Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                     Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                         Vol. 3, Issue 2, March -April 2013, pp.480-485
       Wind Behavior of Buildings with and without Shear Wall
                               Alfa Rasikan*, M G Rajendran **
                     *(Department of Civil Engineering, Karunya University, Coimbatore)
                    ** (Department of Civil Engineering, Karunya University, Coimbatore)

ABSTRACT
        Shear walls are specially designed               building. Shear wall frame interaction systems are
structural walls which are incorporated in               very effective in resisting lateral forces. Abdur
buildings to resist lateral forces that are              Rahman, Saiada Fuadi Fancy and Shamim Ara
produced in the plane of wall due to wind,               Bobby (3) have discussed the analysis of drift due to
earthquake and flexural members. This paper              wind loads and earthquake loads on tall structures.
presents the study and comparison of the                 The drift on high rise structures has to be considered
difference between the wind behavior of                  as it has a notable magnitude. B. Dean Kumar and
buildings with and without shear wall using              B.L.P. Swami (4) have discussed the wind effects
Staad pro.                                               on tall building frames. The wind pressures
                                                         computed by the gust effectiveness factor method
Keywords – Shear wall, STAAD PRO, Wind                   are rational and realistical. Hence it is an important
behavior                                                 and valid point to be considered for the design of
                                                         very tall buildings. T. Kijewski and A. Kareem (5)
1. INTRODUCTION                                          have discussed the full-scale study of the behavior
          Due to the interaction of the earth while      of tall buildings under winds. Figure 1 shows the
rotating the majority of the heat falls up on the        two functions of shear wall.
middle of the equator and only less towards the
north and south pole of the earth. The warm air rises
on the equator and the cold air is pulled in from the
ice caps .This spreads warmth across the globe
which results in moving air patterns. The
characteristics of wind are galloping, gust, ovalling,
flutter, eddies and buffeting.
          he wind flow interacts only with the
external shape of the structure for static structure.
The deflections under the wind load will not be
significant when the structure is very stiff. Hence
the structure is said to be static. For dynamic
structures there is an additional interaction with the
motion of the structure. Due to the action of natural
wind, gusts and other aerodynamic force which will
affect the tall buildings continuously.
          Shear wall mainly resists two types of
forces: shear forces and uplift forces. To resist the
horizontal earthquake forces, shear wall should
                                                         Fig.1.Functions of shear wall
provide the necessary lateral strength and to prevent
the roof or floor above from excessive side-sway,
                                                                     The staad model of the 15 storey
shear walls also should provide lateral stiffness.
                                                         building without shear wall in figure 2 and with
Shear walls are classified into different types. They
                                                         shear wall in figure 3 have been considered to carry
are coupled shear wall, core type shear wall, column
                                                         out the study. Also 20 storey building without shear
support shear wall, frame wall with infill frame,
                                                         wall in figure 4 and with shear wall in figure 5 have
rigid frame shear wall etc.
                                                         been considered to carry out the study. STAAD
          Anshuman. S, Dipendu Bhunia and Bhavin
                                                         PRO 2010 software has been considered for this
Ramjiyani (1) have discussed the solution of shear
                                                         study. The preliminary data for 15 storey building
wall in multi storey building. By providing shear
                                                         and 20 storey building are shown in table 1 and
wall in some frames, the top deflection was reduced
                                                         table 2 respectively.
to permissible deflection. Also it has been observed
                                                         Figure 2 shows the staad model of the 15 storey
that both bending moment and shear force in some
                                                         building without shear wall.
frames were reduced after providing the shear wall.
          P. S. Kumbhare and A. C. Saoji (2) have
discussed the effectiveness of changing reinforced
concrete shear wall location on multi-storeyed


                                                                                                480 | P a g e
Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                    Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                        Vol. 3, Issue 2, March -April 2013, pp.480-485
                                                       Table 1 gives the preliminary details of the 15
                                                       storey building.
                                                       Table 1: Preliminary Data
                                                           Height of each storey 4.0 m
                                                          Number of storey         Fifteen (G+14)
                                                          Shear wall thickness     200 mm
                                                          Grade of concrete and    M20 and Fe 415
                                                          steel
                                                          Size of beam             300 x 400 mm2
                                                          Size of column           600 x 800 mm2

                                                          Location                 Coimbatore


                                                       The 15 storey building is located in Coimbatore.
                                                       Therefore the wind velocity of the building is 39
                                                       m/s. Figure 4 shows the staad model of the 20
                                                       storey building without shear wall.




Fig.2. Staad model of the 15 storey building without
shear wall
Figure 3 shows the staad model of the 15 storey
building with shear wall.




                                                       Fig.4. Staad model of the 20 storey building without
                                                       shear wall
Fig.3.Staad model of the 15 storey building with
shear wall




                                                                                            481 | P a g e
Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                     Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                          Vol. 3, Issue 2, March -April 2013, pp.480-485
Figure 5 shows the staad model of the 20 storey     3. DEFLECTION DIAGRAM
building with shear wall.                              Figure 6 shows the deflection diagram of 15 storey
                                                       building without shear wall.




                                                       Fig.6. Deflection diagram of 15 storey building
Fig.5.Staad model of the 20 storey building with
                                                       without shear wall
shear wall
                                                       Figure 7 shows the deflection diagram of 15 storey
                                                       building with shear wall.
Table 2 gives the preliminary details of the 20
storey building.
Table 2: Preliminary Data
   Height of each 4.0m
   storey
   Number of storey       Twenty(G+19)

  Shear wall thickness      200 mm

  Grade of concrete         M20 and Fe 415
  and steel

  Size of beam              400 x 600 mm2

  Size of column            600 x 800 mm2

  Location                  Coimbatore


The 20 storey building is located in Coimbatore.
Therefore the wind velocity of the building is 39
m/s.
                                                       Fig.7. Deflection diagram of 15 storey building with
                                                       shear wall
2. LOADING CONSIDERATION
         Dead load and live load have been taken as
per IS 875 (Part 1) (1987) and IS 875 (Part 2)(1987)
respectively. Wind load calculation has been done
based on the IS 875 (Part 3) (1987).




                                                                                            482 | P a g e
Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                    Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                        Vol. 3, Issue 2, March -April 2013, pp.480-485
Figure 8 shows the deflection diagram of 20 storey     Table 3: Displacement of 15 storey building with
building without shear wall.                           and without shear wall

                                                       Storey            Displacement              Displacement of
                                                       Numbers           of 15 Storey Building     15 Storey
                                                                         without                   Building with
                                                                         Shear Wall (mm)           Shear Wall (mm)




                                                       Storey 15         145.012                   115.751
                                                       Storey 14         142.332                   112.820
                                                       Storey 13         138.939                   109.411
                                                       Storey 12         134.266                   105.124
                                                       Storey 11         128.200                   99.883
                                                       Storey 10         120.709                   93.663
                                                       Storey 9          111.796                   86.464
                                                       Storey 8          101.491                   78.311
                                                       Storey 7          89.849                    69.241
                                                       Storey 6          76.958                    59.312
                                                       Storey 5          62.961                    48.614
                                                       Storey 4          48.108                    37.303
                                                       Storey 3          32.868                    25.676
                                                       Storey 2          18.160                    14.366
Fig.8. Deflection diagram of 20 storey building
without shear wall                                     Storey 1          5.842                     4.730
Figure 9 shows the deflection diagram of 20 storey
building with shear wall.                              Table 3 gives the displacement of 15 storey building
                                                       with and without shear wall for each storey level.

                                                       4.2. 20 STOREY BUILDING
                                                       Comparison between displacement of 20 storey
                                                       building without shear wall and with shear wall at
                                                       each floor level are shown in table 4.
                                                       Table 4: Displacement of 20 storey building with
                                                       and without shear wall
                                                       Storey       Displacement of        Displacement of
                                                                    20 Storey              20 Storey
                                                       Numbers Building without             Building with
                                                                     Shear Wall (mm) Shear Wall (mm)




                                                        Storey     133.650               114.130
                                                        20
                                                        Storey     130.986               110.642
                                                        19
                                                        Storey     129.435               108.048
                                                        18
                                                        Storey     127.342               105.083
Fig.9. Deflection diagram of 20 storey building with
shear wall                                              17
                                                        Storey     124.492               101.669
                                                        16
4. RESULT AND DISCUSSION
                                                        Storey     120.907               97.803
4.1. 15 STOREY BUILDING
         Comparison between displacement of 15          15
storey building without shear wall and with shear       Storey     116.610               93.497
wall at each floor level are shown in table 3.          14



                                                                                            483 | P a g e
Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                         Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                             Vol. 3, Issue 2, March -April 2013, pp.480-485
   Storey      111.609              88.747                                                 160
   13
   Storey      105.916              83.564                                                 140




                                                            Top storey displacement (mm)
   12
   Storey      99.543               77.958                                                 120
   11                                                                                      100
   Storey      92.505               71.949                                                                                Without shear
   10                                                                                      80                             wall
   Storey 9    84.823               65.558
                                                                                           60                             With shear wall
   Storey 8    76.518               58.812
                                                                                           40
   Storey 7    67.615               51.738
                                                                                           20
   Storey 6    58.144               44.370
                                                                                             0
                                                                                                 15 storey building with and without shear
   Storey 5    48.147               36.744                                                                          wall
   Storey 4    37.690               28.908
                                                         Fig.10. Top storey displacement of 15 storey
   Storey 3    26.901               20.925               building with and without shear wall
                                                         Figure 10 shows that 15 storey building without
   Storey 2    16.096               12.927               shear wall results higher top storey displacement
                                                         when compared to 15 storey building with shear
   Storey 1    6.155                5.325
                                                         wall.
                                                         The top storey displacements of 20 storey building
  Table 4 gives the displacement of 20 storey building   without shear wall and with shear wall are shown in
  with and without shear wall for each storey level.     figure 11.
                                                                                           140
  4.3. TOP STOREY DISPLACEMENTS OF
                                                            Top storey displacement(mm)




  BUILDING WITH AND WITHOUT SHEAR                                                          135
  WALL                                                                                     130
           Comparison     between      top    storey
  displacement of 15 storey building and 20 storey                                         125
  building without shear wall and with shear wall are                                                                      without shear
                                                                                           120                             wall
  shown in table 5.
                                                                                           115                             with shear wall
  Table 5: Top storey displacement of building with
  and without shear wall                                                                   110
Building    Top Storey          Top Storey                                                 105
Model       Displacement of     Displacement of
            Building without    Building with                                              100
             Shear Wall (mm)    Shear Wall(mm)                                                   20 storey building with and without shear
                                                                                                                    wall
15 Storey     145.012             115.751
 Building                                                Fig.11. Top storey displacement of 15 storey
20 Storey     133.650             114.130                building with and without shear wall
 Building
                                                         Figure 11 shows that 20 storey building without
  Table 5 gives the top storey displacement of both 15   shear wall results higher top storey displacement
  storey and 20 storey building with and without shear   when compared to 20 storey building with shear
  wall.                                                  wall.
  The top storey displacement of 15 storey building
  without shear wall and with shear wall are shown in    5. CONCLUSION
  figure 10.                                                     A 15 storey building and 20 storey building
                                                         were analysed with shear wall and without shear
                                                         wall and the displacements of the buildings with
                                                         shear wall and without shear wall were compared.
                                                         From the above results it is seen that the
                                                         displacement for a 15 storey building with shear
                                                         wall was 20.18% less than the 15 storey building



                                                                                                                        484 | P a g e
Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and
                     Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                         Vol. 3, Issue 2, March -April 2013, pp.480-485
without shear wall and the displacement for 20
storey building with shear wall was 14.6% less than
the 20 storey building without shear wall. Hence it
is found that building with shear wall resists wind
load effectively.

REFERENCES
  [1]   Anshuman. S, Dipendu Bhunia , Bhavin
        Ramjiyani,            Solution of Shear Wall
        Location     in     Multistorey      Building,
        International Journal of Civil and
        Structural Engineering,Volume 2, No 2,
        2011,493-506.
  [2]   P. S. Kumbhare, A. C. Saoji, Effectiveness
        of Changing Reinforced Concrete Shear
        Wall Location on Multi-storeyed Building,
        International Journal of Engineering
        Research and Applications, Vol. 2, Issue 5,
        September- October 2012, 1072-1076.
  [3]   Abdur Rahman, Saiada Fuadi Fancy,
        Shamim Ara Bobby, Analysis of drift due
        to wind loads and earthquake loads on tall
        structures by programming language C,
        International Journal of Scientific and
        Engineering Research, Vol. 3, Issue 6,
        June 2012.
  [4]   B. Dean Kumar and B.L.P. Swami, Wind
        effects on tall building frames-influence of
        dynamic parameters, Indian Journal of
        Science and Technology, Vol. 3, No.
        5.May 2010, 583-587.
  [5]   T. Kijewski and A. Kareem, Full-scale
        study of the behavior of tall buildings
        under      winds,      NatHaz       Modeling
        Laboratory,      Department       of     Civil
        Engineering and Geological Sciences,
        University of Notre Dame, Notre Dame, IN
        46556.




                                                                                485 | P a g e

More Related Content

What's hot

Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...
Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...
Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...IRJET Journal
 
Paper id 41201610
Paper id 41201610Paper id 41201610
Paper id 41201610IJRAT
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET Journal
 
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...IRJET Journal
 
IRJET- Time History Analysis of Masonry Infilled RC Frames with Soft Stor...
IRJET-  	  Time History Analysis of Masonry Infilled RC Frames with Soft Stor...IRJET-  	  Time History Analysis of Masonry Infilled RC Frames with Soft Stor...
IRJET- Time History Analysis of Masonry Infilled RC Frames with Soft Stor...IRJET Journal
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...ijsrd.com
 
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...IRJET Journal
 
Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...IRJET Journal
 
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...IAEME Publication
 
IRJET- Seismic Analysis of Confined Masonry Building and RCC Building
IRJET- Seismic Analysis of Confined Masonry Building and RCC BuildingIRJET- Seismic Analysis of Confined Masonry Building and RCC Building
IRJET- Seismic Analysis of Confined Masonry Building and RCC BuildingIRJET Journal
 
IRJET- Seismic Analysis of Multi-Storied Building with Floating Column
IRJET-  	  Seismic Analysis of Multi-Storied Building with Floating ColumnIRJET-  	  Seismic Analysis of Multi-Storied Building with Floating Column
IRJET- Seismic Analysis of Multi-Storied Building with Floating ColumnIRJET Journal
 
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...IJERA Editor
 
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...IRJET Journal
 
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...IRJET Journal
 
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...eSAT Journals
 
Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...eSAT Journals
 

What's hot (19)

Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...
Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...
Enhancing Resistance Capacity of Soft Storey Building by Means of Shearwall I...
 
Paper id 41201610
Paper id 41201610Paper id 41201610
Paper id 41201610
 
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
IRJET-Effect of Shear Wall on Seismic Performance of RC Open Ground Storey Fr...
 
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...IRJET-  	  A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
IRJET- A Parametric Study on the Siesmic Performance of Flat Slab Multi-S...
 
IRJET- Time History Analysis of Masonry Infilled RC Frames with Soft Stor...
IRJET-  	  Time History Analysis of Masonry Infilled RC Frames with Soft Stor...IRJET-  	  Time History Analysis of Masonry Infilled RC Frames with Soft Stor...
IRJET- Time History Analysis of Masonry Infilled RC Frames with Soft Stor...
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
 
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...
A Study on Seismic Response of Reinforced Concrete Framed Buildings with and ...
 
G012263441
G012263441G012263441
G012263441
 
Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...Comparative study on behaviour of RCC and steel – concrete composite multisto...
Comparative study on behaviour of RCC and steel – concrete composite multisto...
 
Ap24275280
Ap24275280Ap24275280
Ap24275280
 
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...
STRUCTURAL COST COMPARISON OF LOW RISE BUILDING HAVING MOMENT RESISTING FRAME...
 
IRJET- Seismic Analysis of Confined Masonry Building and RCC Building
IRJET- Seismic Analysis of Confined Masonry Building and RCC BuildingIRJET- Seismic Analysis of Confined Masonry Building and RCC Building
IRJET- Seismic Analysis of Confined Masonry Building and RCC Building
 
IRJET- Seismic Analysis of Multi-Storied Building with Floating Column
IRJET-  	  Seismic Analysis of Multi-Storied Building with Floating ColumnIRJET-  	  Seismic Analysis of Multi-Storied Building with Floating Column
IRJET- Seismic Analysis of Multi-Storied Building with Floating Column
 
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...
Highly Deformable Energy-Dissipating Reinforced Concrete Elements in Seismic ...
 
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...IRJET-  	  Comparative Study of Flat Slab and Conventional Slab Structure wit...
IRJET- Comparative Study of Flat Slab and Conventional Slab Structure wit...
 
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
IRJET-Performance Improvement of Split Air Conditioner using Evaporative Cool...
 
Pragati towers
Pragati towersPragati towers
Pragati towers
 
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...
Stiffness degradation behavior of retrofitted rc infilled frame under cyclic ...
 
Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...Comparison of performance of lateral load resisting systems in multi storey f...
Comparison of performance of lateral load resisting systems in multi storey f...
 

Viewers also liked (20)

Ca32486491
Ca32486491Ca32486491
Ca32486491
 
Ie3115371544
Ie3115371544Ie3115371544
Ie3115371544
 
Gz3113501354
Gz3113501354Gz3113501354
Gz3113501354
 
Fz3111631166
Fz3111631166Fz3111631166
Fz3111631166
 
Gd3111841188
Gd3111841188Gd3111841188
Gd3111841188
 
Fw3111471149
Fw3111471149Fw3111471149
Fw3111471149
 
Gq3112761281
Gq3112761281Gq3112761281
Gq3112761281
 
Gi3112131218
Gi3112131218Gi3112131218
Gi3112131218
 
Gb3111731177
Gb3111731177Gb3111731177
Gb3111731177
 
Gj3112191223
Gj3112191223Gj3112191223
Gj3112191223
 
Me3421822188
Me3421822188Me3421822188
Me3421822188
 
Mn3422372248
Mn3422372248Mn3422372248
Mn3422372248
 
Mi3422102216
Mi3422102216Mi3422102216
Mi3422102216
 
Mk3422222228
Mk3422222228Mk3422222228
Mk3422222228
 
Jf3416691674
Jf3416691674Jf3416691674
Jf3416691674
 
In3115971601
In3115971601In3115971601
In3115971601
 
Hp3114551461
Hp3114551461Hp3114551461
Hp3114551461
 
Ig3115521556
Ig3115521556Ig3115521556
Ig3115521556
 
Ct34573579
Ct34573579Ct34573579
Ct34573579
 
Cliente – magrass
Cliente – magrassCliente – magrass
Cliente – magrass
 

Similar to Bz32480485

Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...
Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...
Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...IJERA Editor
 
Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall IJERA Editor
 
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...IRJET Journal
 
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...IRJET Journal
 
Structural Analysis of Unbonded Post-Tensioned Shear Wall
Structural Analysis of Unbonded Post-Tensioned Shear WallStructural Analysis of Unbonded Post-Tensioned Shear Wall
Structural Analysis of Unbonded Post-Tensioned Shear WallIRJET Journal
 
Wind Analysis of Tall Building with Floor Diaphragm
Wind Analysis of Tall Building with Floor DiaphragmWind Analysis of Tall Building with Floor Diaphragm
Wind Analysis of Tall Building with Floor DiaphragmIRJET Journal
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...ijsrd.com
 
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...ijsrd.com
 
IRJET- Study of Behaviour of Multi-Storey Building with Shear Walls
IRJET-  	  Study of Behaviour of Multi-Storey Building with Shear WallsIRJET-  	  Study of Behaviour of Multi-Storey Building with Shear Walls
IRJET- Study of Behaviour of Multi-Storey Building with Shear WallsIRJET Journal
 
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...IRJET Journal
 
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...Analysis of High Rise Multistoried Building With and without Shear Wall By Re...
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...IRJET Journal
 
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...Shakerqaidi
 
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...IRJET Journal
 
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...IRJET Journal
 
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...ijsrd.com
 
Earthquake Resistant Design of Low-Rise Open Ground Storey Framed Building
Earthquake Resistant Design of Low-Rise Open Ground Storey  Framed BuildingEarthquake Resistant Design of Low-Rise Open Ground Storey  Framed Building
Earthquake Resistant Design of Low-Rise Open Ground Storey Framed BuildingIJMER
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET Journal
 
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...ijceronline
 
Effect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumEffect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumIRJET Journal
 
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...IAEME Publication
 

Similar to Bz32480485 (20)

Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...
Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...
Review on Effective utilization of RCC Shear walls for Design of Soft Storey ...
 
Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall Analysis of flat slab building with and without shear wall
Analysis of flat slab building with and without shear wall
 
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...
Comparative and Parametric Study of Hillside Gateway Project of Irregular Str...
 
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
IRJET- A Research on Comparing the Effect of Seismic Waves on Multistoried Bu...
 
Structural Analysis of Unbonded Post-Tensioned Shear Wall
Structural Analysis of Unbonded Post-Tensioned Shear WallStructural Analysis of Unbonded Post-Tensioned Shear Wall
Structural Analysis of Unbonded Post-Tensioned Shear Wall
 
Wind Analysis of Tall Building with Floor Diaphragm
Wind Analysis of Tall Building with Floor DiaphragmWind Analysis of Tall Building with Floor Diaphragm
Wind Analysis of Tall Building with Floor Diaphragm
 
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
Lateral Load Analysis of Shear Wall and Concrete Braced Multi-Storeyed R.C Fr...
 
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...
Importance of Modeling of Masonry Infill and Effect of Soft Storey on Seismic...
 
IRJET- Study of Behaviour of Multi-Storey Building with Shear Walls
IRJET-  	  Study of Behaviour of Multi-Storey Building with Shear WallsIRJET-  	  Study of Behaviour of Multi-Storey Building with Shear Walls
IRJET- Study of Behaviour of Multi-Storey Building with Shear Walls
 
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
COMPARATIVE STUDY ON SEISMIC ANALYSIS OF CONVENTIONAL SLAB AND FLAT SLAB STRU...
 
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...Analysis of High Rise Multistoried Building With and without Shear Wall By Re...
Analysis of High Rise Multistoried Building With and without Shear Wall By Re...
 
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...
A Comprehensive Study on the Effect of Regular and Staggered Openings on the ...
 
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...
STUDY OF COMPARISON BETWEEN TWO ATRIUM BUILDINGS IN VARIOUS SEISMIC ZONES WIT...
 
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...
IRJET- Comparative Analysis of Multi-Storied Building with and without Shear ...
 
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...
Influence of Modeling Masonry Infill on Seismic Performance of Multi-Storeyed...
 
Earthquake Resistant Design of Low-Rise Open Ground Storey Framed Building
Earthquake Resistant Design of Low-Rise Open Ground Storey  Framed BuildingEarthquake Resistant Design of Low-Rise Open Ground Storey  Framed Building
Earthquake Resistant Design of Low-Rise Open Ground Storey Framed Building
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
 
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
Effectiveness of Shear Wall-Frame Structure Subjected to Wind Loading in Mult...
 
Effect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumEffect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with Podium
 
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...
EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFOR...
 

Recently uploaded

Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 3652toLead Limited
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxBkGupta21
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionDilum Bandara
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationSlibray Presentation
 
Moving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfMoving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfLoriGlavin3
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfAlex Barbosa Coqueiro
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 

Recently uploaded (20)

Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptx
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An Introduction
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck Presentation
 
Moving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdfMoving Beyond Passwords: FIDO Paris Seminar.pdf
Moving Beyond Passwords: FIDO Paris Seminar.pdf
 
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdf
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
DMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special EditionDMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special Edition
 

Bz32480485

  • 1. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 Wind Behavior of Buildings with and without Shear Wall Alfa Rasikan*, M G Rajendran ** *(Department of Civil Engineering, Karunya University, Coimbatore) ** (Department of Civil Engineering, Karunya University, Coimbatore) ABSTRACT Shear walls are specially designed building. Shear wall frame interaction systems are structural walls which are incorporated in very effective in resisting lateral forces. Abdur buildings to resist lateral forces that are Rahman, Saiada Fuadi Fancy and Shamim Ara produced in the plane of wall due to wind, Bobby (3) have discussed the analysis of drift due to earthquake and flexural members. This paper wind loads and earthquake loads on tall structures. presents the study and comparison of the The drift on high rise structures has to be considered difference between the wind behavior of as it has a notable magnitude. B. Dean Kumar and buildings with and without shear wall using B.L.P. Swami (4) have discussed the wind effects Staad pro. on tall building frames. The wind pressures computed by the gust effectiveness factor method Keywords – Shear wall, STAAD PRO, Wind are rational and realistical. Hence it is an important behavior and valid point to be considered for the design of very tall buildings. T. Kijewski and A. Kareem (5) 1. INTRODUCTION have discussed the full-scale study of the behavior Due to the interaction of the earth while of tall buildings under winds. Figure 1 shows the rotating the majority of the heat falls up on the two functions of shear wall. middle of the equator and only less towards the north and south pole of the earth. The warm air rises on the equator and the cold air is pulled in from the ice caps .This spreads warmth across the globe which results in moving air patterns. The characteristics of wind are galloping, gust, ovalling, flutter, eddies and buffeting. he wind flow interacts only with the external shape of the structure for static structure. The deflections under the wind load will not be significant when the structure is very stiff. Hence the structure is said to be static. For dynamic structures there is an additional interaction with the motion of the structure. Due to the action of natural wind, gusts and other aerodynamic force which will affect the tall buildings continuously. Shear wall mainly resists two types of forces: shear forces and uplift forces. To resist the horizontal earthquake forces, shear wall should Fig.1.Functions of shear wall provide the necessary lateral strength and to prevent the roof or floor above from excessive side-sway, The staad model of the 15 storey shear walls also should provide lateral stiffness. building without shear wall in figure 2 and with Shear walls are classified into different types. They shear wall in figure 3 have been considered to carry are coupled shear wall, core type shear wall, column out the study. Also 20 storey building without shear support shear wall, frame wall with infill frame, wall in figure 4 and with shear wall in figure 5 have rigid frame shear wall etc. been considered to carry out the study. STAAD Anshuman. S, Dipendu Bhunia and Bhavin PRO 2010 software has been considered for this Ramjiyani (1) have discussed the solution of shear study. The preliminary data for 15 storey building wall in multi storey building. By providing shear and 20 storey building are shown in table 1 and wall in some frames, the top deflection was reduced table 2 respectively. to permissible deflection. Also it has been observed Figure 2 shows the staad model of the 15 storey that both bending moment and shear force in some building without shear wall. frames were reduced after providing the shear wall. P. S. Kumbhare and A. C. Saoji (2) have discussed the effectiveness of changing reinforced concrete shear wall location on multi-storeyed 480 | P a g e
  • 2. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 Table 1 gives the preliminary details of the 15 storey building. Table 1: Preliminary Data Height of each storey 4.0 m Number of storey Fifteen (G+14) Shear wall thickness 200 mm Grade of concrete and M20 and Fe 415 steel Size of beam 300 x 400 mm2 Size of column 600 x 800 mm2 Location Coimbatore The 15 storey building is located in Coimbatore. Therefore the wind velocity of the building is 39 m/s. Figure 4 shows the staad model of the 20 storey building without shear wall. Fig.2. Staad model of the 15 storey building without shear wall Figure 3 shows the staad model of the 15 storey building with shear wall. Fig.4. Staad model of the 20 storey building without shear wall Fig.3.Staad model of the 15 storey building with shear wall 481 | P a g e
  • 3. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 Figure 5 shows the staad model of the 20 storey 3. DEFLECTION DIAGRAM building with shear wall. Figure 6 shows the deflection diagram of 15 storey building without shear wall. Fig.6. Deflection diagram of 15 storey building Fig.5.Staad model of the 20 storey building with without shear wall shear wall Figure 7 shows the deflection diagram of 15 storey building with shear wall. Table 2 gives the preliminary details of the 20 storey building. Table 2: Preliminary Data Height of each 4.0m storey Number of storey Twenty(G+19) Shear wall thickness 200 mm Grade of concrete M20 and Fe 415 and steel Size of beam 400 x 600 mm2 Size of column 600 x 800 mm2 Location Coimbatore The 20 storey building is located in Coimbatore. Therefore the wind velocity of the building is 39 m/s. Fig.7. Deflection diagram of 15 storey building with shear wall 2. LOADING CONSIDERATION Dead load and live load have been taken as per IS 875 (Part 1) (1987) and IS 875 (Part 2)(1987) respectively. Wind load calculation has been done based on the IS 875 (Part 3) (1987). 482 | P a g e
  • 4. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 Figure 8 shows the deflection diagram of 20 storey Table 3: Displacement of 15 storey building with building without shear wall. and without shear wall Storey Displacement Displacement of Numbers of 15 Storey Building 15 Storey without Building with Shear Wall (mm) Shear Wall (mm) Storey 15 145.012 115.751 Storey 14 142.332 112.820 Storey 13 138.939 109.411 Storey 12 134.266 105.124 Storey 11 128.200 99.883 Storey 10 120.709 93.663 Storey 9 111.796 86.464 Storey 8 101.491 78.311 Storey 7 89.849 69.241 Storey 6 76.958 59.312 Storey 5 62.961 48.614 Storey 4 48.108 37.303 Storey 3 32.868 25.676 Storey 2 18.160 14.366 Fig.8. Deflection diagram of 20 storey building without shear wall Storey 1 5.842 4.730 Figure 9 shows the deflection diagram of 20 storey building with shear wall. Table 3 gives the displacement of 15 storey building with and without shear wall for each storey level. 4.2. 20 STOREY BUILDING Comparison between displacement of 20 storey building without shear wall and with shear wall at each floor level are shown in table 4. Table 4: Displacement of 20 storey building with and without shear wall Storey Displacement of Displacement of 20 Storey 20 Storey Numbers Building without Building with Shear Wall (mm) Shear Wall (mm) Storey 133.650 114.130 20 Storey 130.986 110.642 19 Storey 129.435 108.048 18 Storey 127.342 105.083 Fig.9. Deflection diagram of 20 storey building with shear wall 17 Storey 124.492 101.669 16 4. RESULT AND DISCUSSION Storey 120.907 97.803 4.1. 15 STOREY BUILDING Comparison between displacement of 15 15 storey building without shear wall and with shear Storey 116.610 93.497 wall at each floor level are shown in table 3. 14 483 | P a g e
  • 5. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 Storey 111.609 88.747 160 13 Storey 105.916 83.564 140 Top storey displacement (mm) 12 Storey 99.543 77.958 120 11 100 Storey 92.505 71.949 Without shear 10 80 wall Storey 9 84.823 65.558 60 With shear wall Storey 8 76.518 58.812 40 Storey 7 67.615 51.738 20 Storey 6 58.144 44.370 0 15 storey building with and without shear Storey 5 48.147 36.744 wall Storey 4 37.690 28.908 Fig.10. Top storey displacement of 15 storey Storey 3 26.901 20.925 building with and without shear wall Figure 10 shows that 15 storey building without Storey 2 16.096 12.927 shear wall results higher top storey displacement when compared to 15 storey building with shear Storey 1 6.155 5.325 wall. The top storey displacements of 20 storey building Table 4 gives the displacement of 20 storey building without shear wall and with shear wall are shown in with and without shear wall for each storey level. figure 11. 140 4.3. TOP STOREY DISPLACEMENTS OF Top storey displacement(mm) BUILDING WITH AND WITHOUT SHEAR 135 WALL 130 Comparison between top storey displacement of 15 storey building and 20 storey 125 building without shear wall and with shear wall are without shear 120 wall shown in table 5. 115 with shear wall Table 5: Top storey displacement of building with and without shear wall 110 Building Top Storey Top Storey 105 Model Displacement of Displacement of Building without Building with 100 Shear Wall (mm) Shear Wall(mm) 20 storey building with and without shear wall 15 Storey 145.012 115.751 Building Fig.11. Top storey displacement of 15 storey 20 Storey 133.650 114.130 building with and without shear wall Building Figure 11 shows that 20 storey building without Table 5 gives the top storey displacement of both 15 shear wall results higher top storey displacement storey and 20 storey building with and without shear when compared to 20 storey building with shear wall. wall. The top storey displacement of 15 storey building without shear wall and with shear wall are shown in 5. CONCLUSION figure 10. A 15 storey building and 20 storey building were analysed with shear wall and without shear wall and the displacements of the buildings with shear wall and without shear wall were compared. From the above results it is seen that the displacement for a 15 storey building with shear wall was 20.18% less than the 15 storey building 484 | P a g e
  • 6. Alfa Rasikan, M G Rajendran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 3, Issue 2, March -April 2013, pp.480-485 without shear wall and the displacement for 20 storey building with shear wall was 14.6% less than the 20 storey building without shear wall. Hence it is found that building with shear wall resists wind load effectively. REFERENCES [1] Anshuman. S, Dipendu Bhunia , Bhavin Ramjiyani, Solution of Shear Wall Location in Multistorey Building, International Journal of Civil and Structural Engineering,Volume 2, No 2, 2011,493-506. [2] P. S. Kumbhare, A. C. Saoji, Effectiveness of Changing Reinforced Concrete Shear Wall Location on Multi-storeyed Building, International Journal of Engineering Research and Applications, Vol. 2, Issue 5, September- October 2012, 1072-1076. [3] Abdur Rahman, Saiada Fuadi Fancy, Shamim Ara Bobby, Analysis of drift due to wind loads and earthquake loads on tall structures by programming language C, International Journal of Scientific and Engineering Research, Vol. 3, Issue 6, June 2012. [4] B. Dean Kumar and B.L.P. Swami, Wind effects on tall building frames-influence of dynamic parameters, Indian Journal of Science and Technology, Vol. 3, No. 5.May 2010, 583-587. [5] T. Kijewski and A. Kareem, Full-scale study of the behavior of tall buildings under winds, NatHaz Modeling Laboratory, Department of Civil Engineering and Geological Sciences, University of Notre Dame, Notre Dame, IN 46556. 485 | P a g e