5.3.5 Drop Phase

Loading...

Flash Player 9 (or above) is needed to view presentations.
We have detected that you do not have it on your computer. To install it, go here.

0 comments

Post a comment

    Post a comment
    Embed Video
    Edit your comment Cancel

    Favorites, Groups & Events

    5.3.5 Drop Phase - Presentation Transcript

    1. 400 V three-phase section 230 V single-phase section
    2. Vd calculated for the three-phase mains, cannot be added to the Vd calculated for the single-phase circuits
    3. Convert the single phase voltage drop values to three phase by multiplying by 1.732. (square root of 3). Then add together the three phase figures and work on the three-phase Vd allowance, which for 400 V works out to 20 V.
    4. Convert the three-phase voltage drop values to single-phase by dividing by 1.732. (√3). Then add together the single-phase figures and work on the single-phase Vd allowance, which for 230 V works out to 11.5 V.
    5. Convert the single-phase voltage drop values to a percentage of 230 V and the three- phase voltage drop values to a percentage of 400 V and add the two percentages to check if 5 % is not exceeded.
    SlideShare Zeitgeist 2009

    + Talia CarbisTalia Carbis Nominate

    custom

    145 views, 0 favs, 0 embeds more stats

    More info about this document

    © All Rights Reserved

    Go to text version

    • Total Views 145
      • 145 on SlideShare
      • 0 from embeds
    • Comments 0
    • Favorites 0
    • Downloads 0
    Most viewed embeds

    more

    All embeds

    less

    Flagged as inappropriate Flag as inappropriate
    Flag as inappropriate

    Select your reason for flagging this presentation as inappropriate. If needed, use the feedback form to let us know more details.

    Cancel
    File a copyright complaint
    Having problems? Go to our helpdesk?

    Categories