  • 1. DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Proposal for Stakeholder Consultation © COPYRIGHT 2009 HYDRO ONE NETWORKS LTD. ALL RIGHTS RESERVED
  • 2. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW LIMITATION OF LIABILITY AND DISCLAIMER Hydro One Networks Inc.’s (“Hydro One”) “Distributed Generation Technical Interconnection Requirements: Interconnections at Voltages 50kV and Below” (the “DG Requirements”) identifies minimum requirements for generation projects connecting to Hydro One’s distribution system. Additional requirements may need to be met by the owner of the generation project to ensure that the final connection design meets all local and national standards and codes and is safe for the application intended. The DG Requirements are based on a number of assumptions, only some of which have been identified. Changing system conditions, standards and equipment may make those assumptions invalid. Use of this document and the information it contains is at the user’s sole risk. Hydro One, nor any person employed on its behalf, makes no warranties or representations of any kind with respect to the DG Requirements, including, without limitation, its quality, accuracy, completeness or fitness for any particular purpose, and Hydro One will not be liable for any loss or damage arising from the use of this document, any conclusions a user derives from the information in this document or any reliance by the user on the information it contains. Hydro One reserves the right to amend any of the requirements at any time. Any person wishing to make a decision based on the content of this document should consult with Hydro One prior to making any such decision. STAKEHOLDER CONSULTATION CONTACT Please forward questions/comments regarding this Document to the following email address: EMAIL: DGConnectionReq@hydroone.com Hydro One has released this document for public stakeholder consultation. The stakeholder consultation process along with an electronic version of this document is available at www.hydroone.com/DG REVISION HISTORY DATE VERSION COMMENTS Proposal – Rev 0 February 2009 New Report
  • 3. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW
  • 4. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW TABLE OF CONTENTS TABLE OF CONTENTS ..................................................................................................................................... 1 LIST OF FIGURES ............................................................................................................................................. 5 LIST OF TABLES ............................................................................................................................................... 6 1 INTRODUCTION .................................................................................................................................. 7 1.1 SCOPE ................................................................................................................................................. 8 1.2 DOCUMENT REPRODUCTION .............................................................................................................. 9 1.3 TERMS AND DEFINITIONS ................................................................................................................. 10 2 HYDRO ONE SYSTEM CHARACTERISTICS ................................................................................. 16 2.1 GENERAL CHARACTERISTICS ........................................................................................................... 16 2.2 SYSTEM FREQUENCY ........................................................................................................................ 16 2.3 VOLTAGE ......................................................................................................................................... 16 2.4 VOLTAGE REGULATION ................................................................................................................... 17 2.5 VOLTAGE AND CURRENT UNBALANCE ............................................................................................. 18 2.6 POWER QUALITY .............................................................................................................................. 18 2.7 FAULT LEVELS ................................................................................................................................. 18 2.8 SYSTEM GROUNDING ........................................................................................................................ 19 2.9 HYDRO ONE NETWORKS INC. DISTRIBUTION SYSTEM FEEDER PROTECTION .................................. 19 2.10 AUTOMATIC RECLOSING (FAULT CLEARING) .................................................................................. 20 2.11 PHASING ........................................................................................................................................... 21 2.12 MULTIPLE SOURCE (NETWORKED) SYSTEM ..................................................................................... 21 2.13 FREQUENCY OF INTERRUPTIONS ...................................................................................................... 21 2.14 ABNORMAL CONDITIONS .................................................................................................................. 22 3 DG TECHNICAL INTERCONNECTION REQUIREMENTS .......................................................... 23 3.1 INTERCONNECTION TECHNICAL REQUIREMENTS............................................................................. 24 3.1.1 Safety ......................................................................................................................................... 24 3.1.2 Adverse Effects to HONI Customers ....................................................................................... 24 3.1.3 Point of Common Coupling ...................................................................................................... 24 3.1.4 Point of Disconnection .............................................................................................................. 26 3.1.5 Voltage ....................................................................................................................................... 27 3.1.6 Voltage and Current Unbalance ............................................................................................... 28 3.1.7 Frequency .................................................................................................................................. 29 3.1.8 Power Factor ............................................................................................................................. 29 3.1.9 Capacity Limitations on Generator Interconnections .............................................................. 30 3.1.9.1 Three Phase Generator Interconnections ........................................................................................... 30 3.1.9.2 Single Phase Generator Interconnections .......................................................................................... 30 3.1.10 Phasing Requirements ............................................................................................................. 31 3.1.11 Interconnection Transformer Configuration............................................................................. 31 3.1.11.1 DG Interconnection to 4-Wire Distribution System ........................................................................... 32 3.1.11.2 DG Interconnection to 3-Wire Distribution System ........................................................................... 41 3.1.12 High Voltage Interrupting Device (HVI) ................................................................................... 44 3.1.12.1 Requirement for Interconnection to 4-Wire Distribution System ...................................................... 45 3.1.12.2 Requirement for Interconnection to 3-Wire Distribution System ...................................................... 45 3.1.12.3 Interrupting Time Requirement .......................................................................................................... 45 1
  • 5. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.13 Station Service for Critical Loads ............................................................................................. 45 3.1.14 Grounding .................................................................................................................................. 46 3.1.15 Fault Levels ............................................................................................................................... 48 3.1.16 Resonance Analysis ................................................................................................................. 48 3.1.17 Self-Excitation Analysis ............................................................................................................ 49 3.1.18 Islanding..................................................................................................................................... 49 3.1.19 Synchronization ......................................................................................................................... 49 3.1.20 Insulation Coordination ............................................................................................................. 51 3.1.21 Equipment Rating and Requirements ...................................................................................... 51 3.1.22 Operating Requirements .......................................................................................................... 52 3.1.23 Metering ..................................................................................................................................... 53 3.1.24 DG Facility Acceptance ............................................................................................................ 53 3.2 PROTECTION REQUIREMENTS .......................................................................................................... 54 3.2.1 General Requirements.............................................................................................................. 54 3.2.2 Hydro One Networks Inc. Distribution System Feeder Protection......................................... 55 3.2.3 Sensitivity and Coordination ..................................................................................................... 55 3.2.4 Protection Operating Times...................................................................................................... 55 3.2.4.1 Interrupting Time for Device Disconnecting Generation ..................................................................... 56 3.2.5 Interrupting Device Rating ........................................................................................................ 56 3.2.6 High Voltage Interrupter (HVI) .................................................................................................. 56 3.2.7 Breaker Fail (BF) ....................................................................................................................... 58 3.2.7.1 BF Protection for HVI............................................................................................................................ 58 3.2.7.2 BF Protection for LVI ............................................................................................................................ 59 3.2.8 Single Phase Generators ......................................................................................................... 59 3.2.9 Three Phase Generators .......................................................................................................... 61 Delta:Wye DGIT Connecting to 3-Wire – Preferred ............................................................................ 63 3.2.9.1 3.2.9.2 Wye-Gnd:Delta DGIT Connecting to 3-Wire - Alternate ..................................................................... 64 3.2.9.3 Wye-Gnd:Delta:Wye-Gnd Connecting to 3-Wire - Alternate .............................................................. 65 3.2.9.4 Wye-Gnd:Delta DGIT Connecting to 4-Wire - Preferred .................................................................... 66 3.2.9.5 Wye-Gnd:Delta:Wye-Gnd Connecting to 4-Wire - Alternate .............................................................. 67 3.2.9.6 Delta:Wye DGIT Connecting to 4-Wire - Alternate ............................................................................. 68 3.2.10 Phase and Ground Fault Protection Requirement .................................................................. 69 3.2.11 Unbalance Protection................................................................................................................ 70 3.2.12 Feeder Relay Directioning ........................................................................................................ 71 3.2.13 Over Frequency/Under Frequency Protection ........................................................................ 71 3.2.14 Overvoltage/Undervoltage Protection...................................................................................... 73 3.2.15 Anti-Islanding Protection ........................................................................................................... 74 3.2.16 Requirement for Transfer Trip .................................................................................................. 75 3.2.16.1 Possible Exemption for DGs Smaller than 500kW ........................................................................... 76 3.2.17 DGEO (Distributed Generator End Open) ............................................................................... 76 3.2.18 Unintentional Energization........................................................................................................ 76 Connection to Hydro One Network’s System.......................................................................... 77 3.2.19 3.2.20 Disconnection of DG facilities .................................................................................................. 77 3.2.20.1 Disconnecting DG Generation ........................................................................................................... 78 3.2.20.2 Disconnecting DG HV Ground Sources ............................................................................................ 78 3.2.21 Reconnection of DG Facility ..................................................................................................... 78 3.2.21.1 Reconnection of Hydro One Source (for a transient fault) ............................................................... 78 3.2.21.2 DG Facility Reconnection................................................................................................................... 79 3.2.21.3 Lock-Out of Hydro One Source (For a Permanent Fault) ................................................................ 81 3.2.21.4 Restoration Following a Sustained Outage or Shutdown................................................................. 82 3.2.22 LSBS (Low Set Block Signal) ................................................................................................... 82 3.2.23 Auto-Resynchronization/Reconnection ................................................................................... 82 3.2.24 Synchronization Protection ....................................................................................................... 83 3.2.25 Telemetry and Targeting .......................................................................................................... 83 2
  • 6. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.26 Transformer Protection ............................................................................................................. 84 3.2.27 Protection from Electromagnetic Interference (EMI) .............................................................. 84 3.2.28 Surge Withstand Performance ................................................................................................. 84 3.2.29 Special Interconnection Protection .......................................................................................... 84 3.2.30 Batteries/DC Supply.................................................................................................................. 85 3.2.31 Protection Scheme Failure ....................................................................................................... 86 3.2.32 Teleprotection Scheme Failure ................................................................................................ 86 3.2.32.1 Transfer Trip Channel Failure ............................................................................................................ 86 3.2.32.2 DGEO Channel Failure ...................................................................................................................... 87 3.2.33 Generators Paralleling for 6 Cycles or Less (Closed Transition Switching) ......................... 87 3.2.34 Instrument Transformers for use in Protection Systems ........................................................ 87 3.2.35 Provision for Future Changes .................................................................................................. 87 3.2.36 Interconnection Protection Acceptance ................................................................................... 88 3.2.37 Protection Summary ................................................................................................................. 89 3.3 CONTROL AND TELECOMMUNICATIONS REQUIREMENTS ................................................................. 90 3.3.1 General ...................................................................................................................................... 90 3.3.2 Control Facilities ........................................................................................................................ 91 3.3.3 Telecommunication Facilities ................................................................................................... 91 3.3.3.1 Reliability Requirements....................................................................................................................... 92 3.3.4 Operating Data, Telemetry and Monitoring ............................................................................. 93 3.3.4.1 Class 1 Generators ............................................................................................................................... 93 3.3.4.2 Class 2 Generators ............................................................................................................................... 93 3.3.4.3 Class 3 Generators ............................................................................................................................... 94 3.3.4.4 Class 4 Generators............................................................................................................................... 95 3.3.4.5 Telemetry Reporting Rates .................................................................................................................. 95 3.3.5 Monitoring Reporting................................................................................................................. 96 3.4 PERFORMANCE REQUIREMENTS ....................................................................................................... 96 3.4.1 Power Quality ............................................................................................................................ 96 3.4.1.1 Voltage Fluctuations (Flicker) .............................................................................................................. 97 3.4.1.2 Voltage and Current Harmonics........................................................................................................... 97 3.4.1.3 Voltage and Current Unbalance........................................................................................................... 98 3.4.1.4 Limitation of DC Injection ..................................................................................................................... 98 3.4.2 Disturbances.............................................................................................................................. 99 3.4.3 Generator................................................................................................................................... 99 3.4.3.1 Reactive Power Requirements ............................................................................................................ 99 3.4.3.2 Speed Governors................................................................................................................................ 100 3.4.3.3 Excitation Equipment .......................................................................................................................... 101 4 METERING REQUIREMENTS ........................................................................................................103 5 CONNECTION PROCESS REQUIREMENTS .................................................................................103 5.1 IMPLEMENTATION ...........................................................................................................................103 5.2 CONNECTION AGREEMENT..............................................................................................................104 6 COMMISSIONING AND VERIFICATION REQUIREMENTS ......................................................105 6.1 HYDRO ONE NETWORKS INC. COVER PROCESS ...........................................................................105 6.2 HYDRO ONE REQUIREMENTS FOR COMMISSIONING AND VERIFICATION ........................................105 7 MAINTENANCE REQUIREMENTS ................................................................................................107 7.1 PROTECTION AND CONTROL SYSTEMS EQUIPMENTS ......................................................................107 8 REPORTING REQUIREMENTS FOR DGS .....................................................................................108 9 REFERENCES ....................................................................................................................................110 3
  • 7. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW A APPENDIX A - DEVICE NUMBER DESCRIPTION .......................................................................113 APPENDIX B – NEUTRAL REACTOR AND GROUNDING TRANSFORMER IMPEDANCE B CALCULATIONS FOR INVERTER BASED DG FACILITIES ......................................................114 APPENDIX C – TIMING DIAGRAMS ..............................................................................................115 C APPENDIX D – ANTI-ISLANDING PROTECTION ........................................................................119 D APPENDIX E – DGEO & LSBS DESIGN CONSIDERATIONS ......................................................134 E APPENDIX F – EXAMPLE OF A SEQUENCE OF EVENTS DURING FAULT CONDITIONS...135 F APPENDIX G – CONFIRMATION OF VERIFICATION EVIDENCE REPORT ..........................137 G APPENDIX H – DISTRIBUTION POLICY – METERING FOR DG - NOP 041 ...........................145 H 4
  • 8. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW List of Figures FIGURE 1: SIMPLIFIED SLD – SHOWS CLEARLY IDENTIFIED PCC .......................................................................... 25 FIGURE 2: PREFERRED DGIT CONFIGURATION FOR 4-WIRE DISTRIBUTION SYSTEMS ............................................. 34 FIGURE 3: ALTERNATE DGIT CONFIGURATION FOR 4-WIRE DISTRIBUTION SYSTEMS ............................................ 36 FIGURE 4: ALTERNATE #2 DGIT CONFIGURATION................................................................................................. 39 FIGURE 5: ALTERNATE DGIT CONFIGURATION FOR FACILITIES < 1 MVA .............................................................. 40 FIGURE 6: PREFERRED DGIT CONFIGURATION FOR 3-WIRE DISTRIBUTION SYSTEM ............................................... 42 FIGURE 7: ALTERNATE DGIT CONFIGURATION FOR 3-WIRE DISTRIBUTION SYSTEM .............................................. 43 FIGURE 8: ALTERNATE DGIT CONFIGURATION FOR 3-WIRE DISTRIBUTION SYSTEM .............................................. 44 FIGURE 9: EXAMPLE PROTECTION FOR A SINGLE PHASE GENERATOR ................................................................... 60 FIGURE 10: PREFERRED CONNECTION FOR 3-WIRE DISTRIBUTION SYSTEM ............................................................ 63 FIGURE 11: ALTERNATE CONNECTION FOR 3-WIRE DISTRIBUTION SYSTEM ........................................................... 64 FIGURE 12: ALTERNATE CONNECTION FOR 3-WIRE DISTRIBUTION SYSTEM ........................................................... 65 FIGURE 13: PREFERRED CONNECTION FOR 4-WIRE DISTRIBUTION SYSTEM ............................................................ 66 FIGURE 14: ALTERNATE CONNECTION FOR 4-WIRE DISTRIBUTION SYSTEM ........................................................... 67 FIGURE 15: ALTERNATE CONNECTION FOR 4-WIRE DISTRIBUTION SYSTEM ........................................................... 68 FIGURE 16: NPCC DIRECTORY D2 REQUIREMENT ............................................................................................... 72 FIGURE 17: NO TRANSFER TRIP WITH 500MS RECLOSURE UPSTREAM ..................................................................115 FIGURE 18: NO TRANSFER TRIP WITH 1S RECLOSURE UPSTREAM ........................................................................116 FIGURE 19: TRANSFER TRIP WITH 500MS RECLOSURE UPSTREAM ........................................................................117 FIGURE 20: TRANSFER TRIP WITH 1S RECLOSURE UPSTREAM ..............................................................................118 FIGURE 21: TYPICAL DISTRIBUTION SYSTEM WITH DG INTERCONNECTIONS .........................................................129 FIGURE 22: DGEO & LSBS DESIGN CONSIDERATION .........................................................................................134 FIGURE 23: SEQUENCE AND TIMING DIAGRAM FOR TRANSIENT FAULTS ..............................................................135 FIGURE 24: SEQUENCE AND TIMING DIAGRAM FOR PERMANENT FAULT ...............................................................136 5
  • 9. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW List of Tables TABLE 1: VOLTAGE LIMITS 0 TO 50,000V ON DISTRIBUTION SYSTEM ................................................................... 17 TABLE 2: OPERATING FREQUENCY RANGE ........................................................................................................... 29 TABLE 3: RESYNCHRONIZATION REQUIREMENTS .................................................................................................. 50 TABLE 4: ARRESTER RATINGS .............................................................................................................................. 51 TABLE 5: TYPICAL PROTECTIONS REQUIRED FOR SINGLE PHASE DG FACILITIES ................................................... 60 TABLE 6: TYPICAL PROTECTIONS FOR THREE PHASE DGS ..................................................................................... 62 TABLE 7: OVER/UNDER FREQUENCY PROTECTION SET POINTS AND CLEARING TIMES ........................................... 72 TABLE 8: OVER/UNDER VOLTAGE PROTECTION SETTING AND CLEARING TIME ..................................................... 73 TABLE 9: DG CLASSIFICATION ............................................................................................................................. 90 TABLE 10: UNPLANNED TELECOMMUNICATION FAILURE RATES AND REPAIR TIMES.............................................. 92 TABLE 11: TELEMETRY REPORTING RATES........................................................................................................... 95 TABLE 12: PST AND PLT FLICKER LIMITS ............................................................................................................. 97 TABLE 13: CURRENT HARMONIC LIMITS .............................................................................................................. 98 TABLE 14: INCIDENT LOGGING ...........................................................................................................................109 6
  • 10. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 1 Introduction This ―Distributed Generation Technical Interconnection Requirements – Interconnections at Voltages 50kV and Below‖ outlines the technical requirements to install or modify Distributed Generation (DG) projects connected to HONI‘s sub-transmission and distribution (systems at ≤ 50kV) feeders. Technical requirements are defined accordingly to the size and type of generation. This document is designed to provide an expeditious interconnection to Hydro One Networks Inc. sub-transmission and distribution system that is both safe and reliable. This document, ―Hydro One Networks Inc. Distributed Generation Technical Interconnection Requirements – Interconnections at Voltages 50kV and Below‖ was prepared by Hydro One Networks Inc. (henceforth referred to as HONI) to guide generator owners and proponents in connecting distributed generators (DGs) to HONI‘s distribution and sub-transmission system. It applies to all interconnecting generators. The additions of DGs to HONI‘s system introduces changes to the sub-transmission and distribution system and its response. It is imperative that a technically sound, reliable and safe interconnection between the DGs and HONI is achieved and this requires diligence from all parties involved. The requirements in this guideline need to be understood by designers, consultants, equipment vendors, manufacturers, DG owners, and operators of the DG‘s and HONI‘s system. These requirements will ensure that the interconnection of the DG to HONI‘s system will:  protect the integrity of HONI system and guarantee reliable and quality service to HONI‘s customers,  ensure that the interconnection is safe at all times for HONI‘s employees, HONI‘s customers, DG owners and operators, and for the general public.  be consistent with the requirements of the OEB and all applicable standards  meet all of HONI‘s protection, operating and metering requirements. This interconnection standard has been developed with reference to the Canadian Standards Association such as C22.3 No. 9-08 – Interconnection of Distributed Resources and Electricity Supply Systems and international standards such as the Institute of Electrical and Electronics Engineers (IEEE) Standard 1547 – Draft Application Guide for IEEE Standard 1547, Interconnecting Distributed Resources with Electric Power Systems. 7
  • 11. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW This document does not constitute a design handbook. DG owners who are considering the development of a generation facility intended for connection to HONI‘s system 1 should engage the services of a professional engineer and/or a registered consulting firm qualified to provide design and consulting services for electrical interconnection facilities in the Province of Ontario. 1.1 Scope This document establishes criteria and requirements for the interconnection of DGs to the distribution and sub-transmission system. It has been tailored specifically to define the requirements for connecting DGs to HONI‘s distribution and sub-transmission system with an operating voltage of 50,000 volts (50kV) or lower. It applies to all induction generators, synchronous generators and inverter-based generators (solar photovoltaic, fuel cell, induction generator with a static power converter or permanent magnet generator with a static power converter). This document contains information pertaining to HONI‘s system and identifies potential issues, such as protection, safety, coordination, reliability and operation which shall be considered at different stages of the project. Chapter 2, ―Hydro One System Characteristics‖ provides operating characteristics of HONI‘s sub-transmission and distribution system. It has been included in this document to ensure that DG owner is aware of HONI‘s sub-transmission and distribution system behaviour. Chapter 2 contains no requirements for the interconnection of DGs and has been provided for informational purposes only. The following sections of this document constitute the requirements that the DG owner must comply with in order to connect to HONI‘s systems:  Chapter 3 - DG Technical Interconnection Requirements  Chapter 4 - Metering Requirements  Chapter 5 - Connection Process Requirements  Chapter 6 - Commissioning and Verification Requirements  Chapter 7 - Maintenance Requirements  Chapter 8 - Reporting Requirements for DGs 1 This document also applies to DGs connecting to Hybrid Feeders (feeders owned partially by HONI) 8
  • 12. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Certain requirements have a separate ―Design Considerations‖ heading which is clearly defined. This information has been provided for informational purposes to aid in the design of the DG facility in certain cases and does not represent a requirement. HONI does not take any responsibility for this information and the engineering consultant designing the DG facility can decide whether to take the information into consideration when designing the project. It is the DG owner‘s responsibility to ensure that all requirements are met. These requirements have been developed to ensure that HONI‘s sub-transmission and distribution system is protected from the DG facility. Additional requirements may be necessary to address unique situations and the DG owner shall be advised of any such requirements at the appropriate stage. Certain requirements of this document state that a deviation from the preferred option (alternative) is available or that certain requirements may be not apply for certain installations. Any exemptions require written approval from HONI. This document does not identify any generator protections and the DG Owner shall ensure that adequate generator protections are installed that will protect the generator from any situation, including problems originating from HONI‘s sub-transmission and distribution system. 1.2 Document Reproduction This document may be reproduced or copied in whole or in part provided that credit is given to Hydro One Networks Inc. and is not sold for profit. 9
  • 13. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 1.3 Terms and Definitions Is defined as… The Term ANSI American National Standards Institute Protection system aimed at detecting islanded conditions Anti-Islanding (see island) and tripping the DG facility from the distribution system if an island forms AVR Automatic Voltage Regulator BF Breaker Fail Fault Interrupting Device – may be a breaker, circuit Breaker switcher, HVI, LVI CCRA Connection Cost Recovery Agreement CEA The Canadian Electricity Association CIA Connection Impact Assessment Class 1 DG DG aggregate capacity at PCC < 250kW 250kW ≤ DG aggregate capacity at PCC < 1500kW Class 2 DG 1.5MW ≤ DG aggregate capacity at PCC < 10MW Class 3 DG Class 4 DG DG aggregate capacity at PCC > 10MW Clearing Time See Trip Time Central Office – A local telephone company office that provides a central point for the termination of CO telecommunication lines and trunks. And where they can be interconnected. CSA The Canadian Standards Association Dual Element Spot Network – Type of TS DESN Distributed Unregulated power generators connected to a distribution Generation (DG) system through a Point of Common Coupling Distributed See Distributed Generation Generator (DG) 10
  • 14. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Distributor The electric utility owning or operating the distribution lines Any power line facilities under the operating authority of the Wires owner (HONI or LDC). Distribution power line facilities Distribution System usually operate below voltages of 27.6kV nominal, line to line See Distributed Generation DG *Formerly referred to as EG – Embedded Generator Distributed Generator End Open – A Signal used to confirm the status of the generator breaker – used to prevent out-of- DGEO phase reclosing onto the generator *Formerly referred to as EGEO – Embedded Generator End Open DGIT See DG Interconnection Transformer All equipment including generators, interface transformer, DG Facility protections, and line on DG side of the PCC DG Interconnection The transformer used to step up the voltage from the DG to Transformer distribution levels DG Owner The entity which owns or leases the DG facility Electrical station that is used to step down a sub- DS transmission voltage to a distribution voltage for distribution to the end use customer DSC Distribution System Code EMI Electromagnetic Interference ESA Electrical Safety Authority F Class Feeder Distribution feeder emanating from a HONI DS or HVDS a single 1 phase or 3 phase line emanating from a Feeder substation to supply load Phenomenon caused by the interaction of system capacitance and nonlinear inductance of a transformer, Ferroresonance usually resulting in very high transient or sustained overvoltage 11
  • 15. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Ground Potential Rise – IEEE defines this as the voltage that a station grounding grid may attain relative to a distant GPR grounding point assumed to be at the potential of remote earth Sinusoidal voltages and currents at frequencies that are Harmonics integral multiples of the fundamental power frequency In this document, high voltage refers to HONI system High Voltage voltage – can be referred to as medium voltage HONI Hydro One Networks Inc. High Voltage Distribution Station – Distribution station connected directly to HONI transmission system (115kV HVDS system). Stepping down transmission voltage to distribution voltage for distribution to the end use customer High Voltage Interrupter – any breaker/fault clearing device that is on the HONI side of the DGIT – voltage rating is HVI usually at medium voltage distribution level Feeders owned partly by HONI and partly by other entities Hybrid Feeders (e.g. HONI owns the first 50% of the feeder, and an LDC own the rest of the feeder). IEEE The Institute of Electrical and Electronics Engineers IED Intelligent Electronic Device IESO Independent Electricity System Operator Interconnection Physical connection of DG to HONI's distribution system facility which allows parallel operation to occur Interconnection See PCC Point An operating condition where a DG(s) is (are) supplying Island load(s) that are not paralleled and synchronized with the main electric utility (electrically separated) Local Distribution Company. An entity that owns a LDC distribution system for the delivery of energy to consumers from the IESO-controlled grid The amount of power supplied or required at a specific Load location 12
  • 16. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Ratio of average load during a designated period to the Load Factor peak (maximum) load in the same period Steady state computer simulation study of voltages and Load Flow Study currents in the distribution system Low Set Block Signal – signal sent over same channel as DGEO which blocks the Low Set Instantaneous Protections LSBS at HONI‘s stations to prevent inadvertent trips due to transformer inrush during energization. LVI Low Voltage Interrupter Medium Voltage See High Voltage Distribution feeder emanating from a HONI TS – usually ≥ M Class Feeder 24.9kV Non Detection Zone – range where passive anti-islanding NDZ protection may not operate within required time due to the small mismatch between generation and load NPCC NorthEast Power Coordinating Council OEB Ontario Energy Board OESC Ontario Electrical Safety Code OGCC Ontario Grid Control Centre The state and operation where the DG Facility is connected Parallel Operation to the Sub-transmission or Distribution System and supplying loads along with the electric grid. PCC Point of Common Coupling The point where an interconnection system is electrically Point of Connection connected to the DG facility. Can be the same as PCC. Refer to Figure 1 for details. A measure of short-term perception of flicker obtained for a Pst ten minute interval PSS Power System Stabilizer A measure of long-term perception of flicker obtained for a Plt two-hour period 13
  • 17. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Protection functions, including associated sensors, relays, Protection Scheme CTs, PTs, power supplies, intended to protect a distribution system or interconnected facility SLD Single Line Diagram A tendency of a system to oscillate at maximum amplitude Resonance at certain frequencies, usually resulting in very high voltages and currents RLSS Rotational Load Shedding Schedules Distribution System returning to normal (frequency and Stabilized voltage) after a disturbance for a period of 5 minutes or as determined by the Wires Owner Sub-transmission 27.6kV or 44kV HONI distribution lines Synchronized See Parallel Operation Telemeter Transfer of metering data using communication systems Total Harmonic Distortion – a measurement of the harmonic distortion present. It is defined as a ratio of the sum of the THD powers of all harmonic components to the power of the fundamental frequency Temporary Overvoltage – oscillatory power frequency overvoltages of relatively long duration – from a few cycles TOV to hours. Any power line facilities under the operating authority of the Transmission Wires Owner usually operating at higher then 50kV System voltages, line to line A signal sent over communication channels from upstream Transfer Trip devices commanding the DG to disconnect from HONI's distribution system The time between the start of the abnormal condition to the Trip Time time where the system disconnects and ceases to energize the distribution system Electrical station that is used to step down transmission TS voltage to a sub-transmission voltage for distribution to the end use customer and DS stations TT See Transfer Trip 14
  • 18. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Test performed on a sample of a particular model/device to Type Test verify its operation and design Wires Owner Utility which owns and/or operates the distribution system 15
  • 19. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 2 Hydro One System Characteristics This section describes the characteristics of Hydro One Networks Inc. Distribution System and identifies aspects that must be taken into consideration when designing a generation facility that will be interconnected with HONI‘s distribution system. The DG owner must be able to operate within the ranges specified in this section. In this document, HONI‘s distribution system may refer to either three phase systems or single phase systems operating at voltages of 50kV and below – includes systems falling under the definition of distribution and sub-transmission system. This section contains no requirements for the interconnection of DGs and has been provided for informational purposes only. 2.1 General Characteristics Most distribution circuits (feeders) in HONI‘s distribution system are supplied radially from a single substation (point of supply). In some areas, some feeders may have alternate points of supply, but will be operated with more than one source of supply only momentarily during switching operations. HONI‘s distribution feeders operate at the following voltages (phase-phase/phase-neutral): 44kV (3-Wire), 27.6/16kV, 25/14,4kV, 13.8/8kV, 12.48/7.2kV, 8.32/4.8kV, 4.16/2.4kV. 2.2 System Frequency The nominal frequency of HONI‘s system is 60Hz. During normal operation (steady state), the frequency may deviate from 59.3Hz to 60.5Hz, or as supplied by the transmission system. Under contingencies the frequency deviations may be larger. 2.3 Voltage The CSA Standard CAN3-C235-83 ―Preferred Voltage Levels for AC Systems, 0 to 50,000V Electric Power Transmission and Distribution‖ provides general guidance for the steady state service voltage levels on the distribution system. Customers supplied by the distribution feeder must have adequate voltage levels as per this standard, with and without distributed generation supplying power for minimum and maximum loading conditions. The operating voltages found on the distribution feeder vary depending on load variation, generation variation and contingency situations. Hydro One Networks standard for voltages on HONI‘s distribution system at the point of delivery during normal operation is typically in the range of +/- 6% of nominal voltage. The CSA voltage 16
  • 20. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW standard (summarized below in Table 1) and the voltage levels at the PCC specified in the CIA report to the DG Owner should be followed by the DG owner. These values may be exceeded under abnormal conditions. Voltage transients and swells can occur on the distribution system at any time due to lightning strikes, single phase to ground faults, and switching, among others. The interconnected DG must be able to operate within the extreme voltage level variations shown in this document and must ensure that the insulation levels and protective equipment in their facility can withstand abnormal voltages on the distribution system. Table 1: Voltage Limits 0 to 50,000V on Distribution System Low Limit (% of nominal) Nominal Voltage (%) High Limit (% of nominal) 94 100 106 2.4 Voltage Regulation HONI utilizes voltage regulating devices throughout the distribution system to maintain an adequate voltage profile along the feeders and ensure that customers receive voltages in the range specified in CSA CAN3-235-83. These regulating devices include line voltage regulators, regulating stations and transformer under-load tap changers at the Transformer Station (TS) or Distribution Station (DS). HONI operates all voltage regulating devices on its distribution system to 125V ±1.5V on a 120V base. The distribution system was designed to correctly operate for unidirectional power flow (from the substation to the customer). Voltage regulating devices were designed to correctly operate under these conditions, however, with the addition of DGs into the system, the power flow can be reversed when the DG is supplying power which may inhibit the voltage regulators to properly regulate the voltage on the feeder. Due to this, wherever there is a possibility of reverse power flow, regulating devices (line voltage regulators, regulating stations and transformer under-load tap changers at the Transformer Station (TS) or Distribution Station (DS)) on HONI‘s distribution system shall be changed to suitable devices that allow bi-directional flow. Steady-state voltage variations at the point of common coupling (PCC) and throughout the distribution system are limited to +/- 6% of the nominal voltage. 17
  • 21. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 2.5 Voltage and Current Unbalance Voltage unbalance due to unbalanced loading and single phase voltage regulation is typical and inevitable and may reach 2% voltage and 10-20% of total feeder load current unbalance along certain sections of the feeder, including at the PCC. The DG facility must not further deteriorate existing unbalanced conditions. In some areas of HONI‘s distribution system these unbalances may be higher and the DG owner shall contact HONI to obtain site-specific data. During abnormal conditions such as faults and single pole reclosing, the unbalance may be very high (current unbalance may be significantly higher than 20%). As per NEMA MG 1-1998, the formula for voltage unbalance is: 100 ×( ) % = ( ) 2.6 Power Quality In HONI‘s distribution system, all interconnected equipment must comply with HONI‘s standards for power quality. IEEE Std. 519, IEEE Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, has been accepted by industry to provide guidance for appropriate performance and power quality limits such as voltage flicker and harmonic contribution limits. This standard states that the recommended practice for utilities is to limit individual frequency voltage harmonics to 3% of the fundamental frequency and the total voltage harmonic distortion (THD) to 5% on the utility side of the PCC. These limits presented in this standard should be used as a design criterion when designing the DG facilities as worst case scenario under normal operation conditions. 2.7 Fault Levels Fault levels on HONI‘s distribution system vary greatly throughout the system. Factors, such as location, generation pattern, and contingencies all contribute to varying fault levels. These fault levels may also change with time as the system expands and new generation comes online. The DG proponents will receive fault levels for the distributions system as well as system impedances for a site that is considered from Hydro One Networks. Maximum allowable fault levels will be provided as well. 18
  • 22. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW The DG interconnection facilities shall be designed with the fault levels, and maximum allowable fault levels considered. The X/R ratios must be evaluated for the equipment selected and the DG facilities shall not increase the fault levels beyond the distribution system design levels for maximum faults. If the levels increase beyond the existing design limits, changes to the distribution system equipment will be required. 2.8 System Grounding HONI‘s distribution facilities are typically operated as uni-grounded (for 3 phase – 3 wire systems) or multi-grounded (for 3 phase – 4 wire systems). The transformer neutral at the substation is either solidly grounded (without any impedance) or effectively grounded through a low impedance at the station (through a neutral reactor, resistor or grounding transformers) to limit the fault levels on ground faults. Distribution facility and DG facility grounding shall conform to the Ontario Electric Safety Code (OESC) and Section 10 of the Canadian Electrical Code. 2.9 Hydro One Networks Inc. Distribution System Feeder Protection HONI will provide to the DG Owner, upon request, all applicable information about HONI‘s distribution system protection scheme on the feeder interconnecting with the DG facility. The general feeder protection scheme utilized on HONI‘s distribution system where DGs are interconnecting is described below for M Class feeders emanating from TSs. The feeder protections can be divided into three states: High Set Instantaneous – Instantaneous protection for close-in feeder faults. Usually set to the first tap on the feeder. Traditionally employed High Set 50A/50NA elements. Current HONI standard for feeders with DGs interconnected is to use the Zone 1 distance (21 – Phase & Ground) element to set the High Set Instantaneous protection. Low Set Instantaneous – Instantaneous protection for faults on the entire length of the feeder. Used primarily as a fuse saving scheme to clear transient faults before fuse elements start melting. Traditionally utilized using Low Set 50B/50NB elements. Current HONI standard for feeders with DGs interconnected is to use the Zone 2 distance (21 – Phase & Ground) element to set the Low Set Instantaneous protection. 19
  • 23. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW – Timed Directionally supervised 51/51N overcurrent elements load/fault discrimination are used for timed protection of HONI‘s distribution feeders. They are set to detect and clear faults in their required zone. All timed overcurrent elements on the distribution system are coordinated with each other to ensure that a minimum number of customers are affected in the case of permanent faults. For the timed overcurrent elements to function properly, all DG sources (both positive sequence and zero sequence sources) need to be removed from the distribution system – refer to the requirements in Section 3.1.12 – High Voltage Interrupting Device. F Class feeders, radiating from DSs, have varying levels of sophistication in their protection schemes. The protections scheme on F Class feeders may need to be upgraded to accommodate DGs. 2.10 Automatic Reclosing (Fault Clearing) HONI‘s sub-transmission and distribution system, utilizes automatic reclosing to quickly clear non permanent faults on the sub-transmission and distribution system, thus, quickly restoring supply. Generally feeder circuit breakers at Transmission Stations use single-shot reclosing and reclosers at Distribution Stations and other locations along the distribution feeder may use single-shot or multi-shot automatic reclosing. Reclosers may trip a single phase, when single phase loads are connected to the feeder, or all three phases. If, after the preset number of reclose attempts, the fault persists, the recloser will lockout and stay open (single phase or three phases will be tripped). The reclose ―dead time‖ (time that the distribution line is de-energized between reclose attempts) varies depending on location and type of recloser and can be obtained from HONI along with all other relevant protection data. The DG facilities shall be designed with auto-reclosing considered. The generator protections need to coordinate with the reclosing times of HONI‘s interrupting devices to ensure that HONI‘s distribution system will not attempt to reclose when the DG is still connected, risking an out-of-phase reclosing (refer to Section 3 for requirements). If single phase tripping is employed on HONI‘s distribution system, the DG shall be designed to protect itself from the unbalance that results. The DG may reconnect to the system after HONI‘s system voltage and frequency return to nominal and after the requirements of Section 3.2.19 and Section 3.2.21 of this document are met. 20
  • 24. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 2.11 Phasing Conductor phasing may not be standardized and as such, the phase sequence and the direction of rotation shall be coordinated between the DG proponent and HONI. 2.12 Multiple Source (Networked) System In some areas of HONI‘s distribution, there may be instances where portions of a distribution feeder are supplied from two different sources (such as during switching events). The added complexity in these instances shall be considered when designing the DG facilities and every precaution shall be taken to ensure that out-of-phase reclosing does not occur whenever interconnecting to a networked system or a system capable of source transferring. The DG facility is required to be removed from service if the source (normal feed) has changed from the one studied in the CIA and remain disconnected until normal supply has been restored. If this requirement changes and multiple sources (alternate feeder) configurations become available for DGs, this document will be updated to reflect any policy changes. The DG Owner will be required to have additional protections to alternative feeder supplies at that time if they wish to have the capability of connecting to alternate sources. 2.13 Frequency of Interruptions HONI‘s distribution feeders are mainly unshielded overhead lines spanning vast distances. They are equipped with insulation levels adequate to withstand expected voltages. Lighting strikes directly to HONI‘s distribution line result in flashovers of the insulators on the feeder and result in protection systems tripping the distribution line. The faults may be temporary in which case a successful reclose will occur (most faults on overhead distribution lines are temporary in nature), or they may be permanent and trip the line until repair crews are dispatched and repair the feeder. Due to the vast distances of the lines and the possibility of frequent momentary trips, the DG proponent should consider a design that will be suitable for these conditions (such as auto-restart). 21
  • 25. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 2.14 Abnormal Conditions The DG Owner shall consider all possible disturbances which occur on HONI‘s distribution system while designing their protection system to ensure that HONI‘s customers and the DG facility are protected. These disturbances can include, but are not limited to the following:  Faults on the system  Frequency excursions  Partial or complete loss of load  Transient overvoltages – caused by lightning strikes or switching operations  Temporary overvoltages  Single phasing of the three phase system – caused by HONI‘s protection equipment, switching or broken conductors  Ferroresonance, overvoltages due to resonance conditions 22
  • 26. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3 DG Technical Interconnection Requirements This ―DG Technical Interconnection Requirements‖ section defines and describes the technical requirements for the distribution system, and the generation facility (generators and interconnection equipment as described in the Distribution System Code) for DG interconnection. The first part, Section 3.1, defines the interconnection technical requirements, the second part, Section 3.2, defines the protection requirements, the third part, Section 3.3, defines the control, telecommunications, and monitoring requirements for interconnected DGs and the fourth part, Section 3.4 defines the performance requirements such as power quality and reactive power requirements. These requirements need to be followed in order to connect to HONI‘s sub-transmission, distribution system and hybrid feeders. In this document, HONI‘s distribution system may refer to either three phase systems or single phase systems operating at voltages of 50kV and below – includes systems falling under the definition of distribution and sub-transmission system. They encourage safe operation and minimize the impact that the DG facility has on HONI‘s distribution system and in turn to HONI‘s customers. Certain requirements in Section 3 of this document state that a deviation from the preferred option (alternative) is available or that certain requirements may be not apply for certain installations. Any exemptions require written approval from HONI. Certain requirements have a separate ―Design Considerations‖ heading which is clearly defined. This information has been provided for informational purposes to aid in the design of the DG facility in certain cases and does not represent a requirement. HONI does not take any responsibility for this information and the engineering consultant designing the DG facility can decide whether to take the information into consideration when designing the project. Beyond the requirements presented here in this document, the DG facility must meet all applicable national, provincial, local and other HONI safety and construction codes. This guide is intended to provide protection to HONI‘s distribution system and does not cover protection of the DG facilities. It is the responsibility of the DG Owner to protect its facilities in a manner that will ensure that events such as outages, short circuits, unbalances, excessive zero sequence currents and negative sequence voltage, and other disturbances do not cause damage to the DG facility. 23
  • 27. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1 Interconnection Technical Requirements 3.1.1 Safety The DG interconnection shall not create a safety hazard to HONI‘s personnel, customers, general public and personnel working in the DG facility. Safety is of primary concern and should be the main consideration when designing the facility. The primary concern of this document is to provide interconnection specifications to ensure that safety will be maintained. All equipment shall be approved by the appropriate authorities (e.g. CSA). The DG facility must have ESA approval prior to a Distribution Connection Agreement with HONI. The DG facilities must be maintained throughout the life of the assets to ensure that the DG facility is operating as designed. 3.1.2 Adverse Effects to HONI Customers The interconnection of the DG facilities must not materially compromise the reliability or restrict the operation of HONI‘s distribution system. The interconnection must not degrade power quality below acceptable levels and if it is found that it significantly deteriorates the performance of the distribution system, it shall be disconnected from the distribution system until appropriate measures are taken to mitigate these negative impacts. 3.1.3 Point of Common Coupling The Point of Common Coupling (PCC) is the location where Hydro One Networks distribution facilities (wires) are connected to the DG Facilities or DG proponent‘s wires and where the transfer of electric power between the DG and HONI takes place. The PCC must be identified on the single line diagram (SLD), as shown below in Figure 1. 24
  • 28. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 1: Simplified SLD – Shows Clearly Identified PCC The DG owner is responsible for the design, construction, maintenance and operation of the facilities and equipment on the DG side of the PCC (all equipment on the DG side of the PCC shall be approved in accordance with Section 2-004 of the Ontario Electrical Safety Code) while HONI will coordinate the design, construction, maintenance and operation of the facilities on HONI‘s side of the PCC. HONI will carry out the engineering, design and construction required for additional changes to HONI‘s system in order to facilitate the DG interconnection. The DG owner may be responsible for the cost of such changes. In certain instances, either HONI or the DG owner may require that their equipment be located on the other side of the PCC. If this is the case, the DG owner must provide the necessary space for HONI to install such equipment and HONI is to approve this site. A 120V AC power service is to be available. When specifications and parameters (such as voltage, frequency, and power quality) are mentioned throughout this document, they must be met at the PCC unless otherwise stated throughout the document. 25
  • 29. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.4 Point of Disconnection To ensure a means of electrically isolating the DG facility from HONI‘s distribution system, a means of isolation must be provided (Load Break Switch) and must be in compliance with the OESC. To conform with recognized standards (this complies with OESC Rule 84-026, IEEE Standard 1547 Clause 4.1.7 and the Distribution System Code (DSC) Appendix F.2 Section 1), the disconnect or isolation device must:  be a Load Break Switch (capable of interrupting maximum rated load)  be readily accessible by Hydro One  be lockable  have no keyed interlocks  be Gang Operated (for three phase installations)  be a Visible Break type  be of appropriate rating  be located between the Hydro One system and the DG Facility  bear warning to the effect that inside parts can be energized when disconnecting means is open  be motorized (single phase DG installations exempt)  have a manual override  be required to disconnect the DG facility from HONI‘s distribution system on a breaker fail condition (protection interface for tripping)  meet all applicable standards and codes (Canadian Electrical Code Part 1 and Part 2)  be capable of being closed onto a fault with complete safety to the operator – Must not be a source of injury during operation, even when closed into a faulted system  be capable of being operated without exposing the operator to any live parts. This point of disconnection is required for the purpose of work protection of Hydro One and DG facility personnel. Switching, tagging and lockout procedures shall be coordinated with HONI. The DG Owner and HONI will mutually agree to the exact location of the disconnect switch. This switch must not be located in a locked facility and where DG facilities have H2S or any other hazardous materials present, it shall be located outside of the hazardous area. 26
  • 30. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW If multiple generators are connected at the DG facility, one disconnect switch must be capable of isolating all of the generators simultaneously. There may be other means of meeting this requirement and any proposals must be reviewed by HONI. 3.1.5 Voltage The DG facility shall ensure that the operation of the DG(s) do(es) not have an objectionable impact on the voltage at the PCC. The DG owner is responsible for ensuring that the voltage at the PCC is maintained as per CSA Standard CAN3- C235-83 ―Preferred Voltage Levels for AC Systems, 0 to 50,000V Electric Power Transmission and Distribution.‖ Voltage variations at the PCC are limited to +/- 6% of the nominal voltage under normal operating conditions. Voltages at all load connections along the feeder must be at least at levels prior to the interconnection of the DG. HONI will define voltage requirements on a case by case basis in the CIA. HONI operates all voltage regulating devices on its distribution system to 125V ±1.5V on a 120V base. The introduction of DGs to HONI‘s distribution system may result in reverse power flow on the feeder. Voltage regulators on HONI‘s distribution system may require to be upgraded to be capable of handling reverse flow. During abnormal conditions, voltage variations may exceed these values. The DG Facilities must protect themselves from abnormal voltage conditions which the distribution system is subjected to. These may include voltage transients, sags and swells caused by lightning, switching, faults, and the loss or switching of customer loads. Insulation levels and protective equipment must be capable of withstanding abnormal voltages on HONI‘s distribution system. The DG should not actively regulate the voltage at the PCC. During normal operation, the DG must be loaded and unloaded gradually to allow adequate time for regulating devices on HONI‘s distribution system to respond and avoid excessive voltage fluctuations. For DGs connected to HONI‘s 4-wire distribution system, temporary over-voltage (TOV) that may be caused by the DG facility interconnection should not exceed 125% of nominal system voltage anywhere on the distribution system and under 27
  • 31. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW no circumstance shall exceed 130%. HONI will advise on action to reduce TOV to limits. For power quality parameters such as voltage dip and flicker requirements, see the Performance Requirements section (Section 3.4). 3.1.6 Voltage and Current Unbalance Voltage and current unbalance are normal on many distribution feeders as they supply many single phase loads and thereby all three phases are never equally loaded. Phase voltage unbalance of 2% and phase current unbalance of 10-20% of total feeder load is common. Unbalanced loads that result in unbalanced phase voltages and currents can cause high neutral currents, negative sequence voltages and currents, zero sequence voltages, thermal overloading of transformers and 3-phase motors, and can cause protective relaying to mis- operate. To protect HONI‘s distribution system and customers, the DG facility must not further deteriorate existing unbalance conditions at the PCC and the distribution system. The phase-phase voltage unbalance of three phase DGs must not be greater than 1% as measured with balanced three phase loading and with no load. The DG facility should also protect itself from highly unbalanced voltages, especially when connected to HONI‘s distribution system where single phase reclosing is used. The DG Interconnection Transformer may supply unbalance current to support the unbalanced load on the feeder. This unbalance current may be present even if the generator is out of service. The proportion of unbalance load current from the DG Interconnection Transformer will vary based on feeder topology, unbalanced loads, voltage and DG location. During abnormal conditions such as faults and single pole reclosing, the unbalance may be very high (current unbalance may be significantly higher than 20%) and it is up to the DG owner to ensure that the DG facilities are protected from damage due to unbalance. Single phase DGs connected to a single phase of HONI‘s distribution system are limited in size (kVA rating) due to the potential impact they may have on distribution system voltage unbalance (see Section 3.1.9 for size limitations). A single phase generator must not negatively impact the unbalance of the nearest three-phase distribution system. Single phase generators shall not cause an 28
  • 32. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW unbalance of greater than 2% when connected alone. If multiple single phase generators are installed, they shall be connected so that an equal amount of generation is applied to each single phase of the distribution line, and this balance must be maintained if one or more of the generating units go offline. 3.1.7 Frequency The generators at the DG facility must operate at a nominal frequency of 60Hz. They must remain synchronously connected for the frequency range presented below in Table 2. For any frequencies beyond those presented in the table, the generator is required to trip instantaneously (see Section 3.2.13) and islanding of DGs connected to HONI‘s distribution system is not allowed at this time. Table 2: Operating Frequency Range Generator Size Frequency Range (Hz) Low Range High Range ≤ 30 kW 59.3 60.5 57.0-59.8 (adjustable set ≥ 30 kW 60.5 point) * Source: IEEE 1547 3.1.8 Power Factor The DG facility shall be capable of operating in the preferred power factor range as specified by HONI, which is typically in the range of 0.9 lag to 0.95 lead. If warranted by local distribution system conditions (such as disturbing the distribution system voltage at the PCC), this range could be narrower or wider and will be specified by HONI. Field settable and fixed dynamic power factor correction techniques may be required. Induction generators consume reactive power and the DG Owner may be required to provide reactive power compensation to correct the power factor at the PCC. Inverters and static power converters must be able to adjust their power factor in the range of at least ± 0.90 at the PCC. For DG facilities that are IESO-impactive (Class 4 DGs), the reactive power compensation at the generator units should be sufficient so as not to cause any material increase in the reactive power requirements at the transmission system transformer station due to the operation of the DGs at all load conditions on the feeder. 29
  • 33. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.9 Capacity Limitations on Generator Interconnections Distribution feeders operating at nominal voltage levels of 13 kV or higher are normally supplied from TS‘s or HVDS‘s. The actual loading for all sections of these types of feeders shall be based on the thermal loading limits corresponding to the specific conductor sizes as well as the actual ratings of other series elements (line switches, regulators, distribution transformers, fuses, etc.) but shall not exceed 400 amps. Distribution feeders operating at nominal voltage levels below 13 kV are normally supplied from DS‘s. The actual loading for all sections of these types of feeders shall be based on the thermal loading limits corresponding to the specific conductor sizes as well as the actual ratings of other series elements (line switches, regulators, distribution transformers, fuses etc.) but shall not exceed 200 amps. During emergencies and planned outages, the DG facility is required to be removed if the source (normal feed) is changed over to an alternate source. The following is a guide for the acceptable total generation limits for feeders operating at standard Hydro One nominal voltage levels of ≤ 13kV, 13.8 kV, 25 kV, 27.6 kV and 44 kV. Please note that the actual acceptable generation limits for feeders are determined from detailed connection impact assessments. 3.1.9.1 Three Phase Generator Interconnections Three phase DGs connecting to HONI‘s distribution at nominal voltage levels of 25kV, 27.6kV, and 44kV usually do not exceed 10MW. If the 27.6kV feeder is supplied via a 44kV:27.6kV step-down transformer, the DG facility will be limited to 5MW per individual connection. Three phase DGs connecting at lower voltage levels (below 15kV) are normally supplied by HONI‘s distribution stations. The individual generation limits of DGs connecting to these feeders shall not exceed 1.0MW. 3.1.9.2 Single Phase Generator Interconnections Individual single phase generators connecting to feeders operating at nominal voltage levels of 13.8kV, 25kV, 27.6kV and 44kV are limited to 30
  • 34. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 150kW output. Single phase generators connecting to feeders operating at nominal voltage levels less than 13kV are limited to 100kW. 3.1.10 Phasing Requirements HONI and the DG Owner shall agree upon the phase sequence and direction of rotation. The DG must connect rotating machines as required to establish correct rotation. 3.1.11 Interconnection Transformer Configuration As per the DSC, Appendix F.2 Section 2, the interconnection transformer shall not cause voltage disturbances or disrupt co-ordination of distribution system ground fault protection. Annex C of CSA Standard C22.3 No.9-08 discusses different DG interconnection transformer configurations and presents each ones advantages and disadvantages. Since the winding configuration of any three phase transformer(s) between the DG and HONI will have an impact on the distribution system, both under steady state and fault conditions, Hydro One Networks has analyzed the different options and has standardized the DG interconnection transformer configuration. This section will describe the allowable transformer configurations for the interconnection of DG‘s to HONI‘s 3-Wire and 4-Wire distribution system. Written approval from HONI will be required for any alternate configuration. The DG Interconnection Transformer may supply unbalance current to support the unbalanced load on the feeder. This unbalance current may be present even if the generator is out of service. The proportion of unbalance load current from the DG Interconnection Transformer will vary based on feeder topology, unbalanced loads, voltage and DG location This directive applies to all DGs connected directly or indirectly (through a hybrid feeder) to the HONI distribution system and applies to Class 1, Class 2, Class 3, and Class 4 generators. Where the DG is connected indirectly to HONI‘s Transmission or Distribution system through an LDC, HONI will assess the impacts of the connection to the HONI system. 31
  • 35. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.11.1 DG Interconnection to 4-Wire Distribution System Preferred Option HONI‘s preferred transformer interconnection configuration and grounding for 4-wire distribution systems is shown below in Figure 2, Wye- Ground:Delta. This configuration will eliminate the damaging TOV associated with high side delta transformer configurations. A neutral reactor in the primary winding may be necessary to limit the ground short circuit current. Sizing of Neutral Reactor for Conventional (Rotating) Generators The neutral reactor, Xn shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Positive and Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: XDG 0 1.5 ≤ ≤ 2.5 XDG 1 to achieve an overall Thevenin Equivalent Positive and Zero Sequence impedance at any point on the feeder with any or all DG sources and HONI sources In-Service of: X0 R0 2< X1 < 3 X1 < 1 and Sizing of Neutral Reactor for DGs with an Inverter Interface The neutral reactor, Xn shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: X0 X0 = 0.6 ± 10% p. u. and R0 ≥ 4 where 1 p.u. is based on the MVA and high side kV rating of the DGIT. Note: DGIT MVA rating assumed to be approximately equal to the generation capacity. See Appendix B for calculation examples. 32
  • 36. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Utilizing this DG interconnection transformer (DGIT) winding configuration and grounding scheme limits the harmful temporary overvoltages on HONI‘s distribution system, however, it adds a ground source and can desensitize HONI‘s protective equipment. Once HONI‘s feeder Low Set instantaneous protection operates, the DGITs along with the generators shall be tripped off using a HVI, which is required for all DGs connected via this transformer configuration (refer to Section 3.1.12 and 3.2.6), as seen in Figure 2. This disconnects the DG facilities DGITs including any ground sources, allowing the timed overcurrent protection on HONI‘s distribution system, such as feeder breaker, inline reclosers, and fuses, to detect all faults on HONI‘s distribution system and coordinate properly. Please refer to Section 2.9 for an explanation of HONI‘s distribution system protection scheme. This DGIT configuration may require a grounding transformer (zig-zag) to be connected on the LV side of the DGIT if the DG facility needs to limit the TOV on the LV side. The ground of the DGIT shall be connected to HONI‘s neutral conductor and the design of the DG facility shall conform to the grounding requirements set in Section 3.1.14. 33
  • 37. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 2: Preferred DGIT Configuration for 4-Wire Distribution Systems 34
  • 38. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Alternate Option #1 An alternate DG interconnection transformer configuration for 4-wire distribution systems is shown in Figure 3. A Wye-ground:Wye-ground transformer configuration is a viable alternative, however, it is required to have a delta tertiary winding to limit the harmonic distortion to HONI‘s distribution system and to limit the TOV‘s on HONI‘s distribution system due to the introduction of the DG on the feeder if the generator is ungrounded or high impedance grounded. Sizing of Neutral Reactor for Conventional (Rotating) Generators The neutral reactor, Xn shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Positive and Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: XDG 0 1.5 ≤ ≤ 2.5 XDG 1 to achieve an overall Thevenin Equivalent Positive and Zero Sequence impedance at any point on the feeder with any or all DG sources and HONI sources In-Service of: X0 R0 2< X1 < 3 X1 < 1 and Sizing of Neutral Reactor for DGs with an Inverter Interface The neutral reactor, Xn shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: X0 X0 = 0.6 ± 10% p. u. and R0 ≥ 4 where 1 p.u. is based on the MVA and high side kV rating of the DGIT. Note: DGIT MVA rating assumed to be approximately equal to the generation capacity. See Appendix B for calculation examples. 35
  • 39. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW This alternate DGIT configuration will eliminate the need for grounding transformers on both the HV and LV side of the DGIT. The ground of the DGIT shall be connected to HONI‘s neutral conductor (as shown in Figure 3) and the design of the DG facility shall conform to the grounding requirements set in Section 3.1.14. An HVI will be required as per Section 3.1.12.1. Figure 3: Alternate DGIT Configuration for 4-Wire Distribution Systems 36
  • 40. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Alternate Option #2 DG installations which utilize multiple transformers that step up the voltage directly to the distribution voltage level and connect to HONI distribution system through a common PCC may be connected as shown in Figure 4. The transformers at these generators may be connected delta on the high side depending on the manufacturer, and in order to facilitate interconnection of these projects, this alternative transformer configuration can be used. This alternative may also be used for inverter based DGs whenever it is more economical to use grounding transformers as opposed to neutral reactors due to the impedance required (Refer to Section 3.1.14, Grounding Requirements). This alternative will require a grounding transformer (zig-zag) to be connected on the HV side of the DGITs to limit the TOV on HONI‘s distribution system. This grounding transformer shall be sized by the DG Owner and reviewed during the Connection Impact Assessment. Sizing of Grounding Transformer for Conventional (Rotating) DGs The grounding transformer shall be sized based on a Thevenin Equivalent of the Positive and Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: XDG 0 1.5 ≤ ≤ 2.5 XDG 1 to achieve an overall Thevenin Equivalent Positive and Zero Sequence impedance at any point on the feeder with any or all DG sources and HONI sources In-Service of: X0 R0 2< X1 < 3 X1 < 1 and 37
  • 41. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Sizing of Grounding Transformer for DGs with an Inverter Interface The grounding transformer shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: X0 X0 = 0.6 ± 10% p. u. and R0 ≥ 4 where 1 p.u. is based on the total MVA rating of the DG Facility (sum of DGITs MVA ratings) and high side kV rating of the DGIT(s). Note: DGIT MVA rating assumed to be approximately equal to the generation capacity. See Appendix B for calculation examples. The grounding transformer shall be located on the DG side of the HVI – Refer to Section 3.1.12.1 for HVI requirements. The design should be a padmount zig-zag transformer installed in accordance to all applicable codes and standards. It shall be solidly connected (not fused) to ensure that the transformer is in service at all times. The grounding transformer‘s ground shall be connected to HONI‘s neutral conductor and the design of the DG facility shall conform to the grounding requirements set out in Section 3.1.14. 38
  • 42. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 4: Alternate #2 DGIT configuration Alternate Option #3 – Available for Installations < 1 MVA HONI‘s preferred transformer interconnection configuration and grounding for 4-wire distribution systems has been shown in Figure 2. The following alternate option shown here in Figure 5 may be allowed in certain cases for small DGs with an aggregate capacity of less than 1 MVA. In the presence of single phase reclosing upstream of the DG on HONI‘s distribution system, consideration should be given to use 3 separate single phase transformers, as this will eliminate the problems associated with backfeed onto faulted phases due to a shared magnetic core. Therefore in the case of a downed conductor, without the presence of a HVI at the DG 39
  • 43. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW facility to disconnect the transformer, the public would not be put at risk due to magnetically coupled voltage on the conductor. This configuration passes harmonics readily and as such, the DG Owner must ensure that harmonic contributions from the facility are within limits, otherwise mitigation will be required. A neutral reactor in the primary winding may be necessary to limit the ground short circuit current and will be determined in the CIA. The neutral reactor, if needed, shall be sized as in the preferred option. Figure 5: Alternate DGIT configuration for facilities < 1 MVA 40
  • 44. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.11.2 DG Interconnection to 3-Wire Distribution System Preferred Option HONI‘s preferred DG interconnection transformer configuration and grounding for 3-wire distribution systems is shown below in Figure 6, Delta: Wye-ground. HONI‘s 3-Wire Distribution Systems have been designed to withstand phase to phase voltages and thus there is no concern of TOV for these connections. Since TOV is not a problem, HONI prefers this option as it does not introduce additional ground sources to HONI‘s distribution system. The requirement for having an HVI installed at the DG facility may be waived. If the HVI requirement is waived, the DG Owner shall decide whether or not to install an HVI. If in the future the requirements change, and the HVI is required, the DG Owner will be obliged to install one at its own cost. An LVI (Low Voltage Interrupter on the generator side of the DGIT) will be required if an HVI is not installed. The design of the DG facility shall take into consideration the possibility of ferroresonance due to the loss of one or two phases and shall take steps to ensure that the DG facility is protected under such an occurrence. Protection systems shall be designed accordingly to ensure that ground faults on HONI‘s distribution system are detected. 41
  • 45. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 6: Preferred DGIT Configuration for 3-Wire Distribution System Alternate Option #1 A Wye-Ground:Delta DG interconnection transformer on HONI‘s 3-Wire distribution system as shown in Figure 7 is not a preferred option, however it may be acceptable if required and will be determined in the CIA. A neutral reactor in the primary winding may be necessary to minimize the ground source current and should be sized such that TOV is limited to a ceiling of 150% of nominal voltage. Due to the addition of a ground source to HONI‘s distribution system, an HVI will be required. This DGIT configuration may require a grounding transformer (zig-zag) to be connected on the LV side of the DGIT to limit the TOV on the LV side. 42
  • 46. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 7: Alternate DGIT configuration for 3-Wire Distribution System Alternate Option #2 A Wye-ground:Wye-ground interconnection transformer on HONI‘s 3-Wire distribution system as shown below in Figure 8 is also not a preferred option, however it may be acceptable if required and will be determined in the CIA. It is required to have a delta tertiary winding to limit the harmonic distortion to HONI‘s distribution system. A neutral reactor in the primary winding may be necessary and should be sized such that TOV is limited to a ceiling of 150% of nominal voltage. 43
  • 47. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 8: Alternate DGIT configuration for 3-Wire Distribution System 3.1.12 High Voltage Interrupting Device (HVI) The following are requirements for a HVI to be installed at the DG facility. This device shall be sized properly to account for present and future anticipated fault levels. The design shall be reviewed and accepted by HONI. If an HVI is not required, a Low Voltage Interrupter (LVI) shall be installed on the low voltage side of the DGIT. 44
  • 48. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.12.1 Requirement for Interconnection to 4-Wire Distribution System A High Voltage Interrupter (HVI) with protection interface for tripping is required for all DGs larger than 1 MVA connected to HONI‘s 4-wire distribution system. This is required to remove the ground source (see Section 3.1.11.1 for DG Interconnection Transformer Configuration) from the distribution network following a fault to allow for proper protection coordination. For DGs smaller than 1 MVA connecting through a Wye- ground:Wye-ground DGIT, the HVI is optional (see Section 3.1.11.1, Alternate #3). 3.1.12.2 Requirement for Interconnection to 3-Wire Distribution System If the DG Interconnection Transformer preferred option (Section 3.1.11.2) is chosen for HONI‘s 3-wire system, the HVI is optional, and the DG Owner shall decide whether to install an HVI or not. If in the future, the requirements change and an HVI will be required, the DG Owner will be obliged to install one at its own cost. For all other alternate options for the DG Interconnection transformer for HONI‘s 3-Wire distribution System, an HVI will be required for DG Facilities. 3.1.12.3 Interrupting Time Requirement When the HVI is the used to disconnect generation from HONI‘s distribution system, it must not exceed the maximum interrupting time of 85ms (5 cycles). 3.1.13 Station Service for Critical Loads A dedicated station service AC power source will be required to supply critical loads (such as the station battery) whenever the HVI or LVI are OPEN. If the station service AC service power source is obtained from either HONI or a local distribution company, the DG owner must ensure that the above station service AC power source cannot be electrically connected to the DG electrical system that is associated with the power transfer from the DG facility to the HONI distribution system (example: the intent is to prevent reverse power from the DG facility to the station service AC supply source. The station service load shall not impose operating restrictions on HONI‘s system when either the Motorized Disconnect 45
  • 49. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Switch (Load Break Switch) or the HVI is opened – generator is disconnected. The station service shall comply with all required load connection standards. 3.1.14 Grounding The DG facilities grounding (generators and interconnection) shall be per manufacturer‘s recommendation and the OESC and follow the requirements set out in this document (refer to Section 3.1.11, Interconnection Transformer Configuration and Section 3.2, Protection requirements section). The grounding of the DG facility must not cause overvoltages that exceed the rating of equipment connected to HONI‘s distribution system. Refer to Section 3.1.5 for voltage requirements). The grounding of the DG facility must not disrupt the coordination of ground fault protection of Hydro One‘s distribution system. As discussed in Section 3.1.11, if the primary HV winding of the DG Interconnection Transformer is grounded, the ground grid of the DG facility is to be connected to HONI‘s ground grid (neutral). For 4-wire DG installations, transformers configured Wye-Gnd:Δ or Wye-Gnd:Δ:Wye-Gnd (refer to Section 3.1.11 for allowable DG Interconnection Transformer configurations) may require a neutral reactor or a grounding transformer. The reactor or grounding transformer shall be sized as follows: Sizing of Neutral Reactor and Grounding Transformer for Conventional (Rotating) Generators The neutral reactor, Xn or grounding transformer shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Positive and Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: XDG 0 1.5 ≤ ≤ 2.5 XDG 1 to achieve an overall Thevenin Equivalent Positive and Zero Sequence impedance at any point on the feeder with any or all DG sources and HONI sources In-Service of: X0 R0 2< X1 < 3 X1 < 1 and 46
  • 50. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Sizing of Neutral Reactor or Grounding Transformer for DGs with an Inverter Interface The neutral reactor, Xn or grounding transformer shall be sized by the DG Owner and reviewed during the Connection Impact Assessment based on a Thevenin Equivalent of the Zero Sequence Reactance of the DG facility (example: at the Point of Connection with the Point of Connection OPEN) that will result in: X0 X0 = 0.6 ± 10% p. u. and R0 ≥ 4 where 1 p.u. is based on:  the total MVA rating of the DG Facility (sum of DGITs MVA ratings) and high side kV rating of the DGIT(s) for Grounding Transformer sizing.  the MVA and high side kV rating of the DGIT for Neutral Reactors sizing. Note: DGIT MVA rating assumed to be approximately equal to the generation capacity. See Appendix B for calculation examples. For 3-wire installations, where the same transformer configuration is chosen, the reactor shall be chosen to provide a TOV ceiling of 150% nominal voltage. In wind farm installations, to limit the exposure of lightning to HONI‘s distribution system, the lightning protection at each wind tower must be electrically separated from the DG facility – Ground grids of wind towers shall be separated from the DG Station ground grid. This can be achieved by ensuring that the wind towers are not bonded to the stations electrical grid. The installation of a wind farm shall not increase the lightning transfer to HONI‘s system. Stand alone studies are required to ensure that GPR meets step and touch potential ESA requirements and must also be submitted to HONI. Design Consideration Ground grids of wind towers shall be separated from the DG Station ground grid. This can be achieved by ensuring that the wind towers are not bonded to 47
  • 51. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW the stations electrical grid. There are different ways to achieve this, such as ensuring that the cables are not bonding the two systems together (can be achieved by designing a span or section of the line overhead). 3.1.15 Fault Levels The impact of DG interconnection facilities on existing equipment ratings, circuit loading and fault levels must be assessed. X/R ratios and maximum short circuit levels must be maintained within acceptable Distribution System design and Transmission System Code (TSC) limits. The DG facilities must not increase the fault levels beyond these limits. Any required changes to distribution system equipment ratings must be assessed by Hydro One and paid for by the DG Owner. 3.1.16 Resonance Analysis The design of the DG facility should include a careful examination of resonance. Resonance can cause damage to HONI‘s distribution system, electrical equipment of HONI‘s customers, and the electrical equipment at the DG facility. Analysis should be conducted by the DG owner to evaluate the possibility of the following resonance conditions and if there is a possibility of them, eliminate their harmful effects:  Ferro-resonance in the transformer – operating information may be provided to the DG Owner upon request (information on single phasing possibilities)  Sub-synchronous resonance due to large rotating machines and/or capacitor banks present on the distribution system  Harmonic resonance with other customer‘s equipment when capacitors are added to HONI‘s distribution system Information on HONI‘s distribution system for the purpose of this analysis can be provided upon request. Resonance analysis should be submitted to HONI for evaluation and review. 48
  • 52. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.17 Self-Excitation Analysis If the DG being installed is an induction generator, studies shall be conducted to assess whether there is a possibility of self-excitation. Information on HONI‘s distribution system for the purpose of this analysis can be provided upon request. Self-excitation analysis should be submitted to HONI for evaluation and review. 3.1.18 Islanding Upon loss of voltage in one or more phases of the HONI distribution system, the DG facility shall automatically disconnect from all of HONI‘s distribution line ungrounded conductors prior to the reclosure of HONI protection equipment. Local islanding detection is required and will be discussed in Section 3.2.15. Intentional islanding is not allowed at this time. 3.1.19 Synchronization The DG facility shall parallel with HONI‘s distribution system without causing a voltage fluctuation at the PCC greater than ± 4% of the prevailing voltage level of the distribution system at the PCC and meet the flicker requirements (Section 3.4.1.1). The DG facility (synchronous and permanent magnet generators) shall remain in synchronism with HONI‘s distribution system while operating in parallel to HONI‘s distribution system. Synchronous generators, self-excited induction generators or inverter-based generators that produce fundamental voltage before the paralleling device is closed can only parallel with HONI‘s distribution system when frequency, voltage, and phase angle differences are within the ranges given below in Table 3 at the moment of synchronization. For synchronous generators, an approved automatic synchronization device is required if the plant is unattended (IEEE device number 25) to ensure that the DG facility will not connect to an energized feeder out of synchronism. 49
  • 53. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Table 3: Resynchronization Requirements Phase Angle Aggregate Rating Frequency Voltage Difference Difference of Generators Difference (Δ V, %) (̊Δ Φ, ̊ ) (Δ f, Hz) (kVA) 0-500 0.3 10 20 >500 – 1500 0.2 5 15 >1500 0.1 3 10 * Source: IEEE 1547 Induction generators and inverter-based generators that do not produce fundamental voltage before the paralleling device is closed, and double-fed generators whose excitation is precisely controlled by power electronics to produce a voltage with magnitude, phase angle, and frequency that match those of the distribution system may not require synchronization facilities. These types of generators shall be tested to determine the maximum startup current. The results shall be used, along with the Distribution System source impedance for the proposed location, to estimate the starting voltage magnitude change and verify that the unit will not cause a voltage fluctuation at the PCC greater than ± 4% of the prevailing voltage level of the distribution system at the PCC and meet the flicker requirements (Section 3.4.1.1). Induction generators may be connected and brought up to synchronous speed by direct application of rated voltage provided that they meet the requirement of voltage drop given above and/or they do not exceed flicker limits at the PCC. Otherwise, other methods such as reduced voltage starting or speed matching using the prime mover prior to connection must be used to respect these voltage drop and flicker limits. Any proposed synchronizing scheme must be submitted to HONI prior to installation and must be able to accommodate automatic reclosing on HONI‘s distribution facilities. For large DG facilities with multiple generator units, staggering the generator reconnections to HONI‘s distribution system may be required and will be coordinated with HONI. Refer to Section 3.2.19, Section 3.2.21 and Section 3.2.23 for further information. 50
  • 54. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.20 Insulation Coordination The DG facility shall be protected against lightning and switching surges such as voltage stresses. Temporary overvoltages may affect equipment, both on the distribution system and the DG facility. Overvoltage protection usually includes using station and line shielding against direct lightning strikes and surge arresters for all wound equipment. The surge arresters are located as close as possible to the equipment they protect. HONI‘s distribution system voltage ratings are shown below in Table 4. Table 4: Arrester Ratings HONI Distribution System Voltage Arrester MCOV Rating System Arrester Phase MCOV (kV) Voltage (kV) 4.16 3 8.32 6 12.5 9 13.8 10 24.9 18 27.6 21 44 39 (intermediate class) 3.1.21 Equipment Rating and Requirements The generation facility interface equipment must be compatible with Hydro One equipment design and ratings under all operating conditions. Considerations include, but are not limited to:  Respecting equipment thermal loading limits  Impact of generation facility fault contribution on equipment rating  If power is able to flow in reverse direction, then all existing voltage regulating and metering devices must be suitable for bi-directional flow. 51
  • 55. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.22 Operating Requirements The following are a list of operating requirements for DGs interconnecting to Hydro One Networks Inc. sub-transmission and distribution system:  Switching that involves manual operation of air break switches will require all connected DG's to come off-line as directed by the Connection Agreement and/or Controlling Authority.  Any source configuration which is not the ―normal‖ source will require all DGs to be disconnected until such a time when the ―normal‖ supply has been restored. Normal supply is defined as the supply configuration that has been studied in the CIA.  Any temporary feeder parallels will require all connected DG's to come off-line as directed by the OGCC.  Transfer Trip and DGEO communications required for DGs 1 MVA and larger, connecting to HONI‘s distribution system at voltages greater than 20 kV.  Transfer Trip initiated for outages upstream of the feeder breaker must be in place back to the generator (i.e. high side faults, bus differential).  For feeders with multiple feeder reclosers, 50% minimum feeder load calculations shall identify remaining loading levels with reclosers in open position.  No automatic reconnection to the system will be allowed unless:  There is always customer contact with the ability to immediately disconnect from the system if requested by the OGCC (24 hours/7 days per week, or  OGCC has the ability to remotely disconnect DG customer from the system, and  Feeder relay studies must be updated if circuit configuration is materially altered. If the source changes from the configuration studied in the CIA, the generator will not be allowed to reconnect.  Automatic Reconnection to HONI‘s distribution system shall be locked out once voltage and frequency are not within operating ranges for a period of 15 minutes on any phase  Legacy facilities need to meet this documents DG Requirements. 52
  • 56. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.1.23 Metering Metering requirements vary with the type and intent of the generation facility. Please consult the IESO Market Rules and the Distribution System Code Section 5 for details. Refer to Section 4 of this document for more information. 3.1.24 DG Facility Acceptance The DG facility interconnecting to HONI‘s distribution system must have a professional engineer licensed in the Province of Ontario declare (stamp and seal) that the DG facility has been designed, tested and constructed in accordance with the requirements of this document, HONI‘s site-specific requirements, prudent utility practice and all applicable standards and codes. HONI shall receive and review all designs from the DG Owner at the proper stage. 53
  • 57. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2 Protection Requirements 3.2.1 General Requirements Abnormal conditions in the DG facility and on HONI‘s distribution system require that the DG facility respond and protect itself and HONI‘s distribution system. This response contributes to the safety of HONI‘s and DG‘s personnel and the general public and avoids damage to both DG facility‘s, HONI‘s and HONI‘s customer‘s equipment. The protection schemes shall be designed to detect the conditions presented in this section of this requirements document including but not limited to:  Balanced and unbalanced faults (line to ground, line to line, three phase) at the DG facility and HONI‘s distribution system (entire distribution feeder that DG is connected to)  Abnormal frequencies  Abnormal voltages  Islanding Conditions The protection schemes employed shall coordinate with HONI‘s distribution system protections and shall be designed for current and anticipated future fault levels. Dedicated communications may be required to facilitate timely clearing of faults. All protection operations shall ensure that the generator(s) and all sources of ground current are tripped within the required time from the start of the disturbance. For DG facilities utilizing a Wye-Ground high side DG Interconnection Transformer (refer to Section 3.1.11 Interconnection Transformer Configuration), both the DGIT and the generators must be tripped within the required clearing time (refer to Section 3.2.4). All protection scheme proposals will need to be reviewed and accepted by Hydro One Networks Inc. 54
  • 58. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.2 Hydro One Networks Inc. Distribution System Feeder Protection HONI will provide to the DG Owner, upon request, all applicable information about HONI‘s distribution system protection scheme on the feeder interconnecting with the DG facility. Information regarding HONI‘s protection system, including philosophy, can be found in greater detail in Section 2.9 HONI‘s distribution system protections may need to be upgraded and/or replaced to accommodate DG interconnections. This may have financial implications for the DG Owner. 3.2.3 Sensitivity and Coordination The DG facilities protection shall provide adequate sensitivity to detect and clear all faults in the DG facility as well as HONI‘s distribution system. The design shall coordinate with other HONI protection system devices at present and anticipated future fault levels. 3.2.4 Protection Operating Times The DG interconnection protection shall disconnect the DG facility from HONI‘s distribution system within the required time as specified in the individual requirements throughout this document – Example: For any phase and ground faults a maximum of 500ms from inception of the fault condition and islanding conditions. This time is measured from the start of the abnormal condition to the time the DG will cease energizing HONI‘s distribution system. This is a maximum clearing time and in certain instances, the clearing time may be more stringent. HONI will determine this in the CIA. Timing diagrams for different events are shown for reference in Appendix C. If the DG facility is required to have a High Voltage Interrupter (refer to Section 3.1.12), there is a requirement to ensure that the DG Interconnection Transformer is disconnected from HONI‘s distribution system under abnormal conditions. Therefore, the protections shall trip both the generators and HVI and clear within the required time. Refer to Section 3.2.20, ―Disconnection of DG Facilities‖, and 55
  • 59. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Section 3.2.21, ―Reconnection to Hydro One Network‘s System‖, for more information. 3.2.4.1 Interrupting Time for Device Disconnecting Generation The interrupting device used to disconnect generation from HONI‘s distribution system must have maximum opening time of 85ms. 3.2.5 Interrupting Device Rating All fault current interrupting devices shall be sized appropriately. Fault contribution from both the DG facility and HONI‘s distribution system shall be used to adequately size all fault current interrupting devices. HONI will provide present and anticipated future fault contribution levels from HONI‘s distribution system. The interrupting device used to disconnect generation from HONI‘s distribution system must have maximum interrupting time of 85ms. For DGs that have a time variant fault contribution characteristics, the characteristics producing the highest fundamental component fault current shall be used – synchronous and induction generators shall use sub transient reactance to calculate fault contribution. Inverter based DGs typically contribute fault current marginally higher than rated full load current (usually 1.2 to 1.5 times the rated load current of the inverter for self-commutated designs and less for line- commutated inverters). Depending on the design, the rotor of double-fed asynchronous motors may be shorted by crowbar action in response to severe faults causing the generator to behave like an induction generator. 3.2.6 High Voltage Interrupter (HVI) NOTE: For the purpose of this document, the HVI will refer to interrupting devices on HONI‘s side of the DG Interconnection Transformer – whether it is high voltage or medium voltage. DG facilities connecting on 4-Wire distribution systems are required to be equipped with a High Voltage Interrupter (HVI) as can be seen in Figure 2, Figure 3, and Figure 4 of Section 3.1.11.1. For DGs smaller than 1 MVA connecting through a Wye-ground:Wye-ground DGIT, the HVI is optional (see Section 3.1.11.1, Alternate #3). 56
  • 60. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW DG facilities connecting on 3-Wire distribution systems are not required to be equipped with a High Voltage Interrupter (HVI) if they connect using the preferred DGIT configuration (Refer to Section 3.1.11.2). All ―Alternate‖ DGIT configurations for 3-Wire connections require an HVI. In the event that an HVI is required, it will be equipped with a protection interface for Tripping. The HVI shall be sized according to the present and future anticipated fault current. The HVI status should be monitored and ―Breaker Fail‖ initiated during every protection trip operation – See Section 3.2.7 for details on Breaker Fail. This requirement is driven by the DG Interconnection Transformer Configuration and the need to remove the ground source from the distribution system before the 1st reclose to ensure that the DG facilities will not adversely affect overcurrent protection devices on HONI‘s distribution system - the feeder and DG HVI will be tripped for feeder faults or feeder islanding conditions (feeder breaker trips instantaneously and independently of DG HVI tripping). Before the 1 st reclose, all the DGs and associated DGITs on the distribution feeder shall be disconnected from the feeder. Upon reclose, the feeder 51 & 51N times overcurrent devices will co-ordinate with reclosers and lateral fuses on HONI‘s distribution system since all current infeeds from the DGs and DGITs are removed. The HVI is also required to prevent backfeed whenever single phase switching can occur upstream of the DG on HONI‘s distribution system Refer to Section 2.9 for more information regarding HONI‘s distribution system protection practices and standards. As the HVI trips, the generators shall trip (LVI or equivalent) and the HVI should reclose back in within the first 30 seconds in the event of a successful reclose operation on HONI‘s feeder – The first DG facility connected to the feeder shall have the HVI reclose within 15 seconds of detecting voltage and frequency within normal limits (refer to Section 2 for details on operating characteristics of HONI‘s Distribution system). There may be a need to stagger multiple DG‘s DGITs energization to minimize the effects of inrush on HONI‘s distribution system and the resulting voltage sag and flicker (additional DG facilities shall be set between 15 seconds and 30 seconds). Refer to Section 3.2.21 for more information on reconnection to HONI‘s system following a momentary and sustained outage and Appendix C for timing diagrams. 57
  • 61. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.7 Breaker Fail (BF) * Breaker Fail may refer to a breaker, HVI, LVI or any fault interrupting device failing. Breaker Fail protection needs to be included in the DG facility‘s protection design for both the High Voltage Interrupter and Low Voltage Interrupter to ensure that a breaker/interrupter failure will not disrupt HONI‘s distribution system and/or the DG facility by ensuring that faults are cleared in a timely fashion. A means of automatic backup isolation is required to allow quick restoration of the distribution feeder. The breaker failure protection should have a maximum pickup time delay after initiation of 0.3s. 3.2.7.1 BF Protection for HVI The DG facility protections shall provide breaker failure protection and trip all LV breakers in the event of the HVI or primary interrupting device failing to isolate the DG facility from HONI‘s distribution system. The motorized disconnect switch (see requirements in Section 3.1.4) shall be opened by a separate auxiliary relay in the event of a breaker fail condition to ensure that the DG facility is properly isolated from HONI‘s system. In the case of a circuit switcher, the interrupter and the motorized disconnect shall be specifically chosen to operate independently. In normal operation, when the HVI isolates the facility, the motorized disconnect switch will follow, opening a short period afterwards. It can also be designed to open sequentially – motorized disconnect opens if HVI does not OPEN following a trip initiation. In the event of a breaker fail condition, the next zone at the DG facility will be tripped via the Low Voltage Interrupter in the facility (LVI) and by removing the prime mover and excitation system as appropriate. The motorized disconnect switch (at the PCC) shall be used to automatically isolate the DG facility from the distribution system. In the event that an alternate interrupting means (fuses or otherwise) is not provided by the DG facility or if such alternate interrupting means fail to coordinate with the opening of the motorized disconnect switch, then the disconnect 58
  • 62. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW switch may incur significant damage when attempting to interrupt a sustained fault current condition as it is not rated for breaking fault current. The design of the DG facility shall take this into consideration when deciding on a location for the Point of Disconnect to ensure that safety of the DG facility personnel, HONI‘s personnel and general public will be ensured. The design of the BF protection for the HVI shall be submitted to HONI for review and acceptance. 3.2.7.2 BF Protection for LVI In the event of the LVI malfunctioning, breaker fail protection is required to ensure that a fault in the DG facility is cleared and will not affect the high voltage system. Breaker fail should trip the HVI (and initiate BF on the HVI) to ensure that the DG facility is isolated from HONI‘s distribution system. For the DG facilities not equipped with an HVI, the motorized disconnect switch (Load Break Switch) shall be opened to isolate the DG facility from HONI‘s distribution system. In the event that an alternate interrupting means (fuses or otherwise) is not provided by the DG facility or if such alternate interrupting means fail to coordinate with the opening of the motorized disconnect switch, then the disconnect switch may incur significant damage when attempting to interrupt a sustained fault current condition. The DG Owner shall take steps to ensure that the DG facility, its equipment and personnel is protected. 3.2.8 Single Phase Generators Single phase generator requirements are summarized below in Table 5. Inverter type generators must be compliant with IEEE Std. 929 Recommended Practice for Utility Interface of PV Systems and be certified to UL 1741 and CSA 22.2-107.1. Figure 9 shows an example protection for single phase generators given for information purposes only. The protection system can be designed differently. The final design of the protection system shall be submitted to HONI for approval as described in Section 3.2.36. 59
  • 63. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Table 5: Typical Protections Required for Single Phase DG Facilities Protection Description IEEE Device # Interconnect Disconnect Device 89 Generator Disconnect Device Over-Voltage Trip 59 Under-Voltage Trip 27 Over Frequency Trip 81O Under Frequency Trip 81U Overcurrent** 50/51 Distance *** 21 Synchronizing Check* 25 Anti-Islanding Protection Refer to Section 3.2.15 Additional Protections May Be Required * Only required for synchronous generators and other types which have standalone capability ** Could be provided by magnetic circuit breaker or fuse *** Distance may be required to be able to detect faults along the entire length of the feeder Figure 9: Example Protection for a Single Phase Generator 60
  • 64. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9 Three Phase Generators Three phase generator typical protection requirements are summarized below in Table 6. Inverter type generators must be compliant with IEEE Std. 929 Recommended Practice for Utility Interface of PV Systems and be certified to UL 1741 and CSA 22.2-107.1. Section 3.2.9.1 through to Section 3.2.9.3 (Figure 10-12) shows example protections for three phase generators depending on the DGIT configuration chosen for DGs connecting to HONI‘s 3-Wire distribution system. Section 3.2.9.4 through to Section 3.2.9.6 (Figure 13-15) shows example protections for three phase generators depending on the DGIT configuration chosen for DGs connecting to HONI‘s 4-Wire distribution system. The protection systems can be designed differently and the examples shown in this document are for informational purposes only. Additional protections may be required. Generator protections are not the focus of this document and no requirements are set by HONI. It is up to the DG Owner to ensure that the generators are protected sufficiently. The final design of the protection system shall be submitted to HONI for approval as described in Section 3.2.36. DG Interface Transformer Configuration Requirements are located in Section 3.1.11. 61
  • 65. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Table 6: Typical Protections for Three Phase DGs Description Device HONI Anti- Synchro- DG Distribution Islanding nization Protection System Protection Protection X - Required O - Optional Transfer Trip Receive TTR* X* DGEO DGEO X* Over-Voltage Trip 59 X X X X Under-Voltage Trip 27 X X X X Over-Frequency Trip 81O X X X X Under-Frequency Trip 81U X X X X Overcurrent 51 X X Neutral Overcurrent 51N X X Voltage Controlled 51V O O Overcurrent Directional Overcurrent 67 O O Directional Neutral 67N O O Overcurrent Transformer Differential 87 O O Distance 21 O** O Ground Distance 21N O** O Ground Overvoltage 59N*** O O Reverse Power 32 O O O Negative Sequence 46 O O O Overcurrent Negative Sequence 47 O O O Voltage High Speed 59I*** O O Overvoltage Synchronization Check 25 X Loss of Excitation 40 O Interconnection 89 X X X Disconnect Device Generator Disconnect X Device * Transfer Trip and DGEO required where available generation is greater than 50% of minimum load, or where reclosure is less than 1 second, or if DG facility is rated at 1 MVA or higher – Refer to Section 3.2.16 ** May be required if complete feeder coverage cannot be guaranteed for entire length of feeder *** May be required if ferroresonance is expected 62
  • 66. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Delta:Wye DGIT Connecting to 3-Wire – Preferred 3.2.9.1 Figure 10: Preferred Connection for 3-Wire Distribution System 63
  • 67. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9.2 Wye-Gnd:Delta DGIT Connecting to 3-Wire - Alternate Figure 11: Alternate Connection for 3-Wire Distribution System 64
  • 68. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9.3 Wye-Gnd:Delta:Wye-Gnd Connecting to 3-Wire - Alternate Figure 12: Alternate Connection for 3-Wire Distribution System 65
  • 69. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9.4 Wye-Gnd:Delta DGIT Connecting to 4-Wire - Preferred Figure 13: Preferred Connection for 4-Wire Distribution System 66
  • 70. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9.5 Wye-Gnd:Delta:Wye-Gnd Connecting to 4-Wire - Alternate Figure 14: Alternate Connection for 4-Wire Distribution System 67
  • 71. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.9.6 Delta:Wye DGIT Connecting to 4-Wire - Alternate Figure 15: Alternate Connection for 4-Wire Distribution System 68
  • 72. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.10 Phase and Ground Fault Protection Requirement The DG facility‘s protection system must ensure that the DG facility will detect and automatically isolate itself from HONI‘s distribution system for:  Internal Faults within the DG facility  External Faults within HONI‘s distribution system – the DG must detect phase and ground faults along the entire distribution feeder that it is connected to – including single phase lateral taps 2 The DG‘s protections must be capable of detecting the following conditions at the DG facility and HONI‘s distribution system feeder which it is interconnected with:  Phase-to-Phase faults  Phase-to-Ground faults  Loss of any phase HONI will provide the DG Owner the maximum impedance fault that the DG facility is required to detect. The protective device selectivity and sensitivity have to be maintained over the full range of minimum to maximum fault currents (present and anticipated future levels) with the DGs infeed. The total clearing time for faults on HONI’s distribution system or for faults in the DG facility is to be no more than 500ms to coordinate with HONI’s reclosure time. The clearing time is measured from the start of the abnormal condition to the time that the DG facility ceases to energize HONI’s distribution system. DG facilities requiring an HVI due to the DGIT winding configuration must ensure that phase and ground fault protection are always operational as long as the HVI is closed – ground fault protection must be operational even if generators are out of service. This is to ensure that the DGIT and resulting ground source will be disconnected from HONI‘s system in the event of a fault and allow proper overcurrent coordination. 2 Must see entire feeder for phase and ground faults – past reclosers/sectionalizers/fuses 69
  • 73. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW A means of automatic backup isolation is required to cater for an HVI or LVI failure condition. The automatic backup isolation is required to allow quick restoration of the distribution system feeder following an HVI or LVI failure condition. The motorized disconnect switch at the PCC shall be used to automatically isolate the DG Facility from the distribution system. In the event that an alternate interrupting means (fuses or otherwise) is not provided by the DG Facility or if such alternate interrupting means fail to coordinate with the opening of the disconnect switch, then the disconnect switch may incur significant damage when attempting to interrupt a sustained fault current condition. All breaker fail protection designs shall be submitted to HONI for review and approval (See requirements in Section 3.2.7). All protective device settings and protection scheme designs must be submitted to HONI for review. Over time, as the system configuration changes, settings may be required to be changed to maintain adequate system protection. Design Consideration Standard overcurrent elements may not cover faults along the entire feeder and may not coordinate with HONI‘s protection systems. Distance (21) type protections may need to be considered. The settings for the distance elements shall be determined by the DG Owner with the information provided by HONI. The distance elements will be required to detect faults along the whole feeder after HONI‘s protections operate and HONI disconnects. It may be impossible for the DG protections to detect all faults over the whole feeder prior to HONI disconnecting due to the apparent impedance before HONI‘s protections trip. Due consideration must be given to apparent impedances due to other DGs connected to the feeder. 3.2.11 Unbalance Protection The DG facility is required to detect single phasing conditions (loss of phase) – Refer to Section 3.2.10. Design Consideration The design of the DG facility should consider using an unbalance or negative sequence relay that will trip the DG on excessive current unbalance, especially 70
  • 74. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW if the DG is installed on a section of HONI‘s distribution system that utilizes single phase tripping. 3.2.12 Feeder Relay Directioning Existing overcurrent protections in HONI‘s distribution system have been designed to clear phase and ground faults downstream of their location as HONI‘s substation has been the one source feeding the fault. With the addition of DGs to HONI‘s distribution system (additional sources), the fault contribution from these DGs may cause HONI‘s protections to operate non-selectively for reverse faults. Feeder relay overcurrent elements may trip for faults on adjacent feeders due to the infeed from DGs on the feeder. To prevent this sympathetic tripping, the relays may need to be directioned to be able to sense reverse fault current conditions. Inline reclosers may also need to be directioned to ensure that faults upstream of the reclosers will not cause the reclosers to operate due to the infeed from the DGs. In addition, communication facilities between the TS and recloser may be required as a result of DGs located downstream of the recloser to facilitate co- ordinated tripping and reclosing. The need to replace/update equipment on HONI‘s distribution system to enable directioning of feeder protections will be specified to the DG Owner in the CIA. 3.2.13 Over Frequency/Under Frequency Protection Over and under frequency protection is required at the PCC of the DG interconnection (see OESC rule 84-014, IEEE Std. 1547 Clause 4.2.4, CSA Std. C22.3 No.9-08). The DG facility interconnection protection scheme shall have the capability of detecting abnormal frequencies and clearing within the times shown below in Table 7. The DG facility must separate from HONI‘s distribution system if these frequency deviations occur within the clearing time. The clearing time is measured from the start of the abnormal condition to the time that the DG facility ceases to energize HONI‘s distribution system. These clearing times are maximum clearing times and may be required to be more stringent. This information will be provided by HONI. For generators > 30 kW, the frequency set points shall be field adjustable while for smaller generators, it may be fixed or field adjustable. 71
  • 75. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW For generators > 30 kW, the lower frequency set points shall be set to comply with the NorthEast Power Coordinating Council (NPCC), ―Directory D2‖, as seen below in Figure 16 – adjustable Lower Frequency set point shall be set to follow the attached graph. The DG may reconnect after the distribution system is stabilized and the requirements of this guide are met. For additional requirements related to reconnection to HONI‘s distribution system refer to Section 3.2.21. Table 7: Over/Under Frequency Protection Set Points and Clearing Times Generator Size Frequency Range (Hz) Clearing Times(s)* > 60.5 0.16 ≤ 30 kW < 59.3 0.16 > 60.5 0.16 < (59.8 – 57.0) - Adjustable – 0.166 > 30 kW adjustable to 300 < 57.0 0.16 * Generators ≤ 30kW – Maximum clearing time Source: IEEE 1547 * Generators > 30kW – Default clearing time Figure 16: NPCC Directory D2 Requirement 72
  • 76. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.14 Overvoltage/Undervoltage Protection Over and under voltage protection is required at the DG facility PCC (IEEE Std. 1547 Clause 4.2.3, DSC Appendix F.2 Section 6.5, CSA C22.3 No.9-08 Clause 7.4.7). The DG facility interconnection protection scheme shall have the capability of detecting abnormal voltages shown in Table 8 and disconnecting the DG facility from HONI‘s distribution system in the clearing times specified (voltage is to be measured phase-neutral for single phase installations or grounded Wye-Wye transformer configurations, otherwise phase-phase voltage shall be used). The voltages shall be detected at the PCC. The clearing time is measured from the start of the abnormal condition and the DG facility ceasing to energize HONI‘s distribution system. These are maximum clearing times and may be more stringent depending on the application. HONI will provide these clearing times if different from the table. For DGs > 30kW, the voltage set point shall be field adjustable and for smaller DGs, it can be fixed or field adjustable. Undervoltage relays should be time-delayed to avoid unnecessary tripping while over-voltage relays may be instantaneous. High speed instantaneous voltage protection may be considered for detecting ferroresonance and self-excitation conditions. Table 8: Over/Under Voltage Protection Setting and Clearing Time Voltage Range (% of base voltage) Clearing Time(s)* V < 50 0.16 50 ≤ V < 88 2.00 110 < V < 120 1.00 V ≥ 120 0.16 * DG ≤ 30 kW – Maximum clearing time Source: IEEE 1547 * DG > 30 kW – Normal clearing time The DG facility may reconnect after HONI‘s distribution system has stabilized and requirements for reconnection in this document are met (refer to Section 3.2.21). 73
  • 77. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.15 Anti-Islanding Protection An electric island is a section of the distribution system which, when disconnected from the rest of the HONI system, remains energized by DGs connected to the feeders. Anti-islanding protection is required to:  Ensure that HONI customers do not experience power quality problems  Prevent out-of-phase reclosing between HONI‘s distribution system and the DG facility  Reduce the risks of safety hazards caused by islanding  Add redundancy to other protections At the present time, HONI will not allow islanded operation. Upon loss of voltage in one or more phases of HONI‘s distribution system, the DG facility shall automatically disconnect from all of HONI‘s ungrounded conductors prior to reclosure. Reclosure times will be provided to the DG owner and are usually between 1.0s and 2.0s. Anti-islanding protection may involve different protection functions. Each DG interconnected to HONI‘s system, shall contain this protection and must demonstrate that the DG facility will not sustain an island longer than permitted. In certain installations, the installation of dedicated communications (transfer trip) and protection schemes may be required for anti-islanding protection and is discussed in Section 3.2.16. Appendix D has detailed information on Anti-Islanding Protection and discusses the different requirements for Transfer Trip. Please refer to this appendix for more information. Induction generators, due to the possibility of self-excitation, also have this requirement. The DG facility, instead of using transfer trip for anti-islanding protection may use an approved Hydro One Networks Anti-Islanding Protection Scheme. At present, there are tests being conducted and if and when any of these schemes is approved by HONI to meet anti-islanding protection requirements, they will be posted in this section in a future revision. To facilitate DG interconnections of 500kW and less, passive Anti-Islanding protections, specifically Rate of Change of Frequency and Vector Jump or Reverse Reactive Power, may be considered as an interim solution until an approved low- 74
  • 78. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW cost failsafe solution is finalized (ENERPULSAR pilot projects currently underway – pulse based anti-islanding protection) These special considerations for DGs less than 500kW have been made to enable these generators to connect with the associated risks of passive anti-islanding technologies without having to wait for an approved standardized solution. It is in the DG Owners interest to make certain that the anti-islanding protection is operational and will operate under all conditions with no non detection zone (NDZ) as the DG Owner will be responsible for the damage to the DG facility that can occur during out-of-phase reclosing. 3.2.16 Requirement for Transfer Trip A Transfer Trip (TT) signal from the upstream feeder breaker/recloser to the DG facility is required for any or all of the following conditions:  When the aggregate DG facility capacity is more than 50% of the minimum feeder load, or  When the aggregate generation capacity on the feeder is more than 50% of the minimum feeder load, or  When the aggregate DG facility capacity is 1 MVA or larger  If the existing reclosing interval time delay setting is short (dead time), typically less than 1.0s If any of the above requirements are met, then the DG facility shall cease to energize HONI‘s distribution system after receiving a transfer trip signal. The DG Facility is also responsible to make certain that upon transfer trip communication loss, the DG facility will trip within 500ms for ―wired communications3‖ and within 5 seconds for wireless communications. The interrupting device used to disconnect generation from HONI‘s distribution system must have maximum opening time of 85ms (time to open after receiving Transfer Trip signal from HONI). 3 Communications medium is wired, such as leased circuits, fibre, etc. 75
  • 79. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.16.1 Possible Exemption for DGs Smaller than 500kW To facilitate DG interconnections of 500kW and less, passive Anti- Islanding protections, specifically Rate of Change of Frequency and Vector Jump or Reverse Reactive Power, may be considered as an interim solution until an approved low-cost failsafe solution is finalized (ENERPULSAR pilot projects currently underway – pulse based anti- islanding protection) These special considerations for DGs less than 500kW have been made to enable these generators to connect with the associated risks of passive anti-islanding technologies without having to wait for an approved standardized solution. 3.2.17 DGEO (Distributed Generator End Open) Hydro One Networks requires a Distributed Generator End Open (DGEO) signal from the DG facility whenever transfer trip is required (see Section 3.2.16) to confirm that the generator end has opened. Hydro One uses the DGEO signal for the auto-reclose supervision of the TS feeder breaker or any upstream protective device. This is to ensure that the DG facility HVI/LVI has opened and there is no risk of out-of-phase reclosing. A combination of HVI and/or LVI status may be used to key the DGEO signal. At the DG end, the DG is required to provide the feeder protection with one signal that takes into account the Low Set Block Signal (Refer to Section 3.2.22 ―LSBS (Low Set Block Signal)) and the DGEO signal. This dual function signal will be set to ‗1‘ when the breaker is open and set to ‗0‘ 1s prior to the energization of the DGITs to allow temporary blocking of the upstream protections to avoid mis-operations due to large inrush currents. Timings for these signals and ―Design Considerations‖ can be found in Appendix E. 3.2.18 Unintentional Energization The DG facility shall not be capable to energize HONI‘s distribution system when the distribution system is de-energized. 76
  • 80. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Connection to Hydro One Network’s System 3.2.19 The DG facility connection is restricted only to the ―normal‖ supply configuration. The normal feeder supply configuration is considered to be when the feeder is supplied from one TS feeder breaker (the normal supply breaker) and all normally open line switches are open, as defined by Hydro One operating diagrams. The CIA will clearly identify the ―normal‖ feeder supply configuration that was studied and was determined to be acceptable for connection. Alternate (abnormal) supply configurations may be required from time-to-time to circumvent contingency situations (equipment failures, maintenance, upgrading and repairs). Under such circumstances the DG facility must be disconnected. Alternate feeder supply configurations are considered to be in effect when the feeder section to which the DG is connected is supplied from other than the ―normal‖ Hydro One TS feeder supply breaker or if any of the normally open feeder-end switches are closed extending the feeder, as shown on the operating diagrams. Although other supply configurations may be of concern, the expected most common alternate feeder supply configurations that will not facilitate DG connection are as follows:  Back-up supply of load customers from the adjacent TS feeder breaker (TS feeder tie switch closed)  Back-up supply of load customers from another TS  Extending supply to load customers connected to an isolated section of an adjacent feeder normally supplied from another source by closing a normally-open feeder-end switch Different conditions need to be met before reconnecting to HONI‘s system, depending if the outage is a momentary outage or sustained outage or shutdown. They are explained below. Automatic Reconnection of the DG facility to HONI‘s system is subject to specific requirements which can be found in Section 3.2.21 and Section 3.2.23. 3.2.20 Disconnection of DG facilities The following steps need to be taken to disconnect the DG facility from HONI‘s distribution system during abnormal conditions or upon the receipt of a TT signal. 77
  • 81. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.20.1 Disconnecting DG Generation For the first occurrence of a fault on any portion of the faulted feeder, Hydro One high-speed sensitive ―low set‖ protection should operate to isolate the Hydro One supply from the fault. The DG generation must also be disconnected without delay to disconnect the DG supply from the fault, to ensure fault extinction, to avoid any sustained DG island condition and to avoid interference with normal Hydro One supply restoration using automatic reclosure. Disconnection of DG generation will be accomplished by TT and/or DG interface protection as outlined in Section 3.2. The DG generation will be disconnected using the same LV devices that were used to synchronize the generation to the Distribution System (or by opening the HVI if the LV devices fail to disconnect). Wherever HV ground sources are present, additional steps listed in Section 3.2.20.2 are required. 3.2.20.2 Disconnecting DG HV Ground Sources As per Section 3.1.11 above, any DG connections that have a HV ground source and a HVI must ensure that the ground sources will be disconnected whenever TT is received or DG Interface protection operates, as outlined in Section 3.2 above, by opening the HVI. 3.2.21 Reconnection of DG Facility The DG facility cannot operate connected to any part of the Distribution System in island mode. The DG cannot reconnect until the Distribution System feeder has been successfully energized from the normal Hydro One source. 3.2.21.1 Reconnection of Hydro One Source (for a transient fault4) This is not a requirement, however it outlines what must take place before the DG can reconnect. Refer to Appendix F for a detailed sequence of events and timing diagram. Following the first protection operation, the Hydro One feeder breaker or recloser will be automatically reclosed to quickly restore supply to load 4 Generally associated with a momentary outage - loss of supply is less than 15 minute 78
  • 82. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW customers. Typical reclosing times are 0.5 to 1 second for feeder breakers and 1.5 to 2 seconds for reclosers. The Hydro One low-set instantaneous (fuse-saving) protections are always blocked when the feeder is re-energized. Blocking the low-set protections prevents an immediate re-trip caused by high energization current associated with transformer inrush and cold-load effects. Only the Hydro One high-set and time-coordinated protections are available at the time of Hydro One reconnection. The high-set and timed protections are coordinated with feeder reclosers and fuses to provide selective isolation of faults on the feeder. Should a fault be established at the time of feeder energization, these protections will operate as required to isolate only those sections of the feeder required to clear the fault, allowing service to be restored to the un-faulted sections. Approximately 10 seconds after a successful automatic reclose operation, all Hydro One feeder protections should be restored to their normal state (complete with the low-set protections enabled). 3.2.21.2 DG Facility Reconnection Reconnection to Hydro One Networks distribution system is a two step process as outlined below for DG Facilities equipped with a required HVI5 DG facilities not requiring a HVI only need to follow Step 2. Step 1 and Step 2 can occur simultaneously if the DG has facilities for synchronizing the generation via the HVI. Step 1: DGIT Re-Energization For DG Facilities not requiring a HVI, this step can be ignored. Where a DG HVI was used to disconnect the DGIT, and the HVI is not used for synchronizing generation, the first step in reconnecting the DG is to close the HVI. However the DGIT must not be re-connected until after the feeder has been successfully re-energized from Hydro One source and the Hydro One feeder protections have been restored to their normal state (10 seconds there-after). To ensure this, the DG HVI can be allowed to automatically reclose only after voltage and frequency 5 Provision of an HVI is dependent on DG Interface Transformer winding configuration – Refer to Section 3.1.11. 79
  • 83. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW are restored within normal limits for a period of 15 seconds (refer to Section 2 for details on operating characteristics of HONI‘s Distribution system). Note: feeder reclosers may have multiple reclose attempts to allow sectionalizers to operate to clear the fault. The 15 second restoration period begins after the final successful reclose. Therefore, restoration time delay should reset every time the feeder is de- energized. For DGIT with large transformer in-rush current, the sensitive Hydro One low-set instantaneous protection may need to be temporarily blocked to prevent re-tripping of the feeder when re-energizing the DGIT. In those cases, just prior to re-energizing the DGIT, the DG facility will need to alter the DGEO signal momentarily to provide a signal to the Hydro One location that the low-set protection needs to be blocked. (Refer to Section 3.2.22 for LSBS requirement). There may also be a need to stagger the re-energization of multiple DGITs, to minimize the effects of inrush on HONI‘s distribution system and the resulting voltage sag and flicker. The HVI closing delay can be set between 15 seconds and 30 seconds – HONI to coordinate the staggered timing. The generators shall stay disconnected during this time. Step 2: Generator Reconnection Following a disturbance to HONI‘s distribution system, no reconnection may take place until HONI‘s system voltage is within 6% of nominal and the frequency is between 59.5Hz and 60.5Hz. The generation facility‘s interconnection system must include an adjustable delay that may delay the reconnection for 5 minutes after Hydro One‘s steady state voltage and frequency are restored to the normal operating ranges identified above, following a momentary outage. The reconnection of multiple DG units on a feeder may require being staggered. 80
  • 84. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Reconnecting generation is most typically done using LV synchronizing facilities. If synchronization occurs via the HVI, Step 1 and Step 2 occur simultaneously. For DG facilities not equipped with a HVI, there may be a requirement to send out a Low Set Block Signal prior to closing of the disconnect switch to energize the DGIT. Refer to Section 3.2.22 for LSBS requirements. Automatic reconnection is not allowed for outages longer than 15 minutes. HONI‘s operators must give permission before reconnection occurs. ―Auto- Additional requirements listed in Section 3.2.23 Resynchronization/Reconnection‖ need to be met for this automatic reconnection following a momentary outage to occur. 3.2.21.3 Lock-Out of Hydro One Source (For a Permanent Fault) This section outlines what occurs on HONI‘s distribution system during a permanent fault condition. Refer to Appendix F for a detailed sequence of events and timing diagram. If a fault re-occurs after a reclose attempt, the affected section of HONI‘s distribution system shall be tripped again. Automatic reclosure will then be inhibited and Hydro One supply will have to be manually restored. Some protective devices have as many as four reclose attempts before reclosing is locked out. Manual restoration of the feeder will be attempted by the Hydro One controlling authority. That may occur within a few minutes where remote control is available. If a remote-controlled manual restoration attempt is successful, and within 15 minutes of the loss of supply, then DG reconnection can proceed as per Section 3.2.21.2 above. Otherwise a sustained outage or shut-down will be necessary (greater than 15 minutes). 81
  • 85. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.21.4 Restoration Following a Sustained Outage or Shutdown No automatic reconnection of the DG facility may occur following a sustained outage or shutdown – when the voltage and/or frequency out of normal operating range on any phase for more than 15 minutes. Permission to reconnect must be given by HONI‘s operators. 3.2.22 LSBS (Low Set Block Signal) To ensure that the energization of the DG Interconnection Transformer following a sustained outage or shutdown does not cause the Low Set Instantaneous protections at HONI‘s feeder breaker to operate, a Low Set Block Signal (LSBS) needs to be sent to HONI‘s feeder protections. At the DG end, the DG is required to provide the feeder protection with one signal that takes into account the Low Set Block Signal (Refer to Section 3.2.22 ―LSBS (Low Set Block Signal)) and the DGEO signal. This dual function signal will be set to ‗1‘ when the breaker is open and set to ‗0‘ 1s prior to the mechanical closing of the HVI, or motorized disconnect switch, such that the feeder protection can recognize the change of status and block the low-set instantaneous prior to the energization of the DG Interface Transformer. Timings for these signals and ―Design Considerations‖ can be found in Appendix E. This is a requirement wherever Transfer Trip and DGEO are required. 3.2.23 Auto-Resynchronization/Reconnection Following a disturbance on HONI‘s distribution system, no reconnection may take place until HONI‘s distribution system voltage and frequency are in the ranges allowed in Section 3.1.5 and 3.1.7 respectively. Auto-resynchronization/reconnection may occur if agreed by HONI for momentary outages (distribution system voltage and frequency out of range for less than 15 minutes). The DG facilities interconnection system must include an adjustable delay (from 5 minutes to 60 minutes after HONI‘s distribution system stabilizes) that may delay the reconnection to HONI‘s system. HONI may coordinate the restart time settings of DGs on the feeder in order to stagger the restarts and minimize the effects of inrush to HONI‘s customers from the DG facilities upon 82
  • 86. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW energization. Refer to Section 3.2.21 for more information on the steps required to automatically reconnect to HONI‘s distribution system. Appendix F contains detailed sequence of events and timing diagrams for informational and design consideration purposes. HONI requires to have the ability to prevent auto-resynchronization/reconnection if operating deems necessary. Auto-resynchronization/reconnection shall be locked out once voltage and frequency are not within operating ranges for a period of 15 minutes on any phase. No automatic reconnection to HONI‘s distribution system will be allowed unless:  There is always customer contact with the ability to immediately disconnect from the system if requested by HONI (24 hours/7 days per week, or  HONI has the ability to remotely disconnect and lockout the DG customer from the system, and  Feeder relay studies must be updated if circuit configuration is materially altered. If the source changes from the configuration studied in the CIA, the generator will not be allowed to reconnect. 3.2.24 Synchronization Protection Any DG facility that is capable of generating its own voltage while disconnected from HONI‘s distribution system shall require proper synchronization facilities before connection is permitted. Interconnection shall be prevented if the DG and HONI‘s distribution system is operating outside the limits specified in Section 3.1.19. 3.2.25 Telemetry and Targeting The DG facilities protection schemes shall have systems in place to record and provide upon request to HONI an electronic record of protective device operations, or failures to operate. Refer to Section 3.3.4 for additional requirements. 83
  • 87. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.26 Transformer Protection Design Consideration Zero sequence currents circulating in the delta of a Wye-Delta transformer during certain load and fault conditions are inevitable and if sustained, may cause damage to the transformer. The design of the DG facility may require transformer protection to prevent damage due to this phenomenon. 3.2.27 Protection from Electromagnetic Interference (EMI) The DG interconnection system must have the capability to withstand electromagnetic interference (EMI) environments in accordance with ANSI/IEEE Std. C37.90.2, ―IEEE Standard for Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceivers.‖ The influence of EMI must not result in a change in state or misoperation of the DG facility – EMI must not result in failure, misoperation or provide inaccurate information from the protection, control and communication functions of the interconnection system. The DG Owner shall provide documentation of compliance. 3.2.28 Surge Withstand Performance The interconnection system must have the capability to withstand voltage and current surges in accordance with the environments defined in IEEE/ANSI Std. C62.41.2, ―IEEE Recommended Practice on Characterization of Surges in Low- Voltage (1000 V and Less) AC Power Circuits‖ or IEEE Std. C37.90.1, ―IEEE Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electric Power Apparatus – Description.‖ The protection, control and communication equipment of the interconnection system shall not fail, misoperate, or provide misinformation due to voltage or current surges. CSA Std. C22.3 No.9-08, ―Interconnection of Distributed Resources and Electricity Supply Systems,‖ provides more detailed information. 3.2.29 Special Interconnection Protection Other protection not specified in this requirements document may be required depending on the application. The DG Owner needs to be aware of site specific 84
  • 88. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW conditions and the nature of HONI‘s distribution system to properly assess the need for additional protections. 3.2.30 Batteries/DC Supply The DG facility requires a reliable power supply for its protections to function. Batteries shall be provided and shall have adequate capacity to ensure that all protection functions operate when the main source of power fails. They shall remain operational for the time required for protection functions to operate properly and disconnect the DG facility from HONI‘s distribution system. This source can be achieved by using batteries and chargers connected to the main service supply or by using an uninterruptable power supply with sufficient capacity for the application. The battery voltage shall be monitored and upon failure, the protection scheme shall be considered failed and DG facility shall be disconnected from HONI‘s distribution system. The following design criteria shall be considered:  The relays connected to the DC supply must not be subjected to sustained overvoltages – if there is a possibility that the DC rating of the equipment will be exceeded, steps shall be taken to ensure that DC voltage limiting devices be installed at each relay  Dual station batteries will not be required for protection and control equipment.  Protection systems designed to back each other up, will be supplied by physically separated and protected DC supplies.  Circuit breakers and HVI‘s shall be powered by separate and dedicated DC supplies.  Separate and independent means are to be used for tripping the HVI and motorized disconnect.  Upon low voltage condition, the protections shall trip the generators and open the HVI. Capacitors shall not be used as the primary means to store energy in lieu of batteries. 85
  • 89. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.31 Protection Scheme Failure The DG facility must promptly disconnect (without delay) from HONI‘s distribution system and notify HONI‘s system operators if the interconnection protection system fails, breaker trip coil fails or if DC supply is lost. The breaker(s) must remain open until such a time when the affected system is returned to normal service condition and the DG facility is safe for reconnection to HONI‘s system. The DG Owner shall provide evidence to HONI that the design of the DG facility is sufficient to mitigate the risks associated with protection scheme failure by using self-diagnostic features (available with IEDs), redundancy or a fail-safe design. The availability (health) of the TT and DGEO signals, the DG self-clearing protection, the DG breaker and the associated power supplies must be continuously monitored by the DG and all DG sources of energy to the distribution system must be immediately disconnected or disabled if any facilities fail or become disabled. The design of the protections at the DG facility shall be done by a qualified professional engineer to ensure that the overall protection scheme will ensure a safe and reliable interconnection to HONI‘s distribution system. Malfunctioning, self-diagnosing relays, shall notify operating personnel, and if no redundancies are in place, shall disconnect the DG facility from HONI‘s distribution system until the malfunction has been repaired. In designs where self diagnostic features do not trip the appropriate breakers upon failure, sufficient backup and/or redundancy protections shall be provided. If electro-mechanical relays are used, the protection and control design shall be of a fail-safe nature to ensure the integrity of the protection scheme under malfunctioning conditions. 3.2.32 Teleprotection Scheme Failure 3.2.32.1 Transfer Trip Channel Failure In the event of the transfer trip communication channel failing, the DG facility shall disconnect from HONI‘s system within 500ms for wired communications, such as fibre and leased circuits, and within 5s for wireless communications. The DG facility protection design shall ensure 86
  • 90. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW that the teleprotection system is failsafe and that upon loss of transfer trip, it will automatically trip the facility. The DG facility shall remain disconnected until the transfer trip channel is repaired. 3.2.32.2 DGEO Channel Failure In the event that the DGEO (refer to Section 3.2.17) communication channel fails, HONI will block its feeder reclosing until the channel is repaired. To maintain the reliability of the system for HONI‘s customers, HONI reserves the right to send transfer trip to the DG and trip the DG in order to allow automatic reclosing on its feeders. The DG Owner shall ensure that repairs are conducted as quickly as possible. 3.2.33 Generators Paralleling for 6 Cycles or Less (Closed Transition Switching) DG facilities paralleling for 6 cycles or less shall have the following protections:  Under-voltage protection to ensure that the generator is not capable of energizing HONI system if it is de-energized  A 6 cycle timer to ensure that the DG will not parallel with HONI‘s distribution system for more than 6 cycles.  Synchronization facilities, where required, must follow the requirements specified in Section 3.1.19 The generator will be exempt from all other requirements of this document. 3.2.34 Instrument Transformers for use in Protection Systems All instrument transformers used in DG facilities for protections shall meet the requirements of IEEE C57.13 or CSA-C60044-6. 3.2.35 Provision for Future Changes The DG Owner shall be responsible to stay aware of future changes to the business environment and technical requirements and make any necessary changes to its facilities. If HONI advises the DG Owner of required changes, the DG Owner will make changes to the DG facility. The DG Owner is responsible for 87
  • 91. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW making any changes to the DG facilities in response to meeting new or revised standards or due to HONI distribution system changes. Therefore it should make any provisions to accommodate changes efficiently. The DG Owner may be responsible for the costs associated with these changes, including changes that originated at HONI‘s request. 3.2.36 Interconnection Protection Acceptance The DG Owner must provide Hydro One Networks Inc. with complete documentation on the proposed interconnection protection scheme with:  a detailed Single Line Diagram  overall description on how the protection will function including during failure modes  details on protection components such as manufacturer and model #  the protection component settings (pickup, timers, etc.)  details on monitoring for the protection system and recording protection operations/misoperations  details on the disconnecting and interrupting device This information will be reviewed by HONI against the requirements of this document and all applicable standards for the potential impacts to HONI‘s distribution system. If HONI proposes any changes, the DG Owner must revise and re-submit the protection information to HONI. All documentation must be submitted together. The latest submissions will be filed by HONI and MUST MATCH the documentation retained by the DG Owner. 88
  • 92. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.2.37 Protection Summary This document discusses the common protection required for DG interconnection to HONI‘s distribution system. The minimum required interconnection protections are:  Over-Voltage  Under-Voltage  Over-frequency  Under-frequency  Overcurrent/Distance protection  Anti-Islanding Protection Other protections may be required depending on the application. All protection designs must ensure proper coordination with HONI‘s protections, be failsafe and ensure that both the DG and HONI‘s distribution system, customers and general public safety are maintained. 89
  • 93. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.3 Control and Telecommunications Requirements 3.3.1 General Control and telecommunications facilities will be required at customer facilities connected to the Hydro One transmission and distribution system for provision of protection and real time operating data. The Customer shall provide battery backup for telemetry in the event that the facility is removed from the HONI transmission or distribution system. Battery backup capacity shall be sufficient for the connection to be re-established. Alternatives to battery backup are subject to approval by HONI. Under the TSC6, DSC and terms of this document, owners of generating stations connected to HONI‘s transmission and distribution facilities have an obligation to provide real time data pertaining to their equipment as required by the capacity at the PCC. Monitoring and control may be required as a result of Renewable Energy Supply Integration initiatives regardless of the capacity as will be determined by HONI. Installation capacity descriptions shall be consistent with the class definitions of IEEE 1547.3 which has been included here in Table 9 for convenience. Table 9: DG Classification Class Generation Capacity at PCC 1 0 kW < DG rating < 250 kW 250 kW ≤ DG rating < 1500 kW 2 1.5 MW ≤ DG rating ≤ 10 MW 3 4 10 MW < DG rating These requirements for real time operating information apply to all customer- owned generating stations connected to HONI‘s transmission or distribution network. The quantities and device statuses, defined below, shall be provisioned, monitored and controlled for continuous transmission to HONI. Such details are to be captured in Schedule I of the Customer‘s TCA, or an appendix in the DCA as required by HONI and the applicable codes. 6 TSC Appendix 1, Schedule E, Section 1.6 90
  • 94. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.3.2 Control Facilities Subject to the agreement between the customer and Hydro One, all or some of the following remote controls shall be provided to Hydro One: (i) Station breakers and switchers (ii) Motorized disconnect switches Transformers‘ ULTC (iii) (iv) 3% and 5% voltage reduction (v) Hold off on feeder breakers (vi) Dynamic generator output control (vii) Other location specific devices At any time, one and only one operating authority shall have remote control of the station. Where the customer maintains an operating centre and control of the station is handed off from the customer to Hydro One at scheduled times, Hydro One will consider the use of an ICCP link between the two control centres. 3.3.3 Telecommunication Facilities Customers can provide real time operating information to HONI directly from the station(s) or from the customer‘s SCADA master, as described below. The customer shall provide the GPS coordinates of the facility to assist in the evaluation of wireless communication alternatives. The customer will provide all the required hardware and software and make arrangements, as needed, with a commercial provider of communication services to deliver the operating data to the demarcation point. Each DG Owner will be responsible for all costs, initial and ongoing, and maintenance of their equipment and communication circuits up to the demarcation point. From the IED at the customer‘s station to HONI‘s control centre using (a) serial DNP 3.0 protocol as follows: 91
  • 95. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW to HONI‘s wireless cellular data hub site and through the gateway to (i) HONI‘s control centre, with the demarcation point being inside HONI‘s hub site. where (i) is not feasible, to HONI‘s communication hub site and (ii) through the gateway to HONI‘s control centre, with the demarcation point being inside HONI‘s hub site (iii) where (i) and (ii) are not feasible, to a HONI HV station and through the RTU or gateway to HONI‘s control centre, with the demarcation point being inside HONI‘s station (iv) where (i) through (iii) are not feasible, through a Frame Relay Network of a common carrier to HONI‘s control centre, with the demarcation point being the CO nearest to the customer‘s station (v) where (i) through (iv) are not feasible, HONI will suggest communication circuit options available for a particular site. Where modems will be used in any of the above communication methods, HONI will determine the modem type and requirements considering communication media, site location, reliability, and amount of data transfer. From a SCADA master through a Frame Relay Network to HONI‘s SCADA (b) master using ICCP. The communication demarcation point will be the CO of a common carrier. 3.3.3.1 Reliability Requirements The delivery of the real time data at the communication demarcation point shall have unplanned failure rates and repair times as described in the table below: Table 10: Unplanned Telecommunication Failure Rates and Repair Times Mean Time Mean Time Failure to Failure to Repair Failure to deliver data from a 4 years 24 hours single station Simultaneous failure to deliver 5 years 4 hours data from 2 to 5 stations Simultaneous failure to deliver data from more than 5 20 years 4 hours stations 92
  • 96. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Prior to connection to HONI facilities, the customer shall submit a reliability evaluation report which demonstrates that the above reliability requirements can be satisfied. The customer must coordinate any planned interruption to the delivery of real time data with Hydro One. 3.3.4 Operating Data, Telemetry and Monitoring In addition to the requirements in the sections of the TSC listed below, the following additional requirements apply: Real-time data to be provided to HONI by the customer: 3.3.4.1 Class 1 Generators Generating facilities with a capacity of less than 250KW shall have provision for monitoring the disconnecting device at the PCC. Provisions for other quantities may be required and shall be determined by HONI. 3.3.4.2 Class 2 Generators Generating facilities with a capacity of greater than or equal to 250KW but less than 1500KW shall provide the following information: A) Analogue Quantities (a) Net active power (MW) output and reactive power (MVAR) flow and direction for each unit or total for the facility (b) Phase to phase or phase to neutral voltages (c) Three phase currents B) Device Statuses (a) All LV breakers/circuit switchers at the PCC 93
  • 97. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW (b) AVRs and PSSs that impact the distribution system (c) All generation rejection selections C) Alarms Provision shall be made for an alarm signal to be generated and transmitted to HONI for transfer trip/DG end open (DGEO), loss of communication (protection schemes) and loss of customer owned interface protection (failed and disabled). A separate alarm must be provided for each circuit supplying the customer. The alarms shall identify the name of the customer facility and the designation of the affected circuit. HONI shall determine requirements based on controlling authority and equipment ownership. Monitoring and control may be required as a result of Renewable Energy Supply Integration initiatives regardless of the capacity as will be determined by HONI 3.3.4.3 Class 3 Generators Generating facilities with a capacity of greater than or equal to 1500KW but less than 10MW shall provide the following information: A) Analogue Quantities (a) Net active power (MW) output and reactive power (MVAR) flow and direction for each unit or total for the facility (b) Phase to phase or phase to neutral voltages (c) Three phase currents B) Device Statuses (a) All LV breakers/circuit switchers at the PCC (b) AVRs and PSSs that impact the distribution system (c) All generation rejection selections C) Alarms 94
  • 98. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Provision shall be made for an alarm signal to be generated and transmitted to HONI for transfer trip/DG end open (DGEO), loss of communication (protection schemes) and loss of customer owned interface protection (failed and disabled). A separate alarm must be provided for each circuit supplying the customer. The alarms shall identify the name of the customer facility and the designation of the affected circuit. HONI shall determine requirements based on controlling authority and equipment ownership. Monitoring and control may be required as a result of Renewable Energy Supply Integration initiatives regardless of the capacity as will be determined by HONI 3.3.4.4 Class 4 Generators Generating facilities with a capacity of greater than 10MW shall provide the same data as identified for Class 3 generators. 3.3.4.5 Telemetry Reporting Rates Table 11 states the minimum requirements for telemetry reporting rates for DGs (Class 1, Class 2, Class 3, and Class 4) interconnecting to HONI‘s distribution system. Table 11: Telemetry Reporting Rates Function Performance Data measurements less than 10 s from change in field monitored quantity Equipment status change less than 10 s from field status change Data skew not applicable Scan period for data Minimum 4 s (1) measurements Scan period for equipment Minimum 4 s (1) status 95
  • 99. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 3.3.5 Monitoring Reporting HV Connected and Class 3 & 4 Facilities Adverse situations involving the operation of the transmission or distribution system, such as false trips or misoperations must be reported to the appropriate Controlling Authority and regulatory authorities. It is expected that any protection operation involving the customer facility will be fully documented along with appropriate records from monitoring devices and provided to HONI immediately following any such operation. Any transmission or distribution connection facility owner must comply with requests for sequence of events records (SER) or digital fault records as requested by HONI or any controlling authority such as the IESO or NPCC within 30 days of request. Waveforms and event data supplied to HONI must be in COMTRADE format. Customer owned stations shall analyze all protection system misoperations in order to take corrective actions to avoid future misoperations. For further requirements, please refer to Section 8. 3.4 Performance Requirements 3.4.1 Power Quality The DG facility must not negatively impact the power quality of Hydro One‘s Distribution System. If the DG facility is found to cause problems and impact the power quality of the system, they may be required to disconnect from HONI‘s system until such a time when appropriate measures have been taken to mitigate the adverse effects that the DG facility has been causing. IEEE Std. 519 should be consulted to determine industry standards for power quality along with the requirements in this document. HONI requires Class 2, Class 3 and Class 4 DG installations (DG facilities greater than 250 kVA) to be equipped with power quality meters that will monitor continuously (and maintain logs) to ensure that power quality is maintained while 96
  • 100. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW the DG is on-line and off-line, and in steady and dynamic states. This power quality device is to be capable of high speed sampling to capture parameters such as voltage, current and harmonics and measures shall be taken to ensure the device is time synchronized. The DG Owner is required to install and commission this at its own expense and shall allow HONI access to such PQ data as required. This will allow HONI and the DG owner to assess the condition of the power output of the DG facility. 3.4.1.1 Voltage Fluctuations (Flicker) The DG facility must not create objectionable flicker for other customers on Hydro One‘s system. The voltage dip at the PCC should not be more than 4% on connecting the single largest generation unit in the facility and should remain within 10% of nominal voltage when the entire facility trips. The DG Owner shall take steps to make sure that flicker requirements are met – may need to add loss of synchronism protection, stagger generator energization, etc. Indicative values of planning levels for P st and Plt in HONI‘s distribution system are shown in the table below. These limits are from IEC 61000-3-7, and the standard should be consulted for more details. These values should be measured by an approved flicker-meter that conforms to CAN/SCA-C610004-15. Table 12: Pst and Plt Flicker Limits 44kV 27.6/25/13.8/12/8/4 kV Pst 0.8 0.9 Plt 0.6 0.7 3.4.1.2 Voltage and Current Harmonics The DG facility shall not inject harmonic current that causes unacceptable voltage distortion on HONI‘s distribution system. The DG facility shall follow the requirements of IEEE Std. 1547 and CSA 22.2 No. 107.1 for maximum harmonic current distortion, also shown below in Table 12, and ensure that the facility is operating within these limits. The DG Owner 97
  • 101. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW and/or HONI may be required to implement measures that will mitigate the harmonic distortions such as by adding harmonic filters, at the DG Owners cost. The CSA standard excludes harmonic currents that are due to harmonic voltage distortions present on HONI‘s distribution system when the DG facility is not connected. Inverters certified to this standard will be considered to meet these requirements. This document does not impose design limits to limit harmonic-caused telephone interference problems as it is almost impossible to predict. However, the DG Owner may want to make sure that the design complies with all applicable standards and will not cause telephone interference. Table 13: Current Harmonic Limits Individual 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 35 ≤ h harmonic h < 11 THD order, h Distortion, percentage 4.0 2.0 1.5 0.6 0.3 5.0 of current†‡ † The current is the greater of the distribution system maximum current integrated demand (15 or 30 minutes) without the DG facility or the DG facility rated current capacity, transformed to the PCC when a transformer exists between the generators and the PCC. ‡ The maximum distortion presented in this table is for odd harmonics. Even harmonics are 25% of the odd harmonics presented above. 3.4.1.3 Voltage and Current Unbalance The DG facility shall be capable of operating under existing conditions and shall not cause deterioration of existing unbalance voltage and current conditions. 3.4.1.4 Limitation of DC Injection 98
  • 102. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW The DC current injection by the DG facility shall not be greater than 0.5% of the full rated output current at the PCC after a period of six cycles following the energization of Hydro One‘s distribution system. 3.4.2 Disturbances The DG facility shall be designed, built and maintained to all applicable codes, regulations and standards, along with the requirements of this document and shall minimize the impact of:  Overvoltages during ground faults  Electric disturbances which can cause irregular power flows  Interference – radio, television and telephone  Audible noise  Other disturbances which may reduce the reliability of HONI‘s distribution system 3.4.3 Generator 3.4.3.1 Reactive Power Requirements The generator‘s system shall operate in the preferred range of 0.9 lag to 0.95 lead. Hydro One Connection Impact Assessments will assess the impact of the generator over the specified range of power factors. For certain Distribution System loading conditions, Hydro One may require the generator to restrict reactive power within a specified range or to operate at a specific power factor level to maintain Distribution System voltage levels within the required ±6%. Field settable fixed and dynamic power factor correction techniques may be used if consultation with Hydro One reveals no adverse affect on the distribution system. 99
  • 103. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW For generators that are IESO impactive, the reactive power compensation at the generating units should be sufficient so as not to cause any material increase in the reactive power requirements at the transmission system transformer station due to operation of the units, at any distribution feeder load conditions. 3.4.3.2 Speed Governors Speed governors control the dynamic machine speed at all times and controls machine active power when the generator is connected to the distribution system. Speed governors are required to control generator speed for synchronization purposes as outlined in Section 3.1.19. Speed governors are required to maintain acceptable power quality as per Section 2.6. Speed governors / generator active power also impacts Distribution System voltage profiles that are affected by both active and reactive power flows along the Distribution System feeders. Speed governors are expected to limit generator active power to the name plate capacity as submitted to Hydro One for the Connection Impact Assessment. Hydro One Connection Impact Assessments will assess the impact of the generator over that range of active power. For certain Distribution System loading conditions, speed governors may be required to limit active power to specific levels as required by Hydro One to maintain Distribution System voltage levels within the required ±6%. Speed governors may also be required to limit active power to specific levels to ensure self-clearing anti-islanding protections remain effective for certain Distribution System loading conditions (generator power output must not exceed 50% of potential minimum islanded load if Transfer Trip is not available). 100
  • 104. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Speed governor response also impact generator stability during power system disturbances and their action needs to be considered in any system stability studies that may be necessary for high impedance generator connections. Large generators (greater than 10 MVA) may have additional excitation equipment requirements as specified by the IESO At any time Hydro One may determine and require other specific speed governor control or performance that is necessary to maintain acceptable Distribution System conditions. 3.4.3.3 Excitation Equipment Excitation equipment controls generator terminal voltage at all times and controls generator reactive power when the generator is connected. Excitation equipment is required to control generator terminal voltage and PCC voltage for synchronization purposes as outlined in Section 3.1.19. Excitation equipment is also required to maintain acceptable power quality as per Section 2.6. Excitation equipment / generator reactive power also impacts Distribution System voltage profiles that are affected by both active and reactive power flows along the Distribution System feeders. Generally, the DG facility should not actively regulate the voltage at the PCC (as per IEEE Standard 1547-2003), when the generator is connected. Otherwise uncoordinated voltage control (such as hunting) could result and cause excessive tap-changer and regulator operations and/or unnecessary fluctuations in Distribution System voltage. If necessary, Hydro One may specify some limited voltage regulation to maintain Distribution System voltage levels within the required ±6% and/or acceptable Power Quality. 101
  • 105. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Excitation equipment is expected to limit generator reactive power to the name plate capacity as submitted to Hydro One for the Connection Impact Assessment. Excitation equipment is required to maintain power factor within a specific range or limits as specified in Section 3.4.3.1. For certain Distribution System loading conditions, Hydro One may require the generator to restrict reactive power within a specified range or to operate at a specific power factor level to maintain Distribution System voltage levels within the required ±6%. Excitation equipment can impact generator stability during power system disturbances. Their action needs to be considered in any system stability studies that may be necessary for high impedance generator connections. Specific excitation equipment features and adjustments may be required to help maintain generator stability during power system disturbances to avoid loss of synchronism, particularly for synchronous generators. Large generators (greater than 10 MVA) may have additional excitation equipment requirements as specified by the IESO At any time Hydro One may determine and require other specific excitation equipment control or performance that is necessary to maintain acceptable Distribution System conditions. 102
  • 106. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 4 Metering Requirements Metering shall be in accordance with Hydro One Networks NOP 041 document ―Policy – Distribution – Metering for Embedded Generators.‖ A copy of this document can be found in Appendix H near the end of this document. 5 Connection Process Requirements The Connection Process is outlined in the Ontario Energy Board Distribution System Code Appendix F1 (reference 1). For a complete description of that process consult the OEB website http://www.oeb.gov.on.ca/OEB/. The following describes the final steps of the connection process (after completion of the initial steps: initial contact, provision of information, generator develops plan, initial consultation, application for impact assessment, Impact Assessment, Decision to Proceed and Establish Scope of Project, Prepare Estimate and Present Offer to Connect). 5.1 Implementation Implementations must proceed in accordance with the Ontario Energy Board Distribution System Code Appendix F1 (reference 1). This involves the following: Both parties commit to project and Generator commits to obtain required approvals. The Generator:  prepares detailed engineering drawings;  submits all detailed plans to ESA for Plan Approval process (including detailed single line diagram, interface protection); and  submits information to Hydro One for design review (including detailed single line diagram, interface protection and metering details)  is recommended to provide this information to Hydro One within 30 days of signing CCA so that design review can be done in a timely manner. 103
  • 107. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Hydro One performs design review to ensure detailed engineering is acceptable. The following is information is provided to the Generator:  the Interface protection design review;  Hydro One reviews detailed single line diagram and interface protection to ensure acceptability; and  Recommend that this review be complete before equipment purchase. Once Generator receives interface protection design review from Hydro One, then:  Generator tenders and awards contracts for equipment;  Builds - including ESA and other approvals;  Connection work; and  Line/equipment upgrades are completed. Generator constructs facility and applies for ESA Electrical Inspection to receive Authorization to Connect. 5.2 Connection Agreement The Generator and Hydro One agree to, and sign, a Connection Agreement. Hydro One and transmitter/host distribution system shall review existing agreements for required revisions. Note: A temporary connection agreement for the purpose of connection for commissioning and verification may be signed at this point while negotiating final Distribution Connection Agreement. 104
  • 108. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 6 Commissioning and Verification Requirements Commissioning and Verification is required in accordance with the Ontario Energy Board Distribution System Code Appendix F1 (reference 1). This involves the following:  Generator arranges for commissioning and testing of the generation facility;  Hydro One witnesses and verifies the commissioning process related to the connection facilities; and  Transmitter/Host Hydro One witness and verify the commissioning process as required 6.1 Hydro One Networks Inc. COVER Process Hydro One requires the use of a ―Confirmation Of Verification Evidence Report‖ (COVER) to track the Generators Commissioning and Verification plans and execution. The Customer Instructions for Completing the COVER form is contained on the form itself (page 8). The complete 8-page COVER form is located in Appendix G. The version of the COVER form may have changed since the time that this document has been published.7 It has been provided for informational purposes only. The newest version will be provided to the DG Owner at the appropriate stage of the project. 6.2 Hydro One Requirements for Commissioning and Verification Hydro One's interest in the commissioning of the generator‘s equipment and systems is limited to protection and control systems that impact operation of Hydro One‘s distribution system. That involves the generator‘s protection and controls used for the distribution system interface and synchronizing facilities for the distributed generation connection. That includes end-end verification of all inputs and outputs (instrument transformers, breaker positions, transfer trips, distributed generator end open schemes), correct processing of those inputs by the protection and control systems for anti- islanding and clearance of external faults, end-end verification of all outputs - breaker tripping, breaker failure initiation, closing interlocks, alarms, and telemetry. Hydro one requires commissioning of those protection and control systems to be complete and thorough. Generator testing should conform to IEEE Standard 1547.1 - 7 The COVER form is subject to periodic review and revision. The current version will be provided by Hydro One. 105
  • 109. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems. That standard specifies the type, production, and commissioning tests that shall be performed to demonstrate that the interconnection functions and equipment of the distributed resources (DR) conform to IEEE Std. 1547. In general terms, the expected commissioning testing and supporting documentation must include: a) Instrument transformer checks (insulation, ratio/polarity, excitation and resistance results). b) Breaker timing trip tests for those breakers used to disconnect the distributed generation from the Distribution System as a result of protection operations. c) Verification of the transformer and neutral reactor impedances that impact the generator ground integration with the Distribution System and correct connection, where applicable. d) Relay setting field work sheets (showing the measured results of the relay calibration checks). Relay element settings/directioning are to be confirmed by AC secondary injection. e) Voltage measurements for any external power supplies used to supply the protections should be recorded. f) For AC and DC measurements, test equipment traceable to NRC standards should be used. g) Functional tests confirming the protection and control logic and timer settings. h) Verification of test trips and alarm processing. Monitoring of breakers outputs using suitable indicators can be used to avoid repeated tripping of the same from different protections, but at least one live trip test per breaker (where the breaker is proven to open) needs to be demonstrated. i) Verification of control interlocks in protections j) Verification of synchronizing system and synch-check controls. k) Voltage phasing checks (prior to first connection). l) Secondary load readings, voltage and current phasor checks (immediately after first connection) to prove correct magnitude and phase angle of all secondary AC voltage and current circuits correspond to primary quantities. Primary current, voltage, MW and MVAr values must be calculated from the measured secondary values and compared to known primary quantities at adjacent locations. m) The completed documentations must clearly indicate the station, protection designation, settings date, test date, the name of the tester(s), relay type 106
  • 110. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW (manufacturer and model), test equipment details (manufacturer, model, serial number, accuracy, last calibration date), instrument transformer ratios. There should be a cross-reference to the submitted design documentation (drawing numbers and revision). n) Verification of Transfer Trips and DGEO end-end checks. This will require participation and coordination with Hydro One. o) The Distributed Generator shall make modifications to correct any problems that are found during commissioning. p) As-constructed drawings (single line diagram showing protection and metering, AC and DC schematics, final relay settings, testing and commissioning results for interface protection etc.) shall be submitted to the Distributor for its records within sixty (60) business days after the connection, as stipulated in the Connection Agreement. As per the COVER, Summary of testing results and certificates must be kept on file for a minimum period of 7 years by the Customer (as indicated by IESO Market Rules, Chp.4, 5.1.3). Hydro One Networks Inc. may require this information, on an exception basis. Complete documentation of all commissioning results will be required for the interface protections and synchronizing controls, signed and stamped by a Professional Engineer registered in the Province of Ontario. Those results must provide complete assurance that the distributed generator equipment has been proven to function correctly, as per the accepted design submissions and the Distribution Connection Agreement. 7 Maintenance Requirements 7.1 Protection and Control Systems Equipments 7.1.1 The Generator shall re-verify its station protections and control systems that impact the Hydro One Distribution System. That would include the systems that were confirmed and verified as part of the COVER process. Maintenance requirements will be equivalent to what Hydro One would require for re-verification of its own facilities that have similar potential impact to the Distribution System, normally every eight (8) years. 7.1.2 Within three (3) months of Connection, the Generator shall provide Hydro One with their proposed protection and control reverification program (including test procedures and schedules). 107
  • 111. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 7.1.3 Within thirty (30) working days of receiving the above documentation or as required by the Code, Hydro One shall notify the Generator that it: (a) agrees with the proposed reverification program and test procedures; or (b) requires changes in the interest of safety or maintaining the reliability of the Distribution System. Such request for changes shall be sent to the Generator Promptly. For those tests that require Hydro One‘s participation or witnessing, the Generator 7.1.4 shall provide Hydro One with no less than fifteen (15) working days notice. Note: All tests must be coordinated and approved ahead of time through the normal outage and work management system planning processes. 7.1.5 The Generator will complete the re-verification in accordance with 7.1.3 above and submit complete documentation of the test results to Hydro One within one month of the completed tests. 8 Reporting Requirements for DGs The Customer shall keep a written or electronic log. This log will record the date and time, along with a description of the incident. The incidents recorded, must include, but are not limited to those in the table below. The Generator must make the log, or a copy of the log, available for the Distributor‘s review upon request, within five (5) working days of that request. The Customer will provide reports to the Distributor, Distribution Eng/Officer (See Schedule F, Contact List - section 1) either on a requested basis, or for specific types on incidents that require reports as per the table within five (5) working days of the incident. The report must include, but is not limited to:  Distributed Generation Facility and/or Generator Name and Account Number  Supply Feeder 108
  • 112. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  Date and time of incident  General description of the incident, including cause, if known  Did the Generator's equipment trip correctly?  Voltage (if available)  Frequency (if available)  Amps  Active Power (kW or MW)  Reactive Power (kVAr or MVAr)  Any available oscillography or digital fault records (DFR) related to the above  Generator connection status (individual units)  Transfer Trip signal status  Distributed Generator End Open signal status  Which relays operated (targets & description)? Any available sequence of events records (SER) related to the above  Corrective actions taken These are the incident types to be recorded: Note: the Distributor may modify the incidents to be logged or recorded in the table below, based on those relevant to the Distribution System specific to this Connection. Table 14: Incident Logging Real Time Incident Logged Report Required Communication Protection System Malfunction or Yes As requested Day of Failure at the Facility (see D.3.9.6) Trip from the Facility‘s Relay Yes As requested Within Hour Operation Electrical failure / incident at the Yes As requested As requested Facility Mechanical failure / incident at the Yes As requested As requested Facility Trip from Feeder incident Yes As requested Within Hour 109
  • 113. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 9 References 1. Ontario Energy Board Distribution System Code Appendix F - Process and Technical Requirements for Connecting Embedded Generation Facilities - Section F.2 Technical Requirements 2. Ontario Energy Board Distribution System Code 3. IEEE Std 1547-2003 - IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems 4. IEEE Std 1547.1-2005 - IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems 5. IEEE P1547.2/D11 Draft Application Guide for IEEE Standard 1547, Interconnecting Distributed 6. IEEE Std 1547.3-2007 - IEEE Guide for Monitoring, Information Exchange, and Control of Distributed Resources Interconnected with Electric Power Systems 7. IEEE Std 519-1992 - IEEE recommended practices and requirements for harmonic control in electrical power systems 8. IEEE Std 929-1988 - IEEE recommended practice for utility interface of residential and intermediate photovoltaic (PV) systems 9. IEEE Std C37.90-2005 - IEEE Standard for Relays and Relay Systems Associated with Electric Power Apparatus 10. IEEE Std C37.90.1-2002 - IEEE Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electric Power Apparatus 11. IEEE Std C37.90.2-2004 - IEEE Standard for Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from Transceivers 12. IEEE Std C37.90.3-2001 - IEEE standard electrostatic discharge tests for protective relays 13. IEEE Std C57.13-2008 - IEEE Standard Requirements for Instrument Transformers 14. IEEE Std C57.13.1-2006 - IEEE Guide for Field Testing of Relaying Current Transformers 15. IEEE Std C57.13.2-2005 - IEEE Standard Conformance Test Procedures for Instrument Transformers 16. IEEE Std 929-1988 - IEEE recommended practice for utility interface of residential and intermediate photovoltaic (PV) systems 17. IEEE Std 1159-1995 - IEEE Recommended Practice for Monitoring Electric Power Quality. 18. IEEE Std 242-2001 - IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems - IEEE Buff Book 19. IEEE Std 1109-1990 - Guide for the Interconnection of User-Owned Substations of Electric Utilities 110
  • 114. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 20. IEEE Std 1001-1988 - IEEE Guide For Interfacing Dispersed Storage and Generation Facilities with Electric Utility Systems 21. IEEE Std 1453-2004 - IEEE Recommended Practice for Measurement and Limits of Voltage Flicker on AC Power Systems 22. IEEE Std 493-2007 - Gold Book - IEEE Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems 23. IEEE Std 1100-2005 - EMERALD BOOK - IEEE Recommended Practice for Powering and Grounding Electronic Equipment 24. IEEE Std 1250-1995 - IEEE Guide for Service to Equipment Sensitive to Momentary Voltage Disturbances 25. IEEE Std 100-1997 - IEEE Standard Dictionary of Electrical and Electronics Terms 26. IEEE Std 315-1975 - Graphic Symbols for Electrical and Electronics Diagrams 27. IEEE Std C37.2-2008 - IEEE Standard Electrical Power System Device Function Numbers, Acronyms, and Contact Designations 28. IEEE Std C37.1-2007 - IEEE Standard for SCADA & Automation Systems 29. IEEE Std 80-2000 - Safety in AC Substation Grounding 30. IEEE Std 81-1983 - Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System Part 1: Normal Measurements 31. IEEE Std C62.23-1995 - IEEE Application Guide for Surge Protection of Electric Generating Plants 32. IEEE Std C37.29-1981 - IEEE Standard for Low-Voltage AC Power Circuit Protectors Used in Enclosures 33. IEEE Std C57.12 - IEEE Standard General Requirements for Liquid Immersed Distribution, Power and Regulating Transformers 34. IEEE Std C57.12.13 - Conformance Requirements for Liquid Filled Transformers Used in Unit Installations including Unit Substations 35. IEEE Std C57.13 - IEEE Standard Requirements for Instrument Transformers 36. IEEE Std C37.20.1-2002 - IEEE Standard for Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear 37. IEEE Std C37.20.2-1999 - IEEE Standard for Metal-Clad Switchgear 38. IEEE Std C37.20.3-2001 - IEEE Standard for Metal-Enclosed Interrupter Switchgear 39. IEEE Std C37.30-1997 - IEEE Standard Requirements for High Voltage Switches 40. IEEE Std C62.41-1991 - IEEE Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits 41. IEEE Std C37.010-1999 - IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 111
  • 115. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW 42. CSA Std C22.1-2009 - Canadian Electrical Code, Part I Safety Standard for Electrical Installations - Twenty-first edition 43. CSA Std C22.2 - Canadian Electric Code Part II 44. CSA Std C22.3 - Canadian Electric Code Part III (Electricity Distribution and Transmission Systems). 45. CSA Std C22.3 No. 9-2008 - Interconnection of Distributed Resources and Electricity Supply Systems 46. CSA Std C235-83-CAN3 - Preferred Voltage Levels for AC Systems, 0 to 50,000 V Electric Power Transmission and Distribution 47. CSA Std C22.2 No. 107.1-95 - Commercial and Industrial Power Supplies 48. CSA Std C22.2 No. 31-M89 (R2000) - Switchgear Assemblies 49. CSA Std C22.2 No. 193-83 (R2000) - High-Voltage Full-Load Interrupter Switches 50. CSA Std CAN3-C308-M85 - Principles and Practices of Insulation Coordination 51. UL 1741 - Inverters, Converters, and Controllers for Use in Independent Power Systems 52. IEC TR3 61000-3-7 - Principles and Practices of Insulation Coordination Assessment of Emission Limits for Fluctuating Loads in MV and HV Power Systems 53. IEC 61000-4-15 - Flickermeter—Functional and Design Specifications 54. IEC 61400-21 - Wind Turbine Generator Systems—Part 21: Measurement and Assessment of Power Quality Characteristics of Grid Connected Wind Turbines—Ed. 1.0 (2001-12). 55. NEMA CC-1 – Electric Power Connectors for Substations 56. NEMA LA-1 – Surge Arresters 57. NEMA MG-1 – Motors 58. W. Xu, K. Mauch, and S. Martel. ―An Assessment of the Islanding Detection Methods and Distributed Generation Islanding Issues for Canada, A report for CANMET Energy Technology Centre‖ -Varennes, Nature Resources Canada, 65 pages. 59. Wilsun Xu, Guibin Zhang, Chun Li, Wencong Wang, Guangzhu Wang, Jacek Kliber, quot;A power line signaling based technique for anti-islanding protection of distributed generators: part I: scheme and analysisquot;, IEEE Trans. Power Delivery, v22, n3, July 2007, pp. 1758 – 1766 60. Wencong Wang, Jacek Kliber, Guibin Zhang, Wilsun Xu, Blair Howell and Tony Palladino, ―A Power Line Signaling Based Scheme for Anti-islanding Protection of Distributed Generators: Part II: Field Test Results‖, IEEE Trans. Power Delivery , v22, n3, July 2007, pp. 1767 – 1772. 61. W. Freitas, Z. Huang, W. Xu, ―A practical method for assessing the effectiveness of vector surge relays for distributed generation applications‖, IEEE Trans. Power Delivery, v20, n1, pp. 57-63, Jan. 2005. 112
  • 116. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW A Appendix A - Device Number Description The following is a list of relevant device numbers and their meaning: 21 - Distance Relay 25 - Synchronizing or Synchronism-Check Device 27 - Undervoltage Relay 31 - Separate Excitation Device 32 - Directional Power Relay 37 - Undercurrent or Underpower Relay 42 - Running Circuit Breaker 46 - Reverse-phase or Phase-Balance Relay 47 - Phase-Sequence Voltage Relay 49 - Machine or Transformer Thermal Relay 50 - Instantaneous Overcurrent 51 - AC Time Overcurrent Relay 52 - AC Circuit Breaker 53 - Exciter or DC Generator Relay 55 - Power Factor Relay 57 - Short-Circuiting or Grounding Device 59 - Overvoltage Relay 60 - Voltage or Current Balance Relay 61 - Machine Split Phase Current Balance 64 - Ground Detector Relay 67 - AC Directional Overcurrent Relay 68 - Blocking Relay 79 - AC-Reclosing Relay 81 - Frequency Relay 86 - Lockout Relay 87 - Differential Protective Relay 88 - Auxiliary Motor or Motor Generator 89 - Line Switch 90 - Regulating Device 91 - Voltage Directional Relay 92 - Voltage and Power Directional Relay 113
  • 117. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix B – Neutral Reactor and Grounding Transformer B Impedance Calculations for Inverter Based DG Facilities The following is two examples for calculating the impedance of grounding transformers for Inverter based DG facilities: Example 1: for 10 MVA DG Facility connected at 27.6 kV, Base impedance = 27.6kV2/10MVA = 76.2Ω, Then X0 = 0.6 x 76.2Ω ± 10% = 45.7Ω ± 10% Example 2: for 2 MVA generation connected at 27.6 kV, Base impedance = 27.6kV2/2MVA = 381 Ω, Then X0 = 0.6 x 381Ω ± 10% = 228.6Ω ± 10% The following is two examples for calculating the impedance of neutral reactors for Inverter based DG facilities: Example 1: for 10 MVA DG Facility, with ten 1 MVA DGITs connected at 27.6 kV, Base impedance = 27.6kV2/1MVA = 762Ω, Then X0 = 0.6 x 762Ω ± 10% = 457.2Ω ± 10% Example 2: for 2 MVA generation connected at 27.6 kV, Base impedance = 27.6kV2/2MVA = 381 Ω, Then X0 = 0.6 x 381Ω ± 10% = 228.6Ω ± 10% 114
  • 118. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix C – Timing Diagrams C The following are a few sample timing diagrams for informational purposes. These have been created to represent a realistic sequence of events and the associated timings for different applications. These times may change due to site specific requirements and thus, timing requirements shall be confirmed with HONI for specific DG projects. Figure 17 and 18 represent timing for fault and island detection for DGs not equipped with Transfer Trip from HONI, coordinating with HONI reclosers with a reclose time of 500ms and 1s respectively. Figure 17: No Transfer Trip with 500ms Reclosure Upstream 115
  • 119. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 18: No Transfer Trip with 1s Reclosure Upstream 116
  • 120. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 19 and 20, shown below, show timing requirements DGs equipped with Transfer Trip from HONI, coordinating with HONI reclosers with a reclose time of 500ms and 1s respectively. Figure 19: Transfer Trip with 500ms Reclosure Upstream 117
  • 121. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 20: Transfer Trip with 1s Reclosure Upstream 118
  • 122. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix D – Anti-Islanding Protection D The following is background information on Anti-Islanding Protection, its purpose, and some rational behind some requirements. Transfer Trip and Distributed Generator End Open is discussed. Also, a typical distribution system is shown and possible island formations are discussed. This information is provided as informational only. Requirements are listed in Section 3 of this document. Transfer Trip, Distributed Generator End Open and Inrush Blocking (LSBS) Transfer Trip (TT), Distributed Generator End Open (DGEO) and Inrush Blocking (Low Set Block Signal – LSBS) are often required to mitigate the adverse impacts of DG connection and islanding, as detailed below.  Transfer Trip (TT) is a protection trip signal that is sent from the Hydro One supply source breaker or recloser to the DG when the DG is required to be disconnected.  Distributed Generator End Open (DGEO) is a real time signal that is continuously sent from the DG to the Hydro One supply source breaker or recloser. It establishes the connection status of the generation equipment. For 3-wire connections, the DGEO signal is derived from all breakers/circuit switchers at the interface between the DG generation and the PCC necessary to establish DG generation connectivity. For 4-wire connections, the DGEO signal is derived from the DG HVI switch only. Refer to Appendix E for more information regarding the DGEO signal.  Low Set Block Signal (LSBS) is a signal that is sent from the DG to the Hydro One supply source breaker or recloser, whenever a large DG interface transformer (DGIT) is being energized. Detection of this signal transition at the Hydro One supply source breaker or recloser location will cause the most sensitive low-set (fuse-saving) protection to be temporarily blocked. This will prevent tripping of the Hydro One supply source during the period when there is large energizing inrush current due to the DGIT. Refer to Appendix E for more information regarding the LSBS signal.  Because the momentary LSBS signal will always be sent just prior to reconnection, (near the end of the DGEO open condition), it is possible to combine both DGEO and the LSBS functions as one signal through a communication channel from the DG facility to the Hydro One source energizing location(s). 119
  • 123. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW DG Islanding DG islanding can expose Hydro One Transmission and Distribution Systems and customers to unstable voltage and frequency and other adverse impacts. A DG island is formed if a DG remains connected to a portion of the Distribution System after that portion is separated from the normal Hydro One supply. Most typically, DG islanding can occur when the feeder breaker or other isolating device at a TS or DS or along a radial-connected feeder is opened. Some of the causes that may lead to DG islanding are as follows:  A fault that is detected and cleared by the utility before it can be detected and cleared by the DG. Most DG islands will be established this way.  Emergency switching of distribution system and loads.  Equipment malfunction.  Operating or human error.  Foreign interference or other acts of nature. Adverse Impacts of DG Islanding Potential adverse impacts of DG islands include: a) Abnormal voltage and frequency excursions outside of the acceptable ranges because of DG voltage regulation limitations. b) Excessive temporary overvoltage (TOV) can occur if DG sources that are not effectively grounded back-feed single-line-ground faults. c) Extreme overvoltage from ferroresonance between the nonlinear magnetizing inductance of DGIT/induction generators and connected capacitance and system capacitance. d) Unpredictable DG energy sources that are not controlled by the utility. This includes generation sources and abnormal phase voltages caused by back-feed through multi- core 3-phase DG interface transformers in the presence of single-phase switching or other open circuit supply conditions. e) Failure to clear certain faults that cannot be detected by DG self-clearing protections within required time. f) Interference with the restoration of normal supply from the utility. g) Asynchronous paralleling if DG is present when Hydro One supply is restored. 120
  • 124. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW The risks of these adverse impacts include: a) Inadequate power quality - voltage and frequency. b) Damage - to customer and utility line equipment as a result of overvoltages or sustained or prolonged electrical faults where protections are insensitive or slow clearing. c) Prolonged customer outages resulting from failed automatic reclosure or delays in establishing safe conditions for isolation and repair of damaged equipment. d) Safety hazards to public and utility workers since lines may be energized when it is assumed to be disconnected from all energy sources. e) Increased liability and costs associated with all of the above. These impacts must be avoided by maintaining adequate controls over the design and operation of the DG interconnections. Transfer Trip (TT) and Distributed Generator End Open (DGEO) schemes are important tools that are required to avoid these adverse effects for certain configurations. Hydro One Supply Stabilizes Voltage and Frequency Hydro One is responsible for supply and voltage regulation of Hydro One Distribution Systems and maintains Distribution System voltages at acceptable levels as required by the OEB. Frequency is maintained very close to 60 Hz by the synchronized interconnection of the Hydro One Transmission System to the Eastern Interconnection of the North American Electric Reliability Corporation (NERC). Voltage and frequency will be maintained under normal system conditions as long as normal Hydro One supply remains connected to the Distribution System. Expected Frequency and Voltage Deviations in DG Islands When a DG island occurs, island voltages and frequency will depend entirely on the interaction between the islanded generation and load. Maintaining an island within acceptable limits would require at least one DG in the island to actively regulate frequency and voltage to match changing island load demands. Furthermore the DG capacity would have to be large enough to sustain the extreme range of load demands that may exist in the island. DGs cannot meet these conditions for the following reasons:  HONI does not permit DG voltage regulation systems to actively regulate voltage. This avoids mal-coordination of Distribution System voltage regulation and excessive operation of Hydro tap-changers and voltage regulators. 121
  • 125. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  Variable production conditions prevent DG capacity from being capable of meeting the exact demands of any specific local loads or power transfers. As a result, DG island frequency and voltage can be expected to drift outside of the acceptable limits because of these inherent DG control and capacity limitations.  The direction (over or under) of frequency and voltage change for a DG island will depend upon the relative mismatch of net real and reactive power between the islanded DG and load. If the active power generation is less than the active power consumed by the load, the island frequency will drop. If the active power generation exceeds the active power consumed by the load, the island frequency will rise.  Change in island voltage magnitude depends similarly on mismatch between distributed generation reactive power output and the reactive power demands of the islanded load.  The rate-of-change of frequency and voltage for a DG island will depend upon many factors. These factors include the amount of power unbalance, network impedances, voltage dependency of the feeder loads and dynamic characteristics of the islanded generation and loads (inertias of the interconnected machines and transient reactances).  Even short duration DG islands may be too long to prevent adverse DG islanding impacts, unless specific design precautions are implemented. Possibility of Extreme Overvoltages and Back-feeds through Customer Transformers  Ferroresonance and single-line-ground faults can cause extreme or excessive over- voltages for some DG island configurations. These over-voltages are capable of causing damage to customer and Hydro One equipment.  Back-feeds through multi-core 3-phase DG interface transformers in the presence of single-phase switching or other open circuit supply conditions. These voltages pose a safety hazard to public and utility workers for fallen conductors or when circuits are assumed to be dead but in fact are energized.  These over-voltage and back-feed effects are largely dependent upon the size, grounding and magnetic-core characteristics of the DG interface transformer (DGIT) connections. There are many ways to avoid or minimize these effects. That includes the following: i. The use of Transfer Trip 122
  • 126. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW ii. Use of a DG HVI to be tripped whenever an unbalanced condition is detected at the DG location iii. Effective-grounding of DGIT iv. Avoiding the use of multi-core transformers for 3-phase connections in the presence of single phase switching upstream, by using three individual single-phase (single-core) DGIT connections v. Avoiding single-phase switching of 3-phase transformers (where possible) or minimizing circuit capacitance from the DGIT to these locations. Automatic Reclosure  Transient faults on over-head line conductors caused by lightning, wind, tree branches falling, or other momentary foreign contact constitute approximately 85-90% of all faults.  Hydro One uses the standard utility practice of automatic reclosure on distribution feeders with over-head line-sections to minimize supply interruptions for transient faults.  Automatic reclosure is not generally used for feeders with extensive underground cable sections because cable faults are exposed to far fewer naturally occurring transient fault conditions. Also faults on cables are much more likely to be permanent requiring repairs. Benefits of Automatic Reclosure Automatic reclosure has the following advantages:  Minimizes supply interruption to customers by automatically restoring the feeder to service as quickly as possible following transient faults.  Minimizes damage at the fault and stress on equipment supplying the fault.  Reduces operating costs. Less time and materials required to repair damage and restore service.  Prevents blowing of fuses at tapped Distribution stations and lateral feeds resulting in all of the above. How Automatic Reclosure Works  For the first occurrence of the fault on any portion of the faulted feeder, high-speed sensitive ―low set‖ protection operates quickly to de-energize the feeder. 123
  • 127. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  Following the first protection operation, the Hydro One feeder breaker or reclosers are automatically reclosed to restore supply to load customers as quickly as possible.  Typical reclosing times are 0.5 to 1 second for feeder breakers and 1.5 to 2 seconds for reclosers.  Reclosing time must allow for the fault to extinguish and de-ionize.  Reclosing time must also allow some time for the inertia and back emf of large motors to decay (to about 40% of normal voltage) and be disconnected by automatic controls. Automatic Reclosure Requires DG to Disconnect Quickly Automatic reclosure can succeed only if the fault arc is extinguished and de-ionized. Otherwise the fault is likely to re-strike after the feeder is re-energized.  If the DG has not disconnected at the time that automatic reclosure takes place, the reclosure would asynchronously re-parallel to all DGs and any rotating motors that remained connected in the island.  Extreme mechanical stresses associated with asynchronous paralleling could damage DG generators, customer motors, switching equipment and any transformers that are connected in series between these energy sources.  The potential impact of asynchronous connection of inverter-fed DGs is less certain and will depend on their individual design. However, if island voltage can be sustained causing other generators and motors to remain connected, then asynchronous reclosure must still be avoided.  For the above reasons, all DGs must be quickly disconnected whenever a feeder fault is detected – before reclosure takes place. Limitations of DG Self-Clearing Protection Response Times  Based on fault in-feed, DGs cannot distinguish between faults on either side of the utility feeder breaker or recloser that supplies them. To avoid nuisance trips, some time delay is required by the DG protection to allow coordination with the faster utility protections to clear those out-of-zone faults. If that delay is too long, automatic reclosure will be impaired.  DG anti-islanding protection cannot prevent DG islanding. It can only detect an island after islanding occurs. 124
  • 128. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  All passive DG anti-islanding detection methods rely on an unbalance or mismatch between distributed generation power output and power demands of the connected load on the isolated island. DG island frequency and voltage can be expected to drift (as per section ―Expected Frequency and voltage deviations in DG islands‖ above).  Close matching of both active and reactive power would be an extremely unlikely condition for a prolonged period. Sooner or later, mismatches will cause the voltage or frequency to drift outside the limits specified in Sections 3.2.13 and 3.2.14.  If by chance the active and reactive power produced by islanded DG happens to be close to the islanded load demand, then the island may survive for a longer period before DG self-clearing protections will detect and disconnect the generation.  In some cases, DG self-clearing anti-islanding protections cannot be relied on to guarantee that the DG will disconnect itself before automatic reclosure takes place. In those cases, TT and DGEO schemes are required. Refer to appropriate sections for requirement conditions. Maximum Detection Times Available for DG Self-Clearing Protections There are limited time windows available following the formation of an island during which time DG self-clearing protections have to disconnect the generator before reclosure takes place.  If there is a fault on the feeder at the time the DG island is formed, the DG fault protection must detect the fault and initiate clearance.  If there is no fault on the feeder at the time the DG island is formed, the DG anti- islanding protection must detect the island condition and disconnect the generation from the Distribution System. Timing diagrams for self-clearing DG protections are shown in Appendix C in Figure 17 and Figure 18 for a 0.5-second reclosure and for a 1.0 second reclosure, respectively. The times are based on the following assumptions and constraints:  The assumed maximum fault detection time for Hydro One instantaneous low set protections is 33ms. More commonly fault detection time will be 16 ms or less.  The reclosure timer is initiated without delay, immediately after the fault is detected by the Hydro One feeder protection. 125
  • 129. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  The assumed maximum Hydro One fault clearance time is 83 ms after the fault is detected (5-cycle breaker opening time for oil dead-tank breakers).8  200 ms fault extinction and de-ionization time and/or drop out of motor controls is required after the last source trips, prior to reclosure.  The DG generator breaker is a 3-cycle breaker. To prevent interference with automatic reclosure (1 second reclosure):  Self-clearing DG anti-islanding protections must be capable of island detection within 617ms to coordinate with a 1 second reclosure time.  DG fault protection must be capable of detecting all 3-phase and phase-ground faults to the extreme ends of the supply feeder within 783ms.  For reclosure times longer than 1 second, the protection response times can be lengthened by equivalent amounts. TT will be required to speed up DG clearance if the above conditions cannot be met. To prevent interference with automatic reclosure with a reclose time of 500ms:  Self-clearing DG anti-islanding protections would have to be capable of detecting an island condition within 117ms.  DG fault protections must be capable of detecting all 3-phase and phase-ground faults to the extreme ends of the supply feeder within 283ms.  It is expected that DG self-clearing protections cannot selectively and reliably detect fault and island conditions in such a short time. TT and DGEO will always be required to speed up DG clearance where 0.5-second reclosure times are used. Transient Response of DG Islands  Hydro One transient stability studies for some typical synchronous generators have demonstrated some consistent effects that various generation-to-feeder load ratios have on DG voltage and speed (frequency). 8 Hydro One clearance time (after fault detection) may be only 50 ms if fast auxiliary relays and 3-cycle breakers are used. 126
  • 130. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  These studies have shown that for 50% generator rating to feeder load ratios, generator frequency declined steadily to about 53 Hz within 1 second. Voltage declined rapidly to about 75% within about 100 ms and recovered somewhat to about 93% within 1 second.  Such frequency excursion to 53 Hz should ensure that the under-frequency protections, set as specified in Section 3.2.13 will clear in much less than 1 second (160 ms for frequency < 59.3 Hz).  Such voltage excursion to 75% may take up to 2 seconds to clear for protection set as per Section 3.2.14 (50 ≤ V < 88%).  For higher generator rating to feeder load ratios, frequency and voltage does not drift outside the limits specified in Sections 3.2.13 and 3.2.14.  Generic models for other types of generators - self-fed induction (SFIG), Double-fed Asynchronous (DFAG), inverters and static power converters are not sufficiently available to guarantee that DG anti-islanding protections will operate in sufficient time for all conditions to prevent interference with automatic reclosure.  Based on the above, Hydro One has established a 50% active power unbalance threshold (DG aggregate capacity / minimum load) above which TT is required to be used to avoid interference with Distribution System automatic reclosure schemes.  This only applies where automatic reclosure time is 1-second or longer. Requirements for Transfer Trip Transfer Trip (TT) is a protection trip signal that is sent from the Hydro One supply source breaker or recloser to the DG when the DG is required to be disconnected. TT is required to prevent the adverse effects of DG islands whenever other means cannot reliably do so or are more expensive. TT is required to quickly disconnect the DG from the Distribution System for the conditions listed in Section 3.2.16. TT timing requirements Refer to Appendix C, Figure 19, and Figure 20 for TT timing requirements. DGEO Requirements  Distributed Generator End Open (DGEO) is a real time signal that is continuously sent from the DG to the Hydro One supply source breaker or recloser. 127
  • 131. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  For ungrounded 3-wire connections, where the DG source cannot contribute ground fault current, the DGEO signal is derived from all breakers/circuit switchers at the interface between the DG generation and the PCC necessary to establish DG generation connectivity. It establishes the connection status of the generation equipment and is used to block automatic reclosure should DG fail to disconnect after the Hydro One supply is disconnected. For 3-wire connections that do not have an HVI, connectivity of the generators will be established by LVI connection logic that mimics all of the possible generation connection paths.  For 4-wire connections, the DGEO signal must be derived from the DG HVI switch only. For 4-wire connections all DG ground sources must be connected to the DG side of the HVI switch and must be disconnected before Hydro One source can be permitted to energize the feeder. That is because any fault that occurs immediately following Hydro One energization of the feeder is almost certain to be permanent, and Hydro One low- set fuse-saving protections are blocked. This allows coordinated clearance of the down- stream reclosers and fuses with the Hydro One source timed protections. DGEO requirements are specified in Section 3.2.17. Low Set Block Signal Requirements The Low Set Block Signal (LSBS) is a signal that must be sent from the DG to the Hydro One supply source breaker or recloser, whenever a DG interface transformers (DGIT) is being energized. This will prevent tripping of the Hydro One supply source during the period when there is large energizing inrush current to the DGIT. Detection of this signal transition at the Hydro One supply source breaker or recloser location will cause the most sensitive low-set (fuse-saving) protection to be temporarily blocked for a short duration, sufficient to allow the DGIT inrush current to subside. The LSBS signal can be combined with the DGEO signal through a shared communication channel from the DG facility to Hydro One. LSBS requirements are specified in Section 3.2.22. 128
  • 132. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Application of TT and DGEO “50% rule” Requirements to DG Islands The 50% TT rule is intended to preserve the benefits of automatic reclosure following transient line fault conditions, by ensuring DGs do not interfere with the successful operation of automatic reclosure schemes. Automatic reclosure is not initiated for other types of permanent faults – recurring line faults, transformer faults, bus faults or breaker failure condition. In these cases, providing other adverse impacts are minimal for short-duration DG islanding, self-clearing anti- islanding protections (over/under voltage and over/under frequency) may be sufficient to disconnect the generation from the island when frequency and voltage transcend the limits specified in Sections 3.2.13 and 3.2.14. In all cases, high reliability is required for all protection schemes that are required to maintain the integrity of the Distribution System. Typical DG islands that can be formed during transient fault conditions are illustrated in Figure 21 and the following discussion below. Figure 21: Typical Distribution System with DG Interconnections 129
  • 133. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Local Area DG Islands Local Distribution System DG Islands are formed whenever feeder reclosers or TS breakers are tripped from feeder or line protections interrupting the supply to a portion of the Distribution System. For each potential local DG island scenario, the aggregate capacity of the islanded DG must be assessed in relation to the minimum connected islanded load. If the islanded DG aggregate capacity is greater than 50% of the minimum load of the connected island, then TT will be required to be sent from the most strategic Hydro One supply location(s) to disconnect the DG to ensure successful reclosure operations. The TT may be sent directly from the Hydro One switching device location to the DG or a cascading arrangement may be used to redirect the TT to the DG via another marshalling location (usually the TS). Recloser DG Island  A recloser DG island forms when a feeder recloser operates for a feeder fault, interrupting the Hydro One supply to a section of a feeder to which DG is connected.  In the example, Figure 21, DG2, DG4 and DG5 will be islanded by the adjacent Hydro One source-side reclosers opening.  Typical automatic reclose times are 1.5 to 2 seconds for reclosers.  To prevent interference with automatic reclosure self-clearing DG anti-islanding protections must be capable of detecting an island condition within about 1.1 second for a 1.5 second reclose time and 1.6 second for a 2-second reclose time.  This will be assured if the aggregate capacity of the islanded DG is less than 50% of the minimum load on the load-side of a feeder recloser. Otherwise, TT will be required to be sent to disconnect the DG whenever the feeder recloser is opened. Feeder-breaker DG Island  A feeder-breaker DG island forms when feeder protection operates for a feeder fault, opening a TS feeder-breaker and interrupting the Hydro One supply to the whole feeder to which DG is connected.  In the example, Figure 21, DG1 – DG4 will be islanded by the opening of the M2 feeder breaker.  Typical automatic reclose times are 0.5 to 1 seconds for feeder breakers. 130
  • 134. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW  To prevent interference with a 1.0 second automatic reclose time, self-clearing DG anti- islanding protections must be capable of detecting an island condition within about 0.6 second. This will be assured if the aggregate capacity of the islanded DG exceeds 50% of the minimum load on the load-side of a feeder recloser. Otherwise, TT will be required to be sent to disconnect the DG whenever the TS breaker is open.  To prevent interference with a.0.5 second automatic reclose time, self-clearing DG anti- islanding protections would have to be capable of detecting an island condition within 117ms. It is expected that DG self-clearing protections cannot selectively and reliably detect fault and island conditions in such a short time. TT and DGEO will always be required to speed up DG clearance where 0.5-second reclosure times are used.  If the aggregate capacity of the islanded DG exceeds 50% of the minimum load on the load-side of the TS breaker, TT will be required to disconnect the DG whenever the TS breaker is opened. LV Bus DG island  An LV bus DG island forms when a main terminal line protection operates for an HV line fault interrupting the Hydro One supply to a DESN TS LV bus to which DG is connected.  In the example, Figure 21, an LV bus DG island would only occur if the bus-tie breaker BY was open and the L2 line protection opens LV transformer-breaker T2Y interrupting the Hydro One supply to the Y bus to which DG1 – DG4 are connected.  Automatic reclosure is initiated from the HV line protection and the LV transformer- breaker Transfer Trip or Remote Trip receive protections. The typical automatic reclose time for a DESN TS LV transformer-breaker is typically 1 second, but that will only be completed after the HV line protection at the main terminal TS automatically recloses, typically in 5 seconds (may be as low as 2 seconds).  To prevent interference with a cumulative 3 second automatic reclosure self-clearing DG anti-islanding protections must be capable of detecting an island condition within about 2.6 seconds.  This will be assured if the aggregate capacity of the islanded DG exceeds 50% of the minimum load on the LV bus. Otherwise, TT will be required to be sent to disconnect the DG whenever the LV transformer breaker and bus-tie breaker are open. 131
  • 135. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW DESN TS LV island  A DESN TS LV island forms when one or more main terminal line protections operate for HV line faults, interrupting the Hydro One supply to a DESN TS to which DG is connected.  In the example, Figure 21, a DESN TS LV would occur if transformer breakers T1B and T2Y are both opened from operation of HV line protections, isolating all of the DG connected to the DESN TS (DG1 – DG4).  Automatic reclosure is initiated from the HV line protection and the LV transformer- breaker Transfer Trip or Remote Trip receive protections. The typical automatic reclose time for a DESN TS LV transformer-breaker is typically 1 second, but that only after the HV line protection at the main terminal TS automatically recloses, typically in 5 seconds (may be as low as 2 seconds).  To prevent interference with a cumulative 3 second automatic reclose time self-clearing DG anti-islanding protections must be capable of detecting an island condition within about 2.6 seconds.  This will be assured if the aggregate capacity of the islanded DG exceeds 50% of the total minimum load on the DESN TS. Otherwise, TT will be required to be sent to disconnect the DG when all of the transformer breakers are open. Wide-Area DG Island  A Wide-Area DG island can be formed when one or more main terminal line protections operate for HV line faults, interrupting the Hydro One supply to all DESN stations and to any HV-connected DS to which DG is connected.  For a two-circuit supply, both circuits would have to be interrupted to cause a wide area DG island.  In the example, Figure 21, a wide area DG island would occur if supply to both HV lines L2 and L2 are interrupted (a double circuit interruption). This is a relatively rare event but can happen during wind storms or other adverse conditions.  For a single-circuit supply, interruption of the line protection for that circuit would cause a Wide-Area DG island.  A Wide-Area DG island will occur if there is no TT from the main terminal station to the DESN station or HV-connected DS or that TT fails causing the DESN station LV breakers to remain closed. In that case, automatic reclosure of the HV lines will restore 132
  • 136. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Hydro One supply to all of the affected Wide-Area, typically in 5 seconds (may be as low as 2 seconds) provided that there is no back-fed voltage detected on the HV lines by the HV breaker automatic reclosure schemes.  A Wide-Area DG island may also occur if the next zone (upstream from Terminal Stations) is tripped. This may occur if the net generation in the wide area network can sustain the load at the time of occurrence. 133
  • 137. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix E – DGEO & LSBS Design Considerations E The following information is a design consideration for implementation of the DGEO and LSBS signals for installations utilizing a High Voltage Interrupter or a High Voltage Disconnect Switch (motorized Load Break Switch). This is for informational purposes only. Feeder (3-Wire) Hydro One Telecom Tx PCC DGEO Trip HVDS TT e Delta Rx s Clo DG1/b DG2/b DGn/b HVDS/b pu T1 HVDS pu do DG1 DG2 DGn T3 CLOSE do pu HVDS Control T2 Critical CLOSE do Load HVDS on 3-Wire Feeder (4-Wire) Hydro One Telecom Tx PCC DGEO Trip TT HVI e Wye os Rx Cl Spare Spare Spare HVI/b pu T1 HVI pu do DG1 DG2 DGn T3 CLOSE do pu HVI Control T2 Critical CLOSE do Load HVI on 4-Wire *HVDS - High Voltage Disconnect Switch Based on Block ing the Low Set Inst at Hydro One for 5 seconds on a falling edge DGEO signal transition Example Teleprotection Delay HVI HVDS Timer T1 Timer T2 Timer T3 # TT Delay DGEO Delay Close Time Close Time PU Delay DO Delay PU Delay DO Delay PU Delay DO Delay 1 16ms 16ms 100ms 0ms 0ms 1s 0ms 0ms 6s 2 16ms 16ms 1s 0ms 0ms 1s 0ms 0ms 6s 3 30ms 250ms 100ms 0ms 0ms 1s 0ms 0ms 6s 4 30ms 250ms 1s 0ms 0ms 1s 0ms 0ms 6s Figure 22: DGEO & LSBS Design Consideration 134
  • 138. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix F – Example of a Sequence of Events During Fault Conditions F The following two figures are a typical sequence of events during abnormal conditions, for both a transient fault and a permanent fault. Note: These diagrams assume that the DG facility requires Transfer Trip and a HVI. This is for informational purposes only. Figure 23: Sequence and Timing Diagram for Transient Faults 135
  • 139. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Figure 24: Sequence and Timing Diagram for Permanent Fault 136
  • 140. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix G – Confirmation of Verification Evidence Report (COVER G Form) The following is HONI‘s COVER Form. An updated version may be available and will be provided by HONI. CONFIRMATION OF VERIFICATION EVIDENCE REPORT (COVER) [Distribution Connected Generation – (DCG)] (Instructions provided on last Page) Section 1 FACILITIES INFORMATION NAME OF CUSTOMER NAME OF FACILITY PROPOSED ENERGIZATION DATE HYDRO ONE OPERATING DESIGNATION CLAIM NOTIFICATION (Investment Planning #) SUPPLY FEEDER DESIGNATIONS Section 2 CONTACT INFORMATION CUSTOMER CONTACT HONI COVER COORDINATOR CONTACT Print Name: Print Name: Title: Title: Date: Date: Tel. #: Tel. #: Email: Email: [COVER - page 1 of 8] 137
  • 141. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW VERIFICATION-PROTECTION & CONTROL Section 3 Protection Group mm/dd/yyyy To verify Legend Results Initials Note # Protection Group to verify: A, B, or A&B Date Legend: C = Confirm Results: P = Pass, F = Fail, N/A = Not Applicable  Is commissioning in compliance with the submitted Commissioning plans?  Are reviewed relay settings applied? Confirm that the following protection systems, as applicable, have been verified to function as per the design: NOTE: Tests marked with an asterisks (*) require Hydro One staff coordination  Line Protection  HV Breaker Failure Protection and Reclose  LV Breaker Failure Protection and Reclose  Transformer Differential  Transformer Backup Protection  Under and Over Frequency  Under and Over Voltage  Transfer Trip / Remote Trip *  Pilot Wire Protection *  Blocking Scheme Circuits *  Generation Rejection & Load Rejection Circuits *  Reverse Power  Gen. Prot. That trip HV Sync Breakers  Instrument Transformer (eg. CTS + CCVTs, etc.)  Monitoring Equipment (eg. DFR, SER, etc.)  Other (Specify) [COVER - page 2 of 8] 138
  • 142. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Section 4A TELEMETRY TESTS BEFORE ENERGIZATION AT CUSTOMER OWNED TS Confirm the following SCADA telemetry quantities, mm/dd/yyy Needed Legend where applicable: Results Initials Note # Date Test Test Needed: D = to be Done y Legend: C = Confirm; Results: P = Pass, F = Fail All Parts: N/A = Not Applicable  HV MW per transformer  HV MVAR per transformer  HV Phase to Phase Voltages (R, W, B)  LV MW per LV Bus  LV MVAR per LV Bus  LV Phase to Phase Voltages (R, W, B)  HV Under-Load Tap Changer Positions  HV Disconnect Switches/HV Circuit Switchers/Breakers Open/Close Status  LV Transformer & Bus Tie Breakers Open/Close Status  LV Capacitor Breakers Open/Close Status  Common Protection Trip Alarm each HV Circuit  Other (specify) Section 4B TELEMETRY TESTS BEFORE ENERGIZATION AT CUSTOMER OWNED GS Confirm the following SCADA telemetry quantities, mm/dd/yyyy Test Needed where applicable Legend Results Initials Note # Date Test Needed: D = to be Done Legend: C = Confirm; Results: P = Pass, F = Fail All Parts: N/A = Not Applicable  MW Flows and Directions  MVAR Flow and Directions  Phase to Phase Voltages  HV switchers/HV breakers/Bus Tie Breakers Open/Close Status  HV Line Disconnect Switches Open/Close Status  Synchronizing Breakers Open/Close Status  AVRs, PSSs status  Generation Rejection Selection Status  LV Breakers/Switchers, Open/Close Status  LV Synchronizing Breakers, Open/Close Status  Protection Trip Alarms  Other (specify) [COVER - page 3 of 8] 139
  • 143. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Section 5 CONFIRMATION OF VERIFICATION-POWER EQUIPMENMT mm/dd/yyyy Legend: C = Confirm, W = Witness Legend Note # Result Initial Date Result: P = Pass, F = Fail All Parts: N/A = Not Applicable Note, some of the following verification may require HONI staff witnessing.  Verify the HV disconnect switches/circuit switchers are suitable as an isolation point per Utility Work Protection Code? NOTE: Any future modifications to the isolation device(s) used to provide supporting guarantees to HONI staff under the Utility Work Protection Code must be re-witnessed by HONI personnel.  Confirm correct operation of the HV disconnect switches/circuit switchers/breakers  Is closing time within manufacturer’s specification?  Is opening time within manufacturer’s specification?  Are the specified HV surge arrestors installed?  Confirm the power transformer Doble test results are within specification  Confirm power transformers connected correctly as per the design.  Confirm the DC system installed (ie battery, charger, dc panel, dc monitoring)? Verified  Does the HV equipment (ie, disconnect switches, circuit switchers, breakers, CVTs, CTs) have the appropriate voltage class and current ratings as per the submitted Single Line Diagram?  Other (specify)  Name of Hydro One Witness: Section 6 ELECTRICAL SAFETY mm/dd/yyyy Legend Date Legend: SD = Supporting Document, N/A = Not Applicable  Prior to energizing any new or modified customer or generator facilities, Electrical Safety Authority (ESA) must provide a Temporary Connection Authorization (Ontario Electrical Safety Code Article 2-014). Attach document.  Prior to final in-service of new or modified customer or generator facilities, ESA must provide Connection Authorization (Code Article 2-012). Attach document.  All customers must provide a letter signed and stamped by a Professional Engineer registered in the province of Ontario stating that their equipment and installation meets CSA and/or other applicable electrical safety standards, prior to ready for Service Date. Attach document. [COVER - page 4 of 8] 140
  • 144. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW NOTES: (For Sections 3, 4A or 4B, 5 & 6) Comments: COVER Coordinator Date Action Resolved: #: Concurrence To Connect: (dd/mm/yyyy) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. By signing* this form, the customer acknowledges that all required verifications specified under this COVER document have Signature of Customer Representative (Note : Must be P. Eng) been completed and that the customer facility design and operation meets the minimum Print Name: standards for customer facilities connected to a Title: distribution system, as per the Distribution Date: System Code. Part I Completed COVER Coordinator Initials *After signing the COVER, the customer shall submit it to the COVER coordinator with a copy to the Account Executive. The COVER Coordinator has reviewed the customer’s Certified COVER document and the Signature of COVER Coordinator customer’s facility may be connected to the grid, Print Name: subject to Controlling Authority’s final review. Title: Date:  The COVER coordinator shall forward (scan/fax) the completed document to the Controlling Authority to initiate the connection (for OGCC controlled distributed generators, the OGCC is the controlling authority. For other feeders the controlling authority will be Provincial Lines). The COVER coordinator shall contact (phone) the Controlling Authority, to notify him/her of the completed COVER. The COVER coordinator will ensure this document is placed within the Distribution Connection Agreement. [COVER - page 5 of 8] 141
  • 145. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Section 7 CONFIRM ON POTENTIAL/ON LOAD CHECKS AT RATED SYSTEM VOLTAGE mm/dd/yyyy Legend: C = Confirm, W = Witness Legend Note # Result Initial Date Result: P = Pass, F = Fail All Parts: N/A = Not Applicable Are phasor (X-Watt meter) readings completed and analyzed by the customer for Protection listed in Section 3? Are phasor (X-Watt meter) readings completed and analyzed by the customer for SCADA quantities listed in Section 4? On Load SCADA Values confirmed consistent with test(s) performed in Section 4A or 4B? NOTES: (For Section 7) #: Comments: COVER Coordinator Date Action Resolved: Concurrence: (dd/mm/yyyy) 1. 2. 3. 4. I/we acknowledge the completion of the COVER as noted and the deficiencies identified in the “NOTES” section have been resolved. Signature of Customer Representative (Note: Must be P. Eng,) Print Name: Title: Date: [COVER - page 6 of 8] 142
  • 146. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Section 8 TEST SUMMARY REPORTS In accordance with the Distribution System Code, Appendix F, for a Generation facility of Small size (pg.13), Mid size (pg.21), and Large size (pg.28), the Customer shall, at Hydro One's request, provide Hydro One with a summary of testing results, including any certificates of inspection or other applicable authorizations or approvals certifying that any of the Customer's new, modified or replacement facilities have passed the relevant tests and comply with all applicable instruments and standards referred to in the code. This information will be kept on file for a period of (7) years by the Customer. DISTRIBUTION LIST (WHEN ALL SECTIONS ARE COMPLETED): Distribution Customer Business Relations Controlling Authority Customer Agent Distribution Records (original) HONI COVER Coordinator [COVER - page 7 of 8] 143
  • 147. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Customer Instructions for Completing the COVER form (DCG) PART 1: PLAN Step 1: Customer Information  Complete Facility and Customer Contact Information of the COVER Form by completing the highlighted portions of Sections 1 & 2. Step 2: Identify the Tests that the Customer Intends to Conduct  Complete Highlighted portions (Protection Group and Legend columns) of Sections 3, where applicable  Complete Highlighted portions of Section 4A or 4B (Test Needed and Legend columns)  Complete Highlighted portions of Sections 5 (Legend column) and 6 (Date Received column) Note: The design review must be finalized prior to completing this step. Step 3: Hydro One’s COVER Coordinator Review  Return COVER Form by email to the HONI COVER Coordinator listed in Section 2  The COVER coordinator will review the proposed and a respond to the acceptability of the proposed COVER tests within 5 business days.  Note: The commissioning plan review must be finalized prior to commencing testing for the next step. PART 2: PRE-ENERGIZATION Step 4: Completion of Testing and Resolution of all Comments  Complete all applicable testing in Sections 3, 4A or 4B, 5 & 6.  Sign off the COVER, in section 6, by a Customer P.Eng Representative, and submit it to the COVER Coordinator and Account Executive.  The COVER coordinator will review the certified COVER and recommend to the Controlling Authority (CA) for connection to the grid by signing section 6 (for OGCC controlled distributed generators, the OGCC is the controlling authority. For other feeders the controlling authority will be Provincial Lines.)  Section 7 testing can only proceed when all salient comments have been resolved and tests completed for Sections 3 to 6. PART 3: POST-ENERGIZATION Step 5: Final Potential and On-load Checks  Controlling Authority will provide authorization to connect to the grid (for OGCC controlled distributed generators, the OGCC is the controlling authority. For other feeders the controlling authority will be Provincial Lines.)  Complete and sign Section 7 when all parts of the COVER form are complete. (Note: cross readings to be performed within 5 business days of placing load on station)  Summary of testing results and certificates must be kept on file for a minimum period of 7 years by the Customer (as indicated by IESO Market Rules, Chp.4, 5.1.3). Hydro One Networks Inc. may require this information, on an exception basis. [COVER - page 8 of 8] 144
  • 148. Rev 0 February 2009 DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS Hydro One Networks Inc. INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW Appendix H – Distribution Policy – Metering for Embedded Generators H NOP 041 The following is HONI‘s Metering for Embedded Generators NOP 041 Policy. It contains the metering requirements for DG interconnection to HONI‘s distribution system. 145
  • 149. 146
  • 150. 147
  • 151. 148
  • 152. 149
  • 153. 150
  • 154. 151
  • 155. 152
  • 156. 153
  • 157. 154
  • 158. 155
  • 159. 156
  • 160. 157