sequence Diagram
For “In Phase” (Zero Phase Sequence) currents to flow in each phase
of the system, there must be a fourth connection (this is typically the
neutral or earth connection).
 IAo+ IBo+ICo=3IAo
IAo
IBo
ICo
N
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 57
Zero Sequence Diagram
N
E
R
3IAo
Resistance Earthed System :-
Zero sequence voltage between N & E is given by
Vo= 3IAo * R
Zero sequence impedance of neutral to earth path
Zo= Vo/ IAo = 3R
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 58
Zero Sequence Equivalent “D y” Transformer”
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 59
Zero Sequence Equivalent “D y” Transformer
Thus, Equivalent single phase zero sequence diagram is as
shown:-
Side terminal Z To
I o
Y side
terminal
N o
(Eo)
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 60
Zero Sequence Equivalent Circuits
9/9/2016
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 61
Equations Defining Shunt Fault
Conditions
It should be noted that for any type of fault there are
three equations that define the fault conditions. They
are as follows:
Single Phase-to-earth (A-E)
Ib= 0 (Ib= 0, Ic = 0, Because Phases B and C do not
contribute to fault current)
Ic = 0
Va = 0 (Va = 0, because voltage at the faulted phase
decreases to Zero)
62
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Equations Defining Shunt Fault
Conditions
Phase-phase (B-C)
Ia= 0 (Ia= 0, Because Phase A does not
contribute to fault current)
Ib =-Ic
Vb = Vc
63
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Equations Defining Shunt Fault
Conditions
Phase-phase-to-earth (B-C-E)
Ia= 0 (Ia= 0, Because Phase A does not
contribute to fault current)
Ib + Ic= In
Vb = Vc=0 (Because voltages at the faulted phases
decrease to Zero)
64
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Equations Defining Shunt Fault
Conditions
Three Phase fault (A-B-C or A-B-C-E)
Ia + Ib + Ic= 0 (Because the system is balanced and
hence In= Ia + Ib + Ic=0)
Va = Vc
Vb = Vc
65
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Single Phase to Earth Fault-1
We recall that for Single Phase to ground fault:
Ib=Ic = 0
Va = 0 and therefore we can write;
I1=1/3(Ia + aIb + a2
Ic)=1/3Ia
I2=1/3(Ia + a2
Ib + aIc)=1/3Ia Therefore
I0=I1=I2= 1/3Ia
I0=1/3(Ia + Ib + Ic)=1/3Ia 66
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Single Phase to Earth Fault-2
Also
Va = 0 and therefore we can write;
V1 +V2 +V0 =0 (Since Va =V1 +V2 +V0 =0)
But
V1 =V-I1Z1,V2=-I2Z2andV0=-I0Z0
Substituting we have;
V-I1Z1 -I2Z2-I0Z0=0 since I1=I2=I0, we have
V=I1(Z1 + Z2+ Z0)
67
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Single Phase to Earth Fault-3
The above analysis indicate that the equivalent circuit
for the fault is obtained by connecting the sequence
networks in series as shown below;
68
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Single Phase to Earth Fault-4
It also follows that;
I1= E/(Z1 + Z2+ Z0)
From the equation described earlier, I0=I1=I2= 1/3Iaandtherefore
Ia = 3I1 = 3E/(Z1 + Z2+ Z0)
69
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Single Phase to Earth Fault-5
In the more general case, with nonzero fault
resistance, the equality of I1; I2 and I0 is maintained, and
3I1 flows through the fault resistance. Therefore, it is
necessary that 3Zf exist in series with the zero
sequence subsystem to achieve the required effect.
The generalized equation is as follows:
Ia = 3I1 = 3E/(Z1 + Z2+ Z0 + 3Zf)
70
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016
Phase to Phase Fault (B-C)-1
We recall that for a phase-phase fault,
Ia = 0, implying
I1=1/3(Ia + aIb + a2
Ic)=1/3(aIb + a2
Ic)
I2=1/3(Ia + a2
Ib + aIc)=1/3(a2
Ib + aIc)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 719/9/2016
Phase to Phase Fault (B-C)-2
Also,
Ib= -Ic
I1=1/3(aIb + a2
Ic) = 1/3(alb-a2
lb) = l/3Ib(a-a2
)
I2=1/3(a2
Ib + aIc) = 1/3(a2
lb-alb) = l/3Ib(a2
-a)
The above equations illustrate that;
I 1 = - I 2
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 729/9/2016
Phase to Phase Fault (B-C)-3
By inspection, the equations for this fault condition
are as follows:
I1=E/(Z1 + Z2)
I2=-E/(Z1 + Z2)
I0 = 0
It must be noted that no zero sequence current exist
since there is no connection to ground.Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 739/9/2016
Phase to Phase Fault (B-C)-4
From the equation below;
I1=1/3(aIb + a2
Ic) = 1/3(alb-a2
lb) = l/3Ib(a-a2
), Since Ib=-Ic
But
a = 1<120° = 1ej2π/3
= -0.5 +j0.866
a2
= 1<240° = 1ej4π/3
= -0.5 -j0.866
Thereforeitfollowsthat,a-a2
= j1.732= j√3 and I1= j√3/3Ib
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 749/9/2016
Phase to Phase Fault (B-C)-5
Finally it implies that;
I1=1/3(aIb + a2
Ic) = 1/3(alb-a2
lb) = l/3Ib(a-a2
)
Since,
a-a2
= j1.732= j√3
I1 = j √3 /3Ib= jIb/ √3 by rationalization.
hence Ib =-j √3 I1
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 759/9/2016
Phase to Phase Fault (B-C)-6
Similarly;
I2=1/3(a2
Ib + aIc) = 1/3(a2
lb-alb) = l/3Ib(a2
-a)
And since
a2
-a = -j1.732= -j√3, we have
I2 = -j √3 /3Ib= -jIb/ √3 by rationalization.
hence Ib =j √3 I2
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 769/9/2016
Phase to Phase Fault (B-C)-7
By inspection, the equations for this fault condition
are as follows:
I1=E/(Z1 + Z2) but Ib =-j √3 I1
Therefore
Ib =-j √3 E/(Z1 + Z2)
Also,Ic =-Ib
Therefore Ic =j √3 E/(Z1 + Z2)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 779/9/2016
Phase to Phase Fault (B-C)-8
In the more general case, with nonzero fault
resistance, the generalized equation, based on the
fault impedance of Zf is expressed below:
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 78
f
cb
ZZZ
Ej
II
++
±
==
21
3
9/9/2016
Double Phase to Ground Fault (B-C-E)
We recall that for double Phase to Ground Fault
(B-C-E), the following equations can be written:
Ia= 0 (Ia= 0, Because Phase A does not
contribute to fault current)
Ib + Ic= In
Vb = Vc=0 (Because voltages at the faulted phases
decrease to Zero)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 799/9/2016
Double Phase to Ground Fault (B-C-E)
From the general equation below, we have:
V-I1Z1 = -I2Z2 from(V1=V2=V0=Va/3) and Vb = Vc=0
Also, Since Ia= 0 (Ia= 0, Because Phase A does not
contribute to fault current)
we have, I1 + I2 + I0= 0
And it follows that;
I1 = -( I2 + I0)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 809/9/2016
Double Phase to Ground Fault (B-C-E)
Vb = Vc=0 (Since voltages at the faulted phases
decrease to Zero)
Also implies, V1 = V2 = V0 = 1/3Va
Given that all three sequence voltages are equal in
phase and magnitude, and given that the sequence
currents sum vectorially to zero, it is obvious that the
three sequence networks are in parallelArmstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 819/9/2016
Double Phase to Ground Fault (B-C-E)
From the fact that
V1 = V2 = V0 = 1/3Va,wecanwrite
V2 = V0, and hence I2Z2 = I0Z0
The negative and zero sequence currents can be derived on the basis
of the current divider principle as shown below:
I2=-I1 Z0/(Z2+ Z0), and I0=-I1 Z2/(Z2+ Z0)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 829/9/2016
Double Phase to Ground Fault (B-C-E)
Equating V1 and V2, we have
V-I1Z1 = -I2Z2 orV = I1Z1 - I2Z2,whereV=E= phase voltage
Substituting I2, I2=-I1 Z0/(Z2+ Z0), into the above equation,
It gives,
 V = I1[Z1 + Z0Z2 /(Z0 + Z2)]
Therefore;
I1= E(Z0 + Z2)/(Z1Z0+Z1Z2 +Z0Z2)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 839/9/2016
Double Phase to Ground Fault (B-C-E)
Finally,
Substituting I2andI0into the above equation,
I2=-I1 Z0/(Z2+ Z0) , I0=-I1 Z2/(Z2+ Z0)
and
I1= E(Z0 + Z2)/(Z1Z0+Z1Z2 +Z0Z2)
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 84
021
2
IaIIaIb ++=
9/9/2016
Double Phase to Ground Fault (B-C-E)
We have;
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 85
020121
20
3
ZZZZZZ
aZZ
EIb
++
−
⋅=
9/9/2016
Three Phase Fault (A-B-C or A-B-C-E)
We recall that for a three phase fault;
Ia + Ib + Ic= 0 (Because the system is balanced and
hence In= Ia + Ib + Ic=0)
Va = Vc
Vb = Vc
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 869/9/2016
Three Phase Fault (A-B-C or A-B-C-E)
It should be noted that, because this fault type is
completely balanced, there are no zero- or negative-
sequence currents;
 By inspection we can write;
I1= E/(Z1+ Zf) also I2 = I0 =0
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 879/9/2016
Three Phase Fault (A-B-C or A-B-C-E)
It finally follows that for a three phase fault;
Ia= Ib = Ic = E/(Z1+ Zf) also I2 = I0 =0
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana 889/9/2016
CONCLUSION-1
It must be emphasized that in very large and complex
networks, system computer programs are used for
short circuit analysis.
In the Electricity Company of Ghana (ECG), ASPEN
software is used for short circuit analysis.
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016 89
CONCLUSION-2
I would like to first of all thank God for His guidance and for the
wisdom and understanding He gave me to put this presentation
together.
Secondly, I appreciate the efforts of Ing. Godfred Mensah/ SM/System
Planning and Mr. Frank Osei Owusu of Protection Applications whom
I understudied when preparing for this presentation.
Finally, I very much appreciate your presence for this
presentation
THANK YOU ALL FOR COMING.!!!
Armstrong Okai Ababio/ Electrical Engineer/
Electricity Company of Ghana9/9/2016 90

More Related Content

What's hot

Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationkhaliq ahmed
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Reactive power and voltage control
Reactive power and voltage controlReactive power and voltage control
Reactive power and voltage controlSourabh sharma
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault AnalysisSANTOSH GADEKAR
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control8141245710
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power systemBalaram Das
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlSANTOSH GADEKAR
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformerSumeet Ratnawat
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptxThien Phan Bản
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation ControlBirju Besra
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizingHimmelstern
 

What's hot (20)

Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Swing equation
Swing equationSwing equation
Swing equation
 
Reactive power and voltage control
Reactive power and voltage controlReactive power and voltage control
Reactive power and voltage control
 
EE6603 - Power System Operation & Control
EE6603 - Power System Operation & ControlEE6603 - Power System Operation & Control
EE6603 - Power System Operation & Control
 
Lecture 02.pptx
Lecture 02.pptxLecture 02.pptx
Lecture 02.pptx
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control
 
PPT Fault Analysis
PPT Fault AnalysisPPT Fault Analysis
PPT Fault Analysis
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
 
Automatic Generation Control
Automatic Generation ControlAutomatic Generation Control
Automatic Generation Control
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Economic load dispatch
Economic load dispatchEconomic load dispatch
Economic load dispatch
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizing
 

Viewers also liked

File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysiskirkusawi
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission linevishalgohel12195
 
Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007Viren Pandya
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis pptkarikalan123
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedureMustafa Ismail
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...vaibyfrndz
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
 
Generics and Inference
Generics and InferenceGenerics and Inference
Generics and InferenceRichard Fox
 
Análisis cluster en sistemas agropecuarios
Análisis cluster en sistemas agropecuariosAnálisis cluster en sistemas agropecuarios
Análisis cluster en sistemas agropecuariosSandra Fumero
 
Electrical Agents
Electrical AgentsElectrical Agents
Electrical AgentsJLS10
 
Work Experience Report - Ganamotse
Work Experience Report - GanamotseWork Experience Report - Ganamotse
Work Experience Report - GanamotseGaenamele Ganamotse
 
Ch 21 Alternating Current
Ch 21 Alternating CurrentCh 21 Alternating Current
Ch 21 Alternating CurrentRohit Mohd
 
Electricity and Magnetism Lesson PowerPoint, Physical Science Unit
Electricity and Magnetism Lesson PowerPoint, Physical Science UnitElectricity and Magnetism Lesson PowerPoint, Physical Science Unit
Electricity and Magnetism Lesson PowerPoint, Physical Science Unitwww.sciencepowerpoint.com
 

Viewers also liked (20)

File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission line
 
Unsymmetrical Fault
Unsymmetrical FaultUnsymmetrical Fault
Unsymmetrical Fault
 
Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedure
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Generics and Inference
Generics and InferenceGenerics and Inference
Generics and Inference
 
Ellis Patents FlexiStrap Cable Straps
Ellis Patents FlexiStrap Cable StrapsEllis Patents FlexiStrap Cable Straps
Ellis Patents FlexiStrap Cable Straps
 
Análisis cluster en sistemas agropecuarios
Análisis cluster en sistemas agropecuariosAnálisis cluster en sistemas agropecuarios
Análisis cluster en sistemas agropecuarios
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
Electrical Agents
Electrical AgentsElectrical Agents
Electrical Agents
 
Work Experience Report - Ganamotse
Work Experience Report - GanamotseWork Experience Report - Ganamotse
Work Experience Report - Ganamotse
 
AE outcome
AE outcomeAE outcome
AE outcome
 
Ch 21 Alternating Current
Ch 21 Alternating CurrentCh 21 Alternating Current
Ch 21 Alternating Current
 
3.3.2 transformers
3.3.2   transformers3.3.2   transformers
3.3.2 transformers
 
Balanced faults
Balanced faultsBalanced faults
Balanced faults
 
Electricity and Magnetism Lesson PowerPoint, Physical Science Unit
Electricity and Magnetism Lesson PowerPoint, Physical Science UnitElectricity and Magnetism Lesson PowerPoint, Physical Science Unit
Electricity and Magnetism Lesson PowerPoint, Physical Science Unit
 

Similar to Understanding symmetrical and asymmetrical faults using MVA and symmetrical component methods

Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...paperpublications3
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.pptAshaLatha456489
 
Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...IAEME Publication
 
POWER SYSTEM ANALYSIS_254ppt.pdf
POWER SYSTEM ANALYSIS_254ppt.pdfPOWER SYSTEM ANALYSIS_254ppt.pdf
POWER SYSTEM ANALYSIS_254ppt.pdfMillionAlemayehu2
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculationsRonald Santos
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)ingcortez
 
1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdfLiewChiaPing
 
Analysis-of-Faults-AREVA.ppt
Analysis-of-Faults-AREVA.pptAnalysis-of-Faults-AREVA.ppt
Analysis-of-Faults-AREVA.pptHariNair812688
 
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic System
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic SystemIRJET- Fault Analysis of Grid Connected Solar Photovoltaic System
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic SystemIRJET Journal
 
Calculation of short circuit currents
Calculation of short circuit currents Calculation of short circuit currents
Calculation of short circuit currents Maria Romina Angustia
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation Chandrabhan Sharma
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Samuel Okhuegbe
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET Journal
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMIJERA Editor
 
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...IRJET Journal
 
PrezentacijaIEEP2013SpremicObradovicX
PrezentacijaIEEP2013SpremicObradovicXPrezentacijaIEEP2013SpremicObradovicX
PrezentacijaIEEP2013SpremicObradovicXSinisa Spremic
 

Similar to Understanding symmetrical and asymmetrical faults using MVA and symmetrical component methods (20)

Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
 
Em manual 1
Em manual 1Em manual 1
Em manual 1
 
Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...
 
POWER SYSTEM ANALYSIS_254ppt.pdf
POWER SYSTEM ANALYSIS_254ppt.pdfPOWER SYSTEM ANALYSIS_254ppt.pdf
POWER SYSTEM ANALYSIS_254ppt.pdf
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)
 
1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf
 
40220130406009 2
40220130406009 240220130406009 2
40220130406009 2
 
Analysis-of-Faults-AREVA.ppt
Analysis-of-Faults-AREVA.pptAnalysis-of-Faults-AREVA.ppt
Analysis-of-Faults-AREVA.ppt
 
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic System
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic SystemIRJET- Fault Analysis of Grid Connected Solar Photovoltaic System
IRJET- Fault Analysis of Grid Connected Solar Photovoltaic System
 
Calculation of short circuit currents
Calculation of short circuit currents Calculation of short circuit currents
Calculation of short circuit currents
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
 
PrezentacijaIEEP2013SpremicObradovicX
PrezentacijaIEEP2013SpremicObradovicXPrezentacijaIEEP2013SpremicObradovicX
PrezentacijaIEEP2013SpremicObradovicX
 
20320140501008
2032014050100820320140501008
20320140501008
 

Understanding symmetrical and asymmetrical faults using MVA and symmetrical component methods

  • 1. Presented by Armstrong Okai Ababio 1 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 2. Goal of the Presentation-1 To Appreciate the use of Ohmic and MVA Methods for Symmetrical Short Circuit Calculation. A symmetrical or balanced fault affects each of the three-phases equally (Three phase fault) 2 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 3. Goal of the Presentation-2 To appreciate the use of Symmetrical Components for Asymmetrical Short Circuit Calculation. An asymmetric or unbalanced fault does not affect each of the three phases equally. Common types of asymmetric faults: line-to-line line-to-ground double line-to-ground The analysis of this type of fault is often simplified by using methods such as symmetrical components. 3 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 4. Introduction The operation of a power system departs from normal after the occurrence of a fault. The most common faults in any electrical installation are short circuits, i.e. a breakdown of insullation between conductive parts which normally are at different potential. Fault give rise to abnormal operating conditions such as excessive current and voltages at certain points in the network. The magnitude of fault current depends on the generated power in the system, the distance to these sources, fault resistance and for ground fault it depends also on the neutral point treatment of the system. 4 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 5. Effect of Faults in a 3 phase Network  A fault will cause voltage and current disturbances, including a complete voltage collapse near the fault location.  The voltage gradient in the ground and across the earthing resistance create dangerous step and touch voltages near the fault.  The dynamic forces of the fault current, the electric arc at the fault location and the thermal effects of the current on the network elements in the current path all cause damage to the plant equipment and personnel.  The voltage and current disturbances interrupt the transmission of power and thus also affect customers. 5 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 6. Effect of Faults-2  A large amount of power is dissipated at the fault point, which means lost of revenue for the utility.  Failure to remove a fault will usually result in rapid expansion of damage to the system.  Various protection equipment are used in guarding against such faults condition. An idea of the magnitudes of such fault currents gives the Engineer the current settings of the various protection devices and ratings of circuit breakers in the network. 6 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 7. Effect of Faults-3  In the light of the above discussed effects of faults, FAULT or SHORT CIRCUIT ANALYSIS is highly needed.  Performing short-circuit calculations requires an understanding of various system components and their interaction.  Components of Power System: Generators, Transformers, Transmission lines, Protection Systems(control and monitoring system), Switch gear, Load. 7 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 8. Types of Fault/ Short Circuits in a 3 phase network Three-phase fault with or without earth (5%)  Phase-to- phase clear of ground (10 – 15%)  Two-phase-to-earth fault (10 – 20%)  Phase-to-earth fault (65 – 70%)  Fault Incident: 85% of faults are overhead line. 50% of these are due to lightning strikes.  L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 8 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 9. 3 PHASE FAULTS-1  A 3-ph fault affects the three-phase network equally (symmetrical fault). They rarely occur. All three conductors are equally involved and carry the same rms short- circuit current. There is the need to use only one conductor for the calculation.  It is valid because system is maintained in a balanced state during fault.  Voltages are equal and 120° apart.  Currents are equal and 120° apart.  Power system plant symmetrical:-  Phase impedance equal  Mutual impedance equal  Shunt admittances equal  Causes:  System energization with maintenance earthing clamps still connected.  1ø faults developing into 3ø faults. Etc. 9 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 10. 3 PHASE FAULTS-2  A 3-ph fault affects the three-phase network symmetrically. They rarely occur. All three conductors are equally involved and carry the same rms short- circuit current. There is the need to use only one phase (conductor ) for the calculation. The Per unit system or MVA method is used for the analysis of Three phase fault. 10 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 11. 3 PHASE FAULTS 11 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 12. 3 PHASE FAULTS 12 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 13. Over View of Per Unit System  Per- Unit Notations. It is used to simplify calculations on system with more than two voltages. ( The √ are eliminated) It can be seen by inspection of any power system diagram that: a. several voltage levels exist in a system b. it is common practice to refer to plant MVA in terms of per unit or percentage values c. transmission line and cable constants are given in ohms/km  Before any system calculations can take place, the system parameters must be referred to 'base quantities' and represented as a unified system of impedances in either, percentage, or per unit values.  Per-unit analysis is based on "normalized" representations of the electrical quantities (i.e., voltage, current, impedance, etc.). The per-unit equivalent of any electrical quantity is dimensionless. It is defined as the ratio of the actual quantity in units (i.e., volts, amperes, ohms, etc.) to an appropriate base value of the electrical quantity.  Per Unit (p.u.) value = Actual value / Base value 13 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 14. Referring Impedances 14 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana Can be derived from V1/V2 = I2/I1 Which translates into V1/V2=(V2/R2)/ (V1/R1) 9/9/2016
  • 15. Formulae used in Per-Unit Calculations  The base quantities are: three-phase power in MVA (MVA rating of largest item or 100MVA) It is constant at all voltages . The line voltage in kV. Fixed at one part and it is transferred through transformers to obtain base voltages of the other part of the system. The following Equations are used in Per- Unit Calculation: - Ip.u = Iactual/ Ibase - Sp.u = Sactual / S base -Vp.u = Vactual / Vbase - Base Current (kA), Ib = MVAb (3ø)/ {1.732 x kVb (L-L)} - Base Impedance (Ohm) Zb= (kV)2 (L-L)/ MVAb 3ø - Zp.u (new) = Z p.u (old) x[MVAb (N) / MVAb (old) ] x[kVb (old) / kVb (new) ]2 15 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 16. Transformer Per Unit Impedance 16 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 17. Transformer Per Unit Impedance 17 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 18. Transformer Percentage Impedance 18 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 19. Transformer Percentage Impedance 19 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 20. Transformer Percentage Impedance 20 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 21. Transformer Percentage Impedance 21 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 22. Transformer Base Voltage Selection 22 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 23. Example 23 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 24. Example 24 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 25. MVA METHOD FOR 3 PHASE SHORT CIRCUIT CALCULATION  The MVA Method is recognized and widely acceptable by industry in calculating power system short circuits where the reactance of all circuit components far exceeds resistance producing a consistently high X/R ratio throughout the system.  Combined MVA of components connected in series and parallel are calculated using the following formulas:  series: MVA1, 2 = MVA1 X MVA2 / (MVA1 + MVA2)  parallel: MVA1, 2 = MVA1 + MVA2  As can be seen from the formulas above, series MVA’s are being calculated same as resistances in parallel. Parallel MVA combinations are done same as resistances in series.  MVA diagram undergoes same reduction process as impedance diagram, only that MVA values are used instead of per unit impedances or reactances. 25 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 26. MVA METHOD FOR 3 PHASE SHORT CIRCUIT CALCULATION  The MVA method is a modification of the Ohmic method where the impedance of a circuit equals the sum of the impedances of components constituting the circuit.  In practice, the MVA method is used by separating the circuit into components and calculating each component with its own infinite bus as shown in figures 1 and 2 below: M 15 MVA Xd = 0.2 20MVA 33 / 11kV X = 10% T2161 / 33 kV X = 10% 161 kV T1 50MVA Line 33kV X = 4.0Ω Sk ’’ = 700MVA Figure 1-One Line Diagram 700 500 272.25 200 75 3ø F. 700 / 1 50 / 0.1 (33)2 / 4 15 / 0.2 20 / 0.1 3ø F. Figure 2- MVA Diagram 1 2 3 4 5 11kV G 103.8 MVA 26 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 27. MVA METHOD FOR 3 PHASE SHORT CIRCUIT CALCULATION  In our example: MVA’s 1& 2 are in series - MVA (1&2) = (700 x 500) / (700 + 500) = 291.67 MVA’s (1&2) & 3 are in series - MVA = (291.67 x 272.25) / (291.67 + 272.25) = 140.81 MVA’s (1,2&3) // MVA 4 - MVA at the point = 140.81 + 75 = 215.81 MVA’s (1,2,3&4) in series with MVA 5 MVA at the Fault point = (251.81 x 200) /(251.81 + 200) = 103.802 Considering Voltage Factor of 1.1, MVA = 103.802 x 1.1 = 114.18 - 3Ø ISC =MVA /(1.732 x Un) =114.18 /(1.732 x 11) = 5.99 kA Per Unit System is more accurate than the MVA method in the analysis of three (3) phase faults. 27 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 28. D.C. Transient and Offsets 28 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 29. END OF PART 1 WAGE OPENER FOR PART 2 RIDDLE!!! 29 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 30. Goal of the Presentation-2 To appreciate the use of Symmetrical Components for Asymmetrical Short Circuit Calculation. An asymmetric or unbalanced fault does not affect each of the three phases equally. Common types of asymmetric faults: line-to-line line-to-ground double line-to-ground The analysis of this type of fault is often simplified by using methods such as symmetrical components. 30 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 31. ASYMMETRICAL OR UNBALANCED FAULTS CALCULATIONS Developed by Charles LeGeyt Fortescue (1876–1936) in 1918. Fortescue was an Electrical Engineer and he worked for Westinghouse Corporation at East Pittsburgh, Pennsylvania. He developed the method of Symmetrical Components to resolve unbalance fault conditions. 31 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 32. UNBALANCED FAULTS-1 Unbalanced Faults may be classified into SHUNT FAULTS and SERIES FAULTS SHUNT FAULTS Line to Ground Line to Line Line to Line to Ground The above faults are described as single shunt faults because they occur at one location and involve a connection between one phase and another or to earth. 32 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 33. UNBALANCED FAULTS-2 Unbalanced Faults may be classified into SHUNT FAULTS and SERIES FAULTS OPEN CIRCUIT/ SERIES FAULTS Single phase open circuit Double phase open circuit 33 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 34. CAUSES OF UNBALANCE FAULTS CAUSES OF SHUNT FAULTS Insulation Breakdown Lightning Discharges Mechanical Damage CAUSES OF OPEN CIRCUIT FAULTS Broken Conductor Operation of Fuses Mal-operation of single phase CB During Unbalanced Faults, symmetry of system is lost. Hence single phase representation is no longer valid for the fault analysis. 34 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 35. Analysis of Unbalanced Faults Unbalanced faults are analysed using :- Symmetrical Components Equivalent Sequence Networks of the Power System Connection of Sequence Networks appropriate to the Type of Fault 35 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 36. Sequence Components The Symmetrical Components consist of three subsystems for an unbalanced three-phase system. They are; Positive Sequence Subsystem-consisting of three phasers of equal magnitude and 120° phase displacement, and having the same phase sequence as the original balanced system of phasers. 36 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 37. Sequence Components The second subsystem is termed the 'negative sequence' system, consisting of three phasers of equal magnitude and 120° phase displacement, and having a phase sequence which is the reverse of the original balanced system of phasers. The final subsystem is termed the 'zero sequence' system, consisting of three phasers of equal magnitude and zero phase displacement. 37 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 38. ILLustration of Symmetrical Components Orientation of the symmetrical components are as follows: V A1 V B1V C1 V C2 V A2 VAo V B2 VBo 120° 240° V Co Zero Sequence Phasors Negative Sequence PhasorsPositive Sequence Phasors 38 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 39. Sequence Components-Three Phase Fault 39 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 40. Sequence Components PHASE TO PHASE FAULT ONLY +VE AND –VE SEQUENCE COMPNENTS EXISTS E Z1 Z2 I a11 I a22 Zo I a00 = 0= 0 Sequence Network Interconnection for phase to phase fault 40 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 41. Sequence Components-Single Phase-Earth Fault. All sequence components are present 41 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 42. By definition, the magnitude and phase angle of any phasor in an unbalanced three-phase system is equal to the vector addition of the symmetrical components from the respective sequence subsystems. Symmetrical Components 42 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 43. Symmetrical Components 43 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 44. Symmetrical Components To provide a mathematical perspective on the preceding discussion of phasor magnitudes and phase displacements, it is necessary to define a phase displacement operator 'a'. a = 1<120° = -0.5 + j0.866 Successive applications of operator 'a' to a given vector will result in rotation of that vector through 120°, 240° and 360°, degrees, as shown below. 44 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 45. Symmetrical Components a = 1<120° = 1ej2π/3 = -0.5 +j0.866  a2 = 1<240° = 1ej4π/3 = -0.5 -j0.866  a3 = 1<360° = 1e]2π = 1 Therefore we have; 45 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 46. Converting from phase value toConverting from phase value to sequence componentssequence components 46 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 47. Converting from phase value to sequence components 47 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 48. Symmetrical Components-Similarly Equations for sequence Currents can be derived 48 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana It can be deduced that In= Ia + Ib + Ic = 3I0 9/9/2016
  • 49. Phase Sequence Equivalent Circuits E a2 E aE I a2 I a I P Q P1 Q1 Z1 = E/I Positive Sequence Impedance 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 49
  • 50. Phase Sequence Equivalent Circuits E aE a2 E I a2 I a I P Q P2 Q2 Z2 = E/I Negative Sequence Impedance For static non-rotating plant :- Z2= Z1 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 50
  • 51. Phase Sequence Equivalent Circuits E I I I P Q P0 Q0 Z0 = E/I 3I Zero Sequence Impedance 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 51
  • 52. Sequence Networks +ve, -ve and zero sequence networks are drawn for a ‘reference’ phase. This is usually taken as the ‘A’ phase. Faults are selected to be ‘balanced’ relative to the reference ‘A’ phase. e.g. For Ø/E faults, we consider an A-E fault For Ø/Ø faults, we consider a B-C fault  Sequence network interconnection is the simplest for the reference phase. 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 52
  • 53. 1. Start with neutral point N1 -All generator and load neutrals are connected to N1  2. Include all source voltages:- Phase-neutral voltage  3. Impedance network:- Positive sequence impedance per phase  4. Diagram finishes at fault point F1 Positive Sequence Diagram N1 E1 Z1 F1 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 53
  • 54. Positive Sequence Diagram G T Line F R N E N1 E1 Z G1 Z T1 Z L1 I1 F1 N1 V1 V1=Positive sequence PH-N voltage at fault point I1=Positive sequence phase current flowing into F1 V1=E1 –I1 (ZG1+ ZT1 + ZL1) System Single Line Diagram Positive Sequence Diagram 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 54
  • 55. Negative Sequence Diagram  Start with neutral point N2 -All generator and load neutrals are connected to N2  No voltages included -No negative sequence voltage is generated!  Impedance network -Negative sequence impedance per phase  Diagram finishes at fault point F2 N2 Z2 F2 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 55
  • 56. Negative Sequence Diagram G T Line F R N E N2 Z G2 Z T2 Z L2 I2 F2 N2 V2 V2=Negative sequence PH-N voltage at fault point I2=Negative sequence phase current flowing into F2 V2= –I2 (ZG2+ ZT2 + ZL2) System Single Line Diagram Negative Sequence Diagram 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 56
  • 57. Zero Sequence Diagram For “In Phase” (Zero Phase Sequence) currents to flow in each phase of the system, there must be a fourth connection (this is typically the neutral or earth connection).  IAo+ IBo+ICo=3IAo IAo IBo ICo N 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 57
  • 58. Zero Sequence Diagram N E R 3IAo Resistance Earthed System :- Zero sequence voltage between N & E is given by Vo= 3IAo * R Zero sequence impedance of neutral to earth path Zo= Vo/ IAo = 3R 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 58
  • 59. Zero Sequence Equivalent “D y” Transformer” 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 59
  • 60. Zero Sequence Equivalent “D y” Transformer Thus, Equivalent single phase zero sequence diagram is as shown:- Side terminal Z To I o Y side terminal N o (Eo) 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 60
  • 61. Zero Sequence Equivalent Circuits 9/9/2016 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 61
  • 62. Equations Defining Shunt Fault Conditions It should be noted that for any type of fault there are three equations that define the fault conditions. They are as follows: Single Phase-to-earth (A-E) Ib= 0 (Ib= 0, Ic = 0, Because Phases B and C do not contribute to fault current) Ic = 0 Va = 0 (Va = 0, because voltage at the faulted phase decreases to Zero) 62 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 63. Equations Defining Shunt Fault Conditions Phase-phase (B-C) Ia= 0 (Ia= 0, Because Phase A does not contribute to fault current) Ib =-Ic Vb = Vc 63 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 64. Equations Defining Shunt Fault Conditions Phase-phase-to-earth (B-C-E) Ia= 0 (Ia= 0, Because Phase A does not contribute to fault current) Ib + Ic= In Vb = Vc=0 (Because voltages at the faulted phases decrease to Zero) 64 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 65. Equations Defining Shunt Fault Conditions Three Phase fault (A-B-C or A-B-C-E) Ia + Ib + Ic= 0 (Because the system is balanced and hence In= Ia + Ib + Ic=0) Va = Vc Vb = Vc 65 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 66. Single Phase to Earth Fault-1 We recall that for Single Phase to ground fault: Ib=Ic = 0 Va = 0 and therefore we can write; I1=1/3(Ia + aIb + a2 Ic)=1/3Ia I2=1/3(Ia + a2 Ib + aIc)=1/3Ia Therefore I0=I1=I2= 1/3Ia I0=1/3(Ia + Ib + Ic)=1/3Ia 66 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 67. Single Phase to Earth Fault-2 Also Va = 0 and therefore we can write; V1 +V2 +V0 =0 (Since Va =V1 +V2 +V0 =0) But V1 =V-I1Z1,V2=-I2Z2andV0=-I0Z0 Substituting we have; V-I1Z1 -I2Z2-I0Z0=0 since I1=I2=I0, we have V=I1(Z1 + Z2+ Z0) 67 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 68. Single Phase to Earth Fault-3 The above analysis indicate that the equivalent circuit for the fault is obtained by connecting the sequence networks in series as shown below; 68 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 69. Single Phase to Earth Fault-4 It also follows that; I1= E/(Z1 + Z2+ Z0) From the equation described earlier, I0=I1=I2= 1/3Iaandtherefore Ia = 3I1 = 3E/(Z1 + Z2+ Z0) 69 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 70. Single Phase to Earth Fault-5 In the more general case, with nonzero fault resistance, the equality of I1; I2 and I0 is maintained, and 3I1 flows through the fault resistance. Therefore, it is necessary that 3Zf exist in series with the zero sequence subsystem to achieve the required effect. The generalized equation is as follows: Ia = 3I1 = 3E/(Z1 + Z2+ Z0 + 3Zf) 70 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016
  • 71. Phase to Phase Fault (B-C)-1 We recall that for a phase-phase fault, Ia = 0, implying I1=1/3(Ia + aIb + a2 Ic)=1/3(aIb + a2 Ic) I2=1/3(Ia + a2 Ib + aIc)=1/3(a2 Ib + aIc) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 719/9/2016
  • 72. Phase to Phase Fault (B-C)-2 Also, Ib= -Ic I1=1/3(aIb + a2 Ic) = 1/3(alb-a2 lb) = l/3Ib(a-a2 ) I2=1/3(a2 Ib + aIc) = 1/3(a2 lb-alb) = l/3Ib(a2 -a) The above equations illustrate that; I 1 = - I 2 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 729/9/2016
  • 73. Phase to Phase Fault (B-C)-3 By inspection, the equations for this fault condition are as follows: I1=E/(Z1 + Z2) I2=-E/(Z1 + Z2) I0 = 0 It must be noted that no zero sequence current exist since there is no connection to ground.Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 739/9/2016
  • 74. Phase to Phase Fault (B-C)-4 From the equation below; I1=1/3(aIb + a2 Ic) = 1/3(alb-a2 lb) = l/3Ib(a-a2 ), Since Ib=-Ic But a = 1<120° = 1ej2π/3 = -0.5 +j0.866 a2 = 1<240° = 1ej4π/3 = -0.5 -j0.866 Thereforeitfollowsthat,a-a2 = j1.732= j√3 and I1= j√3/3Ib Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 749/9/2016
  • 75. Phase to Phase Fault (B-C)-5 Finally it implies that; I1=1/3(aIb + a2 Ic) = 1/3(alb-a2 lb) = l/3Ib(a-a2 ) Since, a-a2 = j1.732= j√3 I1 = j √3 /3Ib= jIb/ √3 by rationalization. hence Ib =-j √3 I1 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 759/9/2016
  • 76. Phase to Phase Fault (B-C)-6 Similarly; I2=1/3(a2 Ib + aIc) = 1/3(a2 lb-alb) = l/3Ib(a2 -a) And since a2 -a = -j1.732= -j√3, we have I2 = -j √3 /3Ib= -jIb/ √3 by rationalization. hence Ib =j √3 I2 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 769/9/2016
  • 77. Phase to Phase Fault (B-C)-7 By inspection, the equations for this fault condition are as follows: I1=E/(Z1 + Z2) but Ib =-j √3 I1 Therefore Ib =-j √3 E/(Z1 + Z2) Also,Ic =-Ib Therefore Ic =j √3 E/(Z1 + Z2) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 779/9/2016
  • 78. Phase to Phase Fault (B-C)-8 In the more general case, with nonzero fault resistance, the generalized equation, based on the fault impedance of Zf is expressed below: Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 78 f cb ZZZ Ej II ++ ± == 21 3 9/9/2016
  • 79. Double Phase to Ground Fault (B-C-E) We recall that for double Phase to Ground Fault (B-C-E), the following equations can be written: Ia= 0 (Ia= 0, Because Phase A does not contribute to fault current) Ib + Ic= In Vb = Vc=0 (Because voltages at the faulted phases decrease to Zero) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 799/9/2016
  • 80. Double Phase to Ground Fault (B-C-E) From the general equation below, we have: V-I1Z1 = -I2Z2 from(V1=V2=V0=Va/3) and Vb = Vc=0 Also, Since Ia= 0 (Ia= 0, Because Phase A does not contribute to fault current) we have, I1 + I2 + I0= 0 And it follows that; I1 = -( I2 + I0) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 809/9/2016
  • 81. Double Phase to Ground Fault (B-C-E) Vb = Vc=0 (Since voltages at the faulted phases decrease to Zero) Also implies, V1 = V2 = V0 = 1/3Va Given that all three sequence voltages are equal in phase and magnitude, and given that the sequence currents sum vectorially to zero, it is obvious that the three sequence networks are in parallelArmstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 819/9/2016
  • 82. Double Phase to Ground Fault (B-C-E) From the fact that V1 = V2 = V0 = 1/3Va,wecanwrite V2 = V0, and hence I2Z2 = I0Z0 The negative and zero sequence currents can be derived on the basis of the current divider principle as shown below: I2=-I1 Z0/(Z2+ Z0), and I0=-I1 Z2/(Z2+ Z0) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 829/9/2016
  • 83. Double Phase to Ground Fault (B-C-E) Equating V1 and V2, we have V-I1Z1 = -I2Z2 orV = I1Z1 - I2Z2,whereV=E= phase voltage Substituting I2, I2=-I1 Z0/(Z2+ Z0), into the above equation, It gives,  V = I1[Z1 + Z0Z2 /(Z0 + Z2)] Therefore; I1= E(Z0 + Z2)/(Z1Z0+Z1Z2 +Z0Z2) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 839/9/2016
  • 84. Double Phase to Ground Fault (B-C-E) Finally, Substituting I2andI0into the above equation, I2=-I1 Z0/(Z2+ Z0) , I0=-I1 Z2/(Z2+ Z0) and I1= E(Z0 + Z2)/(Z1Z0+Z1Z2 +Z0Z2) Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 84 021 2 IaIIaIb ++= 9/9/2016
  • 85. Double Phase to Ground Fault (B-C-E) We have; Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 85 020121 20 3 ZZZZZZ aZZ EIb ++ − ⋅= 9/9/2016
  • 86. Three Phase Fault (A-B-C or A-B-C-E) We recall that for a three phase fault; Ia + Ib + Ic= 0 (Because the system is balanced and hence In= Ia + Ib + Ic=0) Va = Vc Vb = Vc Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 869/9/2016
  • 87. Three Phase Fault (A-B-C or A-B-C-E) It should be noted that, because this fault type is completely balanced, there are no zero- or negative- sequence currents;  By inspection we can write; I1= E/(Z1+ Zf) also I2 = I0 =0 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 879/9/2016
  • 88. Three Phase Fault (A-B-C or A-B-C-E) It finally follows that for a three phase fault; Ia= Ib = Ic = E/(Z1+ Zf) also I2 = I0 =0 Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana 889/9/2016
  • 89. CONCLUSION-1 It must be emphasized that in very large and complex networks, system computer programs are used for short circuit analysis. In the Electricity Company of Ghana (ECG), ASPEN software is used for short circuit analysis. Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016 89
  • 90. CONCLUSION-2 I would like to first of all thank God for His guidance and for the wisdom and understanding He gave me to put this presentation together. Secondly, I appreciate the efforts of Ing. Godfred Mensah/ SM/System Planning and Mr. Frank Osei Owusu of Protection Applications whom I understudied when preparing for this presentation. Finally, I very much appreciate your presence for this presentation THANK YOU ALL FOR COMING.!!! Armstrong Okai Ababio/ Electrical Engineer/ Electricity Company of Ghana9/9/2016 90