Committing to the future                                                   2011Multi-Function Measuring Instruments       ...
Information                                   Measurement Engineering For Multi-Function Measuring Instruments    Measurem...
ContentsMeasuring instrumentsPractical multi-function measuring instrumenttesto 435-1/-2/-3/-4                    All-roun...
testo 435                                 All-round talent for ventilation and Indoor Air Quality    All measurement param...
435-1/-2/-3/-4                                       Probes 435-1/-2/-3/-4 IAQ probes                                     ...
435-1/-2/-3/-4                                       Accessories / Technical data     435-3/-4     Prandtls Pitot tubes   ...
435-1/-2/-3/-4                                        Ordering data Option: Radio 435-1/-2/-3/-4 Radio module for upgradin...
testo 445                                 Service instrument for ventilation/air conditioning systems    The testo 445 VAC...
Measurement systems testo 445                                              Practical accessories and technical data Access...
testo 445                                           Suitable probes at a glance      Probes                               ...
Measurement systems testo 445                                                   Suitable probes at a glance Probes        ...
testo 445                                           Suitable probes at a glance      Probes                               ...
testo 400                               The reference measuring instrument for A/C and ventilation systemsPrecision refere...
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Testo - Multifunction Measuring Instruments
Upcoming SlideShare
Loading in …5
×

Testo - Multifunction Measuring Instruments

606 views
522 views

Published on

Published in: Business, Technology
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total views
606
On SlideShare
0
From Embeds
0
Number of Embeds
1
Actions
Shares
0
Downloads
18
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

Testo - Multifunction Measuring Instruments

  1. 1. Committing to the future 2011Multi-Function Measuring Instruments °C %RH m/s hPa CO2 Lux CO aW rpm mA V
  2. 2. Information Measurement Engineering For Multi-Function Measuring Instruments Measurement and application ranges of flow probes Probe selection Measurement and application ranges of flow probes The flow measurement range 0 to 100 m/s can be divided into three sections: – Low-speed velocity 0 to 5 m/s 100 – Mid-speed velocity 5 to 40 m/s Thermal Vane measurement Vane/temperature Pitot Pitot probe probes to +60 °C measurement tube to tube – High-speed velocity 40 to 100 m/s. to +70 °C probes +600 °C NiCr-Ni Thermal probes are used for accurate measurements in the range 0 to 5 m/s. Vane -40°C 60 +600 °C probes are ideal for velocities from 5 to 40 m/s. The measuring range of the Pitot to to tube depends on the differential pressure probe used. The new 100 Pa probe can +140 °C +350 °C therefore be used for the exact measurement of flow speed from approx. 1 m/s to 12 m/s. The Pitot tube yields optimum results in the higher velocity range. An 40 additional criterion when selecting the right velocity probe is the temperature. Thermal sensors can normally be used at up to approx. +70 °C. Special design vane probes can be used to maximum +350 °C. Pitot tubes are used for 20 temperatures above +350 °C. 15 10 0 Supply/Returns Positioning in air current The air vent greatly changes the relatively The vane probe is set exactly if the flow direction uniform flow inside the duct. Areas of ar is parallel to the vane axis. If the measuring probe higher flow velocity are created at the Lamin is turned slightly in the air current, the value flow free vent surfaces and areas of low in the e of the shown in the instrument changes. The measuring flow velocity and swirl at the grids. centr t probe is positioned exactly in the air current if the duc The flow profile steadies at a value shown is at max. distance from the the grid When measuring in a duct there should also be a depending on the grid design but is minimum of ten diameters of straight run before usually 20 cm. For best accuracy, a Max. values the measuring spot and four diameters of straight large diameter vane is recommended. run after the spot for best results. By design, Min. values The area of the vane helps to get an vanes are less influenced by turbulence than thermal probes or Pitot tubes. Mean values average reading of the turbulent flow from the grid. Site selection Direction of flow D Measurements at suction apertures using a volume flow funnel 10 x D 4xD Even without the disturbing effects of a grid in an aperture, the lines of flow are not directional and the flow profile is irregular. Because a partial vacuum in the duct You should measure in a straight part of the duct, if possible. The duct part should draws air out of the room in a funnel shape even a short distance from the aperture, have a minimum of ten diameters of straight run before the measuring spot and there is no defined area in the room over which a measurement could be made. four diameters of straight run after the measuring spot. The flow profile should not Therefore, only the duct or funnel measurement yields reproducible results. be interrupted in any way by flaps, dips, angles etc. Measuring funnels of various sizes are available for such applications. These create defined flow conditions at a known distance from the grid with a fixed volume. A velocity probe is positioned centrally and secured. The volume flow is calculated from the velocity multiplied by the funnel factor (e.g. funnel factor 22). Flow measurement in ducts As part of approval measurements, indirect measuring procedures (grid measurements) are used to measure air flows. The following procedures are suggested in VDI 2080/EN 12599: – Trivial procedure for grid measurements in square cross-sections. – Centroidal axis procedures for grid measurements in circular cross-sections – Loglinear procedure for grid measurements in circular cross sections. Measuring ambient air velocity using testo 400 in accordance with DIN 1946 Part 2, ANSI/Ashrae 55-1992 Ambient air velocity is a very important parameter in the thermal comfort of people Ambient air velocity in rooms. testo 400 supplies the current and mean air velocities. The maximum Air temperature in °F permissible mean air velocity depends on the air temperature measured by testo 68 70 72 74 76 78 80 1,7 140 Mean air velocity m/s 400 and the amount of turbulence calculated from the air velocity. The example shows a permissible mean air velocity of 0.26 m/s with an air temperature 1,6 120 measured at 24.4 °C and an automatically calculated degree of turbulence of 10 %. 1,5 0% 100 0,4 80 Mean air velocity fpm 10% 0,3 60 20% 40% 0,2 40 60% 0,1 20 0 0 20,0 21,1 22,2 23,3 24,4 25,5 26,7 Air temperature in °C2 Degree of turbulence T
  3. 3. ContentsMeasuring instrumentsPractical multi-function measuring instrumenttesto 435-1/-2/-3/-4 All-rounder for ventilation and indoor air quality Page 4Measurement systemstesto 445 Service instrument for ventilation/air conditioning systems Page 8testo 400 The reference measuring instrument for A/C and ventilation systems Page 13AccessoriesSoftware and Accessories PageComSoft 3 - Professional Professional Software including Data Filing 24Printer PageTesto fast printer Versatile infrared printer for testo 435, 445, 400 26Ethernet adapter PageEthernet adapter Access Ethernet with Testo measuring instruments 27 3
  4. 4. testo 435 All-round talent for ventilation and Indoor Air Quality All measurement parameters for Common product advantages testo 435 air conditioning Wide selection of probes (optional): The testo 435 provides the - IAQ probe for evaluating the indoor air quality via possibility of analysing the indoor CO2, air temperature, indoor air humidity and air. On the one hand, this serves absolute pressure as an indicator for the well-being - Thermal probe with integrated temperature and air of people at their workplaces, and humidity measurement on the other hand as an important and deciding factor in storage - Vane and hot wire probes and production processes. - Radio probes for temperature Easy operation with user profiles In addition to this, the Indoor Air Quality signals whether the air Printout on the testo fast printer (optional) conditioning system (HVAC) is working with as much energy economy as possible, or whether it needs to be adjusted with the help of testo 435. Further product advantages of the variants The parameters CO2 , relative humidity and room temperature Integrated differential pressure measurement (435- are available for evaluating the 3/-4, not retrofittable) quality of the air. Absolute - for flow measurement pressure, draught, Lux, U-value - for monitoring filters and surface temperature can additionally be determined. In Extended instrument function (435-2/-4, not retrofittable) order to determine the volume flow, all the possibilities of flow - Instrument store for 10,000 readings velocity measurement are - PC software for analysing, archiving and available, such as thermal probes, documenting measurement data vane anemometers and Pitot - Humidity probes with radio or wire (optional) tubes. - Lux probe connection possible - Comfort level probe connection possible - Possibility of connecting U-value probe Versatility with wireless probes In addition to classical probes on wires, a wireless measurement up to a distance of 20 m (without obstruction) is possible. Damage to the wire or hindrances in usage are thus eliminated. A maximum of three wireless probes can be recorded and displayed with testo 435. The wireless probes are for the measurement parameters temperature and, depending on the instrument type, humidity. The optional, easily plugged-in radio module can be retrofitted at any time. testo 435-1 testo 435-2 testo 435-3 testo 435-4 testo 435-1, multi-functional meas. testo 435-2, multi-functional testo 435-3, multi-functional testo 435-4, multi-functional meas. instr., for A/C, ventilation and Indoor measuring instrument for A/C, measuring instrument with built-in instr. with built-in differential Air Quality, with battery and ventilation and Indoor Air Quality differential pressure measurement pressure measurement for A/C, calibration protocol with readings memory, PC software for air conditioning, ventilation and ventilation and Indoor Air Quality and USB data transmission cable, Indoor Air Quality, with battery and with readings memory, PC software incl. battery and calibration protocol calibration protocol and USB data transmission cable, with battery and calibration protocol Part no. Part no. Part no. Part no. 0560 4351 0563 4352 0560 4353 0563 43544 Additional information at www.testo.com
  5. 5. 435-1/-2/-3/-4 Probes 435-1/-2/-3/-4 IAQ probes Illustration Meas. range Accuracy Part no.IAQ probe to assess Indoor Air Quality, CO2, 0 to +50 °C ±0.3 °C 0632 1535 0 to +100 %RH ±2 %RH (+2 to +98 %RH)humidity, temperature and absolute pressure 0 to +10000 ppm CO2 ±(50 ppm CO2 ±2% of mv) (0 to +5000 ppm CO2)measurement, with desk-top stand ±(100 ppm CO2 ±3% of mv) (+5001 to +10000 ppm CO2) +600 to +1150 hPa ±3 hPaAmbient CO probe, for detecting CO in buildings 0 to +500 ppm CO ±5% of mv (+100.1 to +500 ppm CO) 0632 1235and rooms ±5 ppm CO (0 to +100 ppm CO) Flow velocity probes Illustration Meas. range Accuracy Part no.Thermal velocity probe with built-in temperature -20 to +70 °C ±0.3 °C 0635 1535and humidity measurement, Ø 12 mm, with 0 to +100 %RH ±2 %RH (+2 to +98 %RH) 0 to +20 m/s ±(0.03 m/s +4% of mv)telescopic handle (max. 745 mm)Vane meas. probe, 16 mm diameter, with +0.6 to +40 m/s ±(0.2 m/s +1.5% of mv) 0635 9535telescopic handle max. 890 mm, e.g. for meas. in Oper. temp. 0 to +60 °Cducts, can be used from 0 to +60 °CVane meas. probe, 60 mm diameter, with +0.25 to +20 m/s ±(0.1 m/s +1.5% of mv) 0635 9335telescopic handle max. 910 mm, e.g. for meas. at Oper. temp. 0 to +60 °Cduct exit, can be used from 0 to +60 °CHot wire probe for m/s and °C, Ø probe head 7.5 0 to +20 m/s ±(0.03 m/s +5% of mv) 0635 1025mm, with telescopic handle (max. 820 mm) -20 to +70 °C ±0.3 °C (-20 to +70 °C) Funnel measurement Illustration Meas. range Accuracy Part no.Vane meas. probe, 100 mm diameter, for +0.3 to +20 m/s ±(0.1 m/s +1.5% of mv) 0635 9435measurements with funnel set 0563 4170 0 to +50 °C ±0.5 °CFunnel set consisting of funnel for disc outlets (Ø 200) and funnel 0563 4170for ventilator (330 x 330 mm) for in- and outgoing air Absolute pressure probes Illustration Meas. range Accuracy Part no.Absolute pressure probe 2000 hPa 0 to +2000 hPa ±5 hPa 0638 1835 Air probes Illustration Meas. range Accuracy t99 Part no.Efficient, robust NTC air probe 115 mm 50 mm -50 to +125 °C ±0.2 °C (-25 to +80 °C) 60 s 0613 1712 ±0.4 °C (remaining range) Ø 5 mm Ø 4 mm Conn.: Fixed cable 1.2 m Surface probes Illustration Meas. range Accuracy t99 Part no.Fast-reaction paddle surface probe, for measurements 145 mm 40 mm 0 to +300 °C Class 2 5sin inaccessible places, e.g. narrow apertures and slots, 0602 0193TC Type K Ø 8 mm Conn.: Fixed cableFast-action surface probe with sprung thermocouple 115 mm -60 to +300 °C Class 2* 3s 0602 0393strip, also for uneven surfaces, measurement range Ø 5 mmshort-term to +500°C, TC Type K Conn.: Fixed cable Ø 12 mmPipe wrap probe for pipe diameter 5 to 65 mm, -60 to +130 °C Class 2* 5s 0602 4592with exchangeable measuring head. Meas. rangeshort-term to +280°C, TC Type K Conn.: Fixed cableClamp probe for measurements on pipes, pipe -50 to +100 °C Class 2* 5s 0602 4692diameter 15 to 25 mm (max. 1"), meas. rangeshort-term up to +130°C, TC Type K Conn.: Fixed cable Immers./penetr. probes Illustration Meas. range Accuracy t99 Part no.Waterproof immersion/penetration probe, TC Type K 114 mm 50 mm -60 to +400 °C Class 2* 7s 0602 1293 Ø 5 mm Ø 3.7 mm Conn.: Fixed cable 1.2 m 435-2/-4 IAQ probes Illustration Meas. range Accuracy Part no.Comfort level probe for degree of turbulence 0 to +50 °C ±0.3 °C 0628 0109 0 to +5 m/s ±(0.03 m/s +4% of mv)measurement with telescopic handle (max. 820mm) and stand, meets EN 13779 requirements max. 820 mmLux probe, for measuring light intensity Accuracy to DIN 5032, Part 6: 0635 0545 f1 = 6% = V(Lambda) adjustment f2 = 5% = cos-like weighting, Class C Humidity probes Illustration Meas. range Accuracy Part no.Humidity/temperature probe -20 to +70 °C ±0.3 °C 0636 9735 0 to +100 %RH ±2 %RH (+2 to +98 %RH) Ø 12 mm Surface probes Illustration Meas. range Accuracy Part no.Temperature probe to determine U-value, triple -20 to +70 °C Class 1 0614 1635sensor system for measuring wall temperature, U-value: ±0.1 ±2% of fsv**modelling clay included An additional probe for measuring outer temperatures is required when determining the U-value e.g. 0613 1712 or 0613 1001 or 0613 1002. * According to standard EN 60584-2, the accuracy of Class 2 refers to -40 to +1200 °C. ** when used with an NTC or wireless humidity probe for measuring outside temperature and 20 K difference between the air inside and outside Additional information at www.testo.com 5
  6. 6. 435-1/-2/-3/-4 Accessories / Technical data 435-3/-4 Prandtls Pitot tubes Illustration Oper. temp. Part no. Pitot tube, 350 mm long, stainless steel, for 0 to +600 °C 0635 2145 measuring flow velocity 350 mm Ø 7 mm Pitot tube, 500 mm long, stainless steel, for 0 to +600 °C 0635 2045 measuring flow velocity 500 mm Ø 7 mm Pitot tube, 1000 mm long, stainless steel, for 0 to +600 °C 0635 2345 measuring flow velocity 1000 mm Ø 7 mm Technical data Probe type NTC Type K Type T Testo humid. sensor, Vane Hot wire Absolute CO2 (IAQ probe) cap. pressure probe Meas. range -50 to +150 °C -200 to +1370 °C -200 to +400 °C 0 to +100 %RH 0 to +60 m/s 0 to+20 m/s 0 to +2000 hPa 0 to +10000 ppm CO2 Accuracy ±0.2 °C (-25 to +74.9 °C) ±0.3 °C (-60 to +60 ±0.3 °C (-60 to +60 See probe data See probe data See probe See probe data See probe data ±0.4 °C (-50 to -25.1 °C) °C) °C) data ±1 digit ±(0.2 °C +0.3% of ±(0.2 °C +0.3% of mv) ±0.4 °C (+75 to +99.9 °C) mv) (remaining range) (remaining range) ±0.5% of mv (remaining range) Resolution 0.1 °C 0.1 °C 0.1 °C 0.1 %RH 0.01 m/s (60 vane) 0.01 m/s 0.1 hPa 1 ppm CO2 0.1 m/s (16 vane) Technical data 435-2/-4 Technical data 435-3/-4 Oper. temp. -20 to +50 °C Probe type Lux Probe type Differential pressure Storage temp. -30 to +70 °C probe, internal Dimensions 220 x 74 x 46 mm Meas. range 0 to +100000 Lux Meas. range 0 to +25 hPa Battery type Alkali manganese, Accuracy See probe data Accuracy ±0.02 hPa (0 to +2 hPa) mignon, Type AA ±1 digit ±1 digit 1% of mv (remaining range) Battery life 200 h (typical vane measurement) Weight 450 g Resolution 1 Lux / 0.1 Hz Overload 200 hPa Material/Housing ABS/TPE/Metal Resolution 0.01 hPa Warranty 2 years Accessories Part no. Accessories Part no. Transport and Protection Printer and Accessories Service case for basic equipment of measuring instrument and probes, 0516 0035 Testo fast printer with wireless infrared interface, 1 roll thermal paper and 4 0554 0549 dimensions: 400 x 310 x 96 mm AA batteries, for printing out measurements on site Service case for measuring instrument, probe and accessories, dimensions 0516 0435 Spare thermal paper for printer (6 rolls), measurement data documentation 0554 0568 520 x 380 x 120 mm legible for up to 10 years Additional Accessories and Spare Parts Spare thermal paper for printer (6 rolls) 0554 0569 Handle for attachable humidity probe head for connection to testo 635, incl. 0430 9735 probe wire, for measurement / calibration of humidity probe head External fast charger for 1-4 AA rech. batteries, incl. 4 Ni-MH rech. batteries 0554 0610 Lithium battery button cellCR2032 mignon type batteries for radio handle 0515 0028 with individual cell charging and charge control display, incl. impulse trickle charging, integrated discharge function, with built-in international mains plug, 100-240 V, 300 mA, 50/60 Hz Plug-in mains adapter, 5 VDC 500 mA with European adapter, 100-250 VAC, 0554 0447 50-60 Hz Calibration Certificates testovent 410, volume flow funnel, Ø 340 mm/330x330 mm, incl. case 0554 0410 ISO calibration certificate/temperature, meas. instr. with surface probe; 0520 0071 calibration points +60°C; +120°C; +180°C testovent 415, volume flow funnel, Ø 210 mm/210x210 mm, incl. case 0554 0415 ISO calibration certificate humidity, Calibration points 11.3 %RH and 75.3 0520 0006 %RH at +25°C Funnel set consisting of funnel for disc outlets (Ø 200) and funnel for 0563 4170 ISO calibration certificate/pressure 0520 0005 ventilator (330 x 330 mm) for in- and outgoing air differential pressure; 5 points distributed over meas. range Connection hose, silicone, 5m long, max. load 700 hPa (mbar) 0554 0440 ISO calibration certificate velocity, hot wire, vane anemometer; calibration 0520 0024 points 0.5; 0.8; 1; 1.5 m/s testo saline pots for control and humidity adjustment of humidity probes, 0554 0660 ISO calibration certificate velocity, hot wire, vane anemometer, Pitot tube; 0520 0004 11.3 %RH and 75.3 %RH with adapter for humidity probe, quick checks or calibration points 1; 2; 5; 10 m/s calibration of humidity probe Sintered PTFE filter, Ø 12 mm, for corrosive media, High humidity range 0554 0756 ISO calibration certificate/Velocity, hot wire, vane anemometer, Pitot tube; 0520 0034 (long-term measurements), high flow velocities. calibration points 5; 10; 15; 20 m/s Stainless steel sintered cap, Ø 12 mm, is screwed onto humidity probe, for 0554 0647 ISO calibration certificate/light, Calibration points 0;500;1000;2000;4000 0520 0010 measurements at higher flow velocities or in contaminated air Lux Adhesive material for fixing and sealing 0554 0761 ISO calibration certificate/CO2, CO2 probes; calibration points 0; 1000; 5000 0520 0033 ppm6 Additional information at www.testo.com
  7. 7. 435-1/-2/-3/-4 Ordering data Option: Radio 435-1/-2/-3/-4 Radio module for upgrading measuring instrument with radio optionCountry versions Radio freq. Part no.Radio module for measuring instrument, 869.85 MHz, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, 869.85 MHz FSK 0554 0188AT, DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NORadio module for measuring instrument, 915.00 MHz FSK, approval for USA, CA, CL 915.00 MHz FSK 0554 0190 Assembled for you: Radio handles with probe head Radio handles with probe head for surface measurement Meas. range Accuracy Resolution t99 120 mm -50 to +350 °C Radio handle: 0.1 °C (-50 to +199.9 °C) 5s 40 Radio handle for attachable probe heads with mm Short-term to +500 °C ±(0.5 °C +0.3% of mv) (-40 to +500 °C) 1.0 °C (remaining range) T/C probe head for surface measurement ±(0.7 °C +0.5% of mv) (remaining range) Ø 5 mm Ø 12 T/C probe head: Class 2 mmCountry versions Radio freq. Part no.Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, DK, FI, 869.85 MHz FSK 0554 0189HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NOT/C probe head for surface measurement, attachable to radio handle, T/C Type K 0602 0394Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL 915.00 MHz FSK 0554 0191T/C probe head for surface measurement, attachable to radio handle, T/C Type K 0602 0394435-2/-4Radio probes incl. humidity probe head Meas. range Accuracy Resolution 0 to +100 %RH ±2 %RH (+2 to +98 %RH) 0.1 %RH Radio handle for attachable probe heads with -20 to +70 °C ±0.3 °C 0.1 °C humidity probe headCountry versions Radio freq. Part no.Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, DK, FI, HU, CZ, PL, GR, CH, 869.85 MHz FSK 0554 0189PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NOHumidity probe head, attachable to radio handle 0636 9736Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL 915.00 MHz FSK 0554 0191Humidity probe head, attachable to radio handle 0636 9736 Radio probes: General technical data Radio handle Measuring rate 0.5 s or 10 s, adjustable Radio transmission Unidirectional Battery type 2 AAA micro batteries on handle Battery life 215 h (meas. rate 0.5 s) Oper. temp. -20 to +50 °C 6 months (meas. rate 10 s) Radio coverage Up to 20 m (without Storage temp. -40 to +70 °C obstructions) Protection class IP54 Additional information at www.testo.com 7
  8. 8. testo 445 Service instrument for ventilation/air conditioning systems The testo 445 VAC instrument Automatic mean calculation and measures temperature, relative volume flow measurement humidity, dew point, absolute Automatic allocation of duct cross- humidity, degree of humidity, section to location (max. 99 locations) enthalpy, all types of air velocity (in Internal data logger (3,000 readings) ducts, duct openings or Simultaneous measurement of up to extractors), volume flow, pressure 6 parameters and indoor air quality. Simultaneous meas. of 6 parameters Data can be saved according to location and then analysed on PC Mains conn. and battery or printed on the Testo fast printer recharging in instr. on site. Prints at touch of button Displays 2 parameters Saves up to 3000 readings Easy operation with testo 445, VAC measuring cursor Selects up to 99 sites instrument, incl. TopSafe, battery and calibration protocol Part no. 0563 44508 Additional information at www.testo.com
  9. 9. Measurement systems testo 445 Practical accessories and technical data Accessories Part no. Technical data Transport and Protection Probe type Type K (NiCr-Ni) Type J (Fe-CuNi) NTCTransport case (plastic) for measuring instrument, probes and accessories 0516 0445Larger version, for safe and clear storage Meas. range -200 to +1370 °C -200 to +1000 °C -50 to +150 °CSystem case (plastic) for measuring instrument, probes and accessories, probes in lid 0516 0400 Accuracy ±0.5% of mv (-200 to 60 °C) ±0.5% of mv (-200 to 60 °C) ±0.5% of mv (+100 to +150make it easy to find parts in case (540 x 440 x 130 mm) ±0.5% of mv (+60 to +1370 ±0.5% of mv (+60 to +1000 °C) ±1 digit °C) °C) ±0.2 °C (-25 to +74.9 °C)System case (aluminium) for measuring instrument, probes and accessories 0516 0410 ±0.3 °C (-60 to +60 °C) ±0.3 °C (-60 to +60 °C) ±0.4 °C (-50 to -25.1 °C)probes in lid make it easy to find parts in case ±0.4 °C (+75 to +99.9 °C) Additional Accessories and Spare Parts9V rech. battery for instrument 0515 0025instead of battery Resolution 0.1 °C (-200 to +1370 °C) 0.1 °C (-200 to +1000 °C) 0.1 °C (-50 to +150 °C)Desk-top power supply with international connection options 0554 1143Cable, 1.5 m long, connects probe with plug-in head to meas. instrument, 0430 0143PUR coating material Probe type Testo humid. sensor, cap. Vane ThermalCable, 5 m long, connects probe with plug-in head to measuring instrument 0430 0145PUR coating material Meas. range 0 to +100 %RH 0 to +60 m/s 0 to +20 m/sExtension cable, 5 m long, between plug-in head cable and instrument 0409 0063 Accuracy See probe data See probe data See probe dataPUR coating material ±1 digit Printer and AccessoriesTesto fast printer with wireless infrared interface, 1 roll thermal paper and 4 0554 0549AA batteriesFast testo 575 printer, incl. 1 roll of thermal paper and batteries 0554 1775 Resolution 0.1 %RH (0 to +100 0.01 m/s (0 to +60 m/s) 0.01 m/s (0 to +10 m/s)infrared thermal line printer with graphics function %RH) 0.1 m/s (+10.1 to +20 m/s)External fast charger for 1-4 AA rech. batteries, incl. 4 Ni-MH rech. batteries 0554 0610with individual cell charging and charge control display, incl. impulse tricklecharging, integrated discharge function, with built-in international mains Probe type Pressure CO2 probeplug, 100-240 V, 300 mA, 50/60 HzSpare thermal paper for printer (6 rolls) 0554 0569 Meas. range See pressure probes 0 to +1 Vol. % CO2 0 to +10000 ppm CO2 Accuracy ±0.1% of mv See probe data ±(100 ppm CO2 ±3% of mv)Spare thermal paper for printer (6 rolls) 0554 0568 (+5000 to +10000 ppm CO2) ±1 digitmeasurement data documentation legible for up to 10 years ±(500 ppm CO2 ±2% of mv) (0 to +5000 ppm CO2)Label thermal paper (Testo patent) for testo 575 printer (6 rolls), can be 0554 0561applied directly Software and Accessories Resolution 0.001 hPa (Sonde 0638 0 Vol. % CO2(0 to +1 1 ppm CO2 (0 to +10000ComSoft 3 - Professional with data management 0554 0830 1345) Vol. % CO2) ppm CO2)incl. database, analysis and graphics function, data analysis, trend curve 0.001 hPa (Sonde 0638 1445)RS232 cable 0409 0178 0.01 hPa (Sonde 0638 1545)connects instrument to PC (1.8 m) for data transfer 1 hPa (Sonde 0638 1645)Ethernet adapter, RS232 - Ethernet incl. software driver, mains unit 0554 1711facilitates data communication in network Probe type CO probe Calibration CertificatesISO calibration certificate velocity ,hot wire, vane anemometer, Pitot 0520 0004 Meas. range 0 to +500 ppm COtube; calibration points 1; 2; 5; 10 m/s Accuracy ±5% of mv (+100 toISO calibration certificate/Velocity 0520 0034 ±1 digit +500 ppm CO)hot wire, vane anemometer, Pitot tube; calibration points 5; 10; 15; 20 m/s ±5 ppm CO (0 to +100 ppm CO)DAkkS calibration certificate/velocity* 0520 0244hot wire, vane anemometer; calibration points 0.5; 1; 2; 5; 10 m/sDAkkS calibration certificate/velocity* 0520 0204 Resolution 1 ppm CO (0 to +500hot wire, vane anemometer, Pitot tube; calibration points 2; 5; 10; 15; 20 m/s ppm CO)*Successor organization of the DKD Oper. temp. 0 to +50 °C Battery life: 6-45 h (depending on probe) Storage temp. -20 to +70 °C Mains conn. and batt. rech. in instr. Calculated humidity parameters: td, g/m3, g/kg Display LCD, 4 lines pressure-compensated, J/g Battery type 9V block battery Calculated volume flow: m3/h (e.g. 0 to 99999 Battery life 45 h m3/h), m3/min, m3/s, I/s, cfm PC RS232 interface Calculated velocity values (density-compensated): 0 to 100 m/s; 0 to 99999 m3/h Weight 255 g Humidity measurement: Measuring range -50 to Material/Housing ABS 180°C; See Probes for accuracy Warranty 2 years Accuracy of Type K, J: Additional error via operation Memory 3000 temperature 0.2 °C (adjustment point) Dimensions 215 x 68 x 47 mm Additional information at www.testo.com 9
  10. 10. testo 445 Suitable probes at a glance Probes Illustration Probe type Meas. range Accuracy Part no. Vane probe, Ø 12 mm, can be attached to handle Vane +0.6 to +20 m/s ±(0.2 m/s ±1% of mv) 0635 9443 0430 3545 or telescopic handle 0430 0941 Oper. temp. (+0.6 to +20 m/s) 180 mm -30 to +140 °C Ø 12 mm Vane/temperature probe, Ø 16 mm, attachable to Vane +0.4 to +60 m/s ±(0.2 m/s +1% of mv) 0635 9540 0430 3545 handle or 0430 0941 telescopic Type K (NiCr-Ni) -30 to +140 °C (+0.4 to +40 m/s) 180 mm ±(0.2 m/s +2% of mv) handle Ø 16 mm (+40.1 to +50 m/s) Vane/temperature probe, Ø 25 mm, can be Vane +0.4 to +40 m/s ±(0.2 m/s ±1% of mv) 0635 9640 attached to 0430 3545 handle or 0430 0941 Type K (NiCr-Ni) -30 to +140 °C (+0.4 to +40 m/s) telescopic handle 180 mm Ø 25 mm Bendable vane probe (can be bent by 90°), Ø 60 Vane +0.25 to +20 m/s ±(0.1 m/s ±1.5% of mv) 0635 9440 mm, attachable to handle 0430 3545 or telescopic Oper. temp. (+0.25 to +20 m/s) Ø 60 mm 0 to +60 °C handle 0430 0941, for meas. on ventilation outlets Bendable vane probe (can be bent by 90°), Ø 100 mm, Vane +0.1 to +15 m/s ±(0.1 m/s ±1.5% of mv) 0635 9340 attachable to handle 0430 3545 or telescopic handle Oper. temp. (+0.1 to +15 m/s) Ø 100 mm 0 to +60 °C 0430 0941, for measurements on ventilation outlets Affordable, robust hot bulb probe, Ø 3 mm, for 150 mm Hot bulb 0 to +10 m/s ±(0.03 m/s ±5% of mv) 0635 1549 measurements in the lower velocity range, with NTC -20 to +70 °C (0 to +10 m/s) handle Ø 4 mm Ø 3 mm Robust hot bulb probe, Ø 3 mm, with handle and Hot bulb 0 to +10 m/s ±(0.03 m/s ±5% of mv) 0635 1049 telescopic handle for measurements in the lower NTC -20 to +70 °C (0 to +10 m/s) velocity range 850 mm Ø 3 mm Quick-action hot wire probe, Ø 10 mm, with Hot wire 0 to +20 m/s ±(0.03 m/s ±4% of mv) 0635 1041 telescopic handle, for measurements in the lower NTC -20 to +70 °C (0 to +20 m/s) velocity range with direction recognition 760 mm Ø 10 mm Vane probe, Ø 16 mm, with telescopic handle, Vane +0.6 to +40 m/s ±(0.2 m/s ±1.5% of mv) 0628 0005 Tmax +60°C (+0.6 to +40 m/s) 700 mm Ø 16 mm Vane probe, Ø 60 mm, with telescopic handle, for Vane +0.25 to +20 m/s ±(0.1 m/s ±1.5% of mv) 0635 9449 integrating velocity measurement (+0.25 to +20 m/s) Ø 60 mm 1100 mm High temperature vane probe, Ø 25 mm, with Vane +0.6 to +20 m/s ±(0.3 m/s ±1% of fsv) 0635 6045 handle for continuous measurements up to Type K (NiCr-Ni) -40 to +350 °C (+0.6 to +20 m/s) +350°C 560 mm Ø 25 mm Precision pressure probe, 100 Pa, measures Differential pressure 0 to +100 Pa ±(0.3 Pa ±0.5% of mv) 0638 1345 differential pressure and velocities (in probe (0 to +100 Pa) combination with Pitot tube) Pressure probe, 10 hPa, measures differential Differential pressure 0 to +10 hPa ±0.03 hPa (0 to +10 hPa) 0638 1445 pressure and velocities (in combination with Pitot probe tube)10 Additional information at www.testo.com
  11. 11. Measurement systems testo 445 Suitable probes at a glance Probes Illustration Probe type Meas. range Accuracy Part no.Pressure probe, 100 hPa, measures differential Differential pressure 0 to +100 hPa ±0.5% of mv (+20 to 0638 1545pressure and velocities (in combination with Pitot probe +100 hPa) ±0.1 hPa (0 to +20 hPa)tube)Pressure probe, 2000 hPa, measures absolute Absolute pressure 0 to +2000 hPa ±5 hPa (0 to +2000 hPa) 0638 1645pressure probePitot tube, 500 mm long, stainless steel, for Oper. temp. 0635 2045measuring flow velocity Ø 7 mm 0 to +600 °C 500 mmPitot tube, 350 mm long, stainless steel, for Oper. temp. 0635 2145measuring flow velocity Ø 7 mm 0 to +600 °C 350 mmPitot tube, 300 mm long, stainless steel, for Oper. temp. 0635 2245measuring flow velocity Ø 4 mm 0 to +600 °C 300 mmPitot tube, 1000 mm long, stainless steel, for Oper. temp. 0635 2345measuring flow velocity Ø 7 mm 0 to +600 °C 1000 mm3-function probe for simultaneous measurement of Hot bulb 0 to +10 m/s ±(0.03 m/s ±5% of mv)(0 to 10 m/s) 0635 1540temperature, humidity and velocity. With plug-in head, Testo humid. sensor, 0 to +100 %RH cap. -20 to +70 °C ±2 %RH (+2 to +98 %RH)0430 0143 connection cable required NTC ±0.4 °C (0 to +50 °C) 270 mm Ø 21 mm ±0.5 °C (remaining range)Comfort level probe for measuring degree of turbulence, Hot wire 0 to +5 m/s ±(0.03 m/s ±4% of mv) 0628 0009with telescopic handle and stand. Fulfills EN 13779 NTC 0 to +50 °C (0 to +5 m/s) Ø 90 mm ±0.3 °C (0 to +50 °C)requirementsCO2 probe measures indoor air quality and monitors the CO2 probe 0 ... +1 Vol. % CO2 ±(50 ppm CO2 ±2% of mv)(0 to +5000 ppm CO2) 0632 1240workplace. With plug-in head, connection cable 0430 0 ... +10000 ppm ±(100 ppm CO2 ±3% of CO2 mv)(+5001 to +10000 ppm0143 or 0430 0145 required CO2)Ambient CO probe, for detecting CO in buildings 0 to +500 ppm CO ±5% of mv (+100.1 to 0632 3331and rooms +500 ppm CO) ±5 ppm CO (0 to +100 ppm CO) More probes Illustration Meas. range Accuracy t90 Part no.Standard ambient air probe up to +70°C 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 12 s 0636 9740 Ø 12 mm -20 to +70 °C %RH) ±0.5 °C (remaining range) Plug-in head. connection cable 0430 0143 or 0430 0145 requiredDuct humidity/temperature probe 180 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 12 s 0636 9715 -20 to +70 °C %RH) ±0.5 °C (remaining range) Ø 12 mm Fixed cable; Cable/length 3 mThin humidity probe incl. 4 attachable protection caps for 250 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 15 s 0636 2130ambient air measurements, measurements in exhaust air -20 to +70 °C %RH) ±0.5 °C (-20 to -10.1 °C) Ø 4 mmducts and equilibrium moisture measurements ±0.5 °C (+50.1 to +70 °C) Plug-in head. connection cable 0430 0143 or 0430 0145 requiredHighly accurate reference humidity/temp. probe Ø 21 mm 0 to +100 %RH ±1 %RH (+10 to +90 ±0.2 °C (+10 to +40 °C) 12 s 0636 9741 -20 to +70 °C %RH)* ±0.4 °C (remaining range) ±2 %RH (remaining Plug-in head. connection cable 0430 0143 or 0430 0145 required range) * in the temperature range from +15°C to +30°CFlexible humidity probe with mini module for 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 20 s 0628 0013meas. e.g. on material testing rigs, module cable -20 to +125 °C %RH) ±0.5 °C (remaining range)length 1500mm, probe tip 50x19x7mm Plug-in head. connection cable 0430 0143 or 0430 0145 requiredSword probe for measuring humidity and 320 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 12 s 0636 0340temperature in stacked material -20 to +70 °C %RH) ±0.5 °C (-20 to -10.1 °C) 18 mm x 5 mm ±0.5 °C (+50.1 to +70 °C) Plug-in head. connection cable 0430 0143 or 0430 0145 requiredHigh humidity level probe w/ heated sensor 300 mm 0 to +100 %RH ±2.5 %RH (0 to ±0.4 °C (-10 to +50 °C) 30 s 0636 2142element, no humidity on sensor -20 to +85 °C +100 %RH) ±0.5 °C (-20 to -10.1 °C) Ø 12 mm ±0.5 °C (+50.1 to +100 °C) Plug-in head. connection cable 0430 0143 or 0430 0145 requiredRobust humidity probe e.g. for measuring 300 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (-10 to +50 °C) 30 s 0636 2140equilibrium moisture or for measurements in -20 to +120 °C %RH) ±0.5 °C (remaining range) Ø 12 mmexhaust ducts to +120°C Plug-in head. connection cable 0430 0143 or 0430 0145 requiredRobust high temperature/humidity probe up to 300 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (+0.1 to +50 °C) 30 s 0628 0021+180°C -20 to +180 °C %RH) ±0.5 °C (remaining range) Ø 12 mm Plug-in head. connection cable 0430 0143 or 0430 0145 requiredFlexible humidity probe (does not retain shape) 1500 mm 100 mm 0 to +100 %RH ±2 %RH (+2 to +98 ±0.4 °C (+0.1 to +50 °C) 30 s 0628 0022for measurements in inaccessible places -20 to +180 °C %RH) ±0.5 °C (-20 to 0 °C) Ø 12 mm ±0.5 °C (+50.1 to +180 °C) Plug-in head. connection cable 0430 0143 or 0430 0145 requiredStandard pressure dew point probe for 300 mm ±0.9 °C tpd (+0.1 to +50 °C tpd) 0 to +100 %RH 300 0636 9840 -30 to +50 °C tpd ±1 °C tpd (-4.9 to 0 °C tpd) smeasurements in compressed air systems ±2 °C tpd (-9.9 to -5 °C tpd) ±3 °C tpd (-19.9 to -10 °C tpd) Plug-in head. connection cable 0430 0143 or 0430 0145 required ±4 °C tpd (-30 to -20 °C tpd)Precision pressure dew point probe for 300 mm 0 to +100 %RH ±0.8 °C tpd (-4.9 to +50 °C tpd) 300 0636 9841 -60 to +50 °C tpd ±1 °C tpd (-9.9 to -5 °C tpd) smeasurements in compressed air systems incl. ±2 °C tpd (-19.9 to -10 °C tpd)cert. with test point -40°C tpd ±3 °C tpd (-29.9 to -20 °C tpd) ±4 °C tpd (-40 to -30 °C tpd) Additional information at www.testo.com 11
  12. 12. testo 445 Suitable probes at a glance Probes Illustration Meas. range Accuracy t99 Part no. Quick-action surface probe with sprung 150 mm -200 to +300 °C Class 2* 3s 0604 0194 thermocouple strip, measuring range short-term to +500 °C Ø 10 mm Plug-in head. connection cable 0430 0143 or 0430 0145 required Super quick-action immersion/penetration probe 150 mm -200 to +600 °C Class 1* 1s 0604 0493 for measurements in liquids Ø 1.5 mm Plug-in head. connection cable 0430 0143 or 0430 0145 required Super quick-action immersion/penetration probe 150 mm 20 mm -200 to +600 °C Class 1* 1s 0604 9794 for measurements in gases and liquids with a Ø 1.4 mm Ø 0.5 mm low-mass tip Plug-in head. connection cable 0430 0143 or 0430 0145 required Pipe wrap probe for pipes up to 2" in diameter -60 to +130 °C Class 2* 5s 0600 4593 Fixed cable Spare meas. head for pipe wrap probe, TC Type K 35 mm -60 to +130 °C Class 2* 5s 0602 0092 15 mm Globe thermometer to measure radiant heat Accuracy corresponds to 0 to +120 °C ±0.5 °C (0 to +49.9 °C) 0554 0670 ISO 7243, ISO 7726, DIN ±1 °C (+50 to +120 °C) Ø 150 mm EN 27726, DIN 33403 requirements Fixed cable *According to standard EN 60584-2, the accuracy of Classes 1 / 2 refer to -40 to +1000/+1200 °C. See testo 400 for more probes Accessories for velocity probes, pressure probes Part no. Accessories: Humidity, 3-function probe Part no. Professional telescopic handle for plug-in vane probes, max. 1 m long 0430 0941 Cable, 1.5 m long, connects probe with plug-in head to meas. instrument 0430 0143 PUR coating material Extension for telescopic handle, 2 m long 0430 0942 Cable, 5 m long, connects probe with plug-in head to measuring instrument 0430 0145 please also order the 0409 0063 extension cable PUR coating material Handle for plug-in vane probes 0430 3545 Extension cable, 5 m long, between plug-in head cable and instrument 0409 0063 PUR coating material Extension cable, 5 m long, between plug-in head cable and instrument 0409 0063 Telescopic handle, max. 1 m, for probe with plug-in head 0430 0144 PUR coating material cable: 2.5 m long, PUR coating material Connection hose, silicone, 5m long 0554 0440 testo saline pots for control and humidity adjustment of humidity probes, 0554 0660 max. load 700 hPa (mbar) 11.3 %RH and 75.3 %RH with adapter for humidity probe Cover plugs for test holes (50 off) 0554 4001 Metal protection cage, Ø 12 mm for humidity probes 0554 0755 for measurement in flow velocities of less than 10 m/s Cap with wire mesh filter, Ø 12 mm 0554 0757 PTFE sintered filter, Ø 21 mm, for corrosive substances 0554 0666 high humidity range (long-term measurements), high velocities Accessories for temperature probes Part no. Sintered PTFE filter, Ø 12 mm, for corrosive media 0554 0756 Silicone heat paste (14g), Tmax = +260°C 0554 0004 High humidity range (long-term measurements), high flow velocities. improves heat transfer in surface probes Stainless steel sintered cap, Ø 21 mm, can be screwed onto humidity probe 0554 0640 Cable, 1.5 m long, connects probe with plug-in head to meas. instrument 0430 0143 protection in case of high mechanical load and high velocities PUR coating material Stainless steel sintered cap, Ø 12 mm, is screwed onto humidity probe 0554 0647 Cable, 5 m long, connects probe with plug-in head to measuring instrument 0430 0145 for measurements at higher flow velocities or in contaminated air PUR coating material PTFE cap, Ø 5 mm, attachable, PTFE material, (5 off) PTFE 0554 1031 Extension cable, 5 m long, between plug-in head cable and instrument 0409 0063 dust protection, high humidity measurements, high flow speeds for humidity PUR coating material probe 0636 2130 Telescopic handle, max. 1 m, for probe with plug-in head 0430 0144 PTFE sintered filter, Ø 12 mm, for corrosive substances 0554 0758 cable: 2.5 m long, PUR coating material high humidity range (non-stop measurements), high flow speeds12 Additional information at www.testo.com
  13. 13. testo 400 The reference measuring instrument for A/C and ventilation systemsPrecision reference classmeasuring instruments haveeverything the professional user VAC module for evaluating theneeds to complete complicated measurement directly on site withmeasurement tasks efficiently, integrated inaccuracy calulationaccurately and conveniently. Clear graphics display Attachable printer 3 user defined function buttons Prints readings on site in thetesto 400 includes the matter of secondsparameters Save up to max. 500,000 readings) or print at the touch of a buttontemperature, CO2, rpm, current, Mains connection/quick batteryvoltage, relative humidity, rechargepressure, flow and volume flow. Attachable printer (optional) Clear graphics displayIntelligent electronics ensure the Prints readings on site in a matter of °Clatest technology is used thanks secondsto software updates. Data communication via PC Data communication with PC,The measuring instrument can User friendly operation with cursor via barcode readeralways keep up with the menu structure 3 user defined functionmeasurement tasks at hand Integrated reading memory for up to buttonsthanks to upgrades. 500,000 readings Saves or prints at the touch of a buttonUpgradable and teachable, highly Easy operation with cursorreliable and of the highest quality -they are the properties whichguarantee that the customer isequipped for the future.Useful instrument functions:• System accuracy up to 0.05 °Cand up to a resolution of 0.001 °C Mains connection/Fast• All functions of testo 650 and battery rechargingtesto 950 2 user-defined probe sockets• Input of cross-sections forvolume flow calculation• Absolute pressurecompensation in thermal probes• Density calculation for velocitymeasurement with reference totemperature, humidity and Meanabsolute pressure 2.0 + 0.8 m/s -• Turbulence degreemeasurement to EN 137729 14760 + 5525 m3/h -• Assessment of volume flowmeasurements with calculation oftotal uncertainty of measurement Assessment of measurement directly onin accordance with EN 12599 location with integrated uncertaintywith VAC module (optional) testo 400 calculation testo 400, multi-functional measuring instrument, incl. measurement value store up to 500,000 readings, VAC-module 1/1 (H 250 / V 500 mm) (determination of volume flow with error calculation), battery, Li-cell and calibration protocol x + + + Can be used for: • Velocity, volume flow • Humidity, pressure + + + + • Temperature • CO2, rpm and current/voltage Part no. 0563 4001 The coordinates required for the grid measurement are shown in the instrument display. The depth information on the vane telescopic handle makes the task that much easier in practice. Additional information at www.testo.com 13

×