Delta VFD Biasing Methods

1,493 views

Published on

This presentation explains specifically how to vary the gain & offset of VFD to make customize Voltage by Frequency curves

Unlock full featured course with 100+ Video Lectures at 30% Discount on "Advanced AC Drive- VFD, Stepper and Servo Drives" lifetime E-Learning course for 39 USD only: https://www.udemy.com/learn-vfd-in-a-day/?couponCode=slideshare2016

Enroll for Advanced Industrial Automation Training with PLC, HMI and Drive Combo with 300+ Video Lecture for 69.3 USD only: http://online.nfiautomation.org/catalog/1769?couponCode=LEARNING_MADE_EASY

0 Comments
2 Likes
Statistics
Notes
  • Be the first to comment

No Downloads
Views
Total views
1,493
On SlideShare
0
From Embeds
0
Number of Embeds
30
Actions
Shares
0
Downloads
164
Comments
0
Likes
2
Embeds 0
No embeds

No notes for slide

Delta VFD Biasing Methods

  1. 1. www.nfiautomation.org Delta VFD Biasing M Series
  2. 2. www.nfiautomation.org VFD Biasing 1 Volt = 5 Hz Pr.03=50Hz--Max. output Freq. Pr.48=0%--bias adjustment Pr.49=0 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.51=0 -- REV disable in negative bias 50 Hz 25 Hz 0 Hz 0 5V 10V
  3. 3. www.nfiautomation.org VFD Biasing 1 Volt = 5 Hz Pr.03= 50Hz--Max. output Freq. Pr.48= 20%--bias adjustment Pr.49= 0 -- bias polarity Pr.50= 100% -- pot. freq. gain Pr.51= 0 -- REV disable in negative bias 50 Hz Bias Adjustment = (Bias Range)/(Full range) x 100 = 10/50 x 100 = 20% 25 Hz Bias Adjustment 10 Hz 0 Hz 0 5V 10V
  4. 4. www.nfiautomation.org VFD Biasing Bias Adjustment = (XV/ Full voltage Range) x 100 (Full Freq. Range – Bias Freq. range) / (Full voltage range) = (Bias Freq. – 0 Hz) / XV Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100 Pot. Freq Gain 50 Hz Pr.03= 50Hz--Max. output Freq. Pr.48= 25%--bias adjustment Pr.49= 0 -- bias polarity Pr.50= 80% -- pot. freq. gain Pr.51= 0 -- REV disable in negative bias 25 Hz Bias Adjustment 10 Hz 0 Hz -2.5V 0 5V 10V
  5. 5. www.nfiautomation.org VFD Biasing Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100 50 Hz Pot. Freq Gain Pr.03= 50Hz--Max. output Freq. Pr.48= 0%--bias adjustment Pr.49= 0 -- bias polarity Pr.50= 200% -- pot. freq. gain Pr.51=0 -- REV disable in negative bias 25 Hz 0 Hz 0 5V 10V 1 Volt = 5 Hz
  6. 6. www.nfiautomation.org VFD Biasing Bias Adjustment = (XV/ Full voltage Range) x 100 (Full Freq. Range – Bias Freq. range) / (Full voltage range) = (Bias Freq. – 0 Hz) / XV Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100 Pot. Freq Gain 50 Hz Pr.03= 50Hz--Max. output Freq. Pr.48= 42.8 %bias adjustment Pr.49= 0 -- bias polarity Pr.50= 70 % pot. freq. gain Pr.51= 0 -- REV disable in negative bias Bias Adjustment 15 Hz 4.28 0 5V 10V
  7. 7. www.nfiautomation.org VFD Biasing Bias Adjustment = (Bias Voltage Range)/(Full Voltage range) x 100 = 1/10 x 100 = 10% 50 Hz Pr.03= 50Hz--Max. output Freq. Pr.48= 10%--bias adjustment Pr.49= 1 -- bias polarity Pr.50= 100% -- pot. freq. gain Pr.51= 0 -- REV disable in negative bias 45 Hz 25 Hz 0 Hz 0 Bias Adjustment 1 5V 10V
  8. 8. www.nfiautomation.org VFD Biasing Bias Adjustment = (Bias Voltage Range)/(Full Voltage range) x 100 = 1/10 x 100 = 10% Pot. Freq Gain 50 Hz Pr.03= 50Hz--Max. output Freq. Pr.48= ____ bias adjustment Pr.49= 1 -- bias polarity Pr.50= ____-- pot. freq. gain Pr.51= 0 -- REV disable in negative bias 25 Hz 0 Hz 0 Bias Adjustment 5V 10V Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100
  9. 9. www.nfiautomation.org VFD Biasing Bias Adjustment = (Bias Voltage Range)/(Full Voltage range) x 100 = 5/10 x 100 = 50% 50 Hz Fwd 25 Hz 2.5V 0 0 Hz 5V Rev 7.5V 10V 25 Hz 50 Hz Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100 Pr.03= 50Hz--Max. output Freq. Pr.48= 50%--bias adjustment Pr.49= 1 -- bias polarity Pr.50= 200% -- pot. freq. gain Pr.51= 1 -- REV disable in negative bias
  10. 10. www.nfiautomation.org VFD Biasing Bias Adjustment = (Bias Voltage Range)/(Full Voltage range) x 100 = 10/10 x 100 = 100% 50 Hz Pr.03=50Hz--Max. output Freq. Pr.48=100%--bias adjustment Pr.49=1 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.51=1 -- REV disable in negative bias 25 Hz 0 Hz 0 5V 10V
  11. 11. 100+ Video Tutorials Coupon Code in $99 $49 https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare Life time Access Course Outline Learn to Code | Code to Learn nfi Learn 4 PLC’s in a Day presents PLC – Programmable Logic Controller Delta DVP 14 SS + 16 SP • 100+ PLC Video Tutorials Allen Bradley M1000 • Doubt Clearing Complementary LIVE Sessions on Team Viewer Siemens S7 200 • Ladder Logic Programming Schneider • PLC Presentations, PLC Circuits, PLC Codes Analog Cards Programming • FREE PLC Simulation Software for Practice 04 AD – Analog to Digital 04DA- Digital to Analog For more courses visit www.nfiautomation.org
  12. 12. PLC & VFD Advanced Course 4 PLC’s Training Platforms $149 Course Link: Course Highlights: http://www.wiziq.com/course/28882-plc-andac-drives-online-certificate-trainaing-course • 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD • 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator • FREE Circuits Diagram For more courses visit www.nfiautomation.org
  13. 13. Thanks www.nfiautomation.org nfi

×