Sc206 Document Transcript

  • 1. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Generating RatesPOWER RATING PRIME STANDBY kVA 188 206POWER kW 150 162Rated Speed r.p.m 1500Standard Voltage V 400Available Voltages V 400/230 - 230/132 - 230 VRated at power factor Cos PhiAmbient conditions of reference: 1000 mbar, 25ºC, 30% relative humidity. Power according to ISO 3046normative.P.R.P. Prime Power - ISO 8528 : prime power is the maximum power available during a variable powersequence, which may be run for an unlimited number of hours per year,between stated maintenance intervals.The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10%overload available forgoverning purposes only.Standby Power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time(500h), within the following limits of maximum operating time: 100% load 25h per year – 90% load 200h peryear. No overload available. Applicable in case of failure of the main in areas of reliable electrical network.
  • 2. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Engine Specifications 1500 r.p.m.ENGINE PRP STANDBYRated Output kW 163 180Manufacturer CumminsModel 6CTA8.3G2No. of Cylindirs and Build 4 Cycle; In-line; 6 Cylinder DieselAspiration and Cooling Turbocharged,after-cooledBore/Stroke mm 114X135Compress the ratio 16.5:1Cooling system Water-cooledEngine Speed/Frequency rpm/Hz 1500/50HZCoolant Capacity L 38Starting System Electric 24 volt DCDisplacement L 8.3Lubricant system Capacity L 24Battery Volatge / Capacity 24VDCGoverning Type Type ElectricalAir Filter Type Dry Load 100% 75% 50% 25%Fuel Consumption L/h 40.0 30.0 20.0 11.0ENGINE--Industrial 4 stroke cooled diesel engine complete with air,fuel and oil filters,electricstarting and charging equipment,engine protection against low water level.COOLING--Radiator and colling fan complete with protection guards,designed to cool engine atspecified output in air temperatures upto 45 ℃,radiators suitable for higher temperatures areavailable.Low water level protection fitted as standard.ELECTRICAL SYSTEM--24V upto.Axial type starter motor,battery charging alternator,high capacitylead acid battery,and battery tray mounted on the generator base frame,and heavy dutyinterconnecting cable with terminations.EXHAUST SYSTEM--Heavy duty industrial exhauset silencer with flexible piping.
  • 3. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Alternator Technical SpecificationsALTERNATOR BRAND LEROY SOMER STAMFORDModel LSA46.2M3 UCI274GExciter System Self-excited, brushlessPoles Num 4Cooling Fan Cast alloy aluminumBearing Single,double shieldedWindings 100% copperConnection Type ReconnectableInsulation Type Class Class HPitch 2/3Amortisseur Winding FullVoltage Regulator A.V.R. (Electronic)Steady Voltage Precision ± 1%Underspeed Protection StandardOverexcitation Protection IP23TIF (1960 Weightings) <50ALTERNATOR--Brushless,self exciting,self regulation,sreen protected,drip proof rated inaccordance with IEC60034.Voltage regulation maintainted within ±0.5% from no load to fullload.between 0.8 lagging and unity.All standard voltages available.
  • 4. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Control Panel Technical SpecificationsControl Panel- ComAp AMF20The base mounted control panel in a vibration isolated sheet steel enclosure.The control panel isequipped as follows:a)Instruments:Analogue Volmeter,Hours Run Meter.Water pressure Meter.b) Controls:Emergency Stop Pushbutton,Volmeter Phase Selector Switch.c) Control module:Standard collocation is ComAp AMF20 Auto start with AMF.Main Features:ΔAutomatic mains failureΔEngine control,Generator protectionΔBuilt in alarms and warningsΔRemote Start operation availableΔDaily / weekly / monthly exerciserΔWeekly operation schedule programsΔFuel pump controlΔECU control and monitoring via J1940 CANBUSΔMains simulationΔBlock heater controlΔField adjustable parametersΔFree MS-Windows Remote monitoringΔLED displaysΔConfigurable analogue inputsΔI/O expansion capabilityProtection Circuits InstrumentsWARNING ENGINEBattery charge failure Engine speedLow battery voltage Oil pressureSHUT DOWNS Coolant temperatureFail to start Run timeEmergency stop Battery voltsLow oil pressure TORHigh engine temperature Voltage (L-N)Over /Under speed Current (L1-L2-L3)Under/over generator frequency FrequencyFailed to reach loading voltage MAINSELECTRICAL TRIP Voltage (L-L, L-N)Generator over current
  • 5. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Generating Sets Standard FeaturesThree phase four wire,output voltage 400V/230V,50HZ,between 0.8 lagging,protection capabilityaccording with the standard of NAME1 and IP23.General Features:ΔComposed of Cummins diesel engine and Stamford or Leroy somer alternatorΔOil and fuel filter fitted,water separatorΔLube-oil drain valve fittedΔElectric Starter Charge motor 24 VD.CΔWater-cooledΔ8-hours operation base tankΔ Auto startΔOptional soundproof and weatherproof canopyΔ3 pole MCCB Delixi breakerΔOperation & Maintenance manualΔSpecial Integrated Steel Base tank and sprayed overall in gloss enamel paintVoltage Regulation:Voltage regulation maintanined within ±0.5%Between 0.8 and 1.0 lagging and unityFrom no load to full loadAt speed droop variation upto 4.5%Frequency Adjustable Ratio:Change load from 0-100%,within 1.0%( electric speed regulator),within 4.5%( mechanical speedregulator)Frequency Undulation:load from 0-100%,frequency undulation within 0.25%No load wire volts max undulation ration within 1.8%Three Phrase balanced load in the order of 5%Effect factor of TelecomTIF better than 50THF to IEC60034 Part 40 better than 2%
  • 6. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Soundproofed Version FeaturesRobust Corrosion Resustant ConstructionΔ Black finish stainless stell lock and hingesΔ Body made from steelcomponents treated with polyester powder coatingExcellent Access for MaintenanceΔ Two large doors on each sideΔ Radiator fill access plateΔlube oil and cooling water drains pipes to exterior of the enclosureSecurity and SafetyΔ Control panel viewing window in a lockable access doorΔ Emergency stop push buttom (red)mounted on enclosure interiorΔ Cooling fan and battery charging alternator fully guardedΔ Exhaust silencing system totally enclosed for operator safely
  • 7. Diesel Generating Sets Model: SC206 INDUSTRIAL RANGE Powered by Cummins Generating Sets other FeaturesGenerating Sets Optional FeaturesΔLow fuel level alarm shutdownΔAutomatic Fuel Filling SystemΔEngine oil feeding and drain pumpΔAuto Transfter Switch( ATS)ΔParallel control panelsΔCircuit Breaker MCCB & ACBΔRemote Control PanelΔweatherproof/soundproof CanopyΔTrailer type GensetsQuality StandardsISO9001:2000,ISO14000,ISO3046ISO8528 BS4999BS5514,AS1359,ICE34CE ComplianceGensets Dimensions & WeightOpen type:LxWxH (mm) Net Weight Kgs2440*980*1710,1500 KGSSilent type:LxWxH (mm) Net Weight Kgs3750*1080*2070, 1800kgs FUZHOU SUNSHINE MACHINERY CO.,LIMITED Fuzhou, Fujian, China. Tel:86-591-88204179 FAX:86-591-87723357 Email: sales@sunshinemach.com www.sunshinegenerator.comSUNSHINE,reserves the right to modify the characteristics of its product at any time in order to incorporate the latest technological developments.The informationcontained in this document may therefore be changed without notice.