Final Presentation 2010 (Building Services)
Upcoming SlideShare
Loading in...5
×
 

Like this? Share it with your network

Share

Final Presentation 2010 (Building Services)

on

  • 6,024 views

Perbentangan Akhir Kajian Intergrasi 2010

Perbentangan Akhir Kajian Intergrasi 2010

Statistics

Views

Total Views
6,024
Views on SlideShare
6,024
Embed Views
0

Actions

Likes
2
Downloads
119
Comments
2

0 Embeds 0

No embeds

Accessibility

Upload Details

Uploaded via as Microsoft PowerPoint

Usage Rights

© All Rights Reserved

Report content

Flagged as inappropriate Flag as inappropriate
Flag as inappropriate

Select your reason for flagging this presentation as inappropriate.

Cancel
  • Full Name Full Name Comment goes here.
    Are you sure you want to
    Your message goes here
    Processing…
Post Comment
Edit your comment

Final Presentation 2010 (Building Services) Presentation Transcript

  • 1. Dibentangkan oleh Mohd Wazir Bin Ahmad Radzi 15SPB08F2011 Muhammad Hazzril Bin Abdul Halim 15SPB08F2015 Muhamad Farid Bin Rahmin 15SPB08F2009 Nama penyelia : En. Cik Nordin Bin NayanPembentangan sesi Julai 2010
  • 2. Pengenalan Objektif Kajian Skop KajianPembentangan sesi Julai 2010
  • 3. Bangunan yang telah kami pilih ialah sebuah rumah banglo 2 tingkat. Sebagai sebuah rumah banglo, ia memerlukan rekabentuk untuk memberi keselesaan kepada pengguna :-  Sistem Pencegahan Kebakaran  Sistem Pengudaraan Dan Penyamanan Udara  Sistem Pencahayaan  Sistem Elektrik  Sistem SanitariPembentangan sesi Julai 2010
  • 4. Objektif projek ini adalah untuk merekabentuk sistem yang diperlukan didalam bangunan bagi memberi keselesaan kepada pengguna. 1. Sistem Pencegahan Kebakaran 2. Sistem Pengudaraan Dan Penyamanan Udara 3. Sistem Pencahayaan 4. Sistem Elektrik 5. Sistem SanitariPembentangan sesi Julai 2010
  • 5. Merekabentuk bangunan perlulah memuaskan dari segi kekemasan danmemberi keselesaan kepada pengguna.Kerja yang dilakukan adalahberkaitan dengan kerja merekabentuk sesebuah bangunan. Di antarakerja yang terdapat didalam skop adalah :-  Sistem Pencegahan Kebakaran  Sistem Pengudaraan Dan Penyamanan Udara  Sistem Pencahayaan  Sistem Elektrik  Sistem SanitariPembentangan sesi Julai 2010
  • 6. Sistem Pencegahan • Sistem yang digunakan untuk menunjukkan Kebakaran lokasi sistem pencegahan kebakaran. • Salah satu daripada sistem yang ada didalam Sistem Pengudaraan bangunan. Contoh sistem pengudaraan ialahDan Penyamanan Udara sistem tingkap, dan pengudaraan mekanikal. • Sistem pencahayaan yang digunakan perlu dikira Sistem Pencahayaan dengan betul supaya tiada kawasan yang tidak mendapat cahaya. • Sistem pendawaian elektrik yang dipasang perlu dikira dengan betul agar jumlah voltan dan Sistem Elektrik ampere supaya tidak mengalami lebihan arus pada litar yang dipasang. • Salah satu daripada keperluan asas yang harus Sistem Sanitari ada pada sesebuah bangunan contoh urinel, lurang, mangkuk tandas, dan sebagainya.Pembentangan sesi Julai 2010
  • 7. Cadangan Tajuk Penulisan Proposal Mendapatkan Pelan Membuat Persiapan Akhir Merekabentuk Mengira Luas Untuk Kertas Sistem-sistem Ruang Cadangan Projek Perkhidmatan Bangunan Membuat Penyerahan Pembentangan Laporan Akhir Akhir Kajian Kepada Penyelaras Integrasi ProjekPembentangan sesi Julai 2010
  • 8. Pembentangan sesi Julai 2010
  • 9. SISTEM PENCEGAHAN KEBAKARAN Teori GambarPerbentangan sesi Julai 2010
  • 10. Sistem Pencegahan Kebakaran BAHAYA SISTEM SISTEM PENCAHAYA PENDUDUKAN PEMADA PENGGERA AN M NOTA 2 KEBAKARA KECEMASAN N NOTA 3 NOTA 4 Kediaman kecil Rumah kediaman _ _ _ persendirian jenis teres rumah sebumbung. Undang-Undang Kecil Sistem Pencegahan Kebakaran ( undang-undang kecil 225 (1), 237 (1) )Pembentangan sesi Julai 2010
  • 11. Peralatan Pencegahan KebakaranPembentangan sesi Julai 2010
  • 12. SISTEM PENYAMANAN UDARA Pengiraan PelanPembentangan sesi Julai 2010
  • 13. Sistem Penyamanan Udara  Menggunakan alat penyamanan udara menggunakan 1 hingga 2.5hp  Ia dapat mengawal tahap kelembapan ruang dan menghasilkan udara yang nyaman  Menggunakan sistem penyamanan udara jenis unit pisah.Pembentangan sesi Julai 2010
  • 14. Merekabentuk kedudukan Penyamanan Udara (Living) Luas = 33.48 m2 Luas dan isipadu ditukarkan pada unit ft2 m2 ft2 m2 0.092 = ft2 = 33.48 m2 0.092 = 363.91 ft2Pembentangan sesi Julai 2010
  • 15. BTUH ruang Jumlah beban penyejukan yang disyaratkan bagi apartment (flats) adalah 40btuh/ft2 363.91 ft2 x 40 Btuh/ft2 = 14556.4 Btu/h Berdasarkan penyejukan untuk ruang ini adalah 14556.4 Btu/h dan model penghawa dingin yang bersesuaian adalah model G18LS yang mempunyai kapasiti penyejukan antara 18000 Btu/h.Pembentangan sesi Julai 2010
  • 16. Pelan Kedudukan Alat Penghawa Dingin Out - door In - doorPembentangan sesi Julai 2010
  • 17. Pelan Kedudukan Outdoor dari Pandangan KiriPembentangan sesi Julai 2010
  • 18. SISTEM PENCAHAYAAN TeoriPembentangan sesi Julai 2010
  • 19. Sistem Pencahayaan  Menggunakan dua jenis lampu iaitu lampu flourescent dan downlight dalam merekabentuk sistem pencahayaan mengikut kesesuaian ruang.  Menggunakan lampu flourescent 1 perumah 2 lampu manakala lampu downlight menggunakan lampu LEDPembentangan sesi Julai 2010
  • 20. Pengiraan Sistem Pencahayaan No. Item Unit & Formula Possibility 1. Room Width (W) m 6.0 2. Room Length (L) m 5.4 3. Room Area, A m² 32.4 4. Ceiling Height, Hc m 3.6 5. Suspension Height, Hs m 0 6. Working Plane Height, Hw m 0.9 7. Mounting Height, Hm Hc-Hs-Hw = m 3.6 – 0 – 0.9 = 2.7 8. Room Index, Rl RI = L x W___ RI = 5.0 x Hm (L+W) 5.4__ 2.7 (6.0 + 5.4) = 1.05Pembentangan sesi Julai 2010
  • 21. 9. Reflectance Ceiling, Rc = 0.7 Wall, Rw = 0.5 Floor, Rf = 0.1 10. Utilisation Factor UF 0.44 11. Maintenance Factor MF @ LLF 0.85 12. Type of Lamp LED-A65-WW5-1W 13. Luminous Flux per Lamp 240 14. Illuminance Services E 50 15. Number of Lamp in each n 1 Luminaires 16. Number of Luminaires N= Ex N= 50 x32.4_ A____ 1 x 240 x 0.44 x 0.85 nx x UF x = 18.05 ≈ 18 MFPembentangan sesi Julai 2010
  • 22. Mengira kedudukan lampu BILANGAN LAMPU = 18 BUAH DIAMETER LAMPU = 4 Inci 6 BUAH LAMPU x = 24" = 61 cm 4" 600 cm - 61 cm = 539 cm = 539 cm bahagi 7 ruang = 77 cm = 0.77 m 3 BUAH LAMPU X 4" = 12 " = 30 cm 540 cm - 30 cm = 510 cm = 510cm bahagi 4 ruang = 127.7 cm = 1.277 mPembentangan sesi Julai 2010
  • 23. Pelan Sistem PencahayaanPembentangan sesi Julai 2010
  • 24. SISTEM PERKHIDMATAN ELEKTRIKPembentangan sesi Julai 2010
  • 25. Sistem Perkhidmatan Elektrik  Antara sistem yang terpenting dalam merekabentuk kerana melibatkan sistem – sistem yang lain contohnya sistem pencahayaan dan sistem penyamanan udara.  Soket juga memainkan peranan penting didalam mengoperasikan peralatan elektrik yang lain.Pembentangan sesi Julai 2010
  • 26. ARUS (A) SAIZ LITAR BIL JENIS BEBAN I= W BIL . LITAR FIUS (A) SKEMATIK V 1 Downlight 5A 87 X 5w = 87 X 100 = 36.25 240 5 5A = 36.25 = 7.25 ≈ 8 Mengikut 5A peraturan IEE perlu ditambah 1 5A litar 5A 5A = 9 litar 5A 5A 5A 5A 2 Flourescent Lamp 3 X 36w = 6 X 100 = 2.5 3 X 18w 240 5 5A 5A = 6 Flourescent = 2.5 = 0.5 lamp ≈ 1 litarPembentangan sesi Julai 2010
  • 27. ARUS (A) SAIZ FIUS BIL . LITAR BIL JENIS BEBAN I= W (A) LITAR SKEMATIK V 1 First Air Condition I = 720 at Dining 240 32A 1 Litar 32A 750w =3 2 Second Air I = 720 Condition at Dining 240 32A 1 Litar 32A 750w = 3 3 Air Condition at I = 1050 Master Bedroom 240 32A 1 Litar 32A 1050w = 4.38 4 Air Condition at I = 720 Family Dining 240 32A 1 Litar 32A 720w = 3 5 Air Condition at I = 1800 Living 240 32A 1Litar 32A 1800w =3Pembentangan sesi Julai 2010
  • 28. ARUS (A) SAIZ LITAR BIL JENIS BEBAN BIL . LITAR I= W FIUS (A) SKEMATIK V 1 Soket keluaran Menggunakan 30A 13A litar gelang 3 soket pada 2 litar kerana keluasan 4 soket pada 3 litar 30A melebihi 100m2 (5 Litar Gelang) Bilangan soket = 30A 18 soket 30A 30A 30APembentangan sesi Julai 2010
  • 29. Pelan Kedudukan Litar ElektrikPembentangan sesi Julai 2010
  • 30. Teori SISTEM SANITARI Pengiraan PelanPembentangan sesi Julai 2010
  • 31. Sistem Sanitari  Menggunakan sistem paip tunggal dalam merekabentuk sistem sanitari.  Hanya melibatkan WC dan Basin yang berhubung pada sistem ini  Merekabentuk sistem yang berupaya membawa aliran kotor ke tempat pengumpulan dan rawatanPembentangan sesi Julai 2010
  • 32. Pengiraan Saiz Paip Pelupusan Rujukan Kiraan Catatan a. Jumlah UL Jumlah 48 UL (Jadual 1 Kadar US B.S Tingkat Bawah 5572, 1978 alatan) WC – 1 X 14 = 14 Basin – 1 X 10 = 10 Jadual 1 Tingkat Atas WC – 1 X 14 = 14 Basin – 1 X 10 = 10 a. Saiz paip cabang Garis pusat adalah Andai kecerunan =1¼ 75mmtetapi disebabkan Garis pusat paip cabang = ada WC maka garis Jadual 2 75mm (Jadual 2 Kadar US mak. pusat saiz paip adalah paip cabang) 100mmPembentangan sesi Julai 2010
  • 33. a. Saiz paip tumpu Garis pusat 100mm Jumlah UL = 48 UL tetapi sama dengan Garis pusat paip tumpu = saiz paip cabang Jadual 3 100mm (Jadual 3 Kadar US Maka US max = paip tumpu) 750mm a. Saiz paip pengudaraan = 50mm Garis pusat Jadual 4 (garis pusat paip tumpu 100mm) pengudaraan 50mmPembentangan sesi Julai 2010
  • 34. Kedalaman Lurang MH1 - 1/40 X 6000mm = 150mm < 600mm MH2 – 1/40 X 6000mm + 600mm = 750mm MH3 – 1/60 X 6000mm + 750mm = 850mm MH4 – 1/60 X 6000mm + 850mm = 950mm MH5 – 1/60 X 6000mm + 950mm = 1050mm Saiz Lurang MH1 = 150mm < 600mm (rujuk jadual 1bagi saiz lurang) 450mm 600mmPembentangan sesi Julai 2010
  • 35. Jadual Rekabentuk Paip PelupusanPembentangan sesi Julai 2010
  • 36. Jadual Rekabentuk LurangPembentangan sesi Julai 2010
  • 37. Kesimpulan Dalam mengkaji dan merekabentuk tentang sistem – sistem di atas, kami dapat mempelajari tentang fakta –fakta dan undang –undang yang ditetapkan untuk merekabentuk sistem tersebut. Kemudian, kami juga telah mempelajari untuk merekabentuk sistem tersebut mengikut akta – akta yang telah ditetapkan.Pembentangan sesi Julai 2010
  • 38. Pembentangan sesi Julai 2010