  • 1. Demonstration Thermography reportCompany Testo Ltd Tester: Newman Lane Andy McGrath Alton, Hampshire, GU34 2QJ Phone: 01420 544433 E-Mail: amcgrath@testo.co.ukDevice Testo 875 series Serial No.: 1434423 Lens: 32 degree wide angle lensCustomer Demonstration Thermography Measuring Site: Report Thermal Surveys Various Sites Various Electrical Installations UK /Applications for Demonstration Purposes Thermal Images with Testo 875 series Thermal Imaging Cameras Measuring Date: Various Measuring DatesTask Demonstration Thermography Report, to demonstrate the Capabilities of the Testo Thermal Imaging cameras and the Testo IR software. Demonstration Thermography Report of various Electrical Installations / Applications. Page 1/18
  • 2. Demonstration Thermography reportFile: Date: Measuring Time:IV_00041.BMT 17/06/2008 15:23:23Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 96.8 0.95 20.0 -Measure point 2 110.0 0.95 20.0 -Measure point 3 109.3 0.95 20.0 -Measure point 4 112.0 0.95 20.0 -Measure point 5 112.2 0.95 20.0 -Measure point 6 91.7 0.95 20.0 -Measure point 7 95.7 0.95 20.0 -Measure point 8 97.6 0.95 20.0 -Remarks:Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electricalequipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.Image of Electrical connections. As can be seen from the spot temperature markers on the thermal image,these connections are showing High temperatures and require further investigation. Page 2/18
  • 3. Demonstration Thermography reportFile: Date: Measuring Time:IV_00393.BMT 12/08/2010 13:45:48Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 38.3 0.95 20.0 -Hot spot 1 49.5 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Blue / Red " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 3/18
  • 4. Demonstration Thermography reportFile: Date: Measuring Time:IV_00218.BMT 28/10/2009 14:38:29Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 45.7 0.95 20.0 -Hot spot 1 142.7 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Iron " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 4/18
  • 5. Demonstration Thermography reportFile: Date: Measuring Time:IV_00223.BMT 28/10/2009 14:44:52Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 33.0 0.95 20.0 -Measure point 2 45.2 0.95 20.0 -Measure point 3 52.3 0.95 20.0 -Hot spot 1 51.6 0.95 20.0 -Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Blue / Red " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 5/18
  • 6. Demonstration Thermography reportFile: Date: Measuring Time:IV_00275.BMT 14/05/2010 11:16:42Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 33.4 0.95 20.0 -Measure point 2 33.6 0.95 20.0 -Hot spot 1 53.5 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Iron " Palette.The Auto Hot Spot Indicator HS1, indicates the Apparent temperature of one of the supply cables.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 6/18
  • 7. Demonstration Thermography reportFile: Date: Measuring Time:IV_00267.BMT 14/05/2010 11:09:59Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksHot spot 1 50.0 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Iron " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 7/18
  • 8. Demonstration Thermography reportFile: Date: Measuring Time:IV_00268.BMT 14/05/2010 11:10:16Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 50.1 0.95 20.0 -Hot spot 1 60.3 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Blue / Red " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 8/18
  • 9. Demonstration Thermography reportFile: Date: Measuring Time:IV_00271.BMT 14/05/2010 11:11:37Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 68.9 0.95 20.0 -Measure point 2 71.1 0.95 20.0 -Hot spot 1 71.9 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Hot / Cold " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 9/18
  • 10. Demonstration Thermography reportFile: Date: Measuring Time:IV_00272.BMT 14/05/2010 11:12:06Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 44.2 0.95 20.0 -Measure point 2 44.0 0.95 20.0 -Hot spot 1 44.8 0.95 20.0 -Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Iron " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 10/18
  • 11. Demonstration Thermography reportFile: Date: Measuring Time:IV_00355.BMT 03/12/2008 10:12:57Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 46.8 0.95 20.0 Spot Temp 1 on Grey Phase of IsolatorMeasure point 2 42.0 0.95 20.0 Spot Temp 2 on Black Phase cableMeasure point 3 39.3 0.95 20.0 Spot Temp 3 on Red Phase cableMeasure point 4 28.8 0.95 20.0 Spot Temp 4 on Blue Phase cableProfile line:Remarks:Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electricalequipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.Isolator SwitchThermal image indicates the spot temperatures of the Phase connections.A temperature profile line graph has been applied horizontally across the cables to highlight the temperaturevariation.As can be seen, the Grey phase is considerably hotter in comparison to the other phases.It is therefore recommended that an inspection of these connections is conducted. Page 11/18
  • 12. Demonstration Thermography reportFile: Date: Measuring Time:IV_00273.BMT 14/05/2010 11:14:58Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 35.1 0.95 20.0 -Hot spot 1 62.6 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The thermal imagehighlights the apparent temperature of a cable enclosed in the conduit.The Thermal image is displayed in " Iron " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. Temperature profiles graphs applied to show temperature variation across components. Page 12/18
  • 13. Demonstration Thermography reportFile: Date: Measuring Time:IV_00423.BMT 11/12/2008 15:36:20Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 83.3 0.95 20.0 Spot Temp 1 Red PhaseMeasure point 2 65.4 0.95 20.0 -Measure point 3 70.5 0.95 20.0 -Hot spot 1 90.7 0.95 20.0 -Profile line:Remarks:Demonstration Thermography Survey.Thermal Survey of Main Electrical Supply Cabinet, using the Testo 875 series Thermal Imaging camera.Thermal and Digital image of all the Supply Panel. This is achieved in the confined space due to the Testo875 camera being equipped as standard with a 32 degree, Wide Angle Lens.3 Spot Temp markers have been added along with the Auto Hot Spot Indicator HS1, to indicate temperaturesalong with a Temperature Profile Line Graph. Page 13/18
  • 14. Demonstration Thermography reportFile: Date: Measuring Time:IV_00356.BMT 03/12/2008 10:13:47Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 37.5 0.95 20.0 Red Phase cableMeasure point 2 41.1 0.95 20.0 Black Phase cableMeasure point 3 41.0 0.95 20.0 Grey Phase cableMeasure point 4 28.5 0.95 20.0 Blue Phase cableHot spot 1 42.3 0.95 20.0 -Profile line:Remarks:Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electricalequipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.Isolator SwitchThermal image indicates the spot temperatures of the Phase connection cables higher up in the control panelabove the Isolator switch.A temperature profile line graph has been applied horizontally across the cables to highlight the temperaturevariation. Page 14/18
  • 15. Demonstration Thermography reportFile: Date: Measuring Time:IV_00040.BMT 16/02/2010 11:31:05Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksHot spot 1 91.1 0.95 20.0 -Profile line:Remarks:Thermal and Digital images taken with Testo 875 series Thermal Imaging camera during a Demonstration ofthe camera.The images taken have been used to compile an example report to demonstrate the capabilities of the TestoThermal Imaging camera and the Testo IR software.The image is of a Conveyor Motor which is part of the Sheeting Production Line.The Auto Hot Spot indicator (HS1) has been applied to the thermal image to automatically indicate thehottest point in the defined area.As can be seen, the Hottest point on the motor is approx 93 deg C.This should be compared to the Manufacturers Operating Temperature range and monitored in the future. Incomparison to other Motors on this Conveyor system, this motor is running at a considerably hottertemperature. Additional Spot temperature markers have been added to other sections of the motor forcomparison purposes. A Temperature Profile Line graph has been applied to give further visualrepresentation of the temperature profile across the motor.The thermal image is displayed in " Iron " Palette. Page 15/18
  • 16. Demonstration Thermography reportFile: Date: Measuring Time:IV_00204.BMT 13/10/2008 16:14:05Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 71.6 0.95 20.0 SpotTemp 1 on Pump Body 1Measure point 2 53.3 0.95 20.0 Spot Temp 2 on Flange connectorMeasure point 3 53.9 0.95 20.0 Spot Temp 3 on Flange connectorMeasure point 4 60.1 0.95 20.0 Spot Temp 4 on Pump Body 2Hot spot 1 72.7 0.95 20.0 -Profile line:Remarks:Demonstration Thermal Images of Electrical Installations.Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The Thermal image is displayed in " Iron " Palette.Some features of the Testo IR software have been applied to the image to highlight / indicate comparativeTemperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in thedefined area. A Temperature profile graph applied, to show temperature variation across components.AnIsotherm has been applied to highlight by colour, the area of the component that is within a definedtemperature range. Page 16/18
  • 17. Demonstration Thermography reportFile: Date: Measuring Time:IV_00702.BMT 14/04/2009 11:44:38Picture parameters:Emissivity: 0.95Refl. temp. [°C]: 20.0Picture markings:Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] RemarksMeasure point 1 39.9 0.95 20.0 Spot Temp 1 for comparison purposes.Measure point 2 38.4 0.95 20.0 Spot Temp 2 for comparison purposes.Measure point 3 46.4 0.95 20.0 Spot Temp 3 for comparison purposes.Measure point 4 40.9 0.95 20.0 Spot Temp 4 for comparison purposes.Hot spot 1 49.1 0.95 20.0 Auto Hot Spot Indicates Hottest point in defined areaProfile line:Remarks:Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera as part of Demonstrationof camera.Images taken to demonstrate the capabilities of the Testo 875 and the Testo IR software.Images are of a Control Motor in a Production Line.The Auto Hot spot indicator has been applied to the thermal image to indicate the Hottest point in the definedarea.Additional Spot Temperature markers have been added to provide temperature comparisons on other partsof the component.A Temperature profile line graph has been applied to show the temperature profile across the component. Page 17/18
  • 18. Demonstration Thermography report Review:Demonstration Report utilising the Testo range of Thermal Imaging cameras and Testo IR software.The objective of this Demonstration Thermography report is to demonstrate the report producing capabilities ofthe software and the Quality of the Thermal images captured with Testo Thermal Imaging cameras.The report is for demonstration purposes only.The images are not to highlight any specific anomalies in Electrical Installations. The images were takenduring Demonstration visits and reproduced to demonstrate the capabilities of the cameras and software.This is an example of the "Standard" report template from the software, using images from Testo ThermalImaging cameras, compiled into a Report using the Testo IR software.The Thermal and Digital images are of various Electrical Installations / Applications.The Thermal images indicate the "Apparent" temperatures on the equipment.As the images are for Demonstration purposes, no account has been made in respect of Emissivity values forMaterials or Reflected Temperature, therefore the indicated temperatures are "Apparent" Temperatures.Some of the features of the camera and the software have been applied to the thermal images.Spot Temperature Markers have been added to the thermal image to indicate temperatures and to highlightthe temperature variation.Auto Hot Spot Indicator has been applied which automatically highlights the hottest point in the defined area.Temperature Profile Line Graph, shows the temperature variation in graph form across the electricalcomponents.The thermal images can been presented in various palettes such as " Iron " and " Blue / Red", from theselection of palettes available in the camera and the software.The Thermal/Digital images are time and date stamped to verify the time and date when the images weretaken.The report also stipulates the emissivity value relating to the thermal image. 27/07/2010 , Andy McGrath Page 18/18