The presentation is about the Training Done at 220 KV GSS, Sanganer, Jaipur

The presentation is about the Training Done at 220 KV GSS, Sanganer, Jaipur

Statistics

Views

Total Views
24,954
Views on SlideShare
24,950
Embed Views
4

Actions

Likes
18
Downloads
0
Comments
4

2 Embeds 4

http://www.slashdocs.com 3
http://www.linkedin.com 1

Accessibility

Categories

Upload Details

Uploaded via as Adobe PDF

Usage Rights

© All Rights Reserved

Report content

Flagged as inappropriate Flag as inappropriate
Flag as inappropriate

Select your reason for flagging this presentation as inappropriate.

Cancel
  • Full Name Full Name Comment goes here.
    Are you sure you want to
    Your message goes here
    Processing…
Post Comment
Edit your comment

Industrial Training Presentation Presentation Transcript

  • 1. Training at 220 KV Grid Sub Station, Sanganer Kumar Mayur Sinha VIIth Sem., B.Tech (Electrical) 0602088(E-2)
  • 2. Power System
  • 3. Rajasthan Rajya Vidyut Prasaran Nigam Limited (RRVPNL)  A company under the Companies Act of1956  Established on 19 July, 2000 by Govt. of Rajasthan under the provisions of the Rajasthan Power Sector Reforms Act, 1999 as the successor company of RSEB.  An ISO 9001:2000 Certified Company  Registered Office at Vidyut Bhawan, Jyoti nagar Jaipur.
  • 4. Duties & Responsibilities of RRVPNL Transmission of bulk power from Intra state generating transmission of stations to inter- electricity phase point of DISCOMS Planning and co- ordination Complying with the relating to intra- directions of RLDC state and SLDC for its transmission operation
  • 5. 220 KV GSS in Jaipur Place No. of Capacity Tranformers (MW) Chomu 6 275.00 Heerapura 5 404.00 Kotputali 5 275.00 Kukas 3 212.50 Phulera 5 193.50 Sanganer 7 312.50 VKIA 3 175.00
  • 6. 220 KV Sanganer  Located at a distance of 11 KM from MNIT  It’s a transmission substation  Initially was 132 KV GSS  Later upgraded to 220KV in the year 1991  Installed transmission capacity of 312.50 MVA (7 tranformers)  Transmission Loss is about 23% in Raj.
  • 7. Control & Operation of GSS Works under the directions of RLDC and SLDC for load dispatch Load dispatch on the basis of the “Hourly GSS schedule” Permission from LDC for line or Transformer shutdown. Work in synchronization with DISCOMS for scheduled maintenance.
  • 8. Incoming Feeders One feeder of 220kv from KTPS. One feeder of 220kv from 400kv GSS Heerapura. One feeder of 220kv from 220 KV GSS Heerapura One feeder of 132kv from 220/132kv GSS Heearapura .
  • 9. Incoming Feeder
  • 10. Ratings of the instrument at the Incoming Feeder Instrument Rating Lightning arrester 198KV CVT 245KV, 200VA CT 800-400-200/1A, 5C, 20KA/1Sec. SF6 Circuit Breaker 245KV, 40KA/3Sec Wave Trap NA Line Isolator 800A
  • 11. SF6 CB Ratings Voltage 245KV Normal Current 2000A Lightning impulse withstand voltage 1050 KV Short circuit breaking current 40 KA Short circuit breaking duration 3 sec Gas Pressure SF6 (20 degree) 7 bar Air Pressure 20 bar Line Charging breaking current 125 A
  • 12. Stepping down of voltage to 132KV
  • 13. 220/132 KV, 100 MVA Transformer Type of Cooling ONAN ONAF OFAF Rated Power HV(MVA) 50 70 100 LV(MVA) 16.67 23.33 33.33 Rated Voltage HV(KV) 220 IV (KV) 132 LV(KV) 11 Rated Line Current HV(A) 131.37 183.92 262.74 IV(A) 218.95 306.53 437.90 LV(A) 874.97 1225.96 1751.44 No. of Phases 3 Max. Temp. rise Top Oil 40 over an ambient of Avg. Winding 55 50 degree Celsius Frequency 50 HZ
  • 14. 220/132 KV, 100 MVA Transformer
  • 15. Ratings of Equipments at 132 KV switchyard EQUIPMENT RATING MAIN BUS-II CVT 220KV//3/110V,200VA ISO. MAIN BUS-II CVT 800A,245KV BUS ISOLATER 145 KV,800A C.B. 1250A,145KV C.T. 400-200-100/5A,3C WT NA It has total of 13 bays with 10 SF6 type of CB & 3 Air Blast CB’s
  • 16. Equipments at 132 KV switchyard
  • 17. Circuit Breakers Air Blast CB SF6 CB
  • 18. 132 KV to 33 KV step down
  • 19. Rating of Tranformers at 33 KV and 11KV switchyards Voltage Power No. of Rating Rating Transformer 132/33KV 40/50MVA 1 132/33KV 20/25MVA 2 132/11KV 10/12.5MVA 1 33/0.4kv 250KVA 1
  • 20. 33 KV Switchyard
  • 21. Equipments at 33 KV Switchyard At total of 18 bays with 11 Vacuum CB & 6 MOCB also 1 SF6 CB Equipment Ratings 33 KV C.T 500-250-125/1A, 2C 33 KV Isolater. Bus 630A 33 KV Circuit Breaker 1250A, 36KV 33 KV capacitor Bank 38 KV, 7.2 MVAR LA 28KV 33 KV PT(ON BUS-I) 33KV/ /3*110V, 100VA
  • 22. 11 KV Switchyard
  • 23. Equipments at 11KV switchyard Equipments Ratings 11 KV Circuit Breaker 1250A,25KA/1Sec 11 KV C.T 400-200-100/5A,2C LA 11KV 11 KV PT ON BUS(3PH) 11KV/110 V, 100VA 11 KV Isolator Bus 400A 11 KV switchyard consisted of 6 bays, with all Vacuum types of CB
  • 24. Outgoing Feeder 132 KV
  • 25. Outgoing Feeder 33KV
  • 26. Outgoing Feeder 11KV
  • 27. Outgoing Feeder 132 KV 33KV 11KV  Purana Ghat  Durgapura -1  Muhana  Niwai  Durgapura-2  Tejawala  Mansarovar-1  Sanganer  Prem nagar  Mansarovar-2  Sitapura  Industrial  Balawala  I.O.C  Watika  Phagi  Malpura gate
  • 28. Fault Operation  Relay trips as fault is detected in the system  Breaker operates  Alarm at control room blows up.  Alarm is manually reset  Breaker is made off after 5 min  If the fault persists , Isolator is removed  Fault if at switchyard is checked  If no local fault present, then fault feeder is contacted.  Supply is resumed after fault removal
  • 29. Maintenance of GSS DAILY JOBS Visual checking for any hot spot Checking of air and gas leakage from the breaker Checking of air and gas pressure of breaker Checking of oil level from CT and CVT
  • 30. Maintenance of GSS MONTHLY JOB Thermo vision scanning of conductor joints and attending to the hot spot available Breaker operation checking from local and remote Isolators operation from remote and local. Measurement of specific gravity and voltage of 220 V D. C Battery cells.
  • 31. Transformer Maintenance Permission from SLDC Switching Load to other Tranformer CB connected is operated Isolators are operated Earthing is provided to remove the residual charge due to induction.
  • 32. Level of Members committee Subdivision level AEN, ARO, JEN Division level XEN, AEN (Concerned) Assist Account officer Circle Level SE, XEN Accounts Officer Vig. / Audit Officer/ XEN(M&P) Chief Engineer CE, SE, Sr. AO, SE (Comml.) level Vig/Audit Officer/SE(M&P) Corporate Level CMD, Director Finance,CE (Comm.), CE (O&M) JPr, Incharge Legal Section