  1. 1. Sharing our Guidance Lighting Circuiting and Design By: Hilmi Tannous
  2. 2. X Lighting Circuiting and Design • Always have a complete Luminaire schedule on plans • Include the Fixture Lamps • Include the Total Fixture Wattage • Include a detailed Fixture description • Include a complete Catalog number • Include the Fixture Voltage Lighting Circuiting 08/01/13 2
  3. 3. X Lighting Circuiting and Design • Always add the details from the previous slide to a client provided Luminaire schedule, like the Casual Male, F21 or JCP projects • Our Master Luminaire schedule is located in: T:EngineeringDetails and Schedules - AutocadDiv 26 - Electrical260000 - ELECTRICAL DRAWING ELEMENTS Lighting Circuiting (cont.) 08/01/13 3
  4. 4. X Lighting Circuiting and Design • When circuiting lighting plans always print the lighting plans and redline the design DO NOT CIRCUIT ON SCREEN! • Count all light fixtures and use different color highlighters • Keep all lights on the same circuits, adjacent to each other Lighting Circuiting (cont.) 08/01/13 4
  5. 5. X Lighting Circuiting and Design • For T8 & T5 Fluorescent Lamps use the total Lamp Wattage • i.e. If you have (2) 32W T8 lamps use 64W • Fluorescent Ballast factor can vary from .76 to 1.18 • BALLASTS SHALL BE INSTANT START, ELECTRONIC TYPE, CLASS P, "A" SOUND RATING AND MAXIMUM HARMONIC CONTENT OF 10% • DIMMING BALLASTS SHALL BE 3-WIRE TYPE, WITH DIMMING CAPABILITY TO 10% OF RATED FULL OUTPUT • ALL FIXTURE / BALLAST / LAMP COMBINATIONS SHALL BE ENERGY SAVING TYPE New Wattage Standards 08/01/13 5
  6. 6. X Lighting Circuiting and Design • GE 3 Lamp Ballast type 23673-GE-332 with 3 lamps the total fixture wattage is 85W. 11W less • Same Ballast with 2 lamps is 65W. 1W more • GE 4 Lamp Ballast type 23675-GE-432 with 3 lamps the total fixture wattage is 113W. 15W less • Same Ballast with 3 lamps is 97W. 1W more • Two level switching fixture with (2) ballasts [ 2-lamps and 1-lamp] total wattage is 61+36= 97W • To be safe use the total Lamp Wattage New Wattage Standards (cont.) 08/01/13 6
  7. 7. X Lighting Circuiting and Design • For CFL use the fixture wattage +4W. I.e. fixture with (2) 16W use 18+18+4= 40W • Except the 42W CFL add 5W • GE CFL13W 1 lamp fixture with 87533-GE1CFL13PH total system wattage is 16W • GE CFL42W 1 lamp fixture with 87573-GE1CFL42PH total system wattage is 47W New Wattage Standards (cont.) 08/01/13 7
  8. 8. X Lighting Circuiting and Design • For HID & HPS lamps: • 39W use 44W • 70W use 78W • 400W use 470W • 575W use 635W • 750W use 840W • 1000W 1130W New Wattage Standards (cont.) 08/01/13 8
  9. 9. X Lighting Circuiting and Design • For traditional incandescent Lamps like types A, use the Wattage of the Lamp • For low voltage MR16 lamps add 10% for ballast factors New Wattage Standards (cont.) 08/01/13 9
  10. 10. X Lighting Circuiting and Design • For LED fixtures: • If the driver is built-in, the total fixture wattage is what the manufacturer advertised, per IEC and DOE standard • For remote driver fixtures and fixtures where the EC has to provide a step down 24V transformer, add the LED wattage and driver efficiency New Wattage Standards (cont.) 08/01/13 10