Guided Level Radar-Levelflex M FMP40
Upcoming SlideShare
Loading in...5
×
 

Like this? Share it with your network

Share

Guided Level Radar-Levelflex M FMP40

on

  • 1,292 views

Continuous Level Transmitter for Level Measurement in Bulk Solids and Liquids. Email: lam.nguyen@vietan-enviro.com HP: 0945 293292

Continuous Level Transmitter for Level Measurement in Bulk Solids and Liquids. Email: lam.nguyen@vietan-enviro.com HP: 0945 293292

Statistics

Views

Total Views
1,292
Views on SlideShare
1,292
Embed Views
0

Actions

Likes
0
Downloads
6
Comments
0

0 Embeds 0

No embeds

Accessibility

Categories

Upload Details

Uploaded via as Adobe PDF

Usage Rights

© All Rights Reserved

Report content

Flagged as inappropriate Flag as inappropriate
Flag as inappropriate

Select your reason for flagging this presentation as inappropriate.

Cancel
  • Full Name Full Name Comment goes here.
    Are you sure you want to
    Your message goes here
    Processing…
Post Comment
Edit your comment

Guided Level Radar-Levelflex M FMP40 Document Transcript

  • 1. TI00358F/00/EN/15.1271198459Technical InformationLevelflex M FMP40Guided Level RadarContinuous Level Transmitter for- Level Measurement in Bulk Solids and Liquids- Interface Measurement in LiquidsApplicationLevel measurementContinuous level measurement of powdery to granularbulk solids e.g. plastic granulate and liquids.• Measurement independent of density or bulk weight,conductivity, dielectric constant, temperature anddust e.g. during pneumatic filling.• Measurement is also possible in the event of foam or ifthe surface is very turbulent.• The HART with 4 to 20 mA analog, PROFIBUS PA andFOUNDATION Fieldbus protocols are available forsystem integration.• Application in safety related systems (overspillprotection) with requirements for functional safety upto SIL 2 in accordance with IEC 61508/IEC 61511-1.• WHG approvalInterface measurementContinuous measurement of interfaces between twoliquids with very different dielectric constants, such as inthe case of oil and water for example.• Measurement independent of density, conductivityand temperature• Electronics version for the simultaneous measurementof the level of interfaces and the total level in liquids.The HART with 4 to 20 mA analog protocol isavailable for system integration• Special version for the measurement of the level ofinterfaces at a constant total level. The PROFIBUS PAand FOUNDATION Fieldbus protocols are availablefor system integration.Your benefitsProbes are available with threaded process connectionsfrom ¾" and flanges from DN40 (1½").• Rope probes, above all for measurement in bulk solids,measuring range up to 35 m.• Rod probes, above all for liquids• Coax probes, for liquids• Simple, menu-guided onsite operation with four-lineplain text display.• Onsite envelope curve on the display for easydiagnosis.• Easy remote operation, diagnosis and measuring pointdocumentation with the free operating programsupplied.• Optional remote display and operation.• With coax probes the measurement is independent ofinternals in the tank and of the installation in thenozzle.• Probe rod and probe rope can be replaced/shortened.• Approvals: ATEX, FM, CSA, TIIS, NEPSI, IECEx.
  • 2. Levelflex M FMP402 Endress+HauserTable of contentsFunction and system design. . . . . . . . . . . . . . . . . . . . . 4Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Used frequency spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Data of the FOUNDATIONFieldbus interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Auxiliary energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Load HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19FISCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Performance characteristics. . . . . . . . . . . . . . . . . . . . 20Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 20Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Reaction time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Influence of ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . 21Operating conditions: installation with levelmeasurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22General information on level measurement . . . . . . . . . . . . . . . . 22Special notes for bulk solids . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Special notes for liquids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Operating conditions: installation with interfacemeasurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32General information on interface measurement . . . . . . . . . . . . . . 32Special information on interface measurement . . . . . . . . . . . . . . 34Operating conditions: general installation instructionsfor special installation situations . . . . . . . . . . . . . . . . 35Probe length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Installation in nozzles > 150 mm high . . . . . . . . . . . . . . . . . . . . 35Installation in DN200 (8") and DN250 (10") nozzles . . . . . . . . . . 35Installation in nozzle ≥ DN300 . . . . . . . . . . . . . . . . . . . . . . . . . . 36Installation with heat insulation . . . . . . . . . . . . . . . . . . . . . . . . . 36Installation at an angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Installation for difficult-to-access process connections . . . . . . . . . 37Replacing a displacer system in an existing displacer chamber . . . 39Operating conditions: Environment. . . . . . . . . . . . . . 40Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Ambient temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Cleaning the probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 40Operating conditions: Process . . . . . . . . . . . . . . . . . . 41Process temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Process pressure limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Dielectric constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Extension of the rope probes through tension and temperature . . 41Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 42Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42General information on flanges . . . . . . . . . . . . . . . . . . . . . . . . . . 44Tolerance of probe length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Material(not in contact with process) . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Material(in contact with process) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Process connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 56CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Overfill prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Telecommunications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Standards and guidelines applied . . . . . . . . . . . . . . . . . . . . . . . . 57Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 58Levelflex M FMP40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Flange with horn adapter to adapt on the following nozzles . . . . 62Remote display FHX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Centering disks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
  • 3. 3 Endress+HauserLevelflex M FMP40Commubox FXA195 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Commubox FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66ToF adapter FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Screw in flange FAX50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Extension rod (Centering) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Mounting-kit isolated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Additional documentation . . . . . . . . . . . . . . . . . . . . . 69Special Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
  • 4. Levelflex M FMP404 Endress+HauserFunction and system designMeasuring principle The Levelflex is a "downward-looking" measuring system that functions according to the ToF method(ToF = Time of Flight). The distance from the reference point (process connection of the measuring device,→ ä 43) to the product surface is measured. High-frequency pulses are injected to a probe and led along theprobe. The pulses are reflected by the product surface, received by the electronic evaluation unit and convertedinto level information. This method is also known as TDR (Time Domain Reflectometry).L00-FMP4xxxx-15-00-00-en-002Reference point of the measurement, details → ä 43Dielectric constantThe dielectric constant (DC) of the medium has a direct impact on the degree of reflection of the high-frequency pulses. In the case of large DC values, such as for water or ammonia, there is strong pulse reflectionwhile, with low DC values, such as for hydrocarbons, weak pulse reflection is experienced.InputThe reflected pulses are transmitted from the probe to the electronics. There, a microprocessor analyzes thesignals and identifies the level echo which was generated by the reflection of the high-frequency pulses at theproduct surface. This clear signal detection system benefits from over 30 years experience with pulse time-of-flight procedures that have been integrated into the development of the PulseMaster® software.The distance "D" to the product surface is proportional to the time of flight t of the impulse:D = c · t/2,where c is the speed of light.Based on the known empty distance "E", the level "L" is calculated:L = E – DReference point for "E" see diagram above.The Levelflex possesses functions for interference echo suppression that can be activated by the user.They guarantee that interference echoes from e.g. internals and struts are not interpreted as level echoes.20mA100%4mA0%DprobelengthLNLFEflange:referencepointofmeasurement
  • 5. Levelflex M FMP40Endress+Hauser 5Interface measurementWhen the high-frequency pulses hit the surface of the medium, only a percentage of the transmission pulse isreflected. In the case of media with a low DC1, in particular, the other part penetrates the medium. The pulseis reflected once more at the interface point to a second medium with a higher DC2. The distance to theinterface layer now can also be determined taking into account the delayed time-of-flight of the pulse throughthe upper medium.L00-FMP4xxxx-15-00-00-en-007OutputThe Levelflex is preset at the factory to the probe length ordered so that in most cases only the applicationparameters that automatically adapt the device to the measuring conditions need to be entered. For modelswith a current output, the factory adjustment for zero point "E" and span "F" is 4 mA and 20 mA. For digitaloutputs and the display module, the factory adjustment for zero point "E" and span "F" is 0 % and 100 %.A linearization function with max. 32 points, which is based on a table entered manually or semi-automatically,can be activated on site or via remote operation. This function allows the level to be converted into units ofvolume or mass, for example.DK1c = c = 300 000 km/s0C =1DK2DK1C0total levelinterface level
  • 6. Levelflex M FMP406 Endress+HauserMeasuring system Probe selectionThe various types of probe in combination with the process connections are suitable for the followingapplications:Probes with 1½" threaded connection or flangeType of probe: 6 mm rope probe 6 mm rope probePA-coated 1)4 mm rope probe 16 mm rod robe 16 mm rod probe,separable probeCoax probeMax. probe length: 35 m 2) 35 m 2) Liquids: 35 mBulk solids: 15 m4 m 10 m 4 mFor application: • Bulk solids • Bulk solidsespecially cereal,flour• Liquidsmeasuring range> 4 m• Liquids• bulk solids onshort measuringranges andsidewaymounting• Interfacemeasurement• Liquids• cramped mountingposition (limitedhead clearance)• Interfacemeasurement• Liquids• InterfacemeasurementSideways capacity: not relevant not relevant not relevant 30 Nm 20 Nm 300 NmTensile loading capacity(min.):rupture load (max.): 3)30 kN35 kN30 kN35 kN12 kN16 kNnot relevant not relevant not relevantFeature 30 Option "B" Option "H" Option "A" Option "K" Option "S, T, U, V" Option "L"1) ø6 mm + 2 mm PA coating.2) Greater lengths available on request.3) Max. load of silo ceiling. If overloaded, the rope tears; the bushing remains air-tight.
  • 7. Levelflex M FMP40Endress+Hauser 7Probes with ¾" threaded connectionStand-alone• Power supply directly from power line (4-wire) or from transmitter power supply unit (2-wire).• Onsite operation with integrated display or remote operation with HART protocol.L00-FMxxxxxx-14-00-06-en-008Type of probe: 4 mm rope probe 6 mm rod probe Coax probeMax. probe length: 35 m 1)1) Greater lengths available on request.2 m 4 mFor application: • Liquidsmeasuring range > 4 m• Liquids• Interface measurement• Liquids• Interface measurementSideways capacity: not relevant 4 Nm 60 NmTensile loading capacity (min.):rupture load (max.): 2)2) Max. load of silo ceiling. If overloaded, the rope tears; the bushing remains air-tight.5 kN12 kNnot relevant not relevantFeature 30 Option "A" Option "P" Option "L"ENDRESS + HAUSERE+–%ENDRESS + HAUSERRMA 4221# % &CopyG H IP Q R S, ( ) ‘A B CPastePageOnPageUpDeleteBkspInsertJ K LT U V_ < >D E FHot Key+ Hot KeyM N OW X Y Z+ * /47.2580375FIELD COMMUNICATOR369-9 6DELTABAR: * * * * * * * *ONLINE1 QUICK SETUP2 OPERATING MENU4 SV 0 °C3 PV 352 mbarHELP SAVEdsdmdmdf das.asdas faasas la.1# % &CopyG H IP Q R S, ( ) ‘A B CPastePageOnPageUpDeleteBkspInsertJ K LT U V_ < >D E FHot Key+ Hot KeyM N OW X Y Z+ * /47.2580375FIELD COMMUNICATOR369-9 6DELTABAR: * * * * * * * *ONLINE1 QUICK SETUP2 OPERATING MENU4 SV 0 °C3 PV 352 mbarHELP SAVEdsdmdmdf das.asdas faasas la.FieldCareFieldCareCommuboxFXA195Field Communicator375, 475FXA195or Field Communicator375, 475transmitter powersupply unitRMA422or RN221N(communication resistorincluded)PLCoperating anddisplay modulePower supply(for 4-wire)Commubox FXA291 withToF Adapter FXA291
  • 8. Levelflex M FMP408 Endress+HauserSystem integration via PROFIBUS PAMaximum 32 transmitters (depending on the segment coupler, 10 in the Ex ia IIC hazardous area accordingto the FISCO Model) can be connected to the bus. The Bus voltage is supplied by the segment coupler.Both onsite as well as remote operation are possible.L00-FMxxxxxx-14-00-06-en-001System integration via FOUNDATION FieldbusMax. 32 transmitters (standard, Ex em or Ex d) can be connected to the bus. In Ex ia IIC explosion protection:the max. number of transmitters is based on the applicable regulations and standards for interconnectingintrinsically safe circuits (EN 60079-14, proof of intrinsic safety). Both onsite as well as remote operation arepossible. The complete measuring system consists of:L00-FMxxxxxx-14-00-06-en-003ENDRESS + HAUSERMicropilot M Prosonic MLevelflex MENDRESS + HAUSERE+–%TPROFIBUS DPPROFIBUS PAFieldCarepersonal computer withFieldCare andProfibard resp. Proficardsegment couplerPLCoperating anddisplay moduleMoreFunctions(valves etc)Commubox FXA291 withToF Adapter FXA291T TENDRESS + HAUSERE+–%1# % &CopyG H IP Q R S, ( ) ‘A B CPastePageOnPageUpDeleteBkspInsertJ K LT U V_ < >D E FHot Key+ Hot KeyM N OW X Y Z+ * /47.2580375FIELD COMMUNICATOR369-9 6DELTABAR: * * * * * * * *ONLINE1 QUICK SETUP2 OPERATING MENU4 SV 0 °C3 PV 352 mbarHELP SAVEdsdmdmdf das.asdas faasas la.1# % &CopyG H IP Q R S, ( ) ‘A B CPastePageOnPageUpDeleteBkspInsertJ K LT U V_ < >D E FHot Key+ Hot KeyM N OW X Y Z+ * /47.2580375FIELD COMMUNICATOR369-9 6DELTABAR: * * * * * * * *ONLINE1 QUICK SETUP2 OPERATING MENU4 SV 0 °C3 PV 352 mbarHELP SAVEdsdmdmdf das.asdas faasas la.EthernetSPSPLCAPIFF linkFOUNDATION FieldbusMicropilot MProsonic MLevelflex MField Communicator375, 475FieldCareControlCareDeltaV...power supplypower conditionerCommubox FXA291 withToF Adapter FXA291operating anddisplay moduleadditionalfunctions(valves etc.)e.g.NI-FBUSconfigurator
  • 9. Levelflex M FMP40Endress+Hauser 9Integration into the tank gauging systemThe Endress+Hauser Tank Side Monitor NRF590 provides integrated communications for sites with multipletanks, each with one or more sensors on the tank, such as radar, spot or average temperature, capacitive probefor water detection and/or pressure sensors. Multiple protocols out of the Tank Side Monitor guaranteeconnectivity to nearly any of the existing industry standard tank gauging protocols.Optional connectivity of analog 4 to 20 mA sensors, digital I/O and analog output simplify full tank sensorintegration. Use of the proven concept of the intrinsically safe HART bus for all on-tank sensors yields extremelylow wiring costs, while at the same time providing maximum safety, reliability and data availability.L00-FMPxxxxx-14-00-06-en-004Levelflex M ProthermoTank SideMonitorFieldCareCommuboxFXA195TankScannerNXA820 NXA820DataConcentratorTCP/IPNXA820Host LinkDCSTankvisionworkstationPressureHART2 wireSupply voltage:16…253 VAC
  • 10. Levelflex M FMP4010 Endress+HauserSystem integration via FieldgateVendor Managed InventoryBy using Fieldgates to interrogate tank or silo levels remotely, suppliers of raw materials can provide theirregular customers with information about the current supplies at any time and, for example, account for themin their own production planning. For their part, the Fieldgates monitor the configured level limits and, ifrequired, automatically activate the next supply. The spectrum of options here ranges from a simple purchasingrequisition via e-mail through to fully automatic order administration by coupling XML data into the planningsystems on both sides.Remote maintenance of measuring equipmentFieldgates not only transfer the current measured values, they also alert the responsible standby personnel, ifrequired, via e-mail or SMS. In the event of an alarm or also when performing routine checks, servicetechnicians can diagnose and configure connected HART devices remotely. All that is required for this is thecorresponding HART operating software (e.g. FieldCare) for the connected device. Fieldgate passes on theinformation transparently, so that all options for the respective operating software are available remotely. Someonsite service operations can be avoided by using remote diagnosis and remote configuration and all others canat least be better planned and prepared.L00-FXA520xx-14-00-06-en-009Note!The number of devices which can be connected in multidrop mode can be calculated by the "FieldNetCalc"program. A description of this program can be found in Technical Information TI00400F/00/EN(Multidrop Connector FXN520).The program is available from your Endress+Hauser sales organization or on the Internet at:www.endress.com. → select your country → download → search: Fieldnetcalc.-FieldgateFXA520ENDRESS+HAUSERRN 221NENDRESS+HAUSERRN 221N.FieldgateFXA52020...45 VDCFXN520FXN520Multidrop-ConnectorFXN520HTTP scriptWeb browser…AnalogueEthernetGSMe.g. 2 x RN221N-B …Channel 1 Channel 2via HART Client:- FieldCare. . .Remote monitoringRemote configuration/diagnostics
  • 11. Levelflex M FMP40Endress+Hauser 11InputMeasured variable The measured variable is the distance between the reference point (see Fig., → ä 43) and the product surface.Subject to the empty distance entered "E" (see Fig., → ä 4), the level is calculated. Alternatively, the level canbe converted into other variables (volume, mass) by means of linearization (32 points).Measuring range Level measurementThe following table describes the media groups and the possible measuring range as a function of the mediagroup.The respective lower group applies for very loose or loosened bulk solids.Reduction of the max. possible measuring range through:• Extremely loose surfaces of bulk solids, e.g. bulk solids with low bulk weight for pneumatic filling.• Buildup, above all of moist products.Note!Due to the high diffusion rate of ammonia it is recommended to use the FMP45 with gas-tight bushing formeasurements in this medium.Interface measurementThe measuring range for interface measurement is limited to 10 m. Larger measuring range available onrequest.Medium group DC (εr) Typical bulk solids Typical liquidsMeasuring rangebare metallic probes PA-coatedRope probes1 1.4 to 1.6 - – Condensed gases, e.g. N2, CO2 4 m, only coax probe -2 1.6 to 1.9– Plastic granulate– White lime, special cement– Sugar– Liquefied gas, e.g. propane– Solvent– Freon– Palm oil25 m to 30 m 12.5 m to 15 m3 1.9 to 2.5– Portland cement, plaster – Mineral oils, fuels 30 m to 35 m -– Flour - - 15 m to 25 m4 2.5 to 4– Grain, seeds − − 25 m to 30 m– Ground stones– Sand– Benzene, styrene, toluene– Furan– Naphthalene35 m 25 m to 30 m5 4 to 7– Naturally moist (ground)stones, ores– Salt– Chlorobenzene, chloroform– Cellulose spray– Isocyanate, aniline35 m 35 m6 > 7– Metallic powder– Carbon black– Coal– Aqueous solutions– Alcohols– Ammonia35 m 35 m
  • 12. Levelflex M FMP4012 Endress+HauserBlocking distance The upper blocking distance (= UB) is the minimum distance from the reference point of the measurement(mounting flange) to the maximum level. At the lowest part of the probe an exact measurement is not possible,see "Performance characteristics", → ä 20.L00-FMP4xxxx-17-00-00-en-006Reference point of the measurement, details → ä 43Blocking distance and measuring range:Note!Within the blocking distance, a reliable measurement can not be guaranteed.Used frequency spectrum 100 MHz to 1.5 GHz100%0%FEUBBLNreferencepointofmeasurementmax. 20 m /67 ftremote displayFHX 40F = measuring spanE = emptydistance(=zero)UB = upperblockingdistanceLN = probelengthB = minimumdistanceoftheprobetothecontainerwallFMP40LN [m]minLN [m]maxUB [m]minRope probe 1 35 1)1) Larger measuring range available on request.0.2 2)2) The indicated blocking distances are preset. At media with DC > 7, the upper blocking distance UB can be reducedfor rod and rope probes on 0.1 m. The upper blocking distance UB can be entered manually.6 mm rod probe 0.3 2 0.2 2)16 mm rod robe 0.3 4 0.2 2)Coax probe 0.3 4 0FMP40 (interface)LN [m]minLN [m]maxUB [m]minCoax probe 0.3 4 016 mm rod probe in the bypass 0.3 4 0.1 1)1) The indicated blocking distances are preset. The upper blocking distance UB can be entered manually.6 mm rod probe in the bypass 0.3 2 0.1 1)Rope probe in free field 2)2) Measurements in free field available on request.0.3 103)3) Larger measuring range available on request.0.1 1)
  • 13. Levelflex M FMP40Endress+Hauser 13OutputOutput signal • 4 to 20 mA (invertible) with HART protocol• PROFIBUS PA:– signal coding: Manchester Bus Powered (MBP)– data transmission rate: 31.25 KBit/s, voltage mode• FOUNDATION Fieldbus (H1):– signal coding: Manchester Bus Powered (MBP)– data transmission rate: 31.25 KBit/s, voltage modeSignal on alarm Error information can be accessed via the following interfaces:• Local display:– Error symbol– Plain text display• Current output, signal on error can be selected (e.g. according to NAMUR recommendation NE43)• Digital interfaceLinearization The linearization function of the Levelflex M allows the conversion of the measured value into any unit oflength or volume and mass or %. Linearization tables for calculating the volume in cylindrical tanks arepreprogrammed. Other tables of up to 32 value pairs can be entered manually or semi-automatically. Thecreation of a linearization table with FieldCare is particularly convenient.Data of the FOUNDATIONFieldbus interfaceBasic DataVirtual communication references (VCRs)Link SettingsDevice Type 1012 (hex)Device Revision 04 (hex)DD Revision 02 (hex)CFF Revision 02 (hex)ITK Version 4.61ITK-Certification Driver-No. www.endress.com / www.fieldbus.orgLink-Master (LAS) cabable YesLink Master / Basic Device selectable Yes; Default: Basic DevceNumber VCRs 24Number of Link-Objects in VFD 24Permanent Entries 1Client VCRs 0Server VCRs 24Source VCRs 23Sink VCRs 0Subscriber VCRs 23Publisher VCRs 23Slot time 4Min. Inter PDU delay 6Max. response delay 10
  • 14. Levelflex M FMP4014 Endress+HauserTransducer BlocksFunction BlocksBlock Content Output valuesSensor Block Contains all parameters related to the measurement • Level or volume1) (channel 1)• Distance (channel 2)1) Depending on the configuration of the sensor-block.Diagnsotic Block Contains diagnostiv information No output valuesDisplay Block Contains parameters to configure the local display No output valuesBlock Content Execution time FunctionalityResource Block The Resource Block contains all the data that uniquelyidentifies the field device. It is an electronic version of anameplate of the device.enhancedAnalog InputBlock 1Analog InputBlock 2The AI block takes the manufacturers input data,selected by channel number, and makes it available to otherfunction blocks at its output.30 ms standardPID Block The PID block serves as proportional-integral-derivativecontroller and is used almost universally to do closed-loop-control in the field including cascade and feedforward.80 ms standardArithmetic Block This block is designed to permit simple use of popularmeasurement math functions. The user does not have toknow how to write equations. The math algorithm isselected by name, chosen by the user for the function tobe done.50 ms standardInput SelectorBlockThe input selector block provides selection of up to fourinputs and generates an output based on the configuredaction. This block normally receives its inputs from AIblocks. The block performs maximum, minimum, middle,average and "first good" signal selection.30 ms standardSignal Characte-rizer BlockThe signal characterizer block has two sections, eachwith an output that is a non-linear function of therespective input. The non-linear function is determined by asingle look-up table with 21 arbitrary x-y pairs.40 ms standardIntegrator Block The Integrator Function Block integrates a variable as afunction of the time or accumulates the counts from aPulse Input block. The block may be used as a totalizerthat counts up until reset or as a batch totalizer that has asetpoint, where the integrated or accumulated value iscompared to pre-trip and trip settings, generating discretesignals when these settings are reached.60 ms standard
  • 15. Levelflex M FMP40Endress+Hauser 15Auxiliary energyElectrical connection Connection compartmentThree housings are available:• Aluminum housing F12 with additionally sealed connection compartment for:– standard– Ex ia– dust ignition-proof• Aluminum housing T12 with separate connection compartment for:– standard– Ex e– Ex d– Ex ia (with overvoltage protection)– dust ignition-proof• Stainless steel 316L (1.4435) housing F23 for:– standard– Ex ia– dust ignition-proofAfter mounting, the housing can be turned 350° in order to make it easier to access the display and theconnection compartment.L00-FMR2xxxx-04-00-00-en-019Ground connection It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in orderto achieve EMC security.Cable glandTerminals For wire cross-sections of 0.5 to 2.5 mm21 12 23 34 41 2 3 4sealed terminalcompartmentF12 housing F23 housingT12 housingType Clamping areaStandard, Ex ia, IS Plastic M20x1.5 5 to 10 mmEx em, Ex nA Metal M20x1.5 7 to 10.5 mm
  • 16. Levelflex M FMP4016 Endress+HauserTerminal assignmentNote!If 4-wire for dust-Ex-applications is used, the current output is intrinsically save.Connect the connecting line to the screw terminals in the terminal compartment.Cable specification:A standard installation cable is sufficient if only the analog signal is used. Use a shielded cable when workingwith a superimposed communications signal (HART).Note!• Protective circuitry against reverse polarity, RFI and over-voltage peaks is built into the device (see alsoTI00241F/00/EN "EMC Test Procedures").• See TI00402F/00/EN for connection to Tank Side Monitor NRF590.2-wire, 4 to 20 mA with HART 4-wire, 4 to 20 mA active with HARTL00-FMxxxxxx-04-00-00-en-015 L00-FMxxxxxx-04-00-00-en-011Commubox FXA195Field Communicator 375, 475power5 6I+ I-1 2L1/L+ N/L-4...20mACommubox FXA195Field Communicator375, 475AC / DCDCalternativelypowerdisplay unit,recorder, PCSplantgroundPROFIBUS PAThe digital communication signal is transmitted to thebus via a 2-wire connection. The bus also provides theauxiliary energy.For further information on the network structure andgrounding and for further bus system componentssuch as bus cables, see the relevant documentation,e.g. Operating Instructions BA034S/04/EN"Guidelines for planning and commissioningPROFIBUS DP/PA" and the PNO Guideline.Cable specification:Use a twisted, shielded two-wire cable, preferablycable type A.L00-FMxxxxxx-04-00-00-en-022Note!For further information on the cable specifications, see Operating Instructions BA034S/04/ENGuidelines for planning and commissioning PROFIBUS DP/PA", PNO Guideline 2.092 "PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).3 41 2+–plantground
  • 17. Levelflex M FMP40Endress+Hauser 17Connector For the versions with a connector M12 or 7/8", the housing does not have to be opened for connecting thesignal line.PIN assignment for M12 connectorPIN assignment for 7/8" connectorFOUNDATION FieldbusThe digital communication signal is transmitted to thebus via a 2-wire connection. The bus also provides theauxiliary energy. For further information on thenetwork structure and grounding and for further bussystem components such as bus cables, see therelevant documentation, e.g. Operating InstructionsBA013S/04/EN "FOUNDATION FieldbusOverview" and the FONDATION Fieldbus Guideline.Cable specification:Use a twisted, shielded two-wire cable, preferablycable type A.L00-FMxxxxxx-04-00-00-en-022Note!For further information on the cable specifications, see Operating Instructions BA013S/04/EN"FOUNDATION Fieldbus Overview", FONDATION Fieldbus Guideline and IEC 61158-2 (MBP).3 41 2+–plantgroundA0011175PIN Meaning1 Signal +2 Not assigned3 Signal –4 EarthA0011176PIN Meaning1 Signal –2 Signal +3 Shield4 Not assigned2134+–nc2143
  • 18. Levelflex M FMP4018 Endress+HauserLoad HART Minimum load for HART communication: 250 ΩSupply voltage HART, 2-wireAll the following values are the terminal voltages directly at the device:HART residual ripple, 2-wire: Uss ≤ 200 mVHART, 4-wire activeResidual ripple HART, 4-wire, DC version: Uss ≤ 2 V, voltage incl.ripple within the permitted voltage (10.5 to 32 V)PROFIBUS PA and FOUNDATION FieldbusThe following values are the voltages across the terminals directly at the device:Communication Current consumption Terminal voltageHARTStandard4 mA 16 V to 36 V20 mA 7.5 V to 36 VEx ia4 mA 16 V to 30 V20 mA 7.5 V to 30 VEx emEx d4 mA 16 V to 30 V20 mA 11 V to 30 VFixed current, adjustable e.g. for solar poweroperation (measured value transmitted via HART)Standard 11 mA 10 V to 36 VEx ia 11 mA 10 V to 30 VFixed current for HART Multidrop modeStandard 4 mA1)1) Start up current 11 mA.16 V to 36 VEx ia 4 mA1) 16 V to 30 VVersion Voltage max. loadDC 10.5 to 32 V 600 ΩAC, 50/60 Hz 90 to 253 V 600 ΩType Terminal voltagestandard 9 V to 32 VEx ia (FISCO model) 9 V to 17.5 VEx ia (Entity concept) 9 V to 24 VSupply voltage 9 V to 32 V 1)1) There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in theappropriate safety instructions (XA).Lift-off voltage 9 V
  • 19. Levelflex M FMP40Endress+Hauser 19Cable entry • Cable gland: M20x1.5 (only cable entry for Ex d)• Cable entry: G½ or ½NPT• PROFIBUS PA M12 plug• FOUNDATION Fieldbus 7/8" plugPower consumption Min. 60 mW, max. 900 mWCurrent consumption HARTPROFIBUS PAMax. 11 mA.FOUNDATION FieldbusFISCOOvervoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use ofovervoltage protection according to EN/IEC 60079-14 or EN/IEC 60060-1 (10 kA, pulse 8/20 μs), it has tobe ensured that:• the measuring device with integrated overvoltage protection with 600 V gas discharge tubes within the T12-enclosure is used, refer to "Ordering information", → ä 58or• This protection is achieved by the use of other appropriate measures (external protection devices e.g.HAW562Z).Communication Output current Current consumption Power consumptionHART, 2-wire 3.6 to 22 mA1)1) For HART-Multidrop: start up current is 11 mA.— min. 60 mW,max. 900 mWHART, 4-wire (90 to 250 VAC) 2.4 to 22 mA ~ 3 to 6 mA ~ 3,5 VAHART, 4-wire (10.5 to 32 VDC) 2.4 to 22 mA ~ 100 mA ~ 1 WNominal current 15 mAStarting current ≤ 15 mAError current 0 mAFISCO/FNICO conformal CompliantPolarity sensitive NoUi 17,5 VIi 500 mA; with overvoltage protection 273 mAPi 5,5 W; with overvoltage protection 1,2 WCi 5 nFLi 0,01 mH
  • 20. Levelflex M FMP4020 Endress+HauserPerformance characteristicsReference operatingconditions• Temperature = +20 °C ±5 °C• Pressure = 1013 mbar abs. ±20 mbar• Humidity = 65 % ±20 %• Reflection factor ≥ 0.8 (surface of the water for coax probe, metal plate for rod and rope probe with min.1 m ∅)• Flange for rod or rope probe ≥ 30 cm ∅• Distance to obstructions ≥ 1 m• For interface measurement:– Coax probe– DC of the lower medium = 80 (water)– DC of the upper medium = 2 (oil)Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the span.If the reference conditions are not met, the offset/zero point arising from the mounting situation may be up to±12 mm for rope and rod probes. This additional offset/zero point can be compensated for by entering acorrection (function "Offset" (057)) during commissioning.Differing from this, the following measuring error is present in the vicinity of the level(electronic version level and interface measurement):If for rope probes the DC value is less than 7, then measurement is not possible in the area of the strainingweight (0 to 250 mm from end of probe; lower blocking distance).Output: Digital AnalogSum of non-linearity,non-repeatability andhysteresisLevel (electronic version level and interface measurement):– Measuring range up to 10 m: ±3 mm– Measuring range >10 m: ±0.03 %For PA-coated rope probes:– Measuring range up to 5 m: ±5 mm– Measuring range > 5 m: ±0.1 %±0.06 %Interface (only for electronic version "K" interface measurement):– Measuring range up to 10 m: ±10 mmIf the thickness of the interface is < 60 mm, the interface can no longerbe differentiated from the overall level such that both output signals areidentical.Offset / Zero ±4 mm ±0.03 %L00-FMP4xxxx-05-00-00-en-001 L00-FMP4xxxx-05-00-00-en-002rod probe and coax probe-80-60-40-200204060800 50 100 150 200 250 300distance from probe end [mm]sumofnon-linearity,non-repeatabilityandhysteresis[mm]DC = 2DC > 7rope probe-80-60-40-200204060800 50 100 150 200 250 300distance from probe end [mm]sumofnon-linearity,non-repeatabilityandhysteresis[mm]DC > 7
  • 21. Levelflex M FMP40Endress+Hauser 21Differing from this, the following measuring error is present for thin interfaces(only for electronic version "K" interface measurement):L00-FMP4xIxx-05-00-00-en-001Resolution • Digital: 1 mm• Analog: 0.03 % of the measuring rangeReaction time The reaction time depends on the configuration.Shortest time:• 2-wire electronics: 1 s• 4-wire electronics: 0.7 sInfluence of ambienttemperatureThe measurements are carried out in accordance with EN 61298-3:• Digital output (HART, PROFIBUS PA, FOUNDATION Fieldbus):– Average TK: 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C.2-wire:• Current output (additional error, in reference to the span of 16 mA):– Zero point (4 mA)Average TK: 0.032 %/10 K, max. 0.35 % over the entire temperature range -40 °C to +80 °C.– Span (20 mA)Average TK: 0.05 %/10 K, max. 0.5 % over the entire temperature range -40 °C to +80 °C.4-wire:• Current output (additional error, in reference to the span of 16 mA):– Zero point (4 mA)Average TK: 0.02 %/10 K, max. 0.29 % over the entire temperature range -40 °C to +80 °C.– Span (20 mA)Average TK: 0.06 %/10 K, max. 0.89 % over the entire temperature range -40 °C to +80 °C.0±10±20±30±40±50060200maximummeasurederror[mm]uppermediumthickness of upper medium[mm]rod probe (example), also valid for coax probelower mediumNo measurementpossible inthis areaInterface
  • 22. Levelflex M FMP4022 Endress+HauserOperating conditions: installation with level measurementGeneral information on levelmeasurementProbe selection (→ ä 6)• Normally, rope probes should be used for bulk solids, rod probes are only suitable for short measuring rangesup to approx. 2 m in bulk solids. This applies above all to applications in which the probe is installed laterallyat an angle and for light and pourable bulk solids.• Normally use rod or coax probes for liquids. Rope probes are used in liquids for measuring ranges > 4 m andwith restricted ceiling clearance which does not allow the installation of rigid probes.• Coax probes are suited to liquids with viscosities of up to approx. 500 cst. Coax probes can measure mostliquefied gases, as of a dielectric constant of 1.4. Moreover, installation conditions, such as nozzles, tankinternal fittings etc., have no effect on the measurement when a coax probe is used. A coax probe offersmaximum EMC safety when used in plastic tanks.• In the case of large silos, the lateral pressure on the rope can be so high that a rope with plastic jacketingmust be used. We recommend PA-coated ropes be used for cereal products wheat, flour etc.Mounting location• Do not mount rod or rope probes in the filling curtain (2).• Mount rod and rope probes away from the wall (B) at sucha distance that, in the event of buildup on the wall, thereis still a minimum distance of 100 mm between the probeand the buildup.• Mount rod and rope probes as far away as possible frominstalled fittings. "Mapping " must be carried out duringcommissioning in the event of distances < 300 mm.• When installing rod and rope probes in plastic containers,the minimum distance of 300 mm also applies to metallicparts outside the container.• Rod and rope probes may not, at times, contact metalliccontainer walls or floors.• Minimum distance of probe end to the container floor (C):– Rope probe: 150 mm– Rod probe: 50 mm– Coax probe: 10 mm• When installing outdoors, it is recommended that you usea protective cover (1) (→ ä 62, "Accessories").• Avoid buckling the rope probe during installation oroperation (e.g. through product movement against silowall) by selecting a suitable mounting location.L00-FMP4xxxx-17-00-00-xx-003BC1 2
  • 23. Levelflex M FMP40Endress+Hauser 23Other installations• Select the mounting location such that the distanceto internals (5) (e.g. limit switch, struts) is> 300 mm over the entire length of the probe, alsoduring operation.• Probe must within the measuring span not touchany internals during operation. If necessary, whenusing rope probes the probe end (4) may be fixed tosecure it (→ ä 26)!.Optimization options• Interference echo suppression: measurement canbe optimized by electronically tuning outinterference echoes.L00-FMP4xxxx-17-00-00-xx-00854Separable probesIf there is little mounting space (distance to theceiling), it is advisable to use separable rod probes(∅16 mm).• max. probe length 10 m (394 in)• max. sideways capacity 20 Nm• probes are separable several times with the lengths:– 500 mm (19.68 in)– 1000 mm (39.37 in)• torque: 15 NmL00-FMP4xxxx-17-00-00-xx-015Centering of probe endIf the centering disk is mounted at the end of theprobe, it enables a reliable measuring.See "Ordering information", → ä 58.• Centering disk for rod probes:– d = 45 mm (DN50 (2"))– d = 75 mm (DN80 (3") + DN100 (4"))L00-FMP4xxxx-17-00-00-en-068Ø dTightening torque15 Nm + 5 Nm
  • 24. Levelflex M FMP4024 Endress+HauserType of probe installation• Probes are mounted to the process connection with threaded connections or flanges and are usually alsosecured with these. If during this installation there is the danger that the probe end moves so much that ittouches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down.The easiest way to fix the rope probes is to screw them to the internal thread on the lower end of the weight(Thread size, → ä 26).• The ideal installation is mounting in a screwed joint / screw-in sleeve which is internally flush with thecontainer ceiling.• If installation takes place in a nozzle, the nozzle should be 50 to 150 mm in diameter and should not bemore than 150 mm high. Installation adapters are available for other dimensions, → ä 35.L00-FMP4xxxx-17-00-00-en-017Welding the probe into the vesselCaution!Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is notpossible, the electronics as well as the HF module must be disconnected. Otherwise the electronics may bedamaged.Special notes for bulk solids<<150 mm( 6")diameter nozzle:< DN150 ( 6")<installation with welding boss installation in nozzle• In the case of bulk solids, as great a distance aspossible from the filling curtain is especiallyimportant to avoid wear.• In concrete silos, a large distance (B) should beobserved between the probe and the concrete wall,if possible ≥ 1 m, but at least 0.5 m.• The installation of rope probes must be carried outcarefully. The rope should not be buckled.If possible, installation should be carried out whenthe silo is empty.• Check the probe regularly for defect.L00-FMP4xxxx-17-00-00-xx-005B
  • 25. Levelflex M FMP40Endress+Hauser 25Installation in concrete silosInstallation, for example, into a thick concrete ceiling should be made flush with the lower edge. Alternatively,the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling.The pipe should kept at a minimum length. Installation suggestions see diagram.L00-FMP4xxxx-17-00-00-en-008Note for installations with rod extension/center washer (accesories):Strong dust generation can lead to build-up behind the center washer.This can cause an interference signal. For other installation possibilities please contact Endress+Hauser.Installation from the side≥100 mm ≥100 mmø80...150 mmmetalExtension rod /Centering(see accessories)metal tube• If installation from above is not possible, theLevelflex can also be mounted from the side.• In this case, always fix the rope probe ("Fixing ropeprobe", → ä 26).• Support rod and coax probe if the lateral load-bearing capacity is exceeded (→ ä 6).Only fix rod probes at the probe end.Caution!Remove or ground the electronics when welding thesleeve as the device will otherwise be destroyed!L00-FMP4xxxx-17-00-00-en-035Ø16mmØ<26mmØ 17...18 mm
  • 26. Levelflex M FMP4026 Endress+HauserFixing rope probeL00-FMP4xxxx-17-00-00-en-027• The end of the probe needs to be secured if theprobe would otherwise touch the silo wall, thecone or another part, or the probe comes closerthan 0.5 m to a concrete wall. This is what theinternal thread in the probe weight is intended for:– 4 mm rope: M14– 6 mm rope: M20• Preferably use the 6 mm rope probe due to thehigher tensile strength when fixing a rope probe• The fixing must be either reliably grounded orreliably insulated ("Accessories", → ä 62).If it is not possible to mount the probe weight witha safe earthed connection, it can be secured usingan isolated eyelet, which is available as anaccessory (→ ä 68).• In order to prevent an extremely high tensile loadand the risk of rope crack, the rope has to be slack.Make the rope longer than the required measuringrange such that there is a sag in the middle of therope that is ≥ 1 cm/m of the rope length. L00-FMP4xxxx-17-00-00-en-019sag of the rope:1cm/m of the ropelength≥Mounting andcontact with abolt4mm-rope: M146mm-rope: M20Reliable, earthed mounting Reliable, isolated mountingMounting-kit isolated(see accessories)
  • 27. Levelflex M FMP40Endress+Hauser 27Tensile loadBulk solids exert tensile forces (maximum admissible values, → ä 6) on rope probes whose height increaseswith:• the length of the probe, i.e. max. cover,• the bulk density of the product,• the silo diameter and• the diameter of the probe ropeThe following diagrams show typical loads for frequently occurring bulk solids as reference values.The calculation is performed for the following conditions:• Suspended probe (probe end not fixed at the bottom)• Free-flowing bulk solid, i.e. mass flow. A calculation for core flow is not possible. In the event of collapsingcornices, considerably higher loads can occur.• The specification for tensile forces contains the safety factor 2, which compensates for the normal fluctuationrange in pourable bulk solids.L00-FMP40xxx-05-00-00-en-007 L00-FMP40xxx-05-00-00-en-008L00-FMP40xxx-05-00-00-en-006 L00-FMP40xxx-05-00-00-en-0050 5 10 15 20 25 30 350102030405060tensileforce,6mmrope[kN]level [m]silica sandsmooth metallic wallssilo diameter 12 msilo diameter 9 msilo diameter 6 msilo diameter 3 m0510152025303540tensileforce,4mmrope[kN]0 5 10 15 20 25 30 35024681012141618tensileforce,6mmrope[kN]level [m]polyethylene pelletssmooth metallic wallssilo diameter 12 msilo diameter 9 msilo diameter 6 msilo diameter 3 m0123456789101112tensileforce,4mmrope[kN]0 5 10 15 20 25 30 3505101520253035tensileforce,6mmrope[kN]level [m]wheatsmooth metallic wallssilo diameter 12 msilo diameter 9 msilo diameter 6 msilo diameter 3 m024681012141618202224tensileforce,4mmrope[kN]0 5 10 15 20 25 30 350102030405060tensileforce,6mmrope[kN]level [m]cementsmooth metallic wallssilo diameter 12 msilo diameter 9 msilo diameter 6 msilo diameter 3 m0510152025303540tensileforce,4mmrope[kN]
  • 28. Levelflex M FMP4028 Endress+HauserSince the tensile forces are also heavily dependent on the viscosity of the product, a higher safety factor isnecessary for highly viscous products and if there is a risk of cornice buildup.In critical cases it is better to use a 6 mm rope instead of a 4 mm one.The same forces also act on the silo cover. On a fixed rope, the tensile forces are definitely greater, but this cannot be calculated. Observe the tensile strength of the probes or ensure that the tensile strength of the probes isnot exceeded (see table, → ä 6).Options for reducing the tensile forces:• Shorten the probe,• If the maximum tensile load is exceeded, check whether it would be possible to use a non-contact Ultrasonicor Level-Radar device.Special notes for liquids • When installing in agitation units, check whether a no-contact process (Ultrasonic or Level-Radar) would bebetter suited, especially if the agitator generates large mechanical loads on the probe.• If Levelflex is, nevertheless, installed in tanks with agitators, it is better to use coax probes which have agreater lateral loading capacity, → ä 6.Additionally the coax probe can be protected against warping, → ä 31.Standard installationUsing a coax probe offers great advantages when the viscosity of the product is < 500 cst and it is certain thatthe product does not accumulate buildup:• Greater reliability:As of dielectric constant=1.4, measurement functions independently of all electrical properties in all liquids.• Internals in the tank and nozzle dimensions do not have any influence on measurement.• Higher lateral load-bearing capacity than rod probes.• For higher viscosity a rod probe is recommended, or using a non-contact measuring principle with theLevel-Radar Micropilot M.Installation in horizontal and upright cylindricaltanks• Use the following types of probe for measuringranges– up to 4 m: rod probe (1) or coax probe (2)– up to 10 m: separable probe– above 10 m: 4 mm rope probe• Installation and possible fixing as with bulk solids.• Any distance from wall, as long as occasionalcontact is prevented.• When installing in tanks with a lot of internals orinternals situated close to the probe:Use a coax probe!L00-FMP4xxxx-17-00-00-yy-02112
  • 29. Levelflex M FMP40Endress+Hauser 29Measurement in corrosive liquidsFor measurement in corrosive liquids use Levelflex M FMP41C. When using plastic tanks it is also possible tomount the probe on the outside of the tank (see installation instructions, → ä 30).Levelflex measures the level of aqueous media through the plastic.Installation in underground tanksUse coax probe for nozzles with large diameters inorder to avoid reflections at the nozzle wall.L00-FMP4xxxx-17-00-00-yy-022Installation in stilling well or bypass• A rod probe can be used for pipe diameters biggerthan 40 mm.• When installing a rod probe into a metallic pipewith internal diameter of up to 150 mm, you haveall the advantages of a coax probe.• Welded joints that protrude up to approx. 5 mminwards do not influence measurement.• If a rod probe is used, the probe length must be100 mm longer than the lower disposal.• It must be ensured that the probe does not comeinto contact with the side wall. Where necessary,use a centering disk at the lower end of the probe(→ ä 61, "Type of Probe:")L00-FMP4xxxx-17-00-00-yy-023min.100
  • 30. Levelflex M FMP4030 Endress+HauserInstallation in plastic containersPlease note that the "guided level radar" measuring principle requires a metallic surface at the processconnection! When installing the rod and rope probes in plastic silos, whose silo cover is also made of plastic orsilos with wood cover, the probes must either be mounted in a ≥ DN50 (2") metallic flange, or a metal sheetwith diameter of ≥ 200 mm must be mounted under the screw-in piece.L00-FMP4xxxx-17-00-00-en-018• It is also possible to mount the probe externally on the tank wall for measuring in Aqueous solutions.Measurement then takes place through the tank wall without contacting the medium. If people are in thevicinity of the probe mounting location, a plastic half pipe with a diameter of approx. 200 mm, or some otherprotective unit, must be affixed externally to the probe to prevent any influences on the measurement.• There must not be any metallic reinforcement rings secured to the tank.• The wall thickness should be < 15 mm for at GFR/PP.• There must be no open space between the tank wall and the probe.metal sheet or metal flangesilo roof of plasticor woodWall thickness for GFK/PP< 15 mmmetal sheet or metal flange
  • 31. Levelflex M FMP40Endress+Hauser 31Supporting probes against warpingFor WHG approval:For probe lengths ≥ 3 m a support is required (see figure).For GL/ABS approval:Rod probes ∅16 mm ≤ 1 m permissible, rod probes ∅6 mm not permissible.For coax probes ≥ 1 m a support is required (see figure).a. Rod probesL00-FMP4xxxx-17-00-00-en-055b. Coax probesØ <26 mm##Ø 17...18 mmProbe rodShort metal pipee.g. welded in placeapprox.50mmSleeve bored tightto ensure electrical contactbetween the rod and sleeve!Ground the probewhen welding the sleeve!L00-FMP4xxxx-17-00-00-en-054
  • 32. Levelflex M FMP4032 Endress+HauserOperating conditions: installation with interfacemeasurementGeneral information oninterface measurementThe Levelflex M with the "Interface" electronics version ("power supply, output" feature) it the ideal choice formeasuring interfaces. However, it is also possible to measure interfaces with a special version of the standarddevice but the total level has to remain constant here. This version is available on request.In addition, the following general conditions must be observed for interface measurement:• The DC of the upper medium must be known and constant. The DC can be determined with the aid of theDC manual CP00019F/00/EN. In addition, whenever the interface thickness is existing and known, theDC can be calculated automatically via FieldCare.• The DC of the upper medium may not be greater than 10.• The DC difference between the upper medium and lower medium must be >10.• The interface must have a minimum thickness of 60 mm (interface electronics version) or 100 mm (specialversion).• Emulsion layers in the vicinity of the interface can severely dampen the signal. However, emulsion layers upto 50 mm are permitted."Interface" electronics version Special versionL00-FMP4xxxx-15-00-00-xx-001 L00-FMP4xxxx-15-00-00-xx-002Function • Measurement of variable interfacesand variable total levels.• Variable assignment of theoutput parameters.• Extended interface functionMeasurement of variable interfaces with theprerequisite of a constant total levelCommissioning Interface-specific menu guidance via onsitedisplay or DTMSpecial configuration, see modification informationSV0107F/00/A2DigitalCommunicationHART PROFIBUS PA, FOUNDATION FieldbusOrderinginformationFMP40 - #### ### K #### FMP40 - #### ### D ###Y (PROFIBUS PA)FMP40 - #### ### F ###Y (FOUNDATION Fieldbus)Y = Special version available on request
  • 33. Levelflex M FMP40Endress+Hauser 33Interface electronics versionThe device with the "Interface" electronics version makes it possible to measure the total level and the interfacelevel simultaneously. The resulting process variables are output using the dynamic variables of the HARTprotocol. The process variables can be flexibly assigned to the dynamic variables (primary, secondary, tertiary,quaternary value).Using the HART loop converter HMX50The dynamic variables of the HART protocol can be converted into individual 4 to 20 mA sections using theHART Loop Converter HMX50. The variables are assigned to the current output and the measuring ranges tothe individual parameters in the HMX50.L00-FMP40xIx-04-00-00-en-004Connection diagram for HART loop converter HMX50(example: passive 2-wire device and current outputs connected as power source)The HART loop converter HMX50 can be acquired using the order number 71063562.Additional documentation: TI00429F/00/EN and BA00371F/00/EN.Dynamic variables of theHART protocolPossible process variable assignment CommentPrimary Value • Interface• Total level• Thickness of the upper layerThe "primary value" is permanentlyassigned to the 4 to 20 mA currentoutputSecondary Value • Interface• Total level• Thickness of the upper layer-Tertiary Value • Interface• Total level• Thickness of the upper layer• Amplitude of the total level signal-Quaternary (4th) Value Amplitude of the interface level signal No variable assignmentStromausgang 1Relais 1Stromausgang 2Stromausgang 3Relais 2Relais 2versorgungEingang123456789111213141519202116171822 23 2424V DC10HART Loop Converter HMX50Levelflex M HARTCommuboxFXA195+-+Current output 1Relay 1Current output 2Current output 3Relay 2PowersupplyInputPowerHART
  • 34. Levelflex M FMP4034 Endress+HauserProbe selection (→ ä 6)• For interface measurement, ideally coax probes or rod probes are used in the bypass/stilling well.• Coax probes are suited to liquids with viscosities of up to approx. 500 cst. Coax probes can measure mostliquefied gases, as of a dielectric constant of 1.4. Moreover, installation conditions, such as nozzles, tankinternal fittings etc., have no effect on the measurement when a coax probe is used. A coax probe offersmaximum EMC safety when used in plastic tanks.• Rod or rope probes for free installation in the tank available on request. Rope probes for free installation inthe tank must always be used with a rod weight in accordance with special products MVTFN0203 orMVT6N0186. Rope probes may not be used in the bypass/stilling well since the end weight always causesinterference reflection which can be misinterpreted during interface measurement.Special information oninterface measurementInstallation in horizontal cylindrical, upright and underground tanks• Use coax probes or rod probes in the bypass/stilling well. A separable probe is available as a special versionfor longer measuring ranges.• Any distance from the wall is possible for coax probes or rod probes in the stilling well. In the case of rodprobes, it must be ensured that the probe does not come into contact with the wall.L00-FMP4xIxx-17-00-00-xx-002Installation in stilling well or bypass• A rod probe can be used for pipe diameters biggerthan 40 mm.• Rod probe installation can take place up to adiameter size of 100 mm. In the event of largerdiameters, a coax probe is recommended.• Welded joints that protrude up to approx. 5 mminwards do not influence measurement.• The pipe may not exhibit any steps in diameter.• If a rod probe is used, the probe length must be100 mm longer than the lower disposal.• In the case of rod probes, it must be ensured thatthe probe does not come into contact with the wall.If necessary, use a centering disk at the end of theprobe.Note!A plastic centering disk has to be used for interfacemeasurement (→ ä 65, "Accessories").L00-FMP4xIxx-17-00-00-xx-003min.100
  • 35. Levelflex M FMP40Endress+Hauser 35Operating conditions: general installation instructions forspecial installation situationsProbe length The measuring range is directly dependent on the probe length.It is better to order probes too long than too short since it is possible to shorten the probe if necessary.In the case of the rope probe with a rod weight, shortening at the probe end weight is only possible with thespecial product in accordance with MVT6N0186. See also modification information MI0079/00/A2.Installation in nozzles> 150 mm highInstallation in DN200 (8") andDN250 (10") nozzlesIf, when installing probes in nozzles DN40 (1½")to 250 (10") with nozzle height (HS) of> 150 mm (6"), the probe could touch the lower edgeof the nozzle due to moving materials in thecontainer, we recommend using an extension rodwith or without centering disk.This accessory consists of the extension rodcorresponding to the nozzle height, on which acentering disk is also mounted if the nozzles arenarrow or when working in bulk solids.This component is delivered separately from thedevice. Please order the probe length correspondinglyshorter. For the exact length of the rod see "Extensionrod (Centering)", → ä 67.Order codes for specific nozzle nominal diametersand heights can be found on → ä 67.Only use centering disks with small diameters (DN40and DN50) if there is no significant buildup in thenozzle above the disk. The nozzle must not becomeclogged with product.L00-FMP4xxxx-17-00-00-en-025#DN50 (2")DN80 (3")DN150 (6")DN200 (8")DN250 (10")centering diskat PPS - GF40For DN200 and DN250in combinationwith horn adapterExtension rodNot for ¾" probe.For rod probe on request.nozzleheightKeep metal tubeat minimum length!When installing the Levelflex in nozzles of> 200 mm (8"), signals are generated by reflectionson the nozzle wall, which can sometimes lead tofaulty measurements in the case of products withsmall dielectric constants. With nozzle diameters of200 mm (8") or 250 mm (10"), therefore, a specialflange with a “horn adapter” must be fitted.Nozzles with nominal diameters greater than250 mm (10") should be avoided.If the rope probe is strongly deflected: use anextension rod/centering HMP40, additionally.L00-FMP4xxxx-17-00-00-en-026DN200 (8")DN250 (10")204 mmmax.~150 mm
  • 36. Levelflex M FMP4036 Endress+HauserInstallation in nozzle ≥ DN300Installationwith heat insulation• If process temperatures are high, FMP40 must be included in normal tank insulation to prevent theelectronics heating up as a result of heat radiation or convection.• The insulation may not exceed beyond the points labeled "MAX" in the drawings.If installation in ≥ 300 mm (12") nozzles isunavoidable, installation must be carried out inaccordance with the sketch on the right.L00-FMP4xxxx-17-00-00-en-034280> 350DN300> DN400pipe150…180øplate diameternozzle diameterplateApprox. flush withthe lower edge ofthe nozzle (± 50 mm).lower edge ofthe nozzleProcess connection with adapterG¾, G1½, ¾NPT or 1½NPTProcess connection with flange DN40 to DN200L00-FMP40xxx-17-00-00-en-003L00-FMP40xxx-17-00-00-en-002MAXmax. 150° C (302° F)tank insulationMAX40max. 150° C (302° F)tank insulation
  • 37. Levelflex M FMP40Endress+Hauser 37Installation at an angleInstallation for difficult-to-access process connectionsFor tight spaces or temperatures above that in the graphic (→ ä 40), the electronics housing can be orderedwith distance pipe or connecting cable (separate housing).• For mechanical reasons, the probe should beinstalled as vertically as possible.• With inclined installations the probe length has tobe adjusted in dependence to the installation angle.– up to 1 m = 30°– up to 2 m = 10°– up to 4 m = 5°.L00-FMP4xxxx-17-00-00-en-048ropeprobemounting angleInstallation with spacer tubeWhen mounting please observe engineering hints(→ ä 22) the following points:• After mounting, the housing can be turned 350° inorder to make it easier to access the display and theconnection compartment.• The max. measuring range is reduced to 34 m.L00-FMP4xxxx-17-00-00-en-014400Ø 60,3Ø 76
  • 38. Levelflex M FMP4038 Endress+HauserInstallation with remote electronics• Wall and pipe bracket is contained in the scope of delivery and already mounted.• When installing, follow the instructions, → ä 22.• Mount housing on a wall or pipe (vertically or horizontally) as shown in the diagram.L00-FMP4xxxx-17-00-00-en-015Note!The protective hose cannot be disassembled at these points (1).The ambient temperature for the connecting pipe (2) between the probe and the electronics must not be greaterthan 105 °C. The version with remote electronics consists of the probe, a connecting cable and the housing.If they are ordered as a complete unit they are assembled when delivered.150ENDRESS+HAUSERLevelflex M65 78ø12985150ENDRESS+HAUSERLevelflex M65 78ø129855252150max.80min.30969494888812327658026075≥ø76114xø8,5112pipewallNote min.bend radius!ø21.3
  • 39. Levelflex M FMP40Endress+Hauser 39Replacing a displacer systemin an existing displacerchamberThe Levelflex M is a perfect replacement for a conventional displacer system in an existing displacer chamber.In addition to the DIN and ANSI flanges, which are available as standard, Endress+Hauser also offers flangesthat suit Fischer and Masoneilan displacer chamber (special product) for this purpose. Thanks to menu-guidedlocal operation, commissioning the Levelflex M only takes a few minutes. Replacement is also possible whenpartially filled, and wet calibration is not required.Your benefits:• No moving parts, thus zero-maintenance operation.• Not sensitive to process influences such as temperature, density, turbulence and vibrations.• The rod probes can be shortened or replaced easily. In this way, the probe can be easily adjusted on site.L00-FMP4xIxx-17-00-00-en-002Planning instructions:• In normal cases, use a rod probe. When installing into a metallic displacer chamber up to 150 mm, you haveall the advantages of a coax probe ("Probe selection", → ä 6).• It must be ensured that the probe does not come into contact with the side wall. Where necessary, use acentering disk at the lower end of the probe ("Type of Probe:", → ä 61).• A centering disk must be adapted as accurately as possible to the internal diameter of the displacer chamberto also ensure perfect operation in the area of the probe end.Additional information on interface measurement• The pipe may not exhibit any steps in diameter. Use the coax probe where necessary.• In the case of rod probes, it must be ensured that the probe does not come into contact with the wall.If necessary, use a centering disk at the end of the probe.Note!A plastic centering disk has to be used for interface measurement ("Accessories", → ä 65).displacer chamber flange
  • 40. Levelflex M FMP4040 Endress+HauserOperating conditions: EnvironmentAmbient temperature range Ambient temperature at the electronics: -40 °C to +80 °C. The function of the LCD display is restricted atTA < -20 °C and TA > +60 °C. A weather protection cover should be used for outdoor operation if the deviceis exposed to direct sunlight.Ambient temperature limits If temperatures above 80 °C are present at the process connection, the permitted ambient temperature isreduced according to the following diagram (temperature derating):L00-FMP40xxx-05-00-00-en-001Storage temperature -40 °C to +80 °CClimate class DIN EN 60068-2-38 (test Z/AD)Degree of protection • With closed housing tested according to:– IP68, NEMA6P (24 h at 1.83 m under water surface)– IP66, NEMA4X• With open housing: IP20, NEMA1 (also ingress protection of the display)Caution!Degree of protection IP68 NEMA6P applies for M12 PROFIBUS PA plugs only when the PROFIBUS cable isplugged in.Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20 to 2000 Hz, 1 (m/s2)2/HzCleaning the probe Depending on the application, contamination or build-up can accumulate on the probe. A thin, even layer onlyinfluences measurement slightly. Thick layers can dampen the signal and then reduce the measuring range.Severe, uneven build-up, adhesion e.g. through crystallization, can lead to incorrect measurement. In this case,we recommend that you use a non-contact measuring principle, or check the probe regularly for soiling.Electromagnetic compatibility(EMC)Electromagnetic compatibility to EN 61326 and NAMUR Recommendation EMC (NE21). Details are providedin the Declaration of Conformity. A standard installation cable is sufficient if only the analog signal is used.Use a shielded cable when working with a superimposed communications signal (HART).When installing the probes in metal and concrete tanks and when using a coax probe:• Interference emission to EN 61326 - x series, electrical equipment Class B.• Interference immunity to EN 61326 - x series, requirements for industrial areas and NAMURRecommendation NE21 (EMC)The measured value can be affected by strong electromagnetic fields when installing rod and rope probeswithout a shielding/metallic wall, e.g. plastic, and in wooden silos.• Interference emission to EN 61326 - x series, electrical equipment Class A.• Interference Immunity: the measured value can be affected by strong electromagnetic fields.T [°C]T [°C]-40 0 50-400406080 100 15080max. process connection temperaturemax. ambient temperature80 °C with separatehousing75 °C with distancesleeve65 °C standard compactF12/T12 housing60 °C standard compactF23 housing
  • 41. Levelflex M FMP40Endress+Hauser 41Operating conditions: ProcessProcess temperature range The maximum permitted temperature at the process connection (see Figure for measuring point) is determinedby the O-ring version ordered:Note!The medium temperature can be higher. However, when using rope probes the stability of the probe rope isreduced by structural changes at temperatures over 350 °C.Process pressure limits All models: -1 to 40 bar.The specified range may be reduced by the selected process connection. The pressure rating (PN) specified onthe flanges refers to a reference temperature of 20 °C, for ASME flanges 100 °F. Observe pressure-temperaturedependency.Please refer to the following standards for the pressure values permitted for higher temperatures:• EN 1092-1: 2001 Tab. 18With regard to their temperature stability properties, the materials 1.4404 and 1.4435 are grouped under13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.• ASME B 16.5a - 1998 Tab. 2-2.2 F316• ASME B 16.5a - 1998 Tab. 2.3.8 N10276• JIS B 2220Note!All Levelflex probes have two levels of sealing. There is an O-ring seal and a molded seal behind that.Dielectric constant • With coax probe: εr ≥ 1.4• Rod and rope probe: εr ≥ 1.6Extension of the rope probesthrough tension andtemperature4 mm rope:• Elongation through tension: at max. permitted tensile load (12 KN): 11 mm/m rope length• Elongation through temperature increase from 30 °C to 150 °C: 2 mm/m rope length6 mm rope:• Elongation through tension: at max. permitted tensile load (30 KN): 13 mm/m rope length• Elongation through temperature increase from 30 °C to 150 °C: 2 mm/m rope lengthO-ring material Min. temperature Max. temperature 1)1) For PA coated probes, the maximal admissible temperature is 100 °C.FKM (Viton) -30 °C +150 °CEPDM -40 °C +120 °CFFKM (Kalrez) -5 °C2)2) The min. temperature of FFKM may be -15 °C if the max. temperature of +80 °C is not exceeded.+150 °Cmeasuredhere
  • 42. Levelflex M FMP4042 Endress+HauserMechanical constructionDesign, dimensions Housing dimensionsL00-F12xxxx-06-00-00-en-001L00-T12xxxx-06-00-00-en-001L00-F23xxxx-06-00-00-en-001ENDRESS+HAUSER65 (2.56) 78 (3.07)max. 110 (4.33)mm (in)85 (3.35)150(5.91)ø129(ø5.08)(Aluminium)F12 housingENDRESS+HAUSER78 (3.07)85 (3.35)65 (2.56)162(6.38)max. 100 (4.33) 94 (3.7)mm (in)ø129(ø5.08)(Aluminium)T12 housingmax. 94 (3.7)mm (in)93 (3.66)ø129(ø5.08)150(5.91)40(1.57)(316L)F23 housing
  • 43. Levelflex M FMP40Endress+Hauser 43Process connection, probe typeL00-FMP4xIxx-06-00-00-en-0071) see SD00288F/00/EN "Steam boiler approval".8888400123276580ø76ø76SW 50SW 60109109ø603 x ø8150202527201525100ø76ø8140ø10ø42,42608M40x1M40x1ø45 / ø754 x ø8.5ø60.3ø21.364.5M5x0.8M10x1 M10x1Ropeø4mm:98mm(“):137mm(1"orFlange)Ropeø6mm:152mm(1"orFlange)¾½½ø45 Option 80, feature “B, D, F, H“ø75 Option 80, feature “C, E, G, I“Threaded connectionG¾ (¾ BSP)or ¾NPTThreaded connectionG1½ (1½BSP)or 1½NPTFlange DN40 to 200or equivalentreference point ofmeasurementVariant “2”:Separatorrope:ø4 mm/or0.16”ø6 mm/0.24”orø6 mm/0.24” + 2 mm/0,08” PA coatingrope probe rod probe coax probeø6/0.24” (on ¾” thread)ø16/0.63” (on 1½” threador flange)ø )ø42,4/1.67” (on 1½” threador flange)21,3/0.84” (on ¾” threadø22/0.87” (on 4 mm/ rope)0.16”ø30/1.18” (on 6 mm/0.24” rope)internal thread:M14 on 4 mm/0.16” ropeM20 on 6 mm/0.24” ropeprobelengthLNProbe rods in Alloy C22consist of 1 piece(can not be dismantled)F12 / T12 / F23 housingTypeofProbe(seefeature80in“Orderingstructure”)Variant “3” :/ “4”remote electronictop entryVariant “4”:remote electronicside entrycoax probefor interface measurementor steam boiler approval1)
  • 44. Levelflex M FMP4044 Endress+HauserGeneral information onflangesThe surface roughness of the surface in contact with the medium, including the sealing surface of the flanges(all standards) made of Hastelloy C, Monel or Tantas, is Ra3.2. Lower surface roughness levels are available onrequest.Tolerance of probe lengthWeightRod probes / Coax probes Rope probesOver 1 m 3 m 6 m 1 m 3 m 6 mUp to 1 m 3 m 6 m 1 m 3 m 6 mAdmissible tolerance (mm) - 5 - 10 - 20 - 30 - 10 - 20 - 30 - 40Levelflex M FMP40+rope probe 4 mmFMP40+ rod orrope probe 6 mmFMP40+rod probe 16 mmFMP40Coax probeWeight for F12 orT12 housingApprox. 4 kg+Approx. 0.1 kg/mProbe length+weight of flangeApprox. 4 kg+Approx. 0.2 kg/mProbe length+weight of flangeApprox. 4 kg+Approx. 1.6 kg/mProbe length+weight of flangeApprox. 4 kg+Approx. 3.5 kg/mProbe length+weight of flangeWeight for F23housingApprox. 7.4 kg+Approx. 0.1 kg/mProbe length+weight of flangeApprox. 7.4 kg+Approx. 0.2 kg/mProbe length+weight of flangeApprox. 7.4 kg+Approx. 1.6 kg/mProbe length+weight of flangeApprox. 7.4 kg+Approx. 3.5 kg/mProbe length+weight of flange
  • 45. Levelflex M FMP40Endress+Hauser 45Material(not in contact with process)T12 and F12 housing (seawater-resistant*, powder-coated)L00-x12xxxx-16-00-00-en-001* Seawater-resistant on request (complete in 316L (1.4404)).Pos. Part Material1 T12 and F12 housing AlSi10Mg2Cover (Display) AlSi10MgSealing Fa. SHS: EPDM 70pW FKNWindow ESG-K-Glass (Toughened safety glass)Sealing of the glass Silicone sealing compound Gomastit 4023Sealing Fa. SHS: EPDM 70 pW FKN Trelleborg: EPDM E7502Cable gland Polyamid (PA), CuZn nickel-platedPlugPBT-GF30 1.0718 galvanizedPE 3.1655Adapter 316L (1.4435) AlMgSiPb (anodized)4Cover (Connection compartment) AlSi10MgSealing Fa. SHS: EPDM 70pW FKN Trelleborg: EPDM E7502/E7515Clamp Screws: A4; Clamp: Ms nickel-plated; Spring washer: A45 Sealing ring Fa. SHS: EPDM 70pW FKN Trelleborg: EPDM E7502/E75156Tag* 304 (1.4301)Rope 316 (1.4401)Crimp sleeve Aluminium7Nameplate* 304 (1.4301)Groove pin* A28 Ground terminal*Screws: A2; Spring washer: A4; Clamp: 304 (1.4301)Holder: 301 (1.4310)9 Screws* A2-70(Aluminium) (Aluminium)ENDRESS+HAUSERIP65Order Code:Ser.-No.:MessbereichMeasuringrangeU 16...36 V DC4...20mAmax. 20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C :At >85°CMadeinGermanyMaulburgMadeinGermanyMaulburgENDRESS+HAUSERIP65Order Code:Ser.-No.:MessbereichMeasuringrangeU 16...36 V DC4...20mAmax. 20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C :At >85°CF12 housingT12 housing987 5 6 98 5 6321421337
  • 46. Levelflex M FMP4046 Endress+HauserF23 housing (seawater-resistant*, corrosion-resistant)L00-x12xxxx-16-00-00-en-001* Seawater-resistant on request (complete in 316L (1.4404)).Pos. Part Material1 F23 housingHousing body: 316L (1.4404); Sensor neck: 316L (1.4435);earth connection block: 316L (1.4435)2Cover 316L (1.4404)Sealing Fa. SHS: EPDM 70pW FKNWindow ESG-K-Glass (Toughened safety glass)Sealing of the glass Silicone sealing compound Gomastit 4023Sealing Fa. SHS: EPDM 70pW FKN Trelleborg: EPDM E7502Cable gland Polyamid (PA), CuZn nickel-platedPlugPBT-GF30 1.0718 galvanizedPE 3.1655Adapter 316L (1.4435)4 Sealing ring Fa. SHS: EPDM 70pW FKN Trelleborg: EPDM E75025Nameplate* 304 (1.4301)Groove pin* A26 Grounding terminal*Screws: A2; Spring washer: A4; Clamp: 304 (1.4301);Holder: 301 (1.4310)7 Screw* A2-708Tag* 304 (1.4301)Rope 316 (1.4401)Crimp sleeve Aluminium316L (1.4404/1.4435)F23 housing6 7 481352
  • 47. Levelflex M FMP40Endress+Hauser 47Wall and pipe bracketL00-FMP4xxxx-16-00-00-xx-005Connecting partsL00-FMP40xxx-16-00-00-xx-002Pos. Part Material1 Bracket 304 (1.4301)2 Bar 304 (1.4301)3 Housing adapter 316L (1.4435)4 Disc 304 (1.4301)5Screw nut A4Washer A2Pos. Part Material1 Adapter 316L (1.4435)2Separator 316L (1.4435)Setscrew A23Adapter 316L (1.4404/1.4435)Setscrew A24 Hose fitting CuZn nickel-plated5 Shrink hose Polyolefin6 Cable PVC213452113 344556451Flange DN40 to 200or equivalentThreaded connectionG¾ (¾BSP)or ¾NPTThreaded connectionG1½ (1½BSP)or 1½NPT
  • 48. Levelflex M FMP4048 Endress+HauserMaterial(in contact with process)Standard variantL00-FMP40xxx-16-00-00-en-001Pos. Part Material1Counter nut 316L (1.4435)Inner conductor Rod/Rope: 318LN (1.4462) Coax: 316L (1.4435)2 Process connection See Ordering information3 Nord-lock washer 1.45474 Insulation sleeve 3/4": PPS-GF40 1-1/2": TFM16005 Press in sleeve 316L (1.4404/1.4435)6 Rope 316 (1.4401)7Ballast weight 316L (1.4435)Set screw A4-708 Screw A2-709Rod 316L (1.4404/1.4435)Connecting bolt 318LN (1.4462)Nord-lock washer 1.454710 Rod 3/4": 316L (1.4404) 1-1/2": 316L (1.4404/1.4435)11 Centering of probe end Disk: 316L (1.4404); Screw: A4; Nordlock: 1.454712 Coax probe 316L (1.4435)Interface measurement:316L (1.4404)Spacer PFAThreaded connectionG¾ (¾BSP)or ¾NPTRope probe Divisible probes Rod probe Coax probe InterfacemeasurementThreaded connectionG1½ (1½BSP)or 1½NPTFlange DN40 to 200or equivalent1435 109 12 1210116781431432 22
  • 49. Levelflex M FMP40Endress+Hauser 49Alloy variantL00-FMP40xxx-16-00-00-en-003DIN/EN flangesEndress+Hauser supplies DIN/EN flanges made of stainless steel according to AISI 316L (DIN/EN materialnumber 1.4404 or 1.4435). With regard to their temperature stability properties, the materials 1.4404 and1.4435 are grouped under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can beidentical.Process connection See "Ordering information", → ä 58.Seal See "Ordering information", → ä 58.Probe See "Ordering information", → ä 58.Pos. Part Material1 Adapter 2.46022 Insulation sleeve TFM16003 Rod probe 2.46024 Flange 316L (1.4404 / 1.4435)5 Flange plating 2.46026 Coax probe 2.4602Spacer PFARod probe Coax probeThreaded connectionG1½ (1½BSP)or 1½NPTFlange DN40 to 200or equivalent3 6314212353
  • 50. Levelflex M FMP4050 Endress+HauserHuman interfaceOperating concept The display of the process value and the configuration of the Levelflex occur locally by means of a large 4-linealphanumeric display with plain text information. The guided menu system with integrated help texts ensuresa quick and safe commissioning.To access the display the cover of the electronic compartment may be removedeven in hazardous area (IS and XP).Remote commissioning, including documentation of the measuring point and in-depth analysis functions, issupported by FieldCare, the graphical operating software for Endress+Hauser time-of-flight systems.Display elements Liquid crystal display (LCD):Four lines with 20 characters each. Display contrast adjustable through key combination.L00-FMxxxxxx-07-00-00-en-001The VU331 LCD display can be removed to ease operation by simply pressing the snap-fit (see graphic above).It is connected to the device by means of a 500 mm cable.The following table describes the symbols that appear on the liquid crystal display:ENDRESS + HAUSERE+–ENDRESS+HAUSERMICROPILOTIIENDRESS+HAUSERMICROPILOTIIIP65IP65OrderCode:Ser.-No.:OrderCode:Ser.-No.:MessbereichMeasuringrangeMessbereichMeasuringrangeU 16...36V DC4...20mAU 16...36V DC4...20mAmax.20mmax.20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C:At >85°CT>70°C:At >85°CLCD(liquid crystal display)Symbols3 keyssnap-fitSymbol MeaningALARM_SYMBOLThis alarm symbol appears when the device is in an alarm state. If the symbol flashes, this indicates awarning.LOCK_SYMBOLThis lock symbol appears when the device is locked, i.e. if no input is possible.COM_SYMBOLThis communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA orFOUNDATION Fieldbus is in progress.SIMULATION_SWITCH_ENABLEThis communication symbol appears when simulation in FOUNDATION Fieldbus is enabled via the DIPswitch.
  • 51. Levelflex M FMP40Endress+Hauser 51Operating elements The operating elements are located inside the housing and are accessible for operation by opening the lid of thehousing.Function of the keysKey(s) MeaningOor V Navigate upwards in the selection list.Edit numeric value within a function.Sor W Navigate downwards in the selection list.Edit numeric value within a function.Xor Z Navigate to the left within a function group.F Navigate to the right within a function group, confirmation.O and ForS and FContrast settings of the LCD.O and Sand FHardware lock / unlockAfter a hardware lock, operation of the device via display or communication is not possible!The hardware can only be unlocked via the display.A release code must be entered to do so.
  • 52. Levelflex M FMP4052 Endress+HauserLocal operation Operation with VU331The LC-Display VU331 allows configuration via 3 keys directly at the device. All device functions can be setthrough a menu system. The menu consists of function groups and functions. Within a function, applicationparameters can be read or adjusted. The user is guided through a complete configuration procedure.Display for level measurementL00-FMRxxxxx-07-00-00-en-002Display for interface measurementL00-FMP4xIxx-07-00-00-en-002XXXXSSOO FFFFHOMEFG00 F000 F001 F002 F003 F004 ...FG01FG02FG03FG04FG05FG06FG07...ENDRESS + HAUSERE+–Headline Position indicatorMain value UnitSymbolSelection listFunction groups -> FunctionsHelp textEnvelopecurveBargraphXXXXSSOO FFFFHOMEFG00 F000 F001 F002 F003 F004 ...FG01FG02FG03FG04FG05FG06FG07...ENDRESS + HAUSERE+–DescriptionPosition indicatorPrimary measuring valueUnit SymbolSelection listFunction groups -> FunctionsHelp textSecondary measuring valueEnvelopecurve
  • 53. Levelflex M FMP40Endress+Hauser 53Remote operation The Levelflex M can be remotely operated via HART, PROFIBUS PA and FOUNDATION Fieldbus. Onsiteadjustments are also possible.Operation with FieldCareFieldCare is an Endress+Hauser Plant Asset Management Tool based on FDT technology. You can use Field-Care to configure all your Endress+Hauser devices, as well as devices from other manufacturers that supportthe FDT standard. Hardware and software requirements you can find on the internet:www.endress.com → select your country → search: FieldCare → FieldCare → Technical Data.FieldCare supports the following functions:• Online configuration of transmitters• Signal analysis via envelope curve• Tank linearization• Loading and saving of device data (upload/download)• Documentation of the measuring pointConnection options:• HART via Commubox FXA195 and the USB port of a computer• PROFIBUS PA via segment coupler and PROFIBUS interface card• Commubox FXA291 with ToF Adapter FXA291 via service interfaceMenu-guided commissioningL00-FMP4xxxx-20-00-00-en-001
  • 54. Levelflex M FMP4054 Endress+HauserSignal analysis via envelope curveTank linearizationL00-FMP4xxxx-20-00-00-en-007L00-fmp-Ixxx-20-00-00-en-041
  • 55. Levelflex M FMP40Endress+Hauser 55Operation with NI-FBUS Configurator (only FOUNDATION Fieldbus)The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedulebased on the fieldbus concepts.You can use the NI-FBUS Configurator to configure a fieldbus network as follows:• Set block and device tags• Set device addresses• Create and edit function block control strategies (function block applications)• Configure vendor-defined function and transducer blocks• Create and edit schedules• Read and write to function block control strategies (function block applications)• Invoke Device Description (DD) methods• Display DD menus• Download a configuration• Verify a configuration and compare it to a saved configuration• Monitor a downloaded configuration• Replace devices• Save and print a configurationOperation with handheld terminal Field Communicator 375, 475With the handheld terminal Field Communicator 375, 475, you can configure all the device functions viamenu operation.Note!Further information on the HART handheld terminal is given in the appropriate Operating Instructionsincluded in the carrying case of the Field Communicator 375, 475.L00-FMP4xxxx-20-00-00-de-011
  • 56. Levelflex M FMP4056 Endress+HauserCertificates and approvalsCE mark The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in thecorresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirmssuccessful testing of the device by affixing to it the CE mark.Ex approval The devices are certified for use in hazardous areas. The safety instructions to be observed are enclosed andreferenced on the nameplate:• Europe: EC type-examination certificate, Safety Instructions XA• USA: FM Approval, Control Drawing• Canada: CSA Certificate of Compliance, Control Drawing• China: NEPSI Explosion Protection Certificate of Conformity, Safety Instructions XA• Japan: TIIS Certificate for Ex-apparatusCorrelation of the Certificates (XA, ZD, ZE) to the device:1) Housing F12/F23/T12-OVP: In combination with electronics B, D or F supply intrinsically safe.XA164FXXXXXXXXXXA165FXXXXXXXXXXA166FXXXXXXXXXA167FXXXXXXXXXA168FXXXXXXXXA172FXXXXXXXXXXXXXXA173FXXXXXXXXXA173FXXXXXXXXXXXA212FXXXXXXXXXXA211FXXXXXXXXXXA213FXXXXXXXXXXXXXA215FXXXXXXXXXXA216FXXXXXXXXXXA217FXXXXXXXXXXXXXXA330FXXXXXXXXXA218FXXXXXXXXA376FXXXXXXXXXA378FXXXXXXXXXXXXXXXXXXXA379FXXXXXXXXXXXXXXXXXXXA380FXXXXXXXXXA381FXXXXXXXA386FXXXXXXXXXXXXXXXXXXXXZD075FXXXXXXXXXZD076FXXXXXXXXXXXZD077FXXXXXXXXXXZD078FXXXXXXXXZD080FXXXXXXXXXZD081FXXXXXXXXXXXZD082FXXXXXXXXXXZD083FXXXXXXXXZD021FXXXXXXXXXXXXXXXXZD106FXXXXXXXXXXXZD107FXXXXXXXXXXXZD109FXXXXXXXXXXZD110FXXXXXXXXXXZD113FXXXXXXXXXXXZD114FXXXXXXXXXXXZD116FXXXXXXXXXXZD117FXXXXXXXXXXZE258FXXXXXXXXZE256FXXXVariantACFGIJKLMNPQRSTUVWX12345678BDFGHK123ABCDEGHJKLMNPQR12345Non-hazardous areaNEPSI Ex emb (ia) IIC T6Non-hazardous area, WHGATEX II 3G Ex nA II T6NEPSI Ex ia IIC T6NEPSI Ex d(ia) IIC T6*TIIS Ex ia IIC T4TIIS Ex d (ia) IIC T4FM DIP Cl.II Div.1 Gr. E-G N.I.CSA General PurposeCSA DIP Cl.II Div.1 Gr. G + coal dust, N.I.NEPSI DIPNEPSI Ex nA II T6FM IS Cl.I,II,III Div.1 Gr. A-G N.I., zone 0, 1, 2FM XP Cl.I,II,III Div.1 Gr. A-G, zone 1, 2CSA IS Cl.I,II,III Div.1 Gr. A-D, G + coal dust, N.I., zone 0, 1, 2CSA XP Cl.I,II,III Div.1 Gr. A-D, G + coal dust, N.I., zone 1, 2IEC Ex td A20/21, Alu blind coverIEC Ex tD A20/22ATEX II 1/2G Ex ia IIC T6 / IECEx zone 0/1ATEX II 1/2D/IEC Ex td A20/21, Alu blind cover 1)ATEX II 2G Ex emb (ia) IIC T6 / IECEx zone 1ATEX II 1/3D/ IEC Ex td A20/22 1)ATEX II 1/2G Ex ia IIC T6, ATEX II 1/3DATEX II 1/2G Ex ia IIC T6, WHGATEX II 1/2G Ex d (ia) IIC T6 / IEC Ex d (ia) IIC T6ATEX II 1/2G Ex ia IIC T6, ATEX II 1/3D, WHG2-wire 4-20mA SIL HART2-wire PROFIBUS PA2-wire FOUNDATION Fieldbus4-wire 90-250VAC 4-20mA SIL HART4-wire 10.5-32VDC 4-20mA SIL HART2-wire 4-20mA HART, Interfacewithout display, via communication4-line display VU331applicable for FHX40F12 Alu, coated IP68 gland M20F12 Alu, coated IP68 thread G1/2F12 Alu, coated IP68 thread NPT1/2F12 Alu, coated IP68 Plug M12F12 Alu, coated IP68 Plug 7/8"T12 Alu, coated IP68 gland M20T12 Alu, coated IP68 thread G1/2T12 Alu, coated IP68 thread NPT1/2T12 Alu, coated IP68 Plug M12T12 Alu, coated IP68 Plug 7/8"T12 Alu, coated IP68 gland M20 + OVT12 Alu, coated IP68 thread G1/2 + OVT12 Alu, coated IP68 thread NPT1/2+OVT12 Alu, coated IP68 Plug M12 + OVPT12 Alu, coated IP68 Plug 7/8" + OVF23 316L IP68 gland M20F23 316L IP68 thread G1/2F23 316L IP68 thread NPT1/2F23 316L IP68 Plug M12F23 316L IP68 Plug 7/8"Feature10Approval:60Power supplyOutput:70Operation:90Housing,Cable entry:
  • 57. Levelflex M FMP40Endress+Hauser 57Overfill prevention WHG. See "Ordering information", → ä 58 (see ZE00256F/00/DE).SIL 2, for 4 to 20 mA output signal (see SD00174F/00/EN "Functional Safety Manual").Telecommunications Complies with "Part 15" of the FCC rules for an "Unintentional Radiator". All probes meet the requirementsfor a "Class A Digital Device".Coax probes and probes mounted in closed metallic vessels also meet the requirement for a "Class B DigitalDevice".Standards and guidelinesappliedThe European directives and standards applied can be taken from the associated EC Declarations ofConformity. In addition, the following also applied for Levelflex M:EN 60529Protection class of housing (IP-code)NAMUR - international user association of automation technology in process industries• NE21Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.• NE43Standardization of the signal level for the failure information of digital transmitters.
  • 58. Levelflex M FMP4058 Endress+HauserOrdering informationLevelflex M FMP40 Device selectionL00-FMP4xxxx-16-00-00-en-003The metallic uninsulated probes are only insulated in the area of the bushing. Thus there is no danger ofelectrostatic charging. The PA-coated rope has been tested and there is no dangerous electrostatic charging.As a result, there are no restrictions on use in Ex-areas for any of the probes.Note!For orders with a display, the housing cover is delivered with an inspection glass. For orders without a display,a dummy cover is delivered.Exception: For orders with the ATEX II 1/2 D dust ignition-proof certificate, a dummy cover is alwaysdelivered, even for orders with a built-in display.F12+F232)F12+F232)F12+F232)T12 T12 T12 T12PA PA PA PA PAFF FF FF FF FFEx emEx iaISEx dXPCertificateElectronic/CommunicationHousingEx-freeareaDust-ExDIP2 Wire4-20 mA/HART1)2 Wire4-20 mA/HART1)2 Wire4-20 mA/HART1)2 Wire4-20 mA/HART1)2 Wire4-20 mA/HART1)4 Wire4-20 mA/HART4 Wire4-20 mA/HART2)Instead of the F12 aluminum housing the F23 stainless steel housing can also be supplied to all 2 wire electronics.1)Also valid for the version “K” 2 Wire, 4 - 20 mA HART, interface measurement.Temperature(depending on O-ring)V Viton, -30 °C to +150 °CE EPDM, -40 °C to +120 °CK Kalrez, -5 °C to +150 °C 1)1) Recommended for steam applications.Pressure (all types) -1 to 40 barWetted parts Rope probes:Flanges: 316L (1.4404 )Process connection: 316L (1.4435), 1.4462Rope: 316L (1.4401)Weight: 316L (1.4435)Rod probes:Flanges: 316L (1.4404)Process connection: 316L (1.4435), 1.4462Rod: 316L (1.4404 / 1.4435)Coax pipe: 316L (1.4435)
  • 59. Levelflex M FMP40Endress+Hauser 59Product structure Levelflex M FMP4010 Approval:A Non-hazardous areaF Non-hazardous area, WHG1 ATEX II 1/2G Ex ia IIC T6/IECEx Zone 0/12 ATEX II 1/2D/IEC Ex td A20/21, Alu blind cover3 ATEX II 2G Ex emb (ia) IIC T6/IECEx Zone14 ATEX II 1/3D/IEC Ex td A20/225 ATEX II 1/2G Ex ia IIC T6, ATEX II 1/3D6 ATEX II 1/2G Ex ia IIC T6, WHG7 ATEX II 1/2G Ex d (ia) IIC T6/ IEC Ex d(ia) IIC T68 ATEX II 1/2G Ex ia IIC T6, ATEX II 1/3D, WHGG ATEX II 3G Ex nA II T6C NEPSI Ex emb (ia) IIC T6I NEPSI Ex ia IIC T6J NEPSI Ex d (ia) IIC T6Q NEPSI DIPR NEPSI Ex nA II T6M FM DIP Cl.II Div.1 Gr. E-G N.I.S FM IS Cl.I,II,III Div.1 Gr. A-G N.I., zone 0, 1, 2T FM XP Cl.I,II,III Div.1 Gr. A-G, zone 1, 2N CSA General PurposeP CSA DIP Cl.II Div.1 Gr. G + coal dust, N.I.U CSA IS Cl.I,II,III Div.1 Gr. A-D, G + coal dust, N.I., zone 0, 1, 2V CSA XP Cl.I,II,III Div.1 Gr. A-D, G + coal dust, N.I., zone 1, 2W IEC Ex td A20/21, Alu blind coverX IEC Ex td A20/22K TIIS Ex ia IIC T4 (in preparation)L TIIS Ex d (ia) IIC T4Y Special version, TSP-No. to be spec.20 Probe:A Rope 4mm / 1/6", mainly liquidB Rope 6mm / 1/4", solidH Rope 6mm / 1/4", PA > steel, solid, Tmax = 100°C / 212°FP Rod 6mm, liquid1 Rod 12mm, liquidK Rod 16mm, mainly liquidL Coax, liquidY Special version, TSP-No. to be spec.30 Probe length:A ..... mm, rope 4mm, 316B ..... mm, rope 6mm, 316C ..... inch rope 1/6", 316D ..... inch, rope 1/4", 316E ..... mm, rope 6mm, PA > steelF ..... inch, rope 1/4", PA > steelK ..... mm, rod 16mm, 316LL ..... mm, coax, 316LM ..... inch, rod 16mm, 316LN ..... inch, coax, 316LP ..... mm, rod 6mm, 316LR ..... inch, rod 6mm, 316LS ..... mm, rod 16mm, 316L, 500mm divisibleT ..... mm, rod 16mm, 316L, 1000mm divisibleU ..... inch, rod 16mm, 316L, 20in divisibleV ..... inch, rod 16mm, 316L, 40in divisible1 ..... mm rod 12mm, AlloyC222 ..... mm coax, AlloyC223 ..... inch, rod 12mm, AlloyC224 ..... inch, coax, AlloyC22Y Special version, TSP-No. to be spec.40 O-ring Material; Temperature:2 Viton; -30...150°C/-22...302°F3 EPDM; -40...120°C/-40...248°F4 Kalrez; -5...150°C/23...302°F9 Special version, TSP-No. to be spec.
  • 60. Levelflex M FMP4060 Endress+Hauser50 Process Connection:ACJ 1-1/2" 150lbs RF, 316/316L flange ANSI B16.5ACM 1-1/2" 150lbs, AlloyC22 >316/316L flange ANSI B16.5ADJ 1-1/2" 300lbs RF, 316/316L flange ANSI B16.5ADM 1-1/2" 300lbs, AlloyC22 >316/316L flange ANSI B16.5AEJ 2" 150lbs RF, 316/316L flange ANSI B16.5AEM 2" 150lbs, AlloyC22 >316/316L flange ANSI B16.5AFJ 2" 300lbs RF, 316/316L flange ANSI B16.5AFM 2" 300lbs, AlloyC22 >316/316L flange ANSI B16.5ALJ 3" 150lbs RF, 316/316L flange ANSI B16.5ALM 3" 150lbs, AlloyC22 >316/316L flange ANSI B16.5AMJ 3" 300lbs RF, 316/316L flange ANSI B16.5AMM 3" 300lbs, AlloyC22 >316/316L flange ANSI B16.5APJ 4" 150lbs RF, 316/316L flange ANSI B16.5APM 4" 150lbs, AlloyC22 >316/316L flange ANSI B16.5AQJ 4" 300lbs RF, 316/316L flange ANSI B16.5AQM 4" 300lbs, AlloyC22 >316/316L flange ANSI B16.5AWJ 6" 150lbs RF, 316/316L flange ANSI B16.5AWM 6" 150lbs, AlloyC22 >316/316L flange ANSI B16.5A3J 8" 150lbs RF, 316/316L flange ANSI B16.5CFJ DN40 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C)CFM DN40 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527)CGJ DN50 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C)CGM DN50 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527)CMJ DN80 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C)CMM DN80 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527)CSJ DN80 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C)CSM DN80 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527)CQJ DN100 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C)CQM DN100 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527)CTJ DN100 PN25/40 B1, 316L flange EN1092-1 (DIN2527 C)CTM DN100 PN25/40, AlloyC22 >316L flange EN1092-1 (DIN2527)CWJ DN150 PN10/16 B1, 316L flange EN1092-1 (DIN2527 C)CWM DN150 PN10/16, AlloyC22 >316L flange EN1092-1 (DIN2527)CXJ DN200 PN16 B1, 316L flange EN1092-1 (DIN2527 C)CRJ Thread ISO228 G3/4, 316LGRJ Thread ISO228 G1-1/2, 316LGRM Thread ISO228 G1-1/2, AlloyC22CNJ Thread ANSI NPT3/4, 316LGNJ Thread ANSI NPT1-1/2, 316LGNM Thread ANSI NPT1-1/2, AlloyC22KDJ 10K 40A RF, 316L flange JIS B2220KDM 10K 40A, AlloyC22 >316L flange JIS B2220KEJ 10K 50A RF, 316L flange JIS B2220KEM 10K 50A, AlloyC22 >316L flange JIS B2220KLJ 10K 80A RF, 316L flange JIS B2220KLM 10K 80A, AlloyC22 >316L flange JIS B2220KPJ 10K 100A RF, 316L flange JIS B2220KPM 10K 100A, AlloyC22 >316L flange JIS B2220YY9 Special version, TSP-No. to be spec.60 Power Supply; Output:B 2-wire; 4-20mA SIL HARTD 2-wire; PROFIBUS PAF 2-wire; FOUNDATION FieldbusK 2-wire; 4-20mA HART, Interface measurementG 4-wire 90-250VAC; 4-20mA SIL HARTH 4-wire 10.5-32VDC; 4-20mA SIL HARTY Special version, TSP-No. to be spec.70 Operation:1 W/o display, via communication2 4-line display VU331, Envelope curve display on site3 Prepared for FHX40, Remote display (Accessory)9 Special version, TSP-No. to be spec.
  • 61. Levelflex M FMP40Endress+Hauser 611)OVP = overvoltage protection80 Type of Probe:B Compact, centering disk d=45mm, 316L, pipe diameter DN50/2"C Compact, centering disk d=75mm, 316L, pipe diameter DN80/3" + DN100/4"D Spacer, center rod d=45mm, 316L, pipe diameter DN50/2", spacer, 400mmE Spacer, center rod d=75mm, 316L,pipe diameter DN80/3" + DN100/4",spacer,400mmF Remote, cable 3m, top, center d=45mm, centering disk d=45mm, 316Lpipe diameter DN50/2", 316LG Remote, cable 3m, top, center d=75mm, centering disk d=75mm, 316L,pipe diameter DN80/3" + DN100/4", 316LH Remote, cable 3m, side, center d=45mm, centering disk d=45mm, 316L,pipe diameter DN50/2"I Remote, cable 3m, side, center d=75mm, centering disk d=75mm, 316L,pipe diameter DN80/3" + DN100/4"1 Compact, basic version2 Spacer, 400mm3 Remote, cable 3m, top entry4 Remote, cable 3m, side entry9 Special version, TSP-No. to be spec.90 Housing; Cable Entry:A F12 Alu, coated IP68; gland M20B F12 Alu, coated IP68; thread G1/2C F12 Alu, coated IP68; thread NPT1/2D F12 Alu, coated IP68; plug M12E F12 Alu, coated IP68; plug 7/8"G T12 Alu, coated IP68; gland M20 (Ex d > thread M20)H T12 Alu, coated IP68; thread G1/2J T12 Alu, coated IP68; thread NPT1/2K T12 Alu, coated IP68; plug M12L T12 Alu, coated IP68; plug 7/8"M T12 Alu, coated IP68; gland M20 + OVP1)N T12 Alu, coated IP68; thread G1/2 + OVP1)P T12 Alu, coated IP68; thread NPT1/2+OVP1)Q T12 Alu, coated IP68; plug M12 + OVP1)R T12 Alu, coated IP68; plug 7/8" + OVP1)1 F23 316L IP68; gland M202 F23 316L IP68; thread G1/23 F23 316L IP68; thread NPT1/24 F23 316L IP68; plug M125 F23 316L IP68; plug 7/8"Y Special version, TSP-No. to be spec.100 Additional Option:A Basic versionB EN10204-3.1 material, wetted parts, (316L wetted parts for rod/coax)inspection certificateC EN10204-3.1 material, pressurized, (316L pressurized for rope version)inspection certificateH 5-point lienearity protocol, see additional spec.J 5-point, 3.1, NACE, 5-point linearity protocol, see additional spec.EN102043.1 material, NACE MR0175 (316L wetted parts),inspection certificateN EN10204-3.1 material, NACE MR0175 (316L wetted parts)inspection certificateS GL/ABS marine certificateY Special version, TSP-No. to be spec.995 Marking:1 Tagging (TAG), see additional spec.2 Bus adress, see additional spec.FMP40- Complete product designation
  • 62. Levelflex M FMP4062 Endress+HauserAccessoriesWeather protection cover A weather protection cover made of stainless steel is available for outdoor installation dds(order code: 543199-0001). The shipment includes the protective cover and tension clamp.L00-FMR2xxxx-00-00-06-en-001Flange with horn adapter toadapt on the following nozzlesENDRESS+HAUSERMICROPILOT IIENDRESS+HAUSERMICROPILOT IIIP65IP65Order Code:Ser.-No.:Order Code:Ser.-No.:MessbereichMeasuringrangeMessbereichMeasuringrangeU 16...36 V DC4...20mAU 16...36 V DC4...20mAmax. 20mmax. 20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C :At >85°CT>70°C :At >85°C70(2.76)mm (in)240 (9.45) 135 (5.31)95(3.74)45°F12 / T12 housingHorn adapter Order-No.G1-1/2" at DN200 / PN16 52014251L00-FMP4xxxx-17-00-00-en-026G1-1/2" at DN250 / PN16 52014252NPT1-1/2" at 8" / 150 psi 52014253NPT1-1/2" at 10" / 150 psi 52014254Material: 316L (1.4435)DN200 (8")DN250 (10")204 mmmax.~150 mm
  • 63. Levelflex M FMP40Endress+Hauser 63Remote display FHX40L00-FMxxxxxx-00-00-06-xx-0001 Micropilot M, Levelflex M, Prosonic M A Wall mounting (without mounting bracket)2 Separate housing FHX40 (IP65) B Pipe mounting (mounting bracket and plate supplied3 Cabel optionally, see product structure)4 PipeNote!For the device families Micropilot FMR2xx, Levelflex FMP4x and Prosonic FMU4x, the remote display FHX40must be only used for the HART communication version.Ordering information:For connection of the remote display FHX40 use the cable which fits the communication version of therespective instrument.ENDRESS+HAUSERENDRESS+HAUSERIP65OrderCode:Ser.-No.:OrderCode:Ser.-No.:MessbereichMeasuringrangeMessbereichMeasuringrangeU 16...36V DC4...20mAU 16...36V DC4...20mAmax. 20mmax. 20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C:At >85°CT>70°C:At >85°C82 (3.23)6,3(0.25)106(4.71)122(4.8)120 (4.72)mm (in)max. 80 (3.15)min. 30 (1.18)96 (3.78)88(3.46)160(6.3)118 (4.65)180(7.09)1122(4.8)80(3.51)23A B4150 (5.91)8,5(0.33)010 ApprovalA Non-hazardous area2 ATEX II 2G Ex ia IIC T63 ATEX II 2D Ex ia IIIC T80°CG IECEx zone1 Ex ia IIC T6/T5S FM IS Cl.I Div.1 Gr.A-D, zone 0U CSA IS Cl.I Div.1 Gr.A-D, zone 0N CSA General PurposeK TIIS Ex ia IIC T6C NEPSI Ex ia IIC T6/T5Y Special version, TSP-no. to be spec.020 Cable1 20m/65ft; for HART5 20 m/65 ft (> PROFIBUS PA / FOUNDATION Fieldbus)9 Special version, TSP-no. to be spec.030 Additional optionA Basic versionB Mounting bracket, pipe 1"/ 2"Y Special version, TSP-no. to be spec.995 Marking1 Messstelle (TAG), see additional spec.FHX40 - Complete product designation
  • 64. Levelflex M FMP4064 Endress+HauserTechnical data (cable and housing)MaterialsL00-FMxxxxxx-00-00-06-de-003Max. cable length 20 m (66 ft) (fixed length including the cast-on plugs)Temperature range -40 to +60 °C (-40 to +140 °F)Degree of protection IP65/67 (housing); IP68 (cable) acc. to IEC 60529Materials Housing: AlSi12; cable glands: nickle plated brassDimensions [mm (in) 122x150x80 (4.8x5.91x3.15) / HxWxDPosition Part Material1Housing/CoverAlSi12,Screw: V2AGround terminal CuZn nickel-plated, Screw: V2A2 Display Glass3 Cable gland CuZn nickel-plated4 Cable PVC5 Mounting bracket 316 Ti (1.4571) or 316 L (1.4435) or 316 (1.4401)6 Nut V4A7 Plate)Screw set (M5316 Ti (1.4571)Spring washer: 301 (1.4310) or V2A Screw: V4A, Nut: V4AENDRESS+HAUSERENDRESS+HAUSERIP65IP65Order Code:Ser.-No.:Order Code:Ser.-No.:MessbereichMeasuring rangeMessbereichMeasuring rangeU 16...36 V DC4...20mAU 16...36 V DC4...20mAmax. 20mmax. 20mMadeinGermanyMaulburgMadeinGermanyMaulburgT>70°C:At >85°CT>70°C:At >85°C41236753
  • 65. Levelflex M FMP40Endress+Hauser 65Centering disks If the probes with rod version are used in stilling well or bypass, it must be ensured that the probe does notcome into contact with the wall. The centering disk fixes the rod probe in the middle of the pipe.Centering disk PEEK Ø1.89 - 3.74 inchThe centering disk is suitable for probes with a rod diameter of 16 mm and can be used in pipes from DN50 (2")up to DN100 (4"). Markings on the 4-leg centering disk ensure a simple tailoring. Hence the centering disk canbe adapted to the pipe diameter. See also Operating Instruction BA00377F/00/EN.• PEEK (statically dissipative)• Measuring range: -60 °C to +200 °COrder-no. 71069064Note!If the centering disk is inserted in an bypass, it must be positioned below the lower bypass outlet.The has to be accounted for when choosing the probe length.Generally, the centering disk should not be mounted higher than 50 mm from the probe end.It is recommended not to insert the PEEK centering disk in the measuring range of the rod probe.Centering disk PFA Ø 1.46 inchThe centering disk is suitable for probes with a rod diameter of 0.63 inch (also coated rod probes) and can beused in pipes from DN40 (1½") upto DN50 (2"). See also Operating Instruction BA00378F/00/EN.• Measuring range: -200 °C to +150 °COrder-no. 71069065max.50710Ø16(0.63in)Ø 48Ø 75Ø 9510A:ø16.4(0.65)B:ø37(1.46)7.8 (0.31)
  • 66. Levelflex M FMP4066 Endress+HauserCommubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface.For details refer to TI00404F/00/EN.Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface (= Endress+HauserCommon Data Interface) to the USB port of a personal computer or laptop.For details refer to TI00405C/07/EN.Note!For the device you need the "ToF adapter FXA291" as an additional accessory.ToF adapter FXA291 The ToF adapter FXA291 connects the Commubox FXA291 via the USB port of a personal computer or laptopto the device. For details refer to KA00271F/00/A2.Screw in flange FAX50Sealing ring EPDM supplied.015 Diamter; MaterialBR1 DN50 PN10/16 A, steel, flange EN1092-1BS1 DN80 PN10/16 A, steel, flange EN1092-1BT1 DN100 PN10/16 A, steel, flange EN1092-1JF1 2" 150lbs FF, steel, flange ANSI B16.5JG1 3" 150lbs FF, steel, flange ANSI B16.5JH1 4" 150lbs FF, steel, flange ANSI B16.5JK2 8" 150lbs FF, PP, max. 3bar abs / 44psia, flange ANSI B16.5XIF UNI flange 2"/DN50/50, PVDF, max. 3bar abs/44psia, suitable for 2" 150lbs/DN50 PN16/10K 50XIG UNI flange 2"/DN50/50, PP, max. 3bar abs/44psia, suitable for 2" 150lbs/DN50 PN16/10K 50XIJ UNI flange 2"/DN50/50, 316L, max. 3bar abs/44psia, suitable for 2" 150lbs/DN50 PN16/10K 50XJF UNI flange 3"/DN80/80, PVDF, max. 3bar abs/44psia, suitable for 3" 150lbs/DN80 PN16/10K 80XJG UNI flange 3"/DN80/80, PP, max. 3bar abs/44psia, suitable for 3" 150lbs/DN80 PN16/10K 80XJJ UNI flange 3"/DN80/80, 316L, max. 3bar abs/44psia, suitable for 3" 150lbs/DN80 PN16/10K 80XKF UNI flange 4"/DN100/100, PVDF, max. 3bar abs/44psia, suitable for 4" 150lbs/DN100 PN16/10K 100XKG UNI flange 4"/DN100/100, PP, max. 3bar abs/44psia, suitable for 4" 150lbs/DN100 PN16/10K 100XKJ UNI flange 4"/DN100/100, 316L, max. 3bar abs/44psia, suitable for 4" 150lbs/DN100 PN16/10K 100XLF UNI flange 6"/DN150/150, PVDF, max. 3bar abs/44psia, suitable for 6" 150lbs/DN150 PN16/10K 150XLG UNI flange 6"/DN150/150, PP, max. 3bar abs/44psia, suitable for 6"/DN150 PN16/10K 150XLJ UNI flange 6"/DN150/150, 316L, max. 3bar abs/44psia, suitable for 6" 150lbs/DN150 PN16/10K 150XMG UNI flange DN200/200, PP, max. 3bar abs/44psia, suitable for DN200 PN16/10K 200XNG UNI flange DN250/250, PP, max. 3bar abs/44psia, suitable for DN250 PN16/10K 250YYY Special version, TSP-No. to be spec.020 Sensor connectionA Thread ISO228 G3/4B Thread ISO228 G1C Thread ISO228 G1-1/2D Thread ISO228 G2E Thread ANSI NPT3/4F Thread ANSI NPT1G Thread ANSI NPT1-1/2H Thread ANSI NPT2Y Special version, TSP-No. to be spec.FAX50 Complete product designation
  • 67. Levelflex M FMP40Endress+Hauser 67Extension rod (Centering)L00-FMP4xxxx-17-00-00-en-025010 ApprovalA Non-hazardous areaM FM DIP Cl.II Div.1 Gr. E-G N.I., zone 21, 22P CSA DIP Cl.II Div.1 Gr. G + Coal dust, N.I.S FM Cl.I, II, III Div.1 Gr. A-G, N.I., zone 0, 1, 2, 20, 21, 22U CSA Cl.I, II, III Div.1 Gr. A-G N.I., zone 0, 1, 21 ATEX II 1G2 AREX II 1D020 Extension rod; Nozzle Height1 115mm; 150-250mm / 6-10"2 215mm; 250-350mm / 10-14"3 315mm; 350-450mm / 14-18"4 415mm; 450-550mm / 14-22"9 Special version, TSP-No. to be spec.030 Center washerA not selectedB DN40 / 1-1/2", inside-d.= 40-45mm, PPSC DN50 /2", inside-d.= 50-57mm, PPSD DN80 / 3", inside-d.= 80-85mm, PPSE DN80 / 3", inside-d.= 76-78mm, PPSG DN100 / 4", inside-d.= 100-110mm, PPSH DN150 / 6", inside-d.= 152-164mm, PPSJ DN200 / 8", inside-d.= 210-215mm, PPSK DN250 / 10", inside-d.= 253-269mm, PPSY Special version, TSP-No. to be spec.HMP40- Complete product designation#DN50 (2")DN80 (3")DN150 (6")DN200 (8")DN250 (10")centering diskat PPS - GF40For DN200 and DN250in combinationwith horn adapterExtension rodNot for ¾" probe.For rod probe on request.nozzleheightKeep metal tubeat minimum length!
  • 68. Levelflex M FMP4068 Endress+HauserMounting-kit isolated Mounting-kit Order-No.For 4mm rope probe 52014249L00-FMP4xxxx-17-00-00-en-036For 6mm rope probe 52014250If a rope probe has to be fixed and a secure groundedmounting is not possible, we recommend using the insulatingsleeve made of PEEK GF-30 with accompanying DIN 580eye-bolt made of stainless steel.Max. process temp. 150 °C.Due to the risk of electrostatic charge, the insulating sleeve isnot suitable for use in hazardous areas. In these cases thefixing must be reliably grounded (→ ä 26).DInsulatingsleeveReliable, isolated mountingeye-boltD = 20 mm atM8 DIN580 for 4 mm ropeD = 25 mm atM10 DIN580 for 6 mm rope
  • 69. Levelflex M FMP40Endress+Hauser 69Additional documentationThis Additional documentation can be found on our product pages on "www.endress.com".Special Documentation Time of Flight Liquid Level MeasurementSelection and engineering for the process industry, SD00157F/00/EN.Radar Tank Gauging brochureFor inventory control and custody transfer applications in tank farms and terminals, SD00001V/00/EN.Technical Information Tank Side Monitor NFR590Technical Information for Tank Side Monitor NRF590, TI00402F/00/EN.Fieldgate FXA520Technical Information for Fieldgate FXA520, TI00369F/00/EN.Operating Instructions Levelflex M FMP40Correlation of Operating Instructions to the device:Tank Side Monitor NFR590Operating Instructions for Tank Side Monitor NRF590, BA00256F/00/EN.Description of Instrument Functions for Tank Side Monitor NRF590, BA00257F/00/EN.Engineering hints PROFIBUS PAGuidelines for planning and commissioning, BA034S/04/EN.Certificates See Section "Certificates and approvals", → ä 56.Device Output Communication OperatingInstructionsDescription ofDevice FunctionsBrief OperatingInstructions (inthe device)FMP40 B, G, H HART BA00242F/00/EN BA00245F/00/EN KA00189F/00/A2K HART (interface) BA00363F/00/EN BA00366F/00/EN KA00283F/00/A2D PROFIBUS PA BA00243F/00/EN BA00245F/00/EN KA00189F/00/A2F FOUNDATION Fieldbus BA00244F/00/EN BA00245F/00/EN KA00189F/00/A2
  • 70. Levelflex M FMP4070 Endress+Hauser
  • 71. Levelflex M FMP40Endress+Hauser 71