SURGE DIVERTER
 Surges,     or transients, are brief overvoltage    spikes or disturbances on a power waveform    that can damage, degra...
   A surge diverter is a piece of equipment that    diverts excess voltages (caused by spikes in the    electrical supply...
   It should not pass any current at normal and    abnormal power frequency voltage.   It should breakdown as quickly as...
 Rod   gap Protector   tube or expulsion type surge diverter Valve   type surge diverter
 Itis a very simple type of diverter and  consists of two 1.5 cm rods, which are bent  at right angles with a gap in betw...
  The string of insulators for an overhead line  on the bushing of transformer has frequently a  rod gap across it. Unde...
  After the surge is over, the arc in the gap is  maintained by the normal supply voltage,  leading to short-circuit on t...
 This type of arrester is also called ‘protector  tube’ and is commonly used on system  operating at voltages up to 33kV....
 The series gap is set to arc over at a  specified voltage lower than the withstand  voltage of the equipment to be prote...
 They   are not very expensive. They   can be easily installed. They are improved form of rod gap arresters as they blo...
 An expulsion type arrester can perform only  limited number of operations as during each  operation some of the fiber ma...
 Valve  type arresters incorporate non linear  resistors and are extensively used on systems,  operating at high voltages...
 The  spacing of the series gaps is such that it  will withstand the normal circuit voltage. An over voltage will cause ...
 When the surge is over the non linear resistor assume high resistance to stop the flow of current.
 Under   normal conditions, the normal system  voltage is insufficient to cause the breakdown  of air gap assembly. On t...
 They provide very effective protection against surges. They operate very rapidly taking less than a second The impulse...
 They may fail to check the surge of very steep wave front reaching the terminal apparatus. This calls for additional ste...
 As  a voltage surge  travelling on the  line reaches the  surge diverter, it  breaks down at a  specified voltage  Vbd....
surge diverters
surge diverters
surge diverters
surge diverters
Upcoming SlideShare
Loading in...5
×

surge diverters

2,327

Published on

surge diverters

0 Comments
1 Like
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total Views
2,327
On Slideshare
0
From Embeds
0
Number of Embeds
0
Actions
Shares
0
Downloads
163
Comments
0
Likes
1
Embeds 0
No embeds

No notes for slide

surge diverters

  1. 1. SURGE DIVERTER
  2. 2.  Surges, or transients, are brief overvoltage spikes or disturbances on a power waveform that can damage, degrade, or destroy electronic equipment within any home, commercial building, or manufacturing facility. Transients can reach amplitudes of tens of thousands of volts. Surges are measured in microseconds.
  3. 3.  A surge diverter is a piece of equipment that diverts excess voltages (caused by spikes in the electrical supply) to earth, thus protecting sensitive electrical and electronic equipment. The surge diverter is normally installed in the main switchboard. The surge diverter ‘shunts’ voltages over 260 volts AC to ground, stopping most power spikes from causing any damage.
  4. 4.  It should not pass any current at normal and abnormal power frequency voltage. It should breakdown as quickly as possible after the abnormal high frequency voltage arrives. It should not only protect the equipment for which it is used but should discharge current without damaging itself. It should interrupt power frequency follow current after the surge is discharge to ground.
  5. 5.  Rod gap Protector tube or expulsion type surge diverter Valve type surge diverter
  6. 6.  Itis a very simple type of diverter and consists of two 1.5 cm rods, which are bent at right angles with a gap in between. One rod is connected to the line circuit and the other rod is connected to earth. The distance between gap and insulator must not be less than one third of the gap length so that the arc may not reach the insulator and damage it. The rod gap should be so set that it breaks down to a voltage not less than 30% below the voltage withstand level of the equipment
  7. 7.  The string of insulators for an overhead line on the bushing of transformer has frequently a rod gap across it. Under normal operating conditions, the gap remains non-conducting. On the occurrence of a high voltage surge on the line, the gap sparks over and the surge current is conducted to earth. In this way excess charge on the line due to the surge is harmlessly conducted to earth
  8. 8.  After the surge is over, the arc in the gap is maintained by the normal supply voltage, leading to short-circuit on the system. The rods may melt or get damaged due to excessive heat produced by the arc. The climatic conditions (e.g. rain, humidity, temperature etc.) affect the performance of rod gap arrester. The polarity of the surge also affects the performance of this arrester.
  9. 9.  This type of arrester is also called ‘protector tube’ and is commonly used on system operating at voltages up to 33kV. It essentially consists of a rod gap in series with a second gap enclosed within the fiber tube. The gap in the fiber tube is formed by two electrodes. The upper electrode is connected to rod gap and the lower electrode to the earth.
  10. 10.  The series gap is set to arc over at a specified voltage lower than the withstand voltage of the equipment to be protected. The follow-on current is confined to the space inside the relatively small fibre tube. Part of the tube material vaporizes, and the high pressure gases so formed are expelled through the vent at the lower end of the tube, causing the power follow-in arc to be extinguished. The device, therefore, has the desired self- clearing property.
  11. 11.  They are not very expensive. They can be easily installed. They are improved form of rod gap arresters as they block the flow of power frequency follow currents.
  12. 12.  An expulsion type arrester can perform only limited number of operations as during each operation some of the fiber material is used up. This type of arrester cannot be mounted on enclosed equipment due to discharge of gases during operation. Due to the poor volt/amp characteristic of the arrester, it is not suitable for protection of expensive equipment
  13. 13.  Valve type arresters incorporate non linear resistors and are extensively used on systems, operating at high voltages. It consists of two assemblies (i) series spark gaps and (ii) non-linear resistor discs The non-linear elements are connected in series with the spark gaps. Both the assemblies are accommodated in tight porcelain container. The spark gap is a multiple assembly consisting of a number of identical spark gaps in series. Each gap consists of two electrodes with fixed gap spacing.
  14. 14.  The spacing of the series gaps is such that it will withstand the normal circuit voltage. An over voltage will cause the gap to break down causing the surge current to ground via the non-linear resistors. The non-linear resistor discs are made of inorganic compound such as thyrite or metrosil. These discs are connected in series. The non-linear resistors have the property of offering a high resistance to current flow when normal system voltage is applied, but a low resistance to the flow of high surge currents.
  15. 15.  When the surge is over the non linear resistor assume high resistance to stop the flow of current.
  16. 16.  Under normal conditions, the normal system voltage is insufficient to cause the breakdown of air gap assembly. On the occurrence of an over voltage, the breakdown of the series spark gap takes place and the surge current is conducted to earth via the nonlinear resistances. Since the magnitude of surge current is very large, the nonlinear elements will offer a very low resistance to the passage of surge. The surge will rapidly go to earth instead of being sent back over the line.
  17. 17.  They provide very effective protection against surges. They operate very rapidly taking less than a second The impulse ratio is practically unity.
  18. 18.  They may fail to check the surge of very steep wave front reaching the terminal apparatus. This calls for additional steps to check steep fronted waves. Their performance is adversely affected by the entry of moisture into the enclosure. This necessitates effective sealing of the enclosure at all times.
  19. 19.  As a voltage surge travelling on the line reaches the surge diverter, it breaks down at a specified voltage Vbd. The voltage across the diverter instantly dips and as the surge current show discharges through it, a constant voltage of value Vr(residual voltag)
  1. A particular slide catching your eye?

    Clipping is a handy way to collect important slides you want to go back to later.

×